Hilti PROFIS Engineering 3.1.

14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HST3-R M20 hef2
Return period (service life in years): 50
Item number: 2105900 HST3-R M20x200 -/60
Filling set or any suitable annular gap filling solution
Specification text: Hilti HST3 stud anchor with 130 mm
embedment, M20 hef2, Stainless steel,
installation per ETA 98/0001, with annular gaps
filled with Hilti Filling set or any suitable gap
solutions,
Effective embedment depth: hef,act = 130.0 mm (hef,limit = - mm), hnom = 145.0 mm
Material: A4
Evaluation Service Report: ETA 98/0001
Issued I Valid: 7/20/2023 | -
Proof: SOFA based on EN 1992-4 and fib bulletin 58, Mechanical
Stand-off installation: grouted standoff; restraint level (anchor plate): 2.00; eb = 5.0 mm; t = 12.0 mm
2
grout compressive strength = 45.00 N/mm
Anchor plate :
R lx x ly x t = 500.0 mm x 600.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked concrete, C40/50, fc,cyl = 40.00 N/mm ; h =300.0 mm, partial material safety factor gc = 1.500
Installation: Hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

Application also possible with HST4-R M20 under the selected boundary conditions.
More information in section Alternative fastening data of this report.

R
- The anchor calculation is based on a rigid anchor plate assumption.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 67.300; Vx = 30.880; Vy = -9.230; no no 94
Mx = 2.880; My = 7.860; Mz = 3.630;

2 Load case/Resulting anchor forces y


5 6

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 14.893 7.622 6.999 -3.020
2 1.804 6.999 6.999 -0.057 3 Tension 4x
3 17.766 5.967 5.147 -3.020
4 4.676 5.147 5.147 -0.057
5 20.638 4.469 3.295 -3.020
6 7.549 3.295 3.295 -0.057

Max. concrete compressive strain: 0.01 [‰] 1 2


Max. concrete compressive stress: 0.35 [N/mm ]
2

Resulting tension force in (x/y)=(-116.7/42.7): 67.326 [kN]


Resulting compression force in (x/y)=(246.9/-291.1): 0.026 [kN] Compression

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 20.638 82.714 25 OK
Pullout Strength* 20.638 32.998 63 OK
Concrete Breakout Failure** 53.297 96.484 56 OK
Splitting failure** 67.326 79.905 85 OK

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gMs

NRk,s [kN] gMs NRd,s [kN] NEd [kN]


115.800 1.400 82.714 20.638
3.2 Pullout Strength

y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gMp

NRk,p [kN] yc g Mp NRd,p [kN] NEd [kN]


35.000 1.414 1.500 32.998 20.638

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

3.3 Concrete Breakout Failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gMc
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
347,100 152,100 195.0 390.0 40.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N z [mm]


0.0 1.000 26.9 0.879 1.000 1.000 493.6
0
y M,N k1 NRk,c [kN] gMc NRd,c [kN] NEd [kN]
1.000 7.700 72.183 1.500 96.484 53.297

Group anchor ID
1, 3, 5

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

3.4 Splitting failure

N
NEd £ NRd,sp = Rk,sp EN 1992-4, Table 7.1
gMsp
0 Ac,N
NRk,sp = NRk,sp · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y h,sp EN 1992-4, Eq. (7.23)
Ac,N
0
NRk,sp = min (NRk,p, N0Rk,c)
0
Ac,N = scr,sp · scr,sp EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,sp £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,sp )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,sp )
{1; (h ) } £ 2.00
2/3 2/3
y h,sp = (hh )min
£ max
ef + 1.5· c1
hmin
EN 1992-4, Eq. (7.24)

0 2
Ac,N [mm ]
2
Ac,N [mm ] ccr,sp [mm] scr,sp [mm] hmin [mm] y h,sp 2
fc,cyl [N/mm ]
795,200 244,036 247.0 494.0 189.0 1.361 40.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1


116.7 0.679 42.7 0.853 0.943 1.000 7.700
0
NRk,sp [kN] gMsp NRd,sp [kN] NEd [kN]
49.497 1.500 79.905 67.326

Group anchor ID
1-6

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 7.622 77.760 10 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength* 5.967 98.712 7 OK
Concrete edge failure in direction x+** 15.441 52.428 30 OK

* highest loaded anchor **anchor group (relevant anchors)


When the input edge distance is set to "infinity", edge breakout verification is not performed in that direction

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gMs
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gMs VRd,s [kN] VEd [kN]
97.200 1.000 97.200 1.250 77.760 7.622

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

4.2 Pryout Strength

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gMc,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
97,500 152,100 195.0 390.0 3.200 40.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] gMc,p VRd,cp [kN] VEd [kN]
7.700 72.183 1.500 98.712 5.967

Group anchor ID
3

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

4.3 Concrete edge failure in direction x+

V
VEd £ VRd,c = Rk,c EN 1992-4, Table 7.2
gMc
0 Ac,V
VRk,c = kT· y b,g · VRk,c · 0
· y s,V · y h,V · y a,V · y ec,V · y re,V EN 1992-4, Eq. (7.40)
Ac,V
1 1
y b,g = = Hilti Method for anchor design in grouted stand-off connections, Hilti, 2023
ab,g C tg
1+ 3
4
d
0 a b 1,5
VRk,c = k9 · dnom · lf · √fck · c1 EN 1992-4, Eq. (7.41)
0,5
a = 0.1 · () lf
c1
EN 1992-4, Eq. (7.42)
0,2

= 0.1 · (
c )
d nom
b EN 1992-4, Eq. (7.43)
1
0 2
Ac,V = 4.5 · c1 EN 1992-4, Eq. (7.44)
c2
y s,V = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.45)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 EN 1992-4, Eq. (7.46)
1
y ec,V = £ 1.00 EN 1992-4, Eq. (7.47)
1+ ( 2 · eV
3 · c1 )
0,5

( )
2
n2 · dnom · fck
y 90°,V = 4.0 · k4 · £ 4.00 fib Bulletin 58, Eq. (10.2-5f1)
VRk,c,^


1
2
y a,V =
(cos aV) + y V
90°,V
2
(sin a ) ³ 1.00 fib Bulletin 58, Eq. (10.2-5f))

lf [mm] dnom [mm] k9 a b 2


fc,cyl [N/mm ] c1 [mm]
130.0 20.00 1.700 0.081 0.063 40.00 200.0
1
C[ ]
y b,g mm
0,25
d [mm] tg [mm]
0.978 0.043 20.0 5.0
0 2
Ac,V [mm ]
2
Ac,V [mm ] y s,V y h,V ec,V [mm] y ec,V
330,000 180,000 1.000 1.000 60.0 0.833

k4 n2 VRk,c,^ [kN] y 90°,V aV [°] y a,V y re,V


1.0 3 80.425 3.090 0.63 1.000 1.000
0
VRk,c [kN] kT gMc VRd,c [kN] VEd [kN]
52.638 1.0 1.500 52.428 15.441

Group anchor ID
1-6

When the input edge distance is set to "infinity", edge breakout verification is not performed in that direction

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)


Steel failure

bN bV a Utilization bN,V [%] Status


0.250 0.057 2.000 7 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.843 0.295 1.500 94 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 15.288 [kN] dN = 1.1422 [mm]


VSk = 3.311 [kN] dV = 0.1905 [mm]
dNV = 1.1580 [mm]
Long term loading:

NSk = 15.288 [kN] dN = 1.5815 [mm]


VSk = 3.311 [kN] dV = 0.2858 [mm]
dNV = 1.6071 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are
valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in
this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• The equations presented in this report are based on metric units. When inputs are displayed in imperial units, the user should be aware that the
equations remain in their metric format.
• Design is only valid if hole is filled to remove clearance, clearance as per EN 1992-4 Table 6.1
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

8 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HST3-R M20 hef2
Profile: no profile Item number: 2105900 HST3-R M20x200 -/60
Hole diameter in the fixture: df = 22.0 mm Maximum installation torque: 180 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 20.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 165.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 189.0 mm
Cleaning: No cleaning of the drilled hole is required

Hilti HST3 stud anchor with 130 mm embedment, M20 hef2, Stainless steel, installation per ETA 98/0001, with annular gaps filled with Hilti Filling
set or any suitable gap solutions

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Torque controlled cordless impact tool
• Properly sized drill bit • Torque wrench
• Hammer

y
250.0 250.0
50.0

5 6
300.0
250.0

3 4
x
250.0

300.0

1 2
50.0

50.0 400.0 50.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -200.0 -250.0 200.0 600.0 - - 4 200.0 0.0 600.0 200.0 - -
2 200.0 -250.0 600.0 200.0 - - 5 -200.0 250.0 200.0 600.0 - -
3 -200.0 0.0 200.0 600.0 - - 6 200.0 250.0 600.0 200.0 - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

12
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

9 Drilling and installation

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

13
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

10 Alternative fastening
10.1 Alternative fastening data

Anchor type and diameter: HST4-R M20


Return period (service life in years): 50
Item number: 2329126 HST4-R M20x200 5-60
Filling set or any suitable annular gap filling solution
Specification text: Hilti HST3 stud anchor with 130 mm embedment, M20 hef2, Stainless steel, installation per ETA 98/0001,
with annular gaps filled with Hilti Filling set or any suitable gap solutions,
Effective embedment depth: hef,act = 130.0 mm (hef,limit = - mm), hnom = 145.0 mm
Material: A4
Evaluation Service Report: ETA-21/0878
Issued I Valid: 10/31/2024 | -
Proof: SOFA based on EN 1992-4 and fib bulletin 58, Mechanical
Stand-off installation: grouted standoff; restraint level (anchor plate): 2.00; eb = 5.0 mm; t = 12.0 mm
2
grout compressive strength = 45.00 N/mm
Anchor plate :
R lx x ly x t = 500.0 mm x 600.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked concrete, C40/50, fc,cyl = 40.00 N/mm ; h =300.0 mm, partial material safety factor gc = 1.500
Installation: Hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

Max. Utilization with HST4-R M20: 94 %


Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

14
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

10.2 Installation data


2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HST4-R M20
Profile: no profile Item number: 2329126 HST4-R M20x200 5-60
Hole diameter in the fixture: df = 22.0 mm Maximum installation torque: 180 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 20.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 165.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 189.0 mm
Cleaning: No cleaning of the drilled hole is required

Hilti HST4 stud anchor with 130 mm embedment, M20, Stainless steel, installation per ETA-21/0878, with annular gaps filled with Hilti Filling set or
any suitable gap solutions

10.2.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Torque controlled cordless impact tool
• Properly sized drill bit • Torque wrench
• Hammer

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

15
Hilti PROFIS Engineering 3.1.14

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 16
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 6, 2024 Date: 4/17/2025
Fastening point:

11 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan