TST Wui
TST Wui
TST WUI
Important !
You must read the function description before operating,
connecting or starting up door controller.
preliminary
public (B)
2005-09-07
WUI_Inbetriebnahme2_GB.doc
TST Startup WUI
Notes
© Copyright 2004 by
FEIG ELECTRONIC GmbH
Lange Straße 4
D-35781 Weilburg-Waldhausen
Tel.: +49 6471 3109-0
http://www.feig.de
This edition replaces all earlier versions.
The specifications contained in this document may be changed without prior notice.
Transmission and reproduction of this document, use and revealing of its contents are not permitted without
express consent. Violations will result in liability for damages. All rights reserved in case of patent granting or
utility model listing.
This Manual is directed especially at persons involved with starting up / commissioning the TST WUI
controller of FEIG ELECTRONIC GmbH. Starting up the controller must be carried out only by officially
trained electrical experts who are familiar with the safety standards of electrical drive and automation
technology.
The entity which has placed the TST WUI controller in service is solely responsible for the completeness of
the startup manual.
This Manual shows only a small range of the controller functions. Further functions and descriptions for
individual door functions as well as more exact specifications for the controller and hazard notes can be
found in the main description.
The collecting of information in this document has been done to the best of our knowledge and with due
diligence. FEIG ELECTRONIC GmbH does not warrant the correctness and completeness of the information
in this document. In particular, FEIG ELECTRONIC GmbH cannot be held liable for following damages due
to faulty or incomplete information.
Since mistakes can never be completely avoided in spite of our best efforts, we always welcome feedback.
The installation recommendations contained in this document presume favorable surrounding conditions.
FEIG ELECTRONIC GmbH assumes no liability for perfect function in environments alien to the system.
FEIG ELECTRONIC GmbH provides no warranty that the information in this document is free of foreign
copyrights. FEIG ELECTRONIC GmbH does not grant any licenses for its own or foreign patents or other
copyrights in connection with this document. Warranty claims against FEIG ELECTRONIC GmbH are the
right of the direct contractual partner only and are not transferable. Warranty is assumed only for the
products supplied by FEIG ELECTRONIC GmbH. There is no warranty for the overall system.
The description of products, their use, possibilities and performance data are not to be taken as assured
properties and are subject to technical changes.
ATTENTION alerts to possible damage to ) refers to useful information which is useful but
not absolutely necessary for using the TST WUI
the controller. controller
Table of Contents
1 Safety information 4
2 Technical data 5
3 Installation of the control system 7
4 Electrical connection 8
4.1 Power supply connection............................................................................................................8
4.2 3-Phase Motor connection ..........................................................................................................9
4.3 1-Phase Motor connection ..........................................................................................................9
4.4 Safety edge connection.............................................................................................................10
4.5 Limit switch connection ............................................................................................................10
7 Inputs overview 12
8 Outputs overview 13
8.1 Outputs of TST WUI ...................................................................................................................13
8.2 Outputs of TST RWUI.................................................................................................................13
1 Safety information
ATTENTION: IMPORTANT SAFETY INSTRUCTIONS
IT IS IMPORTANT FOR THE SAFETY OF PERSONS TO OBSERVE THESE INSTRUCTIONS. THESE
INSTRUCTIONS MUST BE KEPT:
- All work concerning installation, set-up and maintenance must be carried out exclusively by qualified
staff. You must specifically pay attention to the following regulations : VDE0100, EN 50110
(VDE0105), EN 60204 (VDE0113), EN 50178 (VDE0160), EN 60335 (VDE0700), fire prevention
regulations, accident prevention regulations and the regulations relevant to industrial gates
(ZH1/494, EN12453, EN12978)
- The control system should only be opened when the power supply is completely switched off.
- If the potential-free contacts of the relay outputs or other contact points are operated with external
power. i.e. with a dangerous voltage which can still be live after switching off the control system or
when the mains plug is disconnected, an appropriate warning sticker must be clearly visible on the
control system casing. ("ATTENTION! all mains electricity circuits must be switched off before
accessing the connecting terminals.")
- The control system must never be operated when it is open.
- The control system should only be operated with dismantled CEE connector if the mains supply can
be completely disconnected from the control system by means of a corresponding switch. The mains
plug or the switch used as a substitute must be easily accessible.
- If the connecting cable of this appliance is damaged, it must be replaced by the manufacturer or his
after-sales service or by a similarly qualified person in order to avoid dangers.
- Even after switching off the power supply, there are still dangerous voltages for up to ½ a minute on
the DC-bus capacitors. The discharge time until the voltage values are less than 60 V DC is a
maximum of 1 minute. Touching internal control system components during this discharge time is
dangerous.
- If the switching power supply is defective, the discharge time for the DC-bus capacitors to reach less
than 60 V DC can increase significantly. Here, discharge times of up to 2 minutes can occur.
- If the 24 V control system is short-circuited or extremely overloaded, the switching power supply
does not start although the DC-bus capacitors are charged. The display and LEDs remain dark. It is
not possible to start the power supply unit until after the short-circuit or extreme overload has been
resolved.
- After switching off the power, the power supply unit is still supplied for several seconds by the DC-
bus capacitors and still maintains the power supply function for a certain time depending on the
power supply unit loading.
- The control system must not be operated without a connected protection earth. The absence of
protection earth results in dangerous high voltages, caused by discharge capacities, on the control
system housing. The protection earth connection must be carried out in accordance with EN50178
Section 5.2.11.1 for increased leakage currents >3,5mA.
- The system must not be switched on or operated when wet. This can result in destruction of the
control system.
- If the control systems are used outside the specified temperature range, it must be ensured, using a
regulated and monitored heating system, that the specified operating temperature range is
maintained when the power supply is switched on and during operation of the control system.
- It is prohibited to operate the control system if the keypad or screen is damaged.. Damaged keypads
and screens must be replaced. Touching the keypad with sharp objects must be avoided in order to
avoid damaging the keypad. The keypad is basically only intended to be touched with the fingers.
- Before switching on the control system for the first time, it must be ensured that the plug connectors
and evaluation cards (plug-in modules) are in the correct position. Misplaced or skewed plugging-in
the cards can result in damage to the control system as can installing unauthorised third-party cards.
- When the gate is operated in dead-man operating mode, it must be ensured that the gate area can
be viewed by the operator as safety equipment such as safety rail and light barrier are not effective
in this mode.
- It is forbidden to operate the contactors manually. If the protective foil is destroyed, the guarantee is
void.
- The parameter setting and operation of the safety equipment must be checked. The adjustment of
the parameters, bridges and other operating elements must only be carried out by qualified staff.
WARNING Disregarding the safety information can be detrimental to health or damage the
control system.
We do not claim to have fully covered the safety information. Please contact your supplier for further
information about the product.
The manufacturer has carefully tested the appliance hardware and software and the product documentation,
however cannot make any guarantee of complete correctness.
Appliance identification (type plate with information about the name and address of the manufacturer, serial
number, type description, power supply and temperature range) must be done by the user.
2 Technical data
Housing dimensions (W x H x D): ca.: 182 x 320 x 93mm (without emergency stop button)
Mounting: upright
Power supply range for 3-phase 3 x 200 ... 415V ±10% / 50 .. 60Hz
current with N corresponds to mains power supply voltage of
115 ... 240V ±10% / 50 .. 60Hz
Power supply range for 3-phase 3 x 115 ... 240V ±10% / 50 .. 60Hz
current without N corresponds o mains power supply voltage of
115 ... 240V ±10% / 50 .. 60Hz
IMPORTANT N must be connected with L2.
Power supply range for 3-phase 3 x 360 ... 400V ±10% / 50 .. 60Hz
current without N in connection with
the option
TST WU-0.0-A –
Supply adjustment 400V
Required fuse 3x 10A Type K
Power consumption max. 30W
Power supply unit without motor
Power consumption 400V 230V 115V
Power supply unit with AC3 motor at Max. 2.2 kW Max. 1.5 kW Max. 0.75 kW
External power supply (230 V): 230 VAC ±10%, 50...60 Hz
(fused on the printed circuit board: 2 AT)
Control voltage / external power 24 VDC ±5%
supply 2: max. 500 mA including all plug-in modules and 12 V connections
fused via self-resetting semiconductor fuse
External power supply 12V: 11.3 VDC ±5%, regulated, max. 150 mA
Control inputs: 24 VDC / typ.15 mA
min. signal duration for input control commands: > 100 ms
all inputs must be connected potential-free or:
IN1 ... IN8: < 2 V: inactive Æ logical 0
> 17 V: active Æ logical 1
IN9 ... IN10: < 5 V: inactive Æ logical 0
>16 V: active Æ logical 1
Safety chain / emergency stop All inputs must be connected potential-free
< 15 V: inactive Æ logical 0
>17 V: active Æ logical 1
Contact load capacity: ≥ 35 VDC / ≥ 200 mA
If the safety chain is interrupted, no movement of the drive is
possible, not even in deadman
Safety edge input for electric safety edges with 1.2kΩ or 8.2kΩ terminal resistance
and for dynamic optical systems
Relay outputs if inductive loads are switched (e.g. further relays or brakes), they
must be equipped with corresponding noise suppresion
measures (free-wheeling diodes, varistors, RC elements)
Relays K1, K2: ⇒ 24VDC / 500 mA Contacts which have been
⇒ 230 VAC / min. 0.1 A / max. used once for power switching
80 W can no longer switch extra-low
potential-free switching, change- voltage
over contact
Relays K3, ... K14: ⇒ 24VDC / 1A Contacts which have been
⇒ 120 VAC / 0,5A used once for power switching
potential-free switching, N.O. can no longer switch extra-low
contact voltage
Drive output: 3x 400VAC, max. 2.2 kW for AC-3
Reversing contactor is prepared for operating three-phase drives
Max. length of the motor cable: 30m
electromechanical brake 230 VAC-control via switched motor phase and N
Operating temperature range: -10...+50°C
Storage temperature range -20...+70°C
Air humidity up to95% not condensating
Mains cable installation Y, the mains cable must only be replaced by the manufacturer or
his after-sales service or by another qualified person
Equipment mobility stationary
Protection class Protection class I
Equipment type Motor appliance, external motor is not part of the delivery from
FEIG ELECTRONIC GMBH
Vibration low vibration installation, e.g. on a brick wall
Protection class IP54 (IP65 by replacing CEE connection and sealing cable
entries)
All unused cable entries must be closed.
Weight ca. 2.8 kg
Directives Standards:
EMV-Directive: 89/336/EWG EN 50081-1 / 03.93: interference emissions, residential
modified by: 91/263/EWG area
92/031/EWG EN 50081-2 / 03.94: interference emissions, industrial area
93/068/EWG
EN 61000-6-2 / 2001: interference resistance, industrial area
Low voltage directive: EN 60335-1 / 2003: Safety of electrical appliances for
73/023/EWG domestic use and similar purposes /
modified by: 93/068/EWG Part 1
Prototype tested according to: EN12453 / 2001: Usage safety of power-operated gates
– requirements
EN12445 / 2001: Usage safety of power-operated gates
– test methods
Applied national technical EN12978 / 2003: Gates – safety equipment –
specifications concerning the requirements and test methods
directives mentioned above
WARNING ATTENTION
During install of control system, system • Before installation, the control system must be
must be disconnected from the mains. checked to make sure it does not show any
signs of transport or other damage. Damage
inside the control system can result in
significant consequential damages to the
control system and risk of injury to the user.
• Touching the electronic parts, especially the
components of the processor circuit, is
forbidden.
Electronic components can be damaged or
destroyed by electrostatic discharge.
• Before opening the casing cover, it must be
ensured there are no drill filings lying on the
cover which can fall inside the casing.
• It must be ensured the system is disconnected
from the mains during installation.
• Unused cable entries must be sealed using
Figure 1: Cover installation suitable measures in order to guarantee the
Keypad connection protection class IP54 of the casing.
• The cable entries must not be subjected to any
mechanical loads, especially tensile loads.
Min. 100mm
300
50°C
-10°C
80
Ca. 1300
3x400VAC,
N, PE 160
Min. 100mm
4 Electrical connection
• All control voltage inputs are galvanically
WARNING isolated from the power supply by means of a
reinforced insulation. We recommend at least
• Connection, testing and maintenance work on one additional isolation with a nominal voltage
the open control system must only be carried > 230 V (according to EN 60335-1) for all
out in a voltage-free state. You must pay components which are to be connected to the
particular attention to the points mentioned in control system.
the safety information. • Very high electrostatic charges take place
• There are still up to 2 minutes of dangerous especially for fast-operating rollup plastic
voltage after switching off the control system. gates. Damage to the control system can result
• Touching the electronic components is from this voltage discharge. Therefore, suitable
dangerous due to residual voltages. countermeasures must be taken to prevent
electrostatic charging.
• The control system must never be operated
while the housing cover is open. • Maximum cross sections for connection of the
printed circuit board terminals.:
ATTENTION Single Fine strand
wire (with/without
(rigid) wire end
• Before switching on the system for the first
ferrule)
time after completing the wiring, it must be
Screw terminals 2.5 1.5
checked whether all motor connections on the
control system and on the motor are tightened Plug-in terminals 1.5 1.0
and the motor is switched to star or delta Motor terminals 2.5 2.5
correctly. Mains connection 2.5 1.5
L3 L2 L1
L3 L2 L1 13 +A1 L1 L2 L3 13 +A1
1
41 42 43
X28
X22
K500
K501
T1 T2 T3 14 -A2 T1 T2 T3 14 -A2
31 32 33 34 35 36
L3.1
extern
PE PE PE N T1 T2 T3
X20
L1.3 N
X10 N X13 10 11
X14
12 20 21 22
X15
N
PE
L1 L2 L3 13 +A1 L1 L2 L3 13 +A1
-L3
-L2
-L1 1
X28
K 2 0 0 - C lo s e K 200 - O pen
K500
K501
31 32 33 34 35 36
T1 T2 T3 14 +A T1 T2 T3 14 +A1
PE PE PE N T1 T2 T3
X20
L 3 .1 N N 10 11 12 20 21 22
X10 X13 X14 X15
K1 Com
K1 NO
K2 Com
K1 NC
K2 NO
K2 NC
rotating flashing light 1
Magnet voltage
T1 T2 T3
PE
L 1 -3 N PE
400 VAC M
3~
L1 L2 L3 13 +A1 L1 L2 L3 13 +A1
-L3
-L2
-L1
1
X 28
K501
T1 T2 T3 14 -A 2 T1 T2 T3 14 -A2
31 32 33 34 35 36
PE PE PE N T1 T2 T3
X20
L3.1 N N 10 11 12 20 21 22
X10 X13 X14 X15
K1 Com
K1 NO
K2 Com
K1 NC
K2 NO
K2 NC
Rotating flashing light 1
Magnet voltage
U1 V1 U2 W2
PE
N L PE
230VAC
M 1~
„electric“ safety
41 42 43 44 45 51 52 53
X23 edge
X22 41 42 43 44 45 51 52 53
X23
X22
Dynamic optical
J400 system e
43 44 J 400: 1 - 2 3 1 J400
Receiver W hite
Brown
Term inal
8k2
resistor
OFF S300 ON
The Jumper
J 400 is
J400 placed in the Trans-
Inside 3 1
upper right mitter
(brown) corner of the
1,2K 8,2K
PCB
Outside
(white)
43 44 45 54 71
41 42 61 62 63 64 65 66
X24
X22
Limit switch CLOSE
Limit switch OPEN
+24V
Emergency stop circuit
thermopill
IMPORTANT
Check the electrical connection again before operating the control system.
The appliance can be damaged by wrong connections.
IMPORTANT Distance is very much dependent on the type of barrier and the speed, increase the
value for fast gates.
If the movement direction is wrong, the motor rotating field is incorrect: switch off the control
system and change 2 motor connections.
IMPORTANT Limit switch in the end positions must not be run over!
3. Move the barrierto ca. 10 cm before the open position with the ¿ UP key.
IMPORTANT Distance is very much dependent on the type of barrier and the speed, increase the
value for fast gates.
IMPORTANT Limit switch in the end positions must not be run over!
5. If required for the type of barrier: set the top and bottom EMERGENCY limit switches.
)Connect N.C. contacts e.g. in the safety circuit in series with thermopile.
6. Go to parameterisation mode by pressing the Å STOP and ¿ UP keys and select parameter P.980
"Service Mode", open this and set parameter value "2" to "0" (automatic mode)
7. Leave the parameterisation mode by pressing the Å STOP key for a long time (3 sec.).
8. If necessary correct the OPEN and CLOSED limit switch positions by fine adjustment of the stop
positions in automatic mode.
WARNING In order to avoid unintended operation of the barrier, only carry out the
adjustment of the limit switches when EMERGENCY STOP is pressed or the control system is
switched off !
61
X23 51 52 53 54
64 65 66 71 72 73
X25 74 75 76 X24
CLOSE
STOP
+24V
OPEN
GND
+24V
STOP
CLOSE
OPEN
Figure 10: Photo eye connection Figure 11: External control device
7 Inputs overview
1 2 3 8 9 10 4 5 6 7
31 32 33 34 35 36 41 42 43 44 45 51 52 53 54 61 62 63 64 65 66 71 72 73 74 75 76 81 82 83 84 85 86
X20 X22 X23 X24 X25 X26
GND
Si-Lei
Open Ext. 1
GND
+12V
+24V
Pull switch OSCS
GND
GND
GND
Dead man / Auto
+24V
+24V
Pull switch EO
GND
+24V
Arm blocked
GND
Close Ext.
GND
Arm broken / Crash
+24V
Photo eye
Limit CLOSE
Limit OPEN
E-Stop ext. 11
E-Stop ext. 12
E-Stop ext. 21
E-Stop ext. 22
Door switch
Thermopill
8 Outputs overview
K500
K501
T1 T2 T3 14 -A2 T1 T2 T3 14 -A2
35 36
33 34
31 32
PE PE PE N T1 T2 T3
X20
L3.1 N N
X10 X13 X14 10 11 12 20 21 22 X15
K1 Com
K2 Com
K2 NO
K2 NC
K1 NO
K1 NC
T1 T2 T3
Magnet Rotating
PE
voltage flashing light
M
3~
211 212 213 214 215 216 217 218 221 222 223 224 225 226 227 228 231 232 233 234 235 236 237 238
Stop synchrone barrier
Transmission Det. 2 (N)
Counter +
Transmission Det. 1 (V)
Counter -
Barrier Closed
Open synchrone barrier
Barrier Open
¿ UPor A T T E N T I O N:
Not all parameters are directly
the parameter value can be displayed
or modified (see below)
P. . . .
À DOWN visible or modifiable depending display varies according to the
selection
on password and type of
security level set
Parameter editing for selected parameter
1. Control system in Display of the desired parameter
parameterisation mode name P. 0 1 0
2. the current parameter value is
Å STOP (short) Open the parameter displayed:
if the current parameter value in force
5
3. Up key for increasing
¿ Up parameter value
is changed, the decimal positions
flash 6
or Down key for reducing the
À Down parameter value 4
4. the parameter counts as saved when
or
Å STOP (long) save amended parameter
discard amended parameter
value no positions are flashing any more
cancellation, the original parameter
6
STOP (short)
value value is displayed again 4
5. for changing to the display of
Å STOP (short) the parameter name
Display parameter name
P. 0 1 0
Leaving parameterisation mode
STOP (long) parameterisation mode is The last saved value is obtained
Å stopped immediately, gate automatically ....
operation is active again
Reset the control system
Å+¿+À press simultaneously and keep pressed for ca. 3 seconds.
10 Functions
IMPORTANT
Not all parameters are always avaiable and visible. This depends on parametersetting and the used
software version.
Changes of the software and of the parameterfunction can be done without previous announcement.
11 Messages overview