Ic 693 Alg 442
Ic 693 Alg 442
New In Stock!
GE Fanuc
http://www.pdfsupply.com/automation/ge-fanuc/series-90-30/IC693ALG442
Series 90-30
1-919-535-3180
In Stock! Analog 4IN/2OUT IC693A IC693AL IC693ALG
www.pdfsupply.com
Email: [email protected]
12
the%AI and %AQ registers is in a 16-bit 2’s complement format. In current modes, an open-wire
fault is reported to the CPU for each channel. The module can go to a known last state when
system power is interrupted. As long as user power is applied to the module, each output will
maintain its last value, or reset to the low end of the scale (range), as determined by how you have
configured the module.
Each output channel can be configured to operate in ramp mode using ladder logic. In ramp
mode, changes in %AQ data cause the corresponding output channel to ramp to the new %AQ
value. The ramp output consists of steps taken each millisecond until the final value is reached.
High and low alarm limits can be set for all input channels and an open-wire fault (current
output modes) is reported to the CPU for each output channel. All six analog channels may be
updated on every scan, depending on the scan time.
12-2 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
Input Ranges 0 to 20 mA
4 to 20 mA
4 to 20 mA Enhanced
(Table continued on next page)
(Continued from previous page)
Resolution
0 to 20 mA 5 !A (1 LSB = 5 !A)
A)
4 to 20 mA 5 !A (1 LSB = 5 !A)
A)
4 to 20 mA Enhanced 5 !A (1 LSB = 5 !A)
A)
Absolute Accuracy3
All Current Modes " 0.25% of full scale @25#C (77#F) F)
" 0.5% of full scale over specified operating temperature range
Linearity <1 LSB
Common Mode Voltage 200V (maximum)
Common Mode Rejection >70 db at DC; >70 db at 60 Hz
Cross Channel Rejection >80 db from DC to 1 kHz
Input Impedance 250 $
Input Filter Response 29 Hz
Analog Voltage Input
Input Ranges 0 to +10V (unipolar)
–10
10 to +10V (bipolar)
Resolution
0 to +10V 2.5 mV (1 LSB = 2.5 mV)
–10 to +10V 5 mV (1 LSB = 5 mV)
Absolute Accuracy3
Both Voltage Ranges " 0.25% of full scale @25
@25#C (77#F) F)
" 0.5% of full scale over specified operating temperature range
Linearity <1 LSB
Common Mode Voltage 200V (maximum)
Common Mode Rejection >70 db at DC; >70 db at 60 Hz
Cross Channel Rejection >80 db from DC to 1 kHz
Input Impedance 800K $%&typical)
Input Filter Response 29 Hz
Power Requirements
External Supply Voltage Range 20 to 30 VDC (24 VDC typical)
Power Supply Rejection Ratio
(PSRR)4 5 !A/V (typical), 10!A/V (maximum)
Current 25 mV/V (typical), 50mV/V (maximum)
Voltage
Voltage Ripple 10%
Current Consumption
From Internal +5V Supply 95 mA
From External User Supply 129 mA
1In the presence of severe RF interference (IEC 801-3, 10V/m), accuracy may be degraded to "1% FS.
2In the presence of severe RF interference (IEC 801-3, 10V/m), accuracy may be degraded to "4% FS.
3In the presence of severe RF interference (IEC 801-3, 10V/m), accuracy may be degraded to "2% FS.
4PSSR is measured by varying VUSER from 24V to 30V.
Refer to Appendix B for product standards and general specifications.
Current Operation
In the 4 to 20 mA range, user data is scaled so that 4 mA corresponds to a count of 0 and 20 mA
corresponds to a count of 32000. The other ranges are selected by changing the configuration
parameters using the Logicmaster 90-30/20/Micro configurator software or the Hand-Held
Programmer. In the 0 to 20 mA range user data is scaled so that 0 mA corresponds to a count of 0
and 20 mA corresponds to a count of 32000. Full 12-bit resolution is available over the 0 to 20 mA
range.
A 4 to 20 mA Enhanced range can also be selected. When this range is selected, 0 mA corresponds
to a count of –8000,
8000, 4 mA corresponds to a count of 0 (zero) and 20 mA corresponds to a count of
+32000. The Enhanced range uses the same hardware as the 0 to 20 mA range but automatically
provides 4 to 20 mA range scaling with the exception that negative digital values are provided to
the user for input current levels between 4 mA and 0 mA. This gives you the capability of
selecting a low alarm limit that detects when the input current falls from 4 mA to 0 mA, which
provides for open-wire fault detection in 4 to 20 mA applications. High and Low alarm limits are
available on all ranges. Ranges can be configured on a per channel basis.
User data in the %AI registers is in 16-bit 2’ss complement format (0 to 20 mA range only).
Resolution of the converted signal is 12 bits binary (1 part in 4096) on the 0 to 20 mA range.
The placement of the 12 bits from the A/D converter in the %AI data word is shown below.
MSB LSB
X D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 X X
The relationship between the current input and the data from the A/D converter is show below.
a44647 a44654
4000 4000
A/D
A/D
BITS
(decimal)
(decimal)
0 0
0 4 20 0 20
CURRENT (mA) CURRENT (mA)
4 to 20mA RANGE 0 to 20 mA RANGE
If the current source is reversed into the input, or is less than the low end of the current range,
then the module will output a data word corresponding to the low end of the current range
(0000H in %AI). If an input that is out of range is entered (that is, it is greater than 20 mA), the
A/D converter will output up to full scale (corresponding to 7FFFH in %AI).
Voltage Operation
In the 0 to +10 V default range, user data is scaled so that 0 volts corresponds to a count of 0 and
+10 volts corresponds to a count of 32000. The –10 to +10 volt range is selected by changing the
12-4 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
X D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 X X
X=not converted bits
Analog values are scaled over the range of the converter. Factory calibration adjusts the analog
value per bit (resolution) to a multiple of full scale (that is, 2.5 mV/bit for unipolar; 5 mV/bit
for bipolar). This calibration leaves a normal 12-bit converter with 4000 counts (normally 212
= 4096 counts). The data is then scaled with the 4000 counts over the analog range. For
example, the data to the A/D converter for the Analog Voltage Input is scaled as shown below.
a45717
4000
A/D
BITS
(decimal)
0
0 VOLTAGE; 0 to 10V RANGE
10
Current Operation
In the 4 to 20 mA range user data is scaled so that 4 mA corresponds to a count of 0 and 20 mA
corresponds to a count of 32767. In the 0 to 20 mA range, user data is scaled so that 0 mA
corresponds to a count of 0 and 20 mA corresponds to 32000. Note that in the 0 to 20 mA
mode, you can enter a value up to 32767 which provides a maximum output of approximately
20.5 mA. Scaling of the current output for both the 4 to 20 mA range and the 0 to 20 mA range
is shown below. In current mode the module also provides an open loop fault detect which is
reported to the PLC in the %I table.
a44683 a44684
32000 32000
%AQ
%AQ (decimal)
(decimal)
0 0
0 4 20 0 20
CURRENT (mA) CURRENT (mA)
4 to 20 mA Range 0 to 20 mA Range
Voltage Operation
For Voltage Operation in the default unipolar mode (0 to +10 volts), user data is scaled so that 0
volts corresponds to a count of 0 and +10 volts corresponds to a count of 32000. In this mode,
you can enter up to 32767 for an overrange of approximately 10.24 volts output. In the –10 to
+10 volt range user data is scaled so that –10 volts corresponds to a count of –32000 and +10
volts corresponds to a count of +32000. In this range, you can enter –32768 to +32767 for an
overrange of approximately –10.24 volts to +10.24 volts.
Scaling of the voltage output for both the 0 to +10 volt range and the –10 to +10 volt range is
as shown below.
a45718
a44658
32000
32000
%AQ
%AQ
0 (decimal)
(decimal)
32000 0
0 10
10 0 10
VOLTAGE (V)
VOLTAGE (V)
12-6 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
Status Reporting
The Analog Combo module module provides status information to the PLC. This status
information is updated once each PLC sweep and consists of the following items:
! health of the module (all ranges)
! overload or open wire detect (current output mode only)
ov
! alarm low and high status (input channels)
! status of the user-supplied power to the module (all ranges)
Location in System
The Analog Combo module is compatible with all Series 90–30 CPU models and may be installed
in any I/O slot of any Series 90–30 baseplate.
12-8 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
Terminal Assignments
Pin assignments for the 20 terminal I/O connector on the Analog Combo module are as shown
in the following table.
Pin Signal
Number Name Signal Definition
1 24VIN User Supplied +24 Volt Input
2 JMP1 Jumper terminal for connecting 250$%%sense
250 resistor for CH1
3 JMP2 Jumper terminal for connecting 250
250$%%sense resistor for CH2
4 +CH1 Positive connection for differential analog input channel 1
5 +CH2 Positive connection for differential analog input channel 2
6 –CH1 Negative connection for differential analog input channel 1
7 –CH2 Negative connection for differential analog input channel 2
8 JMP3 Jumper terminal for connecting 250
250$%%sense resistor for CH3
9 JMP4 Jumper terminal for connecting 250
250$%%sense resistor for CH4
10 +CH3 Positive connection for differential analog input channel 3
11 +CH4 Positive connection for differential analog input channel 4
12 –CH3
CH3 Negative connection for differential analog input channel 3
13 –CH4 Negative connection for differential analog input channel 4
14 Vout CH1 Voltage output for channel 1
15 Iout CH1 Current output for channel 1
16 Vout CH2 Voltage output for channel 2
17 Iout CH2 Current output for channel 2
18 V COM Common return for voltage outputs
19 I RET Common return for User supplied +24 V and current outputs
20 GND Frame ground connections for cable shields
TERMINALS a47047
FIELD WIRING FIELD WIRING
24VIN
1
2 *
3 JMP1
* 4 (+)
JMP2
(+) 5 IN1
IN2 6 (–)
(–) 7
8
*
+ Vuser 9 JMP3
*
JMP4 10 (+)
– (+) 11 IN3
IN4 12 (–)
(–) 13
14
ICH1 15 VCH1
16
ICH2 17 VCH2
18
COM (I RET) V COM
19
20 FGND **
Notes
1. Each Input channel can be configured independent of other Input channels to
operate as a voltage input or a current input – not both simultaneously.
2. Each Output channel can be configured independent of other Output channels to
operate as a voltage output or a current output – not both simultaneously.
3. Please see Chapter 2 for wiring and shield ground connection information.
12-10 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
a47046
LEDs
O
CHX X4 CURRENT/VOLTAGE A/D
O INPUT SELECT MICRO
PROCESSOR
JMPX O
REFERENCE
+ 15V
VIN O
POWER 15V EPROM
COM O CONVERTER 5V
5V
FGND O OPTO
RAM
ISOLATION
VOLTAGE
SUPERVISOR
EEPROM
DATA
TRANSMIT/RECEIVE BACKPLANE
MULTIPLEXOR INTERFACE VLSI
D/A
CONFIG
Iout O CURRENT
SR/LATCH
DRIVER
%AI ADR Starting address for the %AI standard range %AI0001, or next highest N/A
reference type available reference
%AQ ADR Starting address for the %AQ standard range %AQ0001, or next highest N/A
reference type. available reference
%I ADR Starting address for the %I standard range %I0001, or next highest N/A
reference type available reference
ALARM High limit alarm value –32767 to 32760 +32000 User counts
HIGH
12-12 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
This section describes how to configure the IC693ALG442 Analog Combination module using the
configurator function in Logicmaster 90-30/20/Micro Programming Software. Configuration can
also be done using VersaPro or Control Programming Software. For details refer to the VersaPro
or Control online help.
To configure an Analog Combo module on the I/O Configuration Rack screen, follow these
steps:
1. Move the cursor to the desired rack and slot location. The slot may be either unconfigured
or previously configured.
2. Press the !"#$ %& key ('( ). Your screen will change to one similar to the one shown
'().
below.
4. Currently, there is only one selection. (If more than one selection appears, use your ,-./&.
0&12"234 (or 5..&6) keys to move to Catalog # IC693ALG442.) Press 7342. to accept
this selection and to move to the screen shown below.
5. All the remaining configuration does not have to be done on this screen. You can move
your cursor from field to field by pressing the ,-./&.80&12"234 (or 5..&6) keys.
When you are in the field you want to modify, you can either type in your choice or press
the 9): key to scroll through the available selections (or ;<%=4>9): to reverse the
direction of the scrolling).
Note
The entry in the ;4&? 0&@2 field ((ABCD or D7'CBE8FD7')-!48CBEG)
determines how the outputs will behave when the module is toggled from HIJ to
;9BK mode. When this value is set to ABCD (default), the outputs will retain
their last state. When you change this value to D7'CBE, the output will go to
zero.
12-14 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
%I Status Information
The LM8H2=85@. is the reference address for the %I data and points to the start of the locations
in the %I memory (that is, the Input Table) where status information from the module is reported.
You can select the number of %I status locations reported to the PLC by editing the value in the LM
;%N2 field. Allowable values in the %I Size field are 8, 16, and 24 which refer to the number of
%I locations reported to the PLC. For %I SIZE values 8 or greater, the data brought back is in the
format described in the following tables.
%I Locations Description
%I Module OK - 0 indicates NOT OK, 1 indicates module OK.
%I+1 User Supply OK - Indicates when user supply is in specified limits; reads a 0
when User supply below specified limit, 1 when User supply OK.
%I+2 & %I+3 Reserved for future modules. Not used in this module.
%I+4 through 7 " See definition for these bits below.
" %I+4through 7 (upper 4 bits of first %I byte) hold an error code which is defined as follows:
%I bitnumber 7–44 3 2 1 0
user power ok
0 = user supplied power absent or not
1 = user supplied power OK
unused
error code:
binary hexadecimal error
0000 0 no errors
0001 1 invalid channel
0010 2 invalid alarm level
0011 3 invalid ramp time or step
1000 8 invalid E2 COMMREQ function
If the you send E2 COMMREQ data that reflects an invalid condition, the module will ignore the
COMMREQ command and return an error code in the upper 4 bits of the first %I byte. The
module will NOT stop standard operation if an error is detected; these error bits are for the user’s
information and can be ignored if desired. The error code will remain until you send an E2
COMMREQ to clear the error code or reconfigure the module.
Only the most recent error will be reported; an existing error code will be overwritten if another
error occurs. The priorities for errors are:
1. Invalid COMMREQ function (highest priority)
2. Invalid channel.
3. Invalid data (ramp or alarm parameter) (lowest priority).
Thus, if multiple error conditions exist, the one with the highest priority is reported in the error
code.
%I Locations Description
%I+8 Input: Ch #1 ALARM LO - 0 indicates value above limit; 1 below or =
%I+9 Input Ch #1 ALARM HI - 0 indicates value below limit; 1 above or =
%I+10 Input Ch #2 ALARM LO - 0 indicates value above limit; 1 below or =
%I+11 Input Ch #2 ALARM HI - 0 indicates value below limit; 1 above or =
%I+12 Input Ch #3 ALARM LO - 0 indicates value above limit; 1 below or =
%I+13 Input Ch #3 ALARM HI - 0 indicates value below limit; 1 above or =
%I+14 Input Ch #4 ALARM LO - 0 indicates value above limit; 1 below or =
%I+15 Input Ch #4 ALARM HI - 0 indicates value below limit; 1 above or =
%I Locations Description
%I+16 Output Ch #1 BROKEN WIRE 0 = OK, 1 = Wire Broken
(Current modes only)
%I+17 Output Ch #2 BROKEN WIRE 0 = OK, 1 = Wire Broken
(Current modes only)
%I+18 through %I+23 Reserved for future modules. Not used in this module
One of four input or output ranges can be selected; two are voltage ranges. The default range is 0 to
+10V, where input or output voltage values range from 0 to 10 volts. In input mode they report 0
to 32767 integer values to the CPU and in output mode values between 0 and 32767 are sent to the
module. In the –10 to +10V range, values between –32768 to 32767 are sent or received from the
CPU over an input voltage range of –10 to +10V.
The two current ranges are 4 to 20 mA, and 0 to 20 mA. In each of the current ranges, values
between 0 and 32767 are reported back from the module to sent to the module for the entire
range.
12-16 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
* Allowed Values refers to the values that are valid. If a value outside the specified range is sent, the
module clips it to the nearest valid value before sending it to the Digital to Analog Converter. No
errors are returned.
The following table shows values sent from the module back to the PLC for the Input channels.
The ALARM LO and ALARM HI data fields allow you to enter values that cause alarm
indications to be passed to the PLC. Each channel has a low limit alarm value (ALARM LO) and a
high limit alarm value (ALARM HI). These alarm values cause %I points to be set as indicated in
the tables on page 3-95 and 3-96. Values can be entered in all high and low limit fields. Values
entered without a sign are assumed to be positive. The allowable values are shown in the following
table.
TIME
%AQ VALUE CHANGES
12-18 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
! If the ramp mode is turned off during a ramp, the output will step completely to the final
value (indicated by the corresponding %AQ reference).
! If step mode is turned on during a ramp, the new step is used as soon as the COMMREQ is
processed (assuming that the step is valid).
! If time mode is turned on during a ramp, the module will immediately begin a new ramp
using the present output as the starting output and the present time as the start time.
In all cases, changing the value of the corresponding %AQ reference will cause the output to
begin a new ramp from the present output value.
Error Handling
If the module receives E2 COMMREQ data that indicates an invalid channel or a step height or
ramp time that is out of range, the module will ignore the COMMREQ and return an error code
in the first byte of %I data assigned to the module. The error code will be cleared when a Clear
Errors E2 COMMREQ is sent to the module or when the module is reconfigured. Range
checking of %AQ values received by the module is performed before the values are used in
ramp computations. %AQ data which is out of range is clipped to the nearest valid value by the
module.
The decimal and hexadecimal values which specify COMMREQ data types are shown in Table
3-26. The data format and command word description for the E2 COMMREQ are shown in
Table 3-27. The first word holds the command word, the second word holds data for changing
alarm or ramp parameters and the third word is unused. The %R addresses correspond to the
example command block data in Table 3-25.
12-20 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
You can change the high and low alarm limits for any of the four input channels. Two modes
are available to modify the alarm data: absolute mode and relative mode.
! When using absolute mode
mode, the alarm data sent by the COMMREQ specifies the actual new
alarm value.
! When using relative mode
mode, the alarm data specifies the positive or negative change in the
alarm value that is added to the present value.
The module verifies that the new alarm limit requested is not out of range and does not violate
the condition HIGH>LOW. If an invalid request is made to change an alarm value, the
corresponding error code will be returned in the upper four bits of the first byte of %I references
assigned to the module.
E2 COMMREQ Example
The following ladder logic provides an example of setting up E2 COMMREQ data and issuing
the COMMREQ. As with all COMMREQs, it is recommended that the ladder verify the
completion of the E2 COMMREQ in progress before initiating another. This ensures that the
module does not receive COMMREQs faster than it can process them. One way to do this is to
zero the contents of the COMMREQ status (%R0001 in this example) as the COMMREQ is
enabled. Since the status returned for a completed COMMREQ is never zero, a non-zero status
word will then indicate that the COMMREQ has completed.
In this example, the COMMREQ command block begins at %R0002 and is initialized on the
first scan. It is assumed that the 6 bytes of COMMREQ data sent to the module are moved into
%R0101–%R0103 before the COMMREQ is enabled. The module is located in rack 0, slot 2
so the SYSID input to the COMMREQ is 0002. Setting %T0001 moves zero into the
COMMREQ status word, enables %T0003 for one sweep to initiate the COMMREQ, and sets
%T0002 to begin checking the status word. When a non-zero status word is detected, %T0002
is reset to discontinue checking and %T0004 is set to indicate that the module is ready for the
next COMMREQ. Reference %M0001 is set if a COMMREQ fault occurs.
FST_SCN
BLKMV MOVE MOVE
INT WORD WORD
%R0001
CONST IN1 Q %R0008
+00000 %R0009
CONST IN Q CONST IN Q
CONST E201 0006
IN2 LEN LEN
+00004
00001 00001
CONST IN3
+00000
CONST IN4
+00008
CONST IN5
+00000
CONST IN6
+00000
CONST IN7
+00000
FST_SCN
MOVE MOVE
INT INT
%T0001 %T0002
MOVE S
INT
12-22 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
%T0003 %M0001
COMM_ S
REQ
%R0002 IN FT
CONST
SYSID
0002
CONST TASK
0000
%T0002
NE_
INT
%T0002
CONST I1
+00000 Q R
I2
%R0001 %T0004
S
Module Present
If a module is physically present in a system, it can be added to the system
system’ss configuration by
reading the module into the configuration file. For example, assume that an 4-Channel
Input/2-Channel Output Analog Current/Voltage module is installed in slot 3 of a Model 311
PLC system. It can be added to the configuration with the following sequence. Use the ( and
) arrow cursor keys or the # key to display the selected slot.
Initial Display
H$Q$#870K9R888S;
To add the IC693ALG442 module to the configuration, press the READ/VERIFY, ENT key
sequence. The following screen will be displayed:
H$Q$#85MB8TU$$S;
8MTVQM8W
Selecting %I Reference
At this point the starting %I reference address for the status data returned from the module must
be entered. Notice that the length of the status field ((24
24) is displayed as the first two digits
following the first I on the second line of the display.
Note
This field cannot be changed with the Hand-Held Programmer. However, it can be
changed using the Logicmaster 90-30/20/Micro software configurator function. The
Hand-Held Programmer will always reflect the currently active length of the status
field.
Pressing the ENT key will allow the PLC to select the starting address of the status data. You
can select a specific starting address by pressing the key sequence for the desired address and
pressing the ENT key. For example, to specify the starting address as I17, press the key
sequence 1, 7, ENT.
12-24 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
Note
The configured reference addresses will not be displayed until all three
reference types (%I, %AI and %AQ) have been assigned starting addresses.
Once this is done, the configured addresses can be viewed by scrolling
backward using the ! key.
You can press the CLR key at any time to abort the configuration you have just selected and
return the slot to EMPTY.
After selecting the starting %I address and pressing the ENT key, the following screen is
displayed.
H$Q$#85MB8TU$$S;
5M$VQ5M8W
Note
The configured reference addresses will not be shown until all three reference
types (%I, %AI and %AQ) have been assigned starting addresses. Once this
is done, the configured addresses can be viewed by scrolling backward using
the ! key.
You can press the CLR key while entering the starting address to clear the address field and
enter a different address.
After selecting the starting %AI address and pressing the ENT key, the following screen is
displayed:
H$Q$#85MB8TU$$S;
5O$TQ5O8W
H$Q$#85MB8TU$$S;
5O$TQ5O$#XY$$#+
Once the %AQ starting address has been assigned, the ! key can be used to view the
configured %I and %AI reference addresses. For example, if %I17 and %AI35 are used as
starting addresses then the following screen will be displayed after pressing the key sequence
!, !:
H$Q$#85MB8TU$$S;
8MTVQM$$(ZY$$V$
Scrolling forward from this screen using the " key causes the following screen to be displayed:
H$Q$#85MB8TU$$S;
5M$VQ5M$$#XY$$#[
H$Q$#870K9R888S;
If the CLR key is pressed after the DEL key (instead of the ENT key), the delete operation will
be aborted.
12-26 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
!"#"$%&'(%)*""%+,
-.,/012#-(.0%%%%
The default STOP mode is HOLD, which indicates that each output will hold its last state when
the PLC is placed in STOP mode. You can toggle between the HOLD and DEFLOW modes by
pressing the # key. Pressing this key once causes the following screen to be displayed:
!"#"$%&'(%)*""%+,
-.,/012#012%.(3
In DEFLOW mode, each output will become zero when the PLC is placed in STOP mode.
When the desired mode is displayed, it is accepted by pressing the ENT key. To return to the
previous screen, press the ! key.
!"#"$%&'(%)*""+,
4-%5Y&6#"75"%8
4-%5
You can toggle through the ranges for each channel by pressing the # key. Each range will be
displayed as shown below.
!"#"$%&'(%)*""+,
4-%5Y&6#Y5"795"
!"#"$%&'(%)*""+,
4-%5Y&6#:7)"%;&
!"#"$%&'(%)*""+,
4-%5Y&6#"7)"%;&
When the desired range is displayed, it is accepted by pressing the ENT key. To return to the
previous screen, press the ! key. To view the range display for the next channel, press the "
key. If the " key is pressed, the following screen will be displayed:
!"#"$%&'(%)*""+,
4-%)Y&6#"75"%8
Edit the range for this channel as you did for the first channel. To view the range display for
the first input channel, press the " key.
!"#"$%&'(%)*""+,
4-%5Y&'#"75"%8
You can toggle through the ranges for each input channel by pressing the # key. Each range
will be displayed as shown below.
!"#"$%&'(%)*""+,
4-%5Y&'#Y5"795"
4-%5Y&'#Y5"795"
!"#"$%&'(%)*""+,
4-%5Y&'#:7)"%;&
4-%5
!"#"$%&'(%)*""+,
4-%5Y&'#"7)"%;&
!"#"$%&'(%)*""+,
4-%5Y&'#:Y)"%;&9
When the desired range for the module is displayed, it is accepted by pressing the ENT key. To
return to the previous screen press the ! key.
12-28 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F
IC693ALG442 Analog Combination I/O Module 12
!"#"$%&'(%)*""+,
4-%5%.(#%%%%%"%%
This display contains the entry field for the low alarm limit for this channel. You can enter
positive or negative values using the numeric keys (0 through 9) and the # key. Press the ENT
key to accept the value you have entered. When an alarm value that is not in the allowed range
(–32768
32768 to 32760) is entered, a DATA ERR message will be displayed as shown in the
following example:
!"#"$%0&<&%1!!+,
4-%5%.(#Y$$"""=
The bad data must be corrected before the HHP will allow you to move to another screen.
When a valid low alarm has been entered, press the " key to move to the high alarm limit
screen for this channel. The following screen will be displayed:
!"#"$%&'(%)*""+,
4-%5%-'#%$)"""
This screen contains the entry field for the high alarm limit for this channel. You can enter
positive or negative values using the numeric keys (0 through 9) and the # key. To view the
range screen for the next input channel, press the " key. The following screen will be
displayed:
!"#"$%&'(%)*""+,
4-%)Y&'#"75"%8
4-%)
Edit the ranges and alarm limits for this channel and subsequent channels as you did for the first
channel.
Freeze Mode
If an alarm value in the allowed range (–32768 to 32760) is entered that results in an invalid
condition, such as a low alarm limit greater than an upper alarm limit or a negative alarm for a
channel in a unipolar range, the module will enter freeze mode. In this mode, you will not be
allowed to move beyond the present channel parameters (range, low alarm limit and high alarm
limit) until the invalid condition is corrected or removed. Freeze mode is indicated on the HHP
screen by an asterisk (!) after the slot number. For example, if a low alarm limit of –1000 is
entered for input channel 1 in the 0,10V range the following screen will be displayed:
!"#"$>&'(%)*""+,
4-%5%.(#%Y5"""
If you press either the $ key or the % key to change slots, the following message will be
displayed:
,&81%4-&?@1,A%+,
+1?<BCD%+4.!BC?
If you do not want to save the changes to the CPU, press the CLR key. The following message
will be displayed:
0',4&!0%4-@,A%+,
+1?<BCD%%+4.!BC?
If you do not want to discard the changes you have made, press the CLR key. This will return
you to the last parameter that was being modified with all changes intact.
If you do want to discard the changes you have made, press the ENT key. The Hand-Held
Programmer will then return you to the last parameter that was being modified with the data
reset to its previous value.
If you want to save the data to the CPU from the SAVE CHANGES? screen shown above, press
the ENT key. If the module is in freeze mode, the Hand-Held Programmer will return with a
CFG ERR message on the screen as follows:
!"#"$>42@%1!!%+,
4-%5%.(#%Y5"""
4-%5%.(#%
If all data is valid, the HHP display will move to an adjacent slot when either the $ key or % key
is pressed.
Saved Configurations
Configurations that contain Analog Combo modules can be saved to an EEPROM or MEM card
and read from that device into the CPU at a later time. MEM cards and EEPROMs containing
these configurations can be read into any Release 4 or later Series 90-30 CPU (cannot be read
into a Series 90-20 CPU). Refer to Chapter 2 of the Hand-Held Programmer for Series
90-30/20/Micro Programmable Controllers User’s Manual for detailed information on the Save
and Restore operations.
12-30 Series 90–30 PLC I/O Module Specifications – July 2000 GFK–0898F