20.70 0.25 414.00 0.40 Centerright: Ok! Ok!

The document outlines the structural design for a 3-storey residential building located in Burauen, Leyte, including material properties, column specifications, and reinforcement details. It presents calculations for applied forces, soil pressures, stability checks, and shear design, confirming that all safety ratios are within acceptable limits. The design is verified by Engr. Mark Christian D. Esguerra, ensuring compliance with engineering standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views1 page

20.70 0.25 414.00 0.40 Centerright: Ok! Ok!

The document outlines the structural design for a 3-storey residential building located in Burauen, Leyte, including material properties, column specifications, and reinforcement details. It presents calculations for applied forces, soil pressures, stability checks, and shear design, confirming that all safety ratios are within acceptable limits. The design is verified by Engr. Mark Christian D. Esguerra, ensuring compliance with engineering standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project : 3-STOREY RESIDENTIAL Design by :

LOGO Owner :
Location : BURAUEN LEYTE
Check by : Engr. Mark Christian D. Esguerra
Mark :
Date :
F4
5/1/2022
CANTILEVER FOOTING

Material Properties Column Properties: Reinforcement Details:


Concrete f'c = 20.70 Mpa Width = 0.25 m Location #
Reinforcing fy = 414.00 Mpa Height = 0.40 m Bot Bar Dia = 16.00
Location = CenterRight Along x = 14 OK!
Soil Properties: Footing Properties: Along y = 14 OK!
σall= 75.00

0.42mm
140.00 kPa Length = 2.00 m Cover (mm) =
γ= 18.00 kN/m3 Width = 2.00 m
Thickness = 0.40 m
0.25 m
Depth = 1.50 m
Applied forces:
Load Case Pu Mx My Fx Fy
qa factor
Units kN kN.m kN.m kN kN
Service Load = 162.78 4.53 3.56 1.04 0.76 1.33
2m
Factored Load = 232.68 27.70 20.73 11.47 14.18 1.00

Check for Soil Pressures (Service Load) Check for Stability (Service Load)
Location Total Pressure Remark Overturning Sliding
Corner 1= 0 kPa x-x y-y
x-x y-y
Corner 2= 185.75 kPa Overturn Resisting Overturn Resisting
Corner 3= 178.14 kPa 4.84 290.80052 3.98 160.5761 Ratio Ratio
Corner 4= 0 kPa 60.13864893 40.38368859 191.09 260.37
Ratio 1.00 Safe Safe Safe Safe

Check for Shear Design (Factored Load)


Check Wide Beam Shear Check Punching Shear
-Side +Side Units x-x y-y Unit
185.75 kPa Along x 0.54 - Mpa Unbalance Moment factor = 0.4021642 0.3978397
Along x 0.40 0.34 Mpa Column Location Factor = 30
0 kPa
178.14 kPa Absolute max. Stress = 0.54 MPa ColumnAspect Ratio = 1.6
Under-strenght φ Factor = 0.75 Actual Punching Stress = 0.50 MPa
0 kPa
Allowable Shear Capacity = 0.58 MPa Allowable Shear Capacity = 1.13 Mpa
3D Zoom In Zoom Out
Ratio 0.931 Safe Ratio 0.44 Safe
Detailed Calculations
Check for Stability (Service Load) Check for Soil Pressure (Service Load) Check for Shear (Factored Load) Check for Reinforcement (Factored Load)
Overturning about x-x Soil Pressure Punching Shear Design of steel
Moment = 4.53 Overturn Mom x-x = 4.84 kN-m Net Ultimate Bottom Reinforcement
Shear Force = 0.31 Resisting Mom x-x = 290.80 kN-m soil pressure at critical point Along x Along y Unit
Total = 4.84 Overturn Mom y-y = 3.98 kN-m Point 1 = 227.90 kPa Mu = 144.79 118.72 kN.m
Resisting about x-x Resisting Mom y-y = 160.58 kN-m Point 2 = 314.34 kPa Ru = 0.842 0.691 MPa
Footing Weight = 38.40 Resisting Force = 290.80 kN Point 3 = 297.11 kPa m= 23.529 23.529
Soil Weight = 105.30 Xp = 0.54 Point 4 = 215.41 kPa req'd p = 0.00209 0.00170
Bouyancy = (15.68) Yp = 0.98 Average = 263.69 kPa min p = 0.00338 0.00338
Axial = 162.78 X-ecc = 0.46 Calculation of unbalanced moment transferred by use p = 0.00278 0.00227
Total = 290.80 Y-ecc = 0.02 eccentricity of shear As = 1,719 1,403 mm2

Ratio 60.14 Pu 6ey 6ex β= 1.60 ACI 11.11.2.1.a req'd n2 = 9.00 7.00 pcs
Formula q= 1± ±
Remark = Safe A B L αs = 30.00 ACI 11.11.2.1.b s (mm) = 121.23 121.23 mm
Overturning about y-y Corner Pressure 1 = - kPa b1 = 0.56 m
Moment = 3.98 Corner Pressure 2 = 185.75 kPa b2 = 0.55 m
Shear Force = 0.42 Corner Pressure 3 = 178.14 kPa bo = 1.66 m
Total = 3.98 Corner Pressure 4 = - kPa Critical Area = 0.31 mm2
Resisting about y-y Resultant = 81.74 kN
Footing Weight = 38.40 Check for Shear (Factored Load) γf = 0.60 x-x ACI 13.5.3.2
Soil Weight = 105.30 Wide Beam Shear γf = 0.60 y-y ACI 13.5.3.2
Bouyancy = (15.68) Shear Forces calculated as the volume of γv_x = 0.40 x-x ACI 11.11.7.1
Axial = 32.56 bearing pressures γv_y = 0.40 y-y ACI 11.11.7.1
Total = (15.68) Corner Pressure 1 = 0.540 MPa 𝐽ൗ 0.1162 N/mm2 x-x
𝑐1
Ratio = 40.38 Corner Pressure 2 = - MPa 0.1157 N/mm2 y-y
Remark = Safe Corner Pressure 3 = 0.400 MPa Vu = 0.50 ACI 11.11.5.2.a
Sliding Calculation Corner Pressure 4 = 0.340 MPa φVu = 1.71 ACI 11.11.5.2.b
kp = 2.78 Maximum Stress = 0.540 MPa Calculation of RC punching shear resistance
Pressure mid d = 85.00 without shear reinforcement (φVn = φVc)
Ultimate Shear Capacity
X-Passive Force = 68.00 Vc = φ0.166λ√f'c - ACI 22.5.5.1 Vc (N/mm2) = 1.74 ACI 11.11.2.1.a
Y-Passive Force = 68.00 Reduction factor φ = 0.750 Vc (N/mm2) = 2.86 ACI 11.11.2.1.b
Friction force = 130.86 λ= 1.000 Vc (N/mm ) =
2
1.50 ACI 11.11.2.1.c
Safe Factor x-x = 191.09 Vc = 0.580 MPa φVc (N/mm2) = 1.13
Safe Factor y-y = 260.37 Ratio = 0.931 Ratio = 0.441
Remark = Safe Remark = Safe for beam shear! Remark = Safe for punching shear!