Electrical

The document outlines the electrical specifications and requirements for a school building project, including compliance with the Philippine Electrical Code and local regulations. It specifies the electrical service power, wiring methods, materials, and installation details such as mounting heights for devices. Additionally, it mandates supervision by a registered electrical engineer for all electrical works.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views3 pages

Electrical

The document outlines the electrical specifications and requirements for a school building project, including compliance with the Philippine Electrical Code and local regulations. It specifies the electrical service power, wiring methods, materials, and installation details such as mounting heights for devices. Additionally, it mandates supervision by a registered electrical engineer for all electrical works.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

GENERAL NOTES :

1. ALL ELECTRICAL WORKS SHALL COMPLY WITH THESE PLANS AND SPECIFICATIONS. THE APPLICABLE
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC), THE RULES AND
REGULATIONS OF THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL
POWER COMPANY.

2. THE ELECTRICAL SERVICE POWER SHALL BE 1-PHASE,2-WIRE,230V AC, 60Hz.

3. WIRING METHOD SHALL BE AS FOLLOWS:


RIGID STEEL CONDUIT OR POLYVINYL CHLORIDE CONDUIT SCHEDULE 40 SHALL BE USED AS
SPECIFIED IN THE PLAN.
CANOPY
BASE
CEILING 4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN" UNLESS OTHERWISE
1 2 LEVEL INDICATED IN THE PLAN. THE MINIMUM SIZE WIRE FOR POWER AND LIGHTING CIRCUIT

TOTAL CONNECTED LOADS: 29149 VA


3 4 SPACE STEM

450
29149 5. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP TYPE.
I = (.75) = 95.05 AMPERES
L 230 (130A/95.05A)
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED FOR THE PARTICULAR
FLUORESCENT
GROUND TERMINAL BLOCK LIGHT FIXTURE LOCATION AND USAGE.

7. EQUIPMENT GROUNDING SYSTEM SHALL BE PROVIDED TO THE ELECTRICAL SYSTEM AS PER


PHILIPPINE ELECTRICAL CODE REQUIREMENT.

8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS:


a. LIGHT SWITCH - 1.20M ABOVE FINISH FLOOR
b. CONVENIENCE OUTLET - 0.3M ABOVE FINISH FLOOR

9. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A
FLUORESCENT LIGHT DULY REGISTERED ELECTRICAL ENGINEER.

2 PANELBOARD DIAGRAM 4 FIXTURE MOUNTING DETAIL


EE-1 NOT TO SCALE EE-1 NOT TO SCALE

LEGEND

- 1-18 WATTS COMPACT FLUORESCENT LAMP WITH MEDIUM BASE,


KEYLESS TYPE PORCELAIN RECEPTACLE
TOTAL CONNECTED LOADS: 9359 VA
I @ 85% DF
L 1 - 1 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE
9359 = 34.59 AMPERES
I = .85 (55A/34.59A)
L 230 2 - 2 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE WITH
CANOPY BASE AND STEM 1.5 FT (450mm) LENGTH SIMILAR TO AMCO
AP-1113-1.5 OR APPROVED EQUAL
2
- 2 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE
WF - WALL FAN OUTLET

- SINGLE POLE WALL SWITCH

- DUPLEX SWITCH, 2 SINGLE POLE SWITCHES ON ONE-GANG SWITCH


PLATE

- THREE WAY WALL SWITCH

- 2 THREE WAY WALL SWITCHES ON ONE-GANG SWITCH PLATE

- FAN CONTROL SWITCH


- RACEWAY CONDUIT CONCEALED IN CEILING

- RACEWAY CONDUIT CONCEALED UNDER FLOOR

- PANELBOARD, MARKED AS "LP"

- CKT. BREAKER, RATING AS INDICATED

- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE 15 AMPS,


240 VOLT
5000mm

WP - WEATHERPROOF DUPLEX CONVENIENCE OUTLET,


GROUNDING TYPE,15 AMPS, 240 VOLT
1800mm

TOTAL CONNECTED LOADS: 9895 VA


- CIRCUIT HOMERUN
I L@ 80% DF
9895
I L= (0.80) = 34.42 AMPERES (55A/34.42A) - ENCLOSED AIR CIRCUIT BREAKER
230
FA - FIRE ALARM CONTROL PANEL

F - FIRE ALARM STATION OUTLET

B - FIRE ALARM BELL

1 LOAD SCHEDULE 3 SINGLE LINE DIAGRAM M -

-
SERVICE METER

SERVICE ENTRANCE
EE-1 NOT TO SCALE EE-1 NOT TO SCALE
MDP
- MAIN DISTRIBUTION PANELBOARD

VARIOUS DPWH LOAD SCHEDULE,


(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET) PROPOSED PROJECTS FLUORESCENT LIGHT BOD
FIXTURE MOUNTING DETAIL, 45
NOTE : ADOPTED FROM DEPED STANDARD PLANS STANDARD THREE-STOREY PANEL BOARD DIAGRAM, EE-1
GILBERTO S. REYES RAUL C. ASIS ROGELIO L. SINGSON 47
SCHOOL BUILDING SINGLE LINE DIAGRAM,
OIC, BUILDINGS DIVISION DIRECTOR IV, BOD UNDERSECRETARY SECRETARY GENERAL NOTES AND LEGEND
( 15-CLASSROOMS )
1 2 3 4 5 6 7 8 9 10 11 12 13
54000
4500 9000 9000 9000 9000 9000 4500
955 960 960 1200 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 2100 1000 975
425 425
3950 (TYPICAL)

675
A
STO.

1400

1400
3150

3150
SHE
HE
1750

1750
CLASSROOM 6 CLASSROOM 7 CLASSROOM 8 CLASSROOM 9 CLASSROOM 10

7000
LANDING
LANDING
9500
3850

3850
B UP DN DN UP
2500

2500
C

2 TYP. 2ND & 3RD FLOOR POWER LAYOUT


EE-2 SCALE 1:100 M.

1 2 3 4 5 6 7 8 9 10 11 12 13
54000
4500 9000 9000 9000 9000 9000 4500
975 850 850 1825 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 1825 1400 1275
425 425

A
1400

1400
PWD 4300 PWD
3150

3150
SHE HE
1750

1750
CLASSROOM 1 CLASSROOM 2 CLASSROOM 3 CLASSROOM 4 CLASSROOM 5

7000
LANDING LANDING
9500
3850

3850
B UP UP
2500

2500
C
400

UP UP
1600

1200

1200
4300
8600

1700 3600 3600 1700

5300

1 GROUND FLOOR POWER LAYOUT


EE-2 SCALE 1:100 M.

VARIOUS DPWH
(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET) PROPOSED PROJECTS BOD 46
NOTE : ADOPTED FROM DEPED STANDARD PLANS STANDARD THREE-STOREY POWER LAYOUT EE-2
GILBERTO S. REYES RAUL C. ASIS ROGELIO L. SINGSON 47
SCHOOL BUILDING
OIC, BUILDINGS DIVISION DIRECTOR IV, BOD UNDERSECRETARY SECRETARY
( 15-CLASSROOMS )
1 2 3 4 5 6 7 8 9 10 11 12 13
54000
4500 9000 9000 9000 9000 9000 4500
955 960 960 1200 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 2100 1000 975
425 425
3950 (TYPICAL)

675
A
STO.

1400

1400
3150

3150
SHE
HE

1750

1750
CLASSROOM 6 CLASSROOM 7 CLASSROOM 8 CLASSROOM 9 CLASSROOM 10

7000
LANDING
LANDING
9500
3850

3850
B UP DN DN UP
2500

2500
C

2 TYP. 2ND & 3RD FLOOR LIGHTING LAYOUT


EE-3 SCALE 1:100 M.

1 2 3 4 5 6 7 8 9 10 11 12 13
54000
4500 9000 9000 9000 9000 9000 4500
975 850 850 1825 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 1825 1400 1275
425 425

A
1400

1400
PWD 4300 PWD
3150

3150
SHE HE
1750

1750
CLASSROOM 1 CLASSROOM 2 CLASSROOM 3 CLASSROOM 4 CLASSROOM 5

7000
LANDING LANDING
9500
3850

3850
B UP UP
2500

2500
C
400

UP UP
1600

1200

1200
4300
8600

1700 3600
3600 1700

5300

1 GROUND FLOOR LIGHTING LAYOUT


EE-3 SCALE 1:100 M.

VARIOUS DPWH
(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET) PROPOSED PROJECTS BOD 47
NOTE : ADOPTED FROM DEPED STANDARD PLANS STANDARD THREE-STOREY LIGHTING LAYOUT EE-3
GILBERTO S. REYES RAUL C. ASIS ROGELIO L. SINGSON 47
SCHOOL BUILDING
OIC, BUILDINGS DIVISION DIRECTOR IV, BOD UNDERSECRETARY SECRETARY
( 15-CLASSROOMS )