Baltimore Aircoil Company
Cooling Tower Selection Report
Version: 8.11.21 Asia
Product data correct as of: November 21, 2021
Project Name:
Selection Name:
Project State/Province:
Project Country/Region: Vietnam
Date: August 22, 2022
Model Information Design Conditions
Product Line: Smart Flow Rate: 34.53 l/s
Model: SMT-0713-04J Hot Water Temp.: 37.00 °C
Number of Units: 1 Cold Water Temp.: 32.00 °C
Fan Type: Standard Fan Wet Bulb Temp.: 28.30 °C
Fan Motor: (1) 5.50 = 5.50 kW/Unit Heat Rejection: 721 kW
Total Standard Fan Power: Full Speed, 5.50 BkW/Unit Tower Pumping Head: 27.84 kPa
Intake Option: None Tower Heat Rejection: 772 kW
Internal Option: None Reserve Capability: 7.03 %
Discharge Option: None
Thermal performance at design conditions and standard total fan motor power is certified by the Cooling Technology
Institute (CTI).
Engineering Data, per Unit
Unit Length: 2.22 m
Unit Width: 4.01 m
Unit Height: 2.84 m
Air Flow: 67,937 m³/h
Approximate Shipping Weight: 1,218 kg
Heaviest Section: 0 kg
Approximate Operating Weight: 3,139 kg
Heater kW Data (Optional)
0°F (-17.8°C) Ambient Heaters: (1) 8 kW
-20°F (-28.9°C) Ambient Heaters: (1) 10 kW
Minimum Distance Required for Single Unit:
(For multiple units, refer to Layout Guidelines)
From Solid Wall: 1.1 m
From 50% Open Wall: 1.1 m
Note: These unit weights and dimensions account for the selected fan type for the standard cataloged drive configuration,
but they do not account for other options/accessories. Please contact your local BAC sales representative for
weights and dimensions of units with other options/accessories.
Page 1/3
Baltimore Aircoil Company
Cooling Tower Selection Report
Version: 8.11.21 Asia
Product data correct as of: November 21, 2021
Project Name:
Selection Name:
Project State/Province:
Project Country/Region: Vietnam
Date: August 22, 2022
Model & Fan Motor Model Accessories
Product Line: Smart Intake Option: None
Model: SMT-0713-04J Internal Option: None
Number of Units: 1 Discharge Option: None
Fan Motor: (1) 5.50 = 5.50 kW/Unit Fan Type: Standard Fan
Total Standard Fan Power: Full Speed, 5.50 BkW/Unit
Design Conditions @ Standard Total Fan Motor Power per Unit (5.50 kW)
Thermal performance at design conditions and standard total fan motor power is certified by the Cooling Technology Institute (CTI).
Flow Rate: 34.53 l/s
Hot Water Temp.: 37.00 °C
Cold Water Temp.: 32.00 °C
Wet Bulb Temp.: 28.30 °C
Heat Rejection: 721 kW
Predicted Performance
Fan Motor Alternative = Full Speed, 5.50 BkW
Flow Rate = 34.53 l/s (100.00% of Design)
These performance curves are based on constant fan power.
Applies to Applies to
Warning Design OffDesign
Conditions Conditions
1. One or more selection parameters outside of CTI Certification limits. No Yes
Page 2/3
Baltimore Aircoil Company
Cooling Tower Selection Report
Version: 8.11.21 Asia
Product data correct as of: November 21, 2021
Project Name:
Selection Name:
Project State/Province:
Project Country/Region: Vietnam
Top
Date: August 22, 2022
Sound Pressure (dB)
Octave Distance
Model Information
Band 1.5 m 15 m
Product Line: Smart Intake Option: None
1 76 66
Model: SMT-0713-04J Internal Option: None
2 76 65
Number of Units: 1 Discharge Option: None
3 72 63
Fan Type: Standard Fan
4 69 57
Fan Motor: (1) 5.50 = 5.50 kW/Unit
5 65 53
Total Standard Fan Power: Full Speed, 5.50 BkW/Unit
6 64 52
Octave band and A-weighted sound pressure levels (Lp) are expressed in decibels (dB) 7 59 48
reference 0.0002 microbar. Sound power levels (Lw) are expressed in decibels (dB) 8 52 40
reference one picowatt. Octave band 1 has a center frequency of 63 Hertz. A-wgtd 72 60
Air Inlet End
Sound Pressure (dB) Sound Pressure (dB)
Octave Distance Octave Distance
Band 1.5 m 15 m Band 1.5 m 15 m
1 73 67 1 72 63
2 73 60 2 68 57
3 72 60 3 64 53
4 68 56 4 59 52
5 65 55 5 58 49
6 63 54 6 54 42
7 56 51 7 49 38
8 48 44 8 40 37
A-wgtd 71 61 A-wgtd 63 54
End Air Inlet
Sound Pressure (dB) Sound Pressure (dB)
Octave Distance Octave Distance
Band 1.5 m 15 m Band 1.5 m 15 m
1 72 63 1 73 67
2 68 57 2 73 60
3 64 53 3 72 60
4 59 52 4 68 56
5 58 49 5 65 55
Total Sound Power (dB)
6 54 42 6 63 54
Octave Center Frequency
7 49 38 Lw 7 56 51
Band (Hertz)
8 40 37 8 48 44
1 63 98
A-wgtd 63 54 A-wgtd 71 61
2 125 97
3 250 95
4 500 89
5 1000 85
6 2000 84
7 4000 80
8 8000 73
A-wgtd 92
Note: The use of frequency inverters (variable frequency drives) can increase sound levels.
Note: Sound data is free field data valid for unit installation without elevation, not taking into account any reflections.
Octave band values are shown for indicative purposes only. Values are obtained according to CTI ATC-128
(Test Code for Measurement of Sound From Water-Cooling Towers) for small towers.
Extra Notes: Sound data provided by CTI ATC-128 sound test code revision 2019