0 ratings 0% found this document useful (0 votes) 27 views 17 pages Pec Appendizfdfa
Appendix D provides wiring design examples that demonstrate the application of electrical code provisions for various dwelling units, including calculations for branch circuits, feeders, and service loads. It includes detailed examples for single-family homes of different sizes, illustrating load calculations, conductor selection, and overcurrent protection requirements. The appendix emphasizes the importance of considering future expansion and includes specific examples for various appliances and systems.
AI-enhanced title and description
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here .
Available Formats
Download as PDF or read online on Scribd
Carousel Previous Carousel Next
Save pec appendizfdfa For Later # APPENDIX D
Appendix D. Wiring Design Examples
Introduetion
(A) General. This part contains wiring design
examples to illustrate the application of some of the
provisions of this Code. The examples illustrated
herein, although not exhaustive, cover several scenarios
which are typically encountered by the practitioners.
‘The examples illustrate how to determine the size of
branch circuits, feeders and services. Typical Single-
Family and Multi-Family Dwelling units of different
demand load are presented considering the single phase
and three-phase service systems. Single and multiple
motor examples illustrate how to size the branch circuit
conductors and overload protection. Several overload
protection schemes are presented. Examples on system,
with fire pump to illustrate its special requirement and a
system with a voltage regulator are also included.
(B) Branch Cireuits Required. Forsmall single-family
dwelling unit having a floor area of not more than 50
square meters with load not exceeding 3 680 volt-
amperes, the code permits the use of only one circuit as
illustrated in Example DI [See Section 2.10.1.11(D)].
For the minimum number of branch circuit required,
see Section 2.10.1.11(A) to (C).
(©) Feeder or Service Load Calculation. Feeder
or service load calculation in the examples follows
the method provided in Part 2.20.2. The optional
calculations method of Part 2.20.3 is also illustrated
(See Example D4].
(D) Selection of Conductors. For conductor types and
sizes, refer to 0 through 2000 volt (V) ampacity tables
of Article 3.10 and Section 3.10.2.6 that pertains to
such tables. For the minimum size of service entrance
conductor, see Section 2.30.4.3. Conductor ampacities
given in these examples for copper wires are based
‘on ambient air temperature of 300C except specified
otherwise. In the examples given, conductors are
selected such that their ampacities are at least 125% of
the continuous current through the conductor. Voltage
drops, however, have not been considered in the
selection.
(©) Selection of Overcurrent Protection. Standard
ratings for fuses and inverse time circuit breakers are
listed in Section 2.40.1.6. Maximum rating or setting
of motor branch circuit short-circuit and ground-fault
protective devices are given in Table 4.30.14.6.
(F) Voltage. For uniform application of the provisions
of Articles 2.10, 2.15 and 2.20, 2 nominal voltage of
230 volts is used in computing the ampere load on the
conductor.
(G) Grounding. In conformance to the provisions of,
the code on grounding, illustrations herein show partial
grounding requirements. Feeder and circuit wires
indicated in the examples are for phase wires only.
For sizes of grounding conductors and electrodes, see
Tables 2.50.3.17 and 2.50.6.13 respectively.
(F) Allowance for Future Expansion. It is advisable
to use langer service conductors and the corresponding
overcurrent protective devices to accommodate future
loads depending on the anticipated expansion
EXAMPLE D1
Single Family Dwelling Unit, Up to 50 Square
Meters Floor Area with Load not Exceeding 3 680
Volt-Amperes.*
The dwelling has a floor area of 50 square meters with
typical small appliance loads for small residential units.
1.1 Total Load:
(A) General Lighting and Convenience Receptacle
Load: [See Table 2.20.2.3]
50 m? x 24 volt-amperes per m? 1200 volt-amperes,
(B) Typical Appliance Load:
One electric fiat iron
One television set
1200 volt-amperes
80 volt-amperes
One electric fan 75 volt-amperes
One radio 20 volt-amperes
Total Load 2575 volt-amperes
Total Computed Current: 2 575 VA +230 V =11
Amperes
1.2 Cireuit Requirement:
Use one 20-ampere 2-wire circuit. [See Sections
2.10.2.5(A) and 2.10.1.11(D)].
1.3 Service Entrance Conductors:
Use two 3.5 mm2 (2.0 mm dia.) TW copper wires
(minimum). [See Section 2.30.2.3(B) Exception].
1.4 Service Equipment:
Use one 30-ampere, IPST, 250-volt safety switeh with
one 20-ampere fuse; or use one 20-ampere trip, I-pole,
240-volt enclosed molded case circuit breaker (see
Section 2.40.2.3)
“Note: For loads exceeding 3680 vollamperes. see Section
2.10.1.11(A) to (C) and suceseding examples.APPENDIX D
1.5 Diagrams.
2.6m (2am tar wr OA)
Ltn ete ten, ——!
chara
‘Example D2
Single Family Dwelling Unit, Up to 150 Square
‘Meters Floor Area. (Not More than Six Circuits)
‘The dwelling has a floor area of 145 sq. m. It has the
typical household appliances including one 1.5-Hp
room air-conditioning unit.
2.1 Total Load:
(A) General Lighting and Convenience Receptacle
Load: [See Table 2.20.2.3]
‘Note: Table 220.1.3 includes the receptacle outlets of 20
amperes or less.
145 mm? x 24 volt-amperes per m? 3480 VA
‘The computed load is 3480/230 =15A
One branch circuit of 20-ampere would be
theoretically adequate, however for flexibility and to
allow for future needs provide two 20-ampere branch
cireuits for lighting and convenience outlets,
(B) Small Appliance Load:
[See Sections 2.10.1.11(C)(1) and 2.20.3.13(A)]
‘One 20-ampere @ 1500 VA = 1500 VA
Provide one 20-ampere small appliance
circuit
(© Laundry Circuit:
[See Sections 2.10.1.11(C)(2) and 2.20.3.13(B)]
One 20-ampere @ 1500 VA = 1500 VA
Provide one 20-ampere laundry circuit
Sub-Total 6480 VA,
Application of Demand Factors: (See Table 2.20.3.3)
First 3 000 volt-amperes @ 100% D.F. = 3000 VA
Remainder @ 35% DF.
(3.480 VAx 0.35)
(D) Other Load:
One 1.5-Hp room acu, 10A x 230 V
@ 100% DF.
Provide one 20-ampere room acu
circuit
Total Net Computed Load
2.2 Cireuit Requirement:
= 1218 VA
= 2300 VA
Use five 20-ampere 2-wire branch circuits,
1046
2.3 Service Entrance Conductors:
Total Full Load Current: (See Sections 4.30.2.4 and
4.40.1.7)
Use two 14 mm? TW wires.
Nate I: See Seetion 2203.11 forthe conductor and overeurtent
protection ampere rating.
Note 2: See Section 2.30.2.3(B) for minimum service entrance
conductor.
2.4 Service Equipment:
(A) Maximum Current Rating of Protective Device,
with: (See Section 4.30.42 and Table 4.30.4.2)
(1) Nontime Delay Fuse.
[3 000 VA + 1 218 VA + 300% (2 300 VA)] +
230 V = 48 Amperes
(2) Inverse Time Circuit Breaker.
[3 000 VA + 1 218 VA + 250% (2 300 VA)] +
230 V = 43 Amperes
(B) Service Equipment Rating.
Use one 60-ampere, IPST, 250-volt safety switch with
‘one 60-ampere fuse; or use one 50-ampere trip, I-pole,
240-volt molded case circuit breaker (see Section
2.40.1.6),
"Note: See Section 2.40.14 for protection of conductors
2.5 Diagrams:
a
| Mr one.
mn eee
) Emre
ee
erent 4
aa)
AO TeepeAPPENDIX D
Example D3
Single Family Dwelling Unit, Up to 150 Square
Meters Floor Area. (More than Six Circuits)
‘The dwelling has a floor area of 145 sq. m. It has the
typical household appliances including one 8-kW.
electrie range, two I-Hp room air-conditioning unit,
one 1.5-Hp room air-conditioning unit, and one 1-Hp
‘water pump.
3.1 Total Load:
(A) General Lighting and Convenience Receptacle
Load: [See Table 2.20.2.3]
Note: Table 2.20.13 inchades the receptacle outlets of 20
amperes or less
145 m? x 24 volt-amperes perm? = 3480 VA
‘The computed load is 3480/230 =15A,
One branch circuit of 20-ampere would be
theoretically adequate, however for flexibility and to
allow for future needs provide two 20-ampere branch
circuits for lighting and convenience outlets.
(B) Small Appliance Load:
[See Sections 2.10.1.11(C)(1) and 2.20.3.13(4)]
One 20-ampere @ 1500 VA = 1500 VA
Provide one 20-ampere small
appliance circuit.
(© Laundry Circuit:
[See Sections 2.10.1.11(C)(2) and 2.20.3.13(B)]
One 20-ampere @ 1500 VA = 1500 VA
Provide one 20-ampere laundry circuit
‘Sub-Total 6480 VA
Application of Demand Factors: (See Table 2.20.3.3)
First 3 000 volt-amperes @ 100% D.F. = 3000 VA
Remainder @ 35% DF.
(3.480 VAx 0.35)
(D) Other Load:
One 8-kW electric range @ 80% D-F.
(Sce Table 2.20.3.16)
Provide one 40-ampere electric range
circuit.
‘Two I-Hp room acu, 8A x 230 Vx2
@ 100%DF.
Provide two 20-ampere room acu
circuits.
One 1.5-Hp room acu, 10 Ax 230V
@ 100% DEF.
= 1218 VA
= 6400 VA
= 3680 VA
= 2300 VA
Provide one 20-ampere room acu
circuit
One 1-Hp water pump, 8 A x 230 V
‘i = 1840 VA.
@ 100% DF. see
Provide one 20-ampere water pump
circuit
Total Net Computed Load = 18438 VA
3.2 Circuit Requirement:
Use eight 20-ampere 2-wire branch circuits and one
40-ampere 2-wire branch circuit.
3.3 Service Entrance Conductors:
Total Full Load Current: (See Sections 4.30.2.4 and
4.40.1.7)
[18438 VA + 25% (2 300 VA)] +230 V = 83 Amperes
Use two 38 mm? THW wires.
3.3 Service Entrance Conductors:
Total Full Load Current: (See Sections 4.30.2.4 and
4.40.1.7)
[18438 VA + 25% (2 300 VA)] + 230 V = 83 Amperes
Use two 38 mm? THW wires.
[Note I: See Section 2.40.1.4 forthe conductor and overcurrent
protection ampere rating,
Note 2: See Section 2.30.23 for minimum service entrance
conductor
3.4 Service Equipment:
(A) Maximum Current Rating of Protective Device,
with: (See Section 4.30.4.2 and Table 4.30.4.2)
(1) Nontime Delay Fuse
[3 000 VA + 1 218 VA + 6 400 VA +3 680 VA
+ 300% (2 300 VA) + 1 840 VA] +230 V= 100
Amperes
(2) Inverse Time Circuit Breaker.
[3.000 VA+ 1 218 VA +6 400 VA+ 3 680 VA
“+ 250% (2.300 VA) + 1 840 VA] + 230 V= 95
Amperes
(B) Service Equipment Rating,
Use one 200-ampere, IPST, 250-volt safety switch
with one 125-ampere fuse (renewable); ot (b) use one
125-ampere trip, I-pole, 240-volt molded case circuit
breaker (see Section 2.40.1. 6).
1047APPENDIX D
3.5 Diagrams:
ee a
2 nna
eae” $F
serene omen
Example D4
Single Family Dwelling Unit, Up to 150 Square
Meters Floor Area, Optional Calculation.
Same conditions as Example D3
4.1 Air Conditioning Load: (See Section 2.20.4.3)
Two I-Hp room air-conditioning unit,
8Ax230Vx2 Ale
One 1.5-Hp room air-conditioning unit, _
10Ax230Vx1 ee
4.2 Other Loads:
General lighting and convenience
receptacle load, = 3480 VA
145 mx 24 VA?
One 20-ampere small appliance circuit _
@ 1500 volt-amperes PEsaNE
One 20-ampere laundry circuit a
@ 1500 volt-amperes oe
One 8-kW electric range = 8000 VA,
One 1I-Hp water pump, vs
8Ax230V ae
Total Other Loads 1620 VA
Application of Demand Factors: [See Section
2.20.4.3(C)]
First 10 000 volt-amperes @ 100% D.F. 10000 VA
Remainder @ 40% D.F.
(6 320 VAx 0.40)
Total Net Computed Load
4.3 Circuit Requirement:
2528 VA
18508 VA
Use eight 20-ampere 2-wire branch circuits and one
40-ampere 2-wire branch circuit
1048
4.4 Service Entrance Conductors:
Total Full Load Current:
18508 volt-amperes + 230 V = 80 Amperes
Use two 38 mm2 THW wires.
[Note 1: See Section 2.40.14 for the conductor and overcurrent
protection ampere rating,
Note 2: See Section 230-23 for minimum service entrance
conductor
4.5 Service Equipment:
(A) Maximum Current Rating of Protective Device,
: (See Section 4.30.4.2 and Table 4.30.4.2)
() Nontime Delay Fuse.
[3680 VA + 300% (2300 VA) + 10000 VA +2
528 VA] + 230 V = 100 Amperes
(2) Inverse Time Circuit Breaker.
[3 680 VA + 250% (2 300 VA) + 10000 VA +2
528 VA] +230 V = 95 Amperes
(B) Service Equipment Rating
Use one 200-ampere, IPST, 250-volt safety switch
with one 125-ampere fuse (renewable); or use one
125-ampere trip, 1-pole, 240-volt molded case circuit
breaker (see Section 2.40.1. 6).
4.6 Diagrams:
Same as Example D3.
Example DS
Single Family Dwelling Unit, More than 150 Square
Meters Floor Area, 230 Volts Single Phase Service
‘The dwelling hasa floor area of 250 square meters. [thas
the typical household appliances including two 6-KVA
package type ait-conditioning units, six 1.5-Hp room
air-condition units, two 4-kW wall mounted ovens, one
1.5-KW microwave oven, one 12-KW electric range,
‘one 8-kW clectric range, one 5-kW clothes dryer, four
‘S-kW water heaters, and one I.5-Hp water pump.
5.1 Air Conditioning Load: (See Section 2.20,3.23)
Two 6-KVA package type air-
conditioning units aes
Provide two 70-ampere package type
acu circuits.
Six 2-Hp room air-conditioning units, _ 19599 ya
14 Ax 230Vx6
Provide six 30-ampere room acu
circuits.APPENDIX D
32 Lighting and Convenience Receptacle Load:
(See Section 2.20.3.23)
250 m? x 24 VA/m?
Provide at least two 20-ampere lighting
and convenience receptacle circuits.
"Note: Actual computed lighting load shall be used ifthe total
vvolt-ampere exceeds that obtained ftom the 24 vol-amperes
per square meter method,
= 6000 VA
5.3 Cooking Load: (See Section 2.20.3.16)
‘Two 4-kW wall mounted ovens,
4.000 VA x2
Provide two 30-ampere wall mounted
coven circuits
One 8-kW electric range
Provide one 40-ampere electric range
circuit
= 8000 VA
= 8000 VA
Subtotal Load 16000 VA
Application of Demand Factor: (See Table 2.20.3.16
Column C)
16000 volt-amperes x 0.55
One 1.5 kW microwave oven
(See Table 2.20.3.16 Column B)
Provide one 20-ampere microwave oven
circuit
One 12-KW electric range
(See Table 2.20.3.16 Column A)
Provide one 60-ampere clectric range
circuit
= 8800 VA
= 1200 VA
= 8000 VA
Total Load 18000 VA
5.4 Other Loads:
‘One 20-ampere small appliance circuit
@ 1 500 volt-amperes
[See Section 2.20.1.11(C\(1)]
Provide one 20-ampere small
appliance circuit
= 15000 VA
One laundry washing machine
@ 1 500 volt-amperes
[See Section 2.20.1.11(C)Q)]
Provide one 20-ampere laundry circuit.
One 5-kW clothes dryer
Provide one 30-ampere clothes dryer
circuit,
Four 5-kW water heaters
Provide four 30-ampere water heater
circuits
One 1.5-Hp water pump, 104x230 V_ = 2300 VA
= 1500 VA
= 5000 VA
= 20000 VA
Provide one 20-ampere water pump
circuit
Total Other Loads, 31500 VA
Application of Demand Factor: (See Section
2.20,3.23)
31500 volt-amperes x 0.40 12120 VA
Total Net Computed Load (66240 VA
5.5 Circuit Requirement:
Use six 20-ampere 2-wire branch circuits, thirteen
30-ampere 2-wire branch circuits, one 40-ampere
2-wire branch circuit, one 60-ampere 2-wire branch
circuit and two 70-ampere 2-wire branch circuits.
5.6 Service Entrance Conductor
‘Total Full Load Current: (See Sections 4.30.2.4 and
4.40.1.7)
[67 440 VA + 25% (6 000 VA)] +230 V = 300 Amperes
Use two 325 mm? THW wires.
Note: See Section 2.40.1.4 for conductor and overcurrent
protection ampere rating,
5.7 Service Equipment:
(A) Maximum Current Rating of Protective Device,
with: (See Section 4,30.4.2 and Table 4.30.4.2)
(1) Nontime Delay Fuse.
[300% (6000 VA) + 6000 VA + 19320 VA + 6000
VA + 18000 VA + 12 120 VA] + 230 V = 345
Amperes
(2) Inverse Time Cireuit Breaker.
[250% (6000 VA) + 6000 VA + 19 320 VA +6000
VA + 18 000 VA + 12 120 VA] = 230 V = 332
Amperes
(B) Service Equipment Rating.
Use one 400-ampere, IPST, 250-volt safety switch
with one 400-ampere fuse; or use one 400-ampere
trip, L-pole, 240-volt molded case circuit breaker (see
Section 2.40.1.6)..
Example D6
Single Family Dwelling Unit, More than 150 Square
Meters Floor Area,400/230 Volts Three-Phase
4-Wire Service
Same conditions as Example DS except that the two
6-KVA package type air-conditioning units require
3-phase supply.
1049APPENDIX D
6.1 Branch Cireuit Arrangement:
‘A 3-phase fusible or circuit breaker type panelboard
shall be provided for balanced distribution of single
phase loads.
6.2 Circuit Requirement:
Use two 40-ampere 3-wire branch circuits, six
20-ampere 2-wire branch circuits, thirteen 30-ampere
2-wire branch circuit, one 40-ampere 2-wire branch
circuit, and one 60-ampere 2-wire branch circuit.
6.3 Service Entrance Conductors:
Total Full Load Current: (See Sections 4.30.2.4 and
4.40.1.7)
[66 190 VA + 25% (6 000 VA)] + (400 V)(1.732) = 98,
Amperes.
Use three 50 mm2 + one 50 mm 2 (neutral) THW
wires.
6.4 Service Equipment:
(A) Maximum Current Rating of Protective Device,
with: (See Section 4.30.4.2 and Table 4.30.4.2)
(D) Nontime Delay Fuse.
[300% (6000 VA) + 6 000 VA + 19 320 VA +
6000 VA + 16 750 VA + 12 120 VA] = (400 V)
(1.732) = 112 Amperes
(2) Inverse Time Circuit Breaker.
[250% (6 000 VA) + 6 000 VA + 19 320 VA +
{6 000 VA + 16 750 VA-+ 12 120 VA] + (400 V)
(1.732) = 109 Amperes
(B) Service Equipment Rating.
Use one 200-ampere, 3-pole, 415-volt safety switch
with three 125-ampere fuse (renewable); or use one
125-ampere trip, 3-pole, 415-volt molded case circuit
breaker.
Example D7
Muttifamily Dwelling Unit, 230 Volts Single Phase
Service
Multifamily dwelling having 12 dwelling units with
individual feeder to each dwelling unit. Each dwelling
unit has floor area of 90 square meters and with typical
household appliances including one 8-kW electric range
and one I-Hp room air-conditioning unit.
7.1 Total Load for Each Dwelling Unit:
(A) General Lighting and Convenience Receptacle
Load: [See Table 2.20.2.3]
1050
‘Note: Table 2.20.13 includes the receptacle outlets of
20-ampere or less
90m? x 24 VA/m?
Provide two 20-ampere lighting and
convenience receptacle circuits
(B) Small Appliance Load: [See Sections
2.10.1.11(C)(1) and 2.20.3.13(A)]
One 20-ampere @ 1500 volt-amperes = 1500 VA
Provide one 20-ampere small appliance
circuit
(©) Laundry Circuit Load: [See Sections 2.10.1.11(C)
(2) and 2.20.3.13(B)]
‘One 20-ampere @ 1500 volt-amperes = 1500 VA
Provide one 20-ampere laundry circuit.
Subtotal 5160 VA
Application of Demand Factors: (See Table 2.20.3.3)
First 3 000 volt-amperes @ 100% DF. = 3000 VA
Remainder @ 35% D.F.
(2160 VA x 0.35)
{D) Other Loads:
One 8-KW electric range @ 80% DF.
(Sce Table 2.20.3.16)
Provide one 40-ampere electric range
circuit.
One 1-Hp room acu, 8 Ax 230 V
@ 100% DF.
Provide one 20-ampere room acu
circuit
Total Net Computed Load
(For Each Dwelling Unit)
= 2160 VA
= 756 VA
= 6400 VA
= 1840 VA
= 11996 VA,
7.2 Circuit Requirement for Each Dwelling Unit:
Use five 20-ampere 2-wire branch circuits and one
40-ampere 2-wire branch circuit.
73 Service Feeder Conductors for Each Dwelling
Unit:
Total Full Load Current: (See Sections 4.30.2.4 and
4.40.1.7)
[11996 VA + 25% (1. 840 VA)] +230 V. = 54 Amperes
Use two 22 mm? THW wires.
Note: See Section .202.3 forthe conduetor and overeurent
protection ampere rating.
7.4 Service Equipment for Each Dwelling Unit:
(A) Maximum Current Rating of Protective Device,
with: (See Section 4.30.4,2 and Table 4.30.4.2)APPENDIX D
(@) Nontime Delay Fuse.
[3000 VA + 756 VA + 6 400 VA+ 300% (1 840
‘VA)] +230 V = 68 Amperes
ircuit Breaker.
(2) Inverse Time
[3000 VA + 756 VA + 6400 VA + 250% (1840
‘VA)] +230 V = 64 Amperes
(B) Service Equipment Rating.
Use one 100-ampere, IPST, 250-volt safety switch
with one 100-ampere fuse; or use one 100-ampere
trip, I-pole, 240-volt molded case circuit breaker (see
Section 2.40.16).
75 Total Load for 12 Dwelling Units: [See Section
2.20.4.5(A)]
General lighting and convenience
receptacle load, 2160 VA x 12 ee
Small appliance load, 1500 VAx 12 = 18000 VA
Laundry circuit load, 1500 VAx 12 = 18000 VA
One $4W eleticrnge, 00 VA 55099 vq
One 1-Hp room acu, 1840 VAx 12 _= 22080 VA
‘Total Computed Load 180000 VA
Application of Demand Factors: (See Table 2.20.4.5)
180000 volt-amperes x 0.41 = 73800 VA.
7.6 Main Service Entrance Conductors:
‘Total Full Load Current:
73800 volt-amperes + 230 V= 321 Amperes
Use two 325 mm? or two sets of two 100 mm? THW
wires.
Note: See Section 3.10.14 for conductor in parallel
7.7 Main Service Equipment:
(A) Maximum Current Rating.
73800 volt-amperes + 230 V = 321 Amperes
(B) Service Equipment Rating,
(1) Use one 600-ampere, PST, 250-volt safety switch
with one 500-ampere fuse; or
2) Use one 500-ampere trip. 1-pole, 240-volt
enolosed molded case circuit breaker (see Section
2.40.2.3),
‘Example D8
Multifamily Dwelling Unit, 400/230 Volts Three-
Phase 4-Wire Service
Same conditions as Example D7 except that it has 40
dwelling units and 3-phase 4-wire supply.
8.1 Total Load for Each Dwelling Unit:
Total Net Computed Load:
(Based on Example D7)
8.2 Circuit Requirement for Each Dwelling Unit:
= 11996 VA
Use five 20-ampere 2-wire branch circuits and one
40-ampere 2-wire branch circuit.
8.3 Service Feeder Conductors for Each Dwelling
Unit:
Total Full Load Current: (See Sections 4.30.2.4 and
4.40.17)
[11996 VA + 25% (1 840 VA)] +230 V = 54 Amperes
Use two 22 mm? THW wires.
8.4 Service Equipment for Each Dwelling Unit:
(A) Maximum Current Rating of Protective Device,
with:
(See Section 4.30.4.2 and Table 4.30.4.2)
(1) Nontime Delay Fuse.
[3000 VA +756 VA.+ 6400 VA + 300% (1840
‘VA)] + 230 V = 68 Amperes
(2) Inverse Time Cireuit Breaker.
[3000 VA + 756 VA + 6400 VA + 250% (1840
‘VA)] + 230 V= 64 Amperes
(B) Service Equipment Rating.
‘Use one 100-ampere, IPST, 250-volt safety switch
with one 100-ampere fuse, or use one 100-ampere trip,
L-pole, 240-volt molded case circuit breaker.
8.5 Total Load for 40 Dwelling Units: [See Section
2.20.4.5(A)]
General lighting load,
2160 VAx 40 peers
Small appliance load, é
1500 VA x 40 haa
Laundry circuit load, 3
1500 VA x 40 cna
One &-KW electric range, =320000 VA
8000 VA x 40APPENDIX D
One 1-Hp room acu,
1840 VA x 40 ASU
Total Computed Load 00000 VA
Application of Demand Factor: (See Table 2.20.4.5)
600000 volt-amperes x 0.28 = 168000 VA.
8.6 Main Service Entrance Conductors:
Total Full Load Current:
168 000 volt-amperes + (400 V)(1.732) = 242 Amperes
Use three 200 mm? + one 200 mm* (neutral) THW
wires.
Note: See Section 3.10.14 for conductors in parallel
8.7 Main Service Equipment:
(A) Total Current:
168 000 volt-amperes + (400 V)(1.732) = 242 Amperes
(B) Service Equipment Rating.
Use one 400-ampere, 3-pole, 415-volt safety switch
with three 300-ampere fuses, or use one 250-ampere
trip, 3-pole, 415-volt molded case circuit breaker.
Example D9
Motors, Motor Circuits, and Controllers, Single
Motor
A three-phase, 460 volts, 60 Hz, 25-Hp squirrel cage
induction motor is to be connected for full voltage
starting, It has a full load current of 31.6 amperes, a
service factor of 1.15 and a Code Letter "F" in its
nameplate, The ambient temperature of the place of
installation is 40°C.
9.1 Total Load: (See Table 4.30.14.4)
Full load current of 3-phase, 25-Hp motor ~ 34 Amperes
"Note:The ful load current value used to determine the ampacity
‘of conductors for motors shall be based on Table 4.30.14
9.2 Branch Circuit Conductors: [See Section
4.30.2.2(A)]
125% of Full Load Current:
34 Amperes x 1.25 = 42 Amperes
Use three 14 mm? THW wires
Note: Ampacity of 14 mm2 THW at 400C ambient is 65
Amperes x 0.88 = 57.2 Amperes. See Table 3.10.1.16 for
ampacity correction factors.
1052
9.3 Motor and Branch Circuit Overload Protection:
[See Section 4.30,3.2(A)]
125% of Rated Full Load Current:
31.6 Amperes x 1.25 =39 Amperes(Maximum)
9.4 Branch Circuit Short-Cireuit and Ground Fault
Protection: (See Section 4.30.4.2)
‘The branch circuit maybe protected by any of the four
common types of protective devices, namely: Nontime
delay fuse, Time delay fuse, Instantaneous trip breaker
and Inverse time breaker.
For the protection of a squirrel cage breaker with Code
Letter "F" (See Table 4.30.4.2) the protective device
can be any of the following:
(A) Nontime Delay (NTD) Fuses: (See Table 4.30.4.2)
300% of Full Load Current:
34 Amperes x 3 = 102 Amperes
Use 100 Amperes NTD fuse,
Note: Ifthe 100-A fase isnot suficient forthe starting current
of the motor, see Section 430/4.2(C)(1) Exception No. 2a
(B) Time Delay (TD) Fuses: (See Table 4.30.4.2)
175% of Full Load Current:
34 Amperes x 1.75 = 59 Amperes
Use 60 Amperes TD fuse (See Section 4.30.4.2(C)
Exception No. 2b),
(©) Instantaneous Trip (IT) Breaker: (See Table
430.42)
800% of Full Load Current:
34 Amperes x 8 = 272 Amperes
Use 300 Amperes IT circuit breaker (See Section
4,30.4.2(C) Exception No. 1).
(D) Inverse Time Delay (ITD) Breaker: (See Table
4,30.4.2)
250% of Full Load Current:
34 Amperes x 2.5 = 85 Amperes
Use 100 Amperes ITD circuit breaker.APPENDIX D
9.5 Diagram: ‘
Pee alice iil
L
Example D10
Motors, Motor Circuits, and Controllers, Multiple
Motors
Three squirrel cage induction motors: 25-Hp, 20-Hp
and 10-Hp, all rated at 460 volts, 3-phase, 60 Hz are to
be served by a feeder circuit. Ambient temperature does
not exceed 30°C,
10.1 Total Loads (See Table 430.144) 4
‘One 3-phase, 460 volts, 25-Hp
‘motor ae ee
One 3-phase, 460 volts, 20-Hp 57 amperes
motor
One 3-phase, 460 volts, 10-HP 14 arnperes
motor
25% of Largest Motor (See Section 4.30.2.4)
34 Amperes x 0.25) =8.5 Amperes
Net Computed Current 83.5 Amperes
10.2 Feeder Conductors: [See Table 3.10.2.6(8)(16)]
Use three 22 mm? THW wires.
103 Feeder
4.30.4.3(C)]
Largest Protective Device:
it Protection: [See Section
‘The 25-Hp motor being the largest motor, has the largest
protective device. For the values of the different device,
see Example D9.
(A) Nontime Delay (NTD) Fuses:
Largest NTD fuse
Full load current of 20-Hp motor
(00 Amperes:
27 Amperes
Full load current of 10-Hp motor
Total Computed Current
Use 150 Amperes NTD fuse.
(B) Time Delay (TD) Fuses:
Largest TD fuse
Full load current of 20-Hp motor
Full load current of 10-Hp motor 4 Amperes
= 14 Amperes
41 Amperes
0 Amperes
27 Amperes
Total Computed Current = 101 Amperes
Use 100 Amperes TD fuse.
(©) Inverse Time Delay (ITD) Breaker:
Largest ITD fuse =90 Amperes
Full load current of 20-Hp motor
Full load current of 10-Hp motor
Total Computed Current
Use 125 Amperes ITD fuse.
Note: Only fuses andlor inverse time cireuit breakers ate
allowed for this type of installation. [See Sestion 430.4.3(C)
Oh
104 Diagram:
31 Amperes
Bip Ny tp
Note 1: For single motor taps, refer to Section 4.30.4.3(D),
Note 2; (On Fire Pump Application) For installations including
fire pumps, See Sections 2 30,6.3(A) Exception, 230.6.13(6),
2,30,7.1(A) Exception No, 4, and 2.30.7.5 Exception No. 4
Example Dit
‘Voltage Regulators, Single Phase, 60 Hz, 165-280
Volts Input, 230 Volts Output VR
Determine the size of input feeder wires and overcurrent
protection fora SKVA, l-phase, 60 hertz, 165-280 volts
input, 230 volts output automatic voltage regulator.
1, = SKVAx 1000
z 165V
= 30 Amperes
Use 8.0 mm? (3.2 mm dia.) THW for feeder wire and
60-ampere fuse or 40-ampere trip molded case circuit
breaker.
1053APPENDIX D
‘Example DI2
Voltage Regulators, Three-Phase, 60 Hz, 350-530
‘Volts Input, 230 Volts Output VR.)
Determine the size of input feeder wires and overeurfent
protection fora 30KVA, 3-phase, 60 hertz, 350-530 volts
qaget 230 vali GR ince volnage Regular
30KVA x 1000
350 Vx 1.732
= 50 Amperes
Use 14 may THW for feeder wire and 60-ampere fase
cr 60-ampere trip molded case circuit breaker.
Example D13
Available Short Circuit Current
Calculate the maximum symmetrical fault current that
would be supplied through a single phase distribution
transformer rated at 100 kVA, 230 volts if its impedance
is 2.5%. Assuming that the primary source is of infinite
capacity and neglecting all other impedances.
transformer volt-amperes
se" Secondary voltage
100000
= + 34.1
Te a0 34.78
pee I (fault current,
‘etsy Z symmetrical)
434.78
= os 717391 amperes
Example D14
Simplified Fault Current Calculation
‘A small factory is to be supplied at 230 volts, 3 ph,
60 hz by a bank of the distribution transformers rated
at 100 KVA each with a bank impedance of 5%, This
bank is connected to 34.5 kV Meralco line with a short
circuit capacity of 1000 MVA. The power system is
shown below.
Determine the maximum symmetrical fault currents
at points "a", "b" and "c" using the per-unit method,
Determine the minimum symmetrical interrupting
ratings of molded case circuit breakers A, B, and C.
(Note, thar for this example other impedance have been
neglected. However, for actual design, consider all impedances
of lines, bsbars and other line devices.)
Procedure using the Per-Unit Method:
1. Draw system diagram
2. Draw impedance diagram
3, Obtain the Source Short Circuit level at the vicinity
from the utility company. (1000000 kVA for Metro
1054
puZ,,=~ motor kVA/motor =
Faltespciy 1 00 MYA,
nowa
Ey
ees
3n2s0mm@ yi] «|
iw sere
ont fod m
(00 one
aI
ronvancon @
Manila grid)
4, Select kVA base. (Any convenient value may do but.
preferably the transformer capacity. Use 300 kVA)
5, Compute PU value of utility source, (pu Zs)
KVA base 300
ea iy SCKVA 1090000. "0? P™
6. Compute PU for transformer, (pu Z,)
= lrpedancein percent __5.(BivEN) _ 95 4,
100 100
7. Compute PU value for feeder lines,
a. From Handbooks, obtain impedance of
lines comesponding to size, type and number
of conductors, in steel conduits or nonferrous
conduits, ete.
[For 3-250 mm? cable in steel conduit, 100 ft (30.4
1m) long, Z = 0.00546 ohm]
b. Convert cable impedance from "ohm" to “pu”,
(puzZ,)
z= —chm impedance _KVA base
ae KV square +1000
0.00546 300,
i x SO — -0.031 pu
(0.230 x 0.230 1000 x
8, Compute PU value for motor contribution, (pu
2)
EVA base 300
rooo2se “975 P"
impedance
Average induction motor impedance per IEEE Std
141
9. Compute for short circuit currents at designated
points.
9.1 Draw impedance diagram,
9.2 Draw simplified diagram with values.APPENDIX D
9.3 Combine impedance (pu Ze) up to the fault
94 Compute short circuit current, I,
(symmetrical)
_ __ Pu voltage
Nera) =
base kVA x 1000
paz, _1.732.x base voltage
9.5 Ifasymmetrical values of short circuit currents
are needed, multiply the symmetrical values by
125.
10. Computations at Fault Points:
10.1 Fault at "a" (The fault current to be cleared
by Breaker A comes only from the transformer.
There are no contributions from the motors.)
a. Single line diagram
Unity bus, 1 000
sod
4. Fault current at "a"
2 E - base VA.
eam) Z, 1,732 x base voltage
10 300000
00503 1.732 x230
14972 amperes RMS
Say 15 000 A RMS symmetrical
Cireuit breaker “A” should be rated not less then 15000
AIC symmetrical
10,2 Fault at "b" (The fault current comes from
the transformer plus the contribution from the
motors. The total current is to be cleared by
Breaker B.)
a. Single line diagram
Sasa” paar * “O30
isms 240 4 Bae
aa
1085APPENDIX D
. Simplified diagram_
Ze= 00803
pees:
d. Fault current at "b"
10 300000
o 0.0403, 1.732 x 230
= 18687 amperes RMS
Sey 19 000 A RMS symmetrical
Circuit breaker “B” should be rated not less than 19000)
AIC symmetrical
10.3 Faultat"c" (The fault currents will eome from
the transformer and the two motors. However,
the final fault current is reduced because of the
impedance of the line to fault "
ingle line diagram
b. Impedance diagram
oe i fH
Cri ngtces
. Simplified diagram
Ze = 0.0403,
28= 0031
ve
Zt= 0.0713
. Fault current at "c"
te 10 300000
en 07a 1.732 x 230
= 1100 amperes RMS
Say 11 000 A RMS symmetrical
Cireuit breaker “C” should be rated not less than 11000
AIC symmetricalAPPENDIX D
Example DIS
Voltage Drop Calculation
A3 ph, 230-volt, 60 Hz electric motor draws a full load
current of 20 amperes at 80% load power factor. It is
connected to a panelboard 30.5 m away with 3x 5.5
mm2 THWN copper conductors in steel conduit. The
panelboard which draws a total current of 295 amperes
from a 3 ph, 460-230-volt transformer bank is. 15.2 m
away and is supplied by 3 x 250 mm? THWN copper
conductors in steel conduit
Calculate: (a) the voltage drop at the panelboard; and
(b) the percent voltage drop at the terminals of the
motor assuming that the voltage at the transformer
bushing is 230 volts and neglecting the effect of voltage
phase shift due to load power factor.
Basic Formulas:
(A) Voltage drop (VD)=KDI x¥R7FX? Eq.(1)
where I= line current, amperes
D = Distance of the device from the
source
k= Constant (2 for I-phase and 1.732
for 3-phase)
R= line ac resistance, ohms
X = line reactance at 60 hz, ohms
(B)Pereent __(VDyy+VD,)x100% 54 (9)
voltage drop Voltage supply (V,) a
From Table 10.1.1.9 Altemating Current Resistance
and Reactance For 600V Cables
(0.029 ohm/305m (75°C) 250 ma? eable in
steel conduit
1.2 ohms30Smn (75°C) 5.5 mim? cable in
steel conduit
0.048 ohav30Sm (60 Hz) 250 mn cable in
steel conduit
0.063 obn/305m (60 Hz) 5.5 mum? cable in
steel conduit
R (3-ph) =
X (3-ph)
Hence:
Solving for (a) voltage drop at panelboard, Use Equation
(1) multiplied by length ratio:
() VD, = 1.732(295)V0.029? + 0.048? x 15.2/305,
= 1.428 volt (Answer)
‘Voltage at panelboard: V = 230 - 1.428 = 228.572 volts
(b) Sotving for percent voltage drop at motor terminals
VD,, = 1.732(20)V1.2? + 0,063 x 30.5/305
.163 volts (Voltage drop at motor terminals)
Add the voltage drops at motor terminals and panel
board and divided by 230-volt:
Percent 1.428 +4.163
voltage drop ~ 230
= 2.43 % (Answer) - total voltage drop at motor terminals
from the voltage supply (transformer secondary) from Eq,
2)
x 100
Example D16
Feeder Ampacity Determination for Generator
Field Control
[see Sections 2.20.2.1, 4.30.2.4, 4.30.2.4 Exception
No. 1, 6.20.2.3, 6.20.24, 6.20.7.1, and Tables
4.30.2.2(E) and 6.20.2.4]
Determine the conductor ampacity for a 460-V 3-phase,
60-Hz ac feeder supplying a group of six elevators.
The 460-V ac drive motor nameplate rating of the
largest MG set for one elevator is 40 hp and 52 A,
and the remaining elevators each have a 30-hp, 40-A,
ac drive motor rating for their MG sets. In addition
to a motor controller, each elevator has a separate
motion/operation controller rated 10 A continuous to
operate microprocessors, relays, power supplies, and
the elevator car door operator. The MG sets are rated
continuous.
Conduetor Ampacity
Conductor ampacity is determined as follows:
(A) Per Sections 6.20.2.3(D) and 6.20.7.1(B)(1), use
Table 4.30.2.2(B), for intermittent duty (elevators).
For intermittent duty using a continuous rated motor,
the percentage of nameplate current rating to be used
is 140%.
(B) For the 30-hp ac drive motor,
140% x 40A=S6A.
For the 40-hp ac drive motor,
140% x52A=73A,
(©) The total conductor ampacity is the sum of all the
‘motor currents,
(1 motor x 73 A) + (5 motors x 56 A) = 353 A
(D) Per Section 6.20.24 and Table 6202.4, the
conductor (feeder) ampacity would be permitted to be
reduced by the use of a demand factor. Constant loads
are not included (see Section 6.20.2.4, FPN). For six
elevators, the demand factor is 0.79.
Therefore, feeder diverse ampacity = 0.79 X 353 A
279 A.
(©) Per Sections 4.30.2.4 and 2.15.13
Controller continuous current = 125% x 10 A= 12.5 A
1057APPENDIX D
Figure D16
(E) The total feeder ampacity is the sum of the diverse
current and all the controller continuous current.
T7279 A+ (6 elevators x 12.5. A) = 354A
(G) This ampacity would be permitted to be used to
select the wire size. See Figure D16.
Example D17
Feeder Ampacity Determination for Adjustable
Speed Drive Control
[see Sections 2.15.1.3, 4.30.2.4, 4,30.2.4 Exception No,
2, 6.20.23, 6.20.2.4, 6.20.7.1, and Tables 4.30.2.2(E),
and 6.20.24]
Determine the conductor ampacity for a 460-V, 3-phase,
60-Hz ac feeder supplying a group of six identical
elevators. The system is adjustable-speed SCR de drive.
The power transformers are external to the drive (motor
controller) cabinet. Each elevator has a separate motion/
operation controller connected to the load side of the
main line disconnect switch rated 10 A continuous to
= 95KVAx 1000
© BX 460V x 0.90 eff.
S 133A
‘operate microprocessors, relays, power supplies, and
the elevator car door operator. Each transformer is rated
95 KVA with an efficiency of 90%.
Conductor Ampacity. Conductor ampacity is
determined as follows:
(A) Calculate the nameplate rating of the transformer:
(B) Per Section 6.20.2.3(D), for six elevators, the total
conductor ampacity is the sum of all the currents.
6 elevators X 133 A= 798A
(©) Per Section 6.20.2.4 and Table 6.20.2.4, the
conductor (feeder) ampacity would be permitted to be
1058
reduced by the use of a demand factor. Constant loads
are not included (see Section 6.20.2.3, FPN No. 2). For
six elevators, the demand factor is 0.79.
Therefore, feeder diverse ampacity = 0.79 x 798 A
= 630A
(D) Per Sections 4.30.2.4 and 2.15.1.3, the controller
continuous current = 125% x 10A= 12.5 A
(E) The total feeder ampacity is the sum of the diverse
current and all the controller constant current.
T git 630.A + (6 elevators x 12.5 A) = 705A
(F) This ampacity would be permitted to be used to
select the wire size. See Figure D17.
jem
OF
etiam
Figure D17
Lighting and Small Appliance Load
Lighting (20 m x 3 mx 33 VA perm!) = 1980 VA
Small appliance (1500 VA x I circuit) = 1500 VA
Laundry (1500 VA x | circuit) 500 VA
Subtotal 4980 VA
First 3000 VA at 100% = 3000 VA
Remainder (4980 VA ~ 3000 VA = 1980
VA) x 35%
93 VA
Total 3693 VA
3 693 VA~ 230 V = 16.06 A per leg
Lighting and appliances = 16.06.
Heater (1 000 VA + 230 V) 35.0
Fan (200 VA x 125% +230 V) = 109A
Dishwasher (400 VA + 230 V) 74a
Range (7 000 VA x 0.8 + 230 V) = 24354
‘Total amperes 47.59
Use a minimum 50-A supply cord.APPENDIX D
Example D18
Mobile Home, Single Phase, 2-wire Service
A mobile home floor is 20 m by 3m and has one small
appliance circuit, one laundry area circuit, a 1000-VA
heater, a 200-VA exhaust fan, a 400-VA dishwasher, and
a 7000-VA electric range.
Lighting and Small Appliance Load
Lighting (12 mx 3 mx 33 VApern?) = 1188 VA
‘Small appliance (1500 VA x I circuit) = 1500 VA
Laundry (1500 VA.x I circuit) 500 VA
Subtotal 4188 VA
First 3000 VA at 100% = 3000 VA.
Remainder (4188 VA — 3000 VA = 1980
waren aueye
‘Total 3416 VA
3416 VA + 230 V = 14.85 A per leg
Lighting and appliances
Heater (1000 VA +230 V)
Fan (200 VA x 125% +230 V)
Dishwasher (400 VA + 230 V)
Range (7000 VA.x 0.8 +230 V)
Total amperes
Use a minimum 50-A supply cord.
Example D19
Park Trailer, Single Phase, 2-Wire
‘A park trailer floor is 12 m by 3 m and has one small
appliance circuit, a 1000-VA heater, a 200-VA exhaust
fan, 2 400-VA dishwasher, and a 7000 VA electric range.
Example D20
Store Building
Noneontinuous Loads
Reveptacle Load (see Section 2.20.3.5)
80 receptacles at 180 VA. = 14400 VA
10000 VA at 100% (0000 VA
14400 VA - 10000 VA= 4400 at 50% = 2200 VA.
Subtotal 12200 VA
Continuous Loads
General Lighting*
270 mat 24 VA per m* = 6480 VA
Show Window Lighting Load
9 mat 200 VA per 300 mm. = 6000 VA
Cree Sign Circuit [see 2.20.2.5(G) _yaqq vq
Subtotal 13680 VA
Subtotal from noncontinuous
Total noncontinuous loads + continuous
loads
A store 15 m by 18 m, or 270 m2, has 9 m of show
‘window. There are a total of 80 duplex receptacles. The
service is 240 V, single phase 2-wire (one conductor
grounded) service. Actual connected lighting load is 8
500 VA.
Calculated Load (see Section 2.20.3.1)
"In the example, 125% of the actual connected lighting
oad (8 500 VA x 1.25= 10 625 VA) is less than 125% of
the load from Table 2.20.2.3, so the minimum lighting
oad from Table 2.20.2.3 is used in the calculation. Had
the actual lighting load been greater than the value
calculated from Table 2.20.23, 125% of the actual
connected lighting load would have been used.
Minimum Number of Branch Cireuits Required
General Lighting: Branch circuits need only be installed
to supply the actual connected load [see Section
2.10.1.11(B)]
8500 VA 1.25 = 10625 VA.
10625 VA +230 V=46.A
The lighting load would be permitted to be served by
15- or 20-A circuit with combined capacity equal to 46
Aor greater. The feeder capacity as well as the number
of branch-circuit positions available for lighting circuits
in the panelboard must reflect the full calculated load of
9000 VA x 1.25 = 11250 VA.
Show Window
6000 VA x 1.25 = 7500 VA
7800 VA +230 V=33 A
‘The show window lighting is permitted to be served by
circuit with a capacity equal to 33 A or greater.
Receptacles required by 2.10.3.13 are assumed to be
included in the receptacle load above if these receptacles
do not supply the show window lighting load,
Subtotal from noncontinuous = 12200 VA
Subtotal continuous load at 125%
(13680 VA x 1.25)
‘Total 29300 VA
29300 VA~ 230 V= 1274
17100 VA.
Receptacles
Receptacle Load:14400 VA +230 V=63.A
1059APPENDIX D
The receptacle load would be permitted to be served by
circuit with a capacity equal to 63 A or greater.
Minimum Size Feeder (or Service) Overcurrent
Protection [see Section 2.15.1.3 or 2.30.7.1]
The next higher standard size is 150 A (see Section
2.40.16)
inimum Size Feeders (or Service Conductors)
Required [see 2.15.1.2, 2.30.4,3(A)]
29300 VA+ 230 V= 127A
Service or feeder conductor is 50 mm2 Cu per Section
2.15.1.3 and Table 3.10.2.5 (with 75°C terminations),
Example D21
Industrial Feeders in a Common Raceway
An industrial multi-building facility has its service at the
rear of its main building, and then provides 480Y/277-
volt feeders to additional buildings behind the main
building in order to segregate certain processes. The
facility supplies its remote buildings through a partially
enclosed access corridor that extends from the main
switchboard rearward along a path that provides
convenient access to services within 15 m of each
additional building supplied. Two building feeders
share a common raceway for approximately 45 m and
run in the access corridor along with process steam and
control and communications cabling. The steam raises
the ambient temperature around the power raceway to
as much as 35°C. Ata tee fitting, the individual building
feeders then run to each of the two buildings involved.
The feeder neutrals are not connected to the equipment
grounding conductors in the remote buildings. All
distribution equipment terminations are listed as being
suitable for 75°C connections
Each of the two buildings has the following loads:
Lighting, 11 600 VA, comprised of clectric-
discharge luminaires connected at 277 V
Receptacles, 22 240-volt, 10- or 15- ampere
receptacles on general-purpose branch circuits,
supplied by separately derived 400Y/230V 3phase
wire wye systems in each of the buildings
1-Air compressor, 460 volt, three phase, 7.5 hp
1-Grinder, 460 volt, three phase, 1.5 hp
3-Welders, AC transformer type (nameplate: 23
amperes, 480 volts, 60 percent duty cycle)
3-Industrial Process Dryers, 480 volt, three phase,
15 kW each (assume continuous use throughout
certain shifts)
1060
Determine the overcurrent protection and conductor
size for the feeders in the common raceway, assuming
the use of XHHW-2 insulation (90°C):
Calculated Load {Note: For reasonable precision, volt-
ampere calculations are carried to three significant
figures only; where loads are converted to amperes,
the results are rounded to the nearest ampere [sce
2.20.1.5(B)}}
Noncontinuous Loads
Receptacle Load (see 2.20.3.5)
22 receptacles at 180 VA
Welder Load [see 6.30.2.1(A),
Table 6.30.2.1(A)]
Each welder: 480V x 23A x 0.78
All 3 welders: [see 6.30.2.1(B)]
(demand factors 100%, 100%, 85%
respectively)
8611.2 VA+ 8611.2 VA + 7319.52
VA
Subtotal, Noncontinuous Load
= 3960 VA
= 8611.2 VA
= 24541.92 VA
“FiIBI2 VA
Motor Loads (see Section 4.30.2.4, Table 4.30.13.10)
Air compressor: 11 A x 480 Vx \3_ = 9150 VA
Grinder: 3A x 480 V x V5 490 VA
Largest motor, additional 25%: 2290 -VA
Subtotal, Motor Load 13900 VA
Byusing4.30.2.4, the motor loadsand the noncontinuous
loads can be combined for the remaining calculation.
‘Subtotal for load calculations,
Noncontinuous Loads
Continuous Loads
= $1013.12 VA
General Lighting = 11600 VA
3 Industrial Process Dryers 15 _
reas = 45000 VA
Subtotal, Continuous Loads 16600 VA
Overcurrent protection (see Section 2.15.1.3)
The overcurrent protective device must accommodate
125% of the continuous load, plus the noncontinuous
load:
Continuous Loads = 56600 VA
51013.12 VA,
Noncontinuous Loads
‘Subtotal, actual load [actual load
in amperes}:
99000 VA+ (480V = \3)= 119A]
(25% of 56,600 VA) (See2.15.1.3) = 14200 VA
107013.12 VA
‘Total VA 121213.12 VAAPPENDIX D
Conversion to amperes using three significant figures:
121213.12 VA/ @80V * ¥3)= 145.84.
Minimum size overcurrent protective device: 145.8 A.
Minimum standard size overcurrent protective device
(see 2.40.1.6): 150 amperes
Where the overcurrent protective device and_its
assembly are listed for operation at 100 percent of its
rating, a 125 ampere overcurrent protective device
would be permitted. However, overcurrent protective
device assemblies listed for 100 percent of their rating
are typically not available at the 125-ampere rating,
(See Section 2.15.1.3 Exception.)
Ungrounded Feeder Conductors
‘The conductors must independently mect requirements
for (1) terminations, and (2) conditions of use throughout
the raceway run,
Minimum size conductor at the overcurrrent device
termination [sce 1.10.1.14(C) and 2.15.1.2(A) (1), using
75°C ampacity column in Table 3.10.1,16]: 50 mm2.
Minimum size conductors in the raceway based on
actual load [see Article 1.1, Ampacity, and 3.10.2.6(B)
(2)a and correction factors to Table 3.10.2.6(B)(16)|:
107013.12 VA/ 0.7 / 0.96 = 159245.71 VA.
(70% = 3.10.2.6(B)(2)a) & (0.96 = Correction factors to
Table 3.10.2.6(B)(16)
Conversion to amperes:
159 245.12 VA/ (480 V = V3)
9154 A
Note that the neutral conductors are counted as current-
carrying conductors [see Section 3.10.2.6(B)(4)e] in this
example because the discharge lighting has substantial
nonlinear content. This requires a 60 mm2 conductor
based on the 90°C column of Table 3.10.2.6(B)(16)
Therefore, the worst case is given by the raceway
conditions, and 60 mm? conductors must be used. If
the utility corridor was at normal temperatures (30°C),
and if the lighting at each building were supplied from
the local separately derived system (thus requiring no
neutrals in the supply feeders) the raceway result (107
013.12 VA/0.8 = 133 766.4 VA; 133 766.4 VA(480V x
3)= 160.9 A, ora 38 mm? conductor @ 90°C) could not
be used because the termination result (50 mm? based
on the 75°C column of) would become the worst case,
requiring the larger conductor.
In every case, the overcurrent protective device
shall provide overcurrent protection for the feeder
conductors in accordance with their ampacity as
provided by this Code (see Section 2.40.1.4). A 90°C
(60 mm2 conductor has a Table 3.10.1.16 ampacity of
195 amperes. Adjusting for the conditions of use (35°C
ambient temperature, 8 current-carrying conductors in
the common raceway),
195 amperes * 0.96 0.7= 131 A
‘The 150-ampere circuit breaker protects the 60 mm?
feeder conduetors, because 2.40.1.4(B) permits the use
of the next higher standard size overcurrent protective
device. Note that the feeder layout precludes the
application of 3.10.1.15(a)(2) Exception.
Feeder Neutral Conduetor (see 2.20.3.22)
Because 2.10,1.11(B) does not apply to these buildings,
the load cannot be assumed to be evenly distributed
across phases. Therefore the maximum imbalance must
be assumed to be the full lighting load in this ease,
or 11600 VA. (11 600 VA/277 V = 42 amperes.) The
ability of the neutral to return fault current [see Section
2.50.2.13(B)(2)(2)] is not a factor in this calculation,
Although the neutral runs between the main switchboard
and the building panelboard, likely terminating on a
busbar at both locations, the busbar connections are
part of listed devices and are not “separately installed
pressure devices.” Therefore 1.10.1.14(C)(2) does not
apply, and the normal termination temperature limits
apply. In addition, the listing requirement to gain
exemption from the additional sizing allowance under
continuous loading (see Section 2.15.1.3 Exception)
covers not just the overcurrent protective device, but
its entire assembly as well. Therefore, since the lighting
load is continuous, the minimum conductor size is
‘based on 1.25 * (11 600 VA/277V) = 52 amperes, to be
evaluated under the 75°C column of Table 3.10.2.6(B)
(16). The minimum size of the neutral is 14 mm? This
size is also the minimum size required by 2.15.1.2(A)
(1), because the minimum size equipment grounding
conductor for a 150 ampere circuit, as covered in Table
2,50.6.13, is 14 mm?
1061