PA Cable TDS - R1

The document is a Material Submittal Form (MSF) for the TRIL IT City Phase-1B project, detailing the submission of FRLS armored cables for fire detection and alarm systems. It includes project information, material specifications, compliance with standards, and contractor reviews. The form also outlines the approval process and lists approved makes for various equipment and materials related to the project.

Uploaded by

Mohd Mansir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views15 pages

PA Cable TDS - R1

The document is a Material Submittal Form (MSF) for the TRIL IT City Phase-1B project, detailing the submission of FRLS armored cables for fire detection and alarm systems. It includes project information, material specifications, compliance with standards, and contractor reviews. The form also outlines the approval process and lists approved makes for various equipment and materials related to the project.

Uploaded by

Mohd Mansir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

MATERIAL SUBMITTAL FORM (MSF)

Part A: Project & Record Information:

Project Name TRIL IT City Phase-1B MSF.Ref.No JCI-TRIL-PAS-T-3&4-PH1B-


TDS-08
Client MIKADO REALTORS PRIVATE LIMITED Rev.No 1
Employer Tata Realty Submission Date 11/1/2024
PMC BOQ Ref: if any I.C.B.1.4
Engineer Sanjiv Kumar Approx. Qty 20520
Contractor Johnson Control

Part B: Material Submittal Discipline:

Civil Architectural Landscape IT


Related Discipline
Mechanical/HVAC Electrical Plumbing Others (Specify)

Part C: Material Details Attachment Checklist

Spec’s. Ref. 1 Compliance checklist


V.II,Appexndix V . C.4

Supplying, installing, testing and commissioning of FRLS armored


cables 2c x 1.5 sq mm armored cable for fire detection and alarm
system . Armored cables as per BS standards. Cables shall be
Specified Material
estimated per Speaker basis as per the drawings.The quoted rate shall 2 Copy of the related specs
(Specification/BOQ) be inclusive of suitable saddles spacers, hardware,fire rated
junction/Back boxes & Glands for termination etc. complete as per
specifcation.

Proposed Material
3 Copy of the related drawings
(Specification/BOQ)
2c x 1.5 sq mm Fire Survival armored cable

Manufacturer's /Brand/Make 4 Copy of the related BOQ


Masterflex

Model No./Series No. 5 Copy of the related Standards


NA

Size,Thickness,Colour,Shape 6 Material Technical Data Sheet


2c x 1.5 sq mm , (Black)
Meeting Requirement in
Specification/BOQ (Yes/No) 7 Material/Lab Test Certificate
If No, Specify the Reason YES

Applicable Standard Test


8 Warranty
Results
IS: 7098 (Part I)1988, BS: 5308 PT1 & BS: 7846

Supplier Name & Address 9 Tata Realty Previous Approvals


MASTERFLEXO CABLE PRIVATE LIMITED

IGBC/ USGBC Approval 10 Other Relevant Approvals

Justification of Alternative
11 License of Manufacturer
Material

Part D: Contractors Internal Review 12 ISO 9001 Certificate

QA/QC MEP TEAM 11 Sample with Sample Tag

IGBC/USGBC Compliance
Name 12
Approval
Concrete Mix Design (Applicable
Signature 13
only for Concrete Submittal)

Date 14 Others

We do certify that the material submitted herewith has been reviewed in details and in accordance with the Contract Documents (BOQ,
Specification)except as otherwise stated here above.

Template Ref: COEG03-TTR-GENE-QU-CN-TMT-004, Rev- R1, Date: 01-09-2020


MATERIAL SUBMITTAL FORM (MSF)
Part E: Engineers Review / Approval (Design/MEP Consultant /PMC/ Tata Realty)
Consultant Comments -
PA system cable should be fire survival as per IS:17505.
Snapshot is attached for your ready reference.

Contractor Reply -
Please refer attached Fire Survival Cable TDS for Approval.

Client/ Engineer/MEP A- Approved C- Revised and resubmit


Consultant (Tata Realty)
Approval B- Approved with comments D- Rejected

Note(1): Client’s/ Engineer’s approval is for conformance with information given and design concept expressed in Contract Documents. Approval does not authorize changes to
Contract Documents. Client’s/ Engineer’s approval does not relieve the Contractor from his contractual obligation to ensure conformance to all Contract Documents. Any deviations,
to the Contract Documents found subsequent to Client’s/ Engineer’s approval are to be corrected by the Contractor at no extra Cost/Time to the Employer.

S.No Description Name & Designation & Company Signature Date

Project -QAQC Manager/Engineer - Civil items


Regional Architect - Architectural items MEP
1 Manager / Regional architect - MEP Fittings & Fixture
MEP Manager- MEP embedded material
Regional architect - Landscape items

Design Consultant - Structure / Arch/MEP/Façade /


2
Landscape

3 Corporate Design / Corporate Quality

4 Project Head

Template Ref: COEG03-TTR-GENE-QU-CN-TMT-004, Rev- R1, Date: 01-09-2020


C CABLES & ACCESSORIES FOR FAS & PA

a CABLES & ACCESSORIES FOR FAS

1.1 Supplying, installing, testing and commissioning of FRLS cables 2 core 1.5 Sqmm armored
cable for fire detection and alarm system. Armoured cables as per BS standard . Cable should
be RED in color, Cables shall be estimated per device basis as per the drawings. Cabling for
response indicator/ Input & Output modules to field equipment/ power shall not be considered Rmt 23237 23237 46473
seperately as device. The quoted rate shall be inclusive of suitable saddles spacers,
hardware,fire rated junction/Back boxes & Glands for termination etc. complete as per
specifcation.

1.2 Supplying, installing, testing and commissioning of FRLS armored cables 18 AWG,2 paired (4
nos conductor ) armored Sheilded twin twisted pairs ATC cable for fire detection and alarm
system. Armored cables as per BS standards. The quoted rate shall be inclusive of suitable Mtrs. 300 300 600
saddles spacers, hardware,fire rated junction boxes/Back & Glands for termination etc.
complete as per specifcation.

1.3 Supplying, installing, testing and commissioning of 2 mm thick GI trunking with cover of the
following sizes complete with angle iron supports/hanging arrangement etc

a. 50 x 600 x 50 Mtrs. 116 116 232

b. 50 x 450 x 50 Mtrs. RO

c. 50 x 300 x 50 Mtrs. 315 315 630

d. 50 x 150 x 50 Mtrs. RO

b CABLES & ACCESSORIES FOR PA SYSTEM

1.4 Supplying, installing, testing and commissioning of FRLS armored cables 2c x 1.5 sq mm
armored cable for fire detection and alarm system . Armored cables as per BS standards.
Cables shall be estimated per Speaker basis as per the drawings.The quoted rate shall be RMT 10260 10260 20520
inclusive of suitable saddles spacers, hardware,fire rated junction/Back boxes & Glands for
termination etc. complete as per specifcation.

c supply installation testing commissioning of 25mm Heavy duty PVC Conduit including chase
cutting in wall and finishing, complete as per specifcation. RM 400 400 800

d supply installation testing commissioning of 100X50X1.6 mm Raceway, white Coloured,


complete as per specifcation. RM 460 460 920
APPENDIX III

LIST OF APPROVED MAKES FOR EQUIPMENT & MATERIALS

Contractor is free to select any of the approved makes listed as long as the makes comply with the
specification and performance requirements given elsewhere in the tender documents.

Once Proposed and approved, the Contractor shall use the same makes throughout the Projects

A. LIST OF MAKES FOR PA SYSTEM

Sl.No Product Description Tender Approved Makes

Ateis - Switzerland
Bosch
Integrated digital audio amplifier to be
GE
1 integrated with Digital voice control in the
Honeywell Notifire
fire panel
NETRACK
WALLRACK
Ateis - Switzerland
Bosch
2 Speakers wall mounted - 6W
GE
Honeywell Notifire
Ateis - Switzerland
Bosch
3 Speakers ceiling mounted - 6W
GE
Honeywell Notifire
Ateis - Switzerland
Announcement console complete with
Bosch
4 microphone and Minimum 2 Zone
GE
selection.
Honeywell Notifire
PHILIPS
Integrated music source consisting of DVD
AHUJA
5 player (should be capable of playing
SONY
MP3,VCD,DVD).
BOSCH
Batra Henlay
Caliplast
2C x 1.5 sq.mm PVC sheathed copper Lappkabel
conductor 1100 volts grade armoured Neolex
6
FRLS cable (from Audio amplifiers to First Polycab
speaker Rolex
RR Kabel
Technoflex
AKG
16-gauge 25 mm dia MS Conduits with BEC
7
Accessories. NIC
Wimco
Birla-3M
Raychem
8 LT Jointing Kit / Termination
REPL
Safe Kit
Baliga Lighting
Cable Glands Double Compression with
9 Comet
earthing links
Cosmos

STR-26
Sl.No Product Description Tender Approved Makes

Control Well
10 PVC Glands
Lapp
Comet
Cosmos
11 Bi-metallic Cable Lug
Hax Brass (Copper Alloy India)
Anchor
Lapp Kabel
Havells
PVC insulated copper conductor stranded
12 L&T
flexible wires (HFFR) -
Polycab
Rallison Cables
R R Kabel

AKG
13 Metallic / GI Conduit (ISI approved) BEC
Vimco

PLICA India Pvt. Ltd.


14 Lead Coated Flexible GI Conduit
Flexicon
AKG
BEC
D Plast
15 PVC Conduit & Accessories (ISI approved) Dimond
Duraline
Polypack
Precision
ABB Tvisha
Anchor Roma Classic
16 a. Switch & Socket Crabtree - Murano
Legrand - Absolut
Wipro Stylus +
Connect Well
17 Terminal Blocks Elmex
Wago
18 Industrial Socket
Clipsal
Gewiss
19 18 a. Splash Proof Neptune Balls
ELCON-PCE
Schneider Electric
BCH
20 18 b. Metal Clad
MDS
ABB
BCH
GE Power Control
21 Timer Larsen & Toubro
MDS Legrand
Schneider Electric
Siemens

STR-27
Sl.No Product Description Tender Approved Makes

Amar Raja
BCH
Exide
22 Sealed Maintenance Free Batteries
Global (Rocket)
Hitachi
Shinkobe
Emerson
APC-MGE
23 UPS Socomec
GE
EATON

Indiana
MK (raceway)
Cable Trays (Factory Fabricated) /
25 OBO Bettermann
Raceways
Profab
Techno Fab

ABB (T Max)
Larsen & Toubro (D- Sine)
26 Moulded Case Circuit Breaker (MCCB)
Schneider Electric (Compact NSX/ NS)
Siemens (3VL)
ABB
Hager (L & T)
27 Motor Protection Circuit Breaker(MPCB)
Schneider Electric
Siemens
ABB
Hager (L&T)
28 Miniature Circuit Breakers (MCB)
Schneider Electric (Multi 9)
Siemens

STR-28
C. LIST OF MAKES FA SYSTEM
Sl.No Product Description Tender Approved Makes
Edwards EST3
Honeywell Esser 3000
Intelligent and electronically addressable
1 Johnson IFC 3030/IFC 640
photoelectric smoke detector
Notifier
Siemens Fire Finder series
Edwards EST3
Intelligent and electronically addressable, rate Honeywell Esser 3000
2 of rise cum fixed temperature thermistor type Johnson IFC 3030/IFC 640
heat detector Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
Intelligent and electronically addressable
3 Johnson IFC 3030/IFC 640
smoke cum heat detector (Multi sensor)
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
4 Fault Isolator Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
5 Addressable control relay modules Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
6 Addressable monitoring module Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series

Edwards EST3
Honeywell Esser 3000
7 Addressable Single action Manual Call Points Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series

8 MCP cover with local buzzer apart from hooter. -


Edwards EST3
Honeywell Esser 3000
Electronic loud hooters with strobe lights of
9 Johnson IFC 3030/IFC 640
110 Cd intensity
Notifier
Siemens Fire Finder series

Edwards EST3
Round speaker (should be directly
Honeywell Esser 3000
interfaced/connected with Fire panel for
10 Johnson IFC 3030/IFC 640
Emergency Voice Evacuation System Ceiling
Notifier
mounting arrangement (2 watts)
Siemens Fire Finder series

STR-34
Sl.No Product Description Tender Approved Makes

Edwards EST3
Round speaker (should be directly
Honeywell Esser 3000
interfaced/connected with Fire panel for
11 Johnson IFC 3030/IFC 640
Emergency Voice Evacuation System Wall
Notifier
/Column mounting arrangement (2 watts)
Siemens Fire Finder series

Edwards EST3
Honeywell Esser 3000
2-way communication Addressable Fire
12 Johnson IFC 3030/IFC 640
Fighter's Telephone Jack
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
13 2-way communication Fire Fighter's Handset Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Honeywell
Johnson
14 Response indicator unit.
Schneider
Siemens
D-LINK
15 Layer switch Cisco
Netgear
Molex
Panduit
16 Optic Fibre Communication Cable 6 core R&M
Systimax
TYCO AMP

Batra Henlay
Caliplast
Lapp kabel
Copper, multi strand, ATC, Mylar Taped Neolex
17
shielded armoured cable Polycab
Rolex
RR Kabel
Technoflex

Batra Henlay
Caliplast
Lappkabel
Neolex
32 Armoured power cables
Polycab
Rolex
RR Kabel
Technoflex

Batra Henlay
Caliplast
Lappkabel
Neolex
18 LAN cable. (Cat- 6)
Polycab
Rolex
RR Kabel
Technoflex

STR-35
Sl.No Product Description Tender Approved Makes
Birla-3M
Raychem
19 LT Jointing Kit / Termination
REPL
Safe Kit
Baliga Lighting
Cable Glands Double Compression with
20 Comet
earthing links
Cosmos
Control Well
21 PVC Glands
Lapp

Comet
Cosmos
22 Bi-Metallic Cable Lug
Hax Brass (Copper Alloy India)

Anchor
Lapp Kabel
Havells
PVC insulated copper conductor stranded
23 L&T
flexible wires (HFFR) -
Polycab
Rallison Cables
R R Kabel
AKG
24 Metallic / GI Conduit (ISI approved) BEC
Vimco
PLICA India Pvt. Ltd.
25 Lead Coated Flexible GI Conduit
Flexicon
AKG
BEC
D Plast
26 PVC Conduit & Accessories (ISI approved) Dimond
Duraline
Polypack
Precision
ABB Lumina/ Classic
Anchor (Roma)
Crabtree
27 Switch & Socket
Legrand (Mosaic)
Siemens
Wipro (North-West)
Connect Well
Elmex
28 Terminal Blocks
Wago

29 Industrial Socket

Clipsal
Gewiss
29.a Splash Proof Neptune Balls
ELCON-PCE
Schneider Electric

STR-36
Sl.No Product Description Tender Approved Makes
BCH
29.b Metal Clad
MDS
ABB
BCH
GE Power Control
30 Timer Larsen & Toubro
MDS Legrand
Schneider Electric
Siemens
Amar Raja
BCH
Exide
31 Sealed Maintenance Free Batteries
Global (Rocket)
Hitachi
Shinkobe
Emerson
APC-MGE
32 UPS Socomec
GE
EATON
Indiana
MK (raceway)
Maheshwari Electricals
OBO Bettermann
33 Cable Trays (Factory Fabricated) / Raceways Profab
Pushpak
Techno Fab
Gripple

ABB (T Max)
Larsen & Toubro (D-Sine)
34 Moulded Case Circuit Breaker (MCCB)
Schneider Electric (Compact NSX/ NS)
Siemens (3VL)
ABB
Hager (L & T)
35 Motor Protection Circuit Breaker(MPCB)
Schneider Electric
Siemens
ABB
Hager (L&T)
36 Miniature Circuit Breakers (MCB)
Schneider Electric (Multi 9)
Siemens

STR-37
Addendum 2 - Fire Alarm & Public Address System Works for TRIL IT City Tower 3 & 4
Sl.No Reference Queries Clarification
Fire Alarm & Public Address System

1 General Only BMS Integration with FAS has been considered in our offer, please confirm Ok
Quoted for Conventional Hooter cum strobe with Control module and power
2 Bill of Quantities Section A Item 1.10 supply as addressable Hooter Cum strobe is not available in the Edwards make. Ok, Control module to be consider for each hooter for addressing.
Please confirm.
We have proposed System Sensor(By Honeywell) Response indicator. Please
3 Bill of Quantities Section A Item 1.17 OK
confirm.
As per the Pre-bid clarification and given schematic the FACP panels in Tower-3
and Tower-4 are interconnected, but the required cable for connectiing both the
4 General Refer Section 3 Bill of Quantities R2, Section-C- Line Item a -1.2
panels is not given in the BOQ. Please provide the cable with qty to propose.
Please clarify.

As mentioned in the Pre-bid clarification "Scope to be considered with seamless


integration with the existing system". Seamless integartion with Panel is not
We require seamless integration with existing software.
5 General possible, we can integrate the exisitng system in such a way that only alerts can be
Intalled system is Honeywell xls 3000.
displayed in the proposed panels of Tower-3 and Tower -4. Please confirm.
Please provide exisitng FAS system details like make and model no.
There is no approved make for Beam detector, hence we have quoted for
6 Bill of Quantities Section A Item 1.13 Proposed beam detector must be intergated with the FACP panel.
Edwards Make. Please confirm.
7 Bill of Quantities Section C Item 1.1 Kindly provide the cable length in running meters instead of Points. Qty provided in running mtrs. Refer Section 3 Bill of Quantities R2
As per PAS schematic 15 Zones in each Tower shown in the schematic, accordingly
8 Bill of Quantities Section B Item 1.1a Bidder to evaluate the controller as per the system architecture.
we have considered controllers in our offer, please confirm.
Please provide the speaker location details and floor wise qtys to check on the
9 General Refer drawings provided with the tender documents
optimization of the Speaker tapping and zoning.
Touch screen IP Based Microphones are asked in the BOQ, but the make we
10 General Kindly comply to technical specification.
proposed has keypad based callstation, please approve the same.
Line item 1.4 - Can we propose "6W wall mount Wooden speaker" in place of " 6
11 Bill of Quantities Section B Item 1.4 Kindly comply to technical specification.we require metal cabinet only
W Wall Mounted Box Type Metal Cabinet"
Line item 1.5 - Can we propose "20W wall mount Wooden speaker" in place of
12 Bill of Quantities Section B Item 1.5 Kindly comply to technical specification.we require metal cabinet only
"20 W Wall Mounted Type Metal Projector Speaker"
6 W Ceiling Mounted Speaker with Metal Grille Multi Tapping Feature as per
13 Bill of Quantities Section B Item 1.3 ok
specification.
Quoted for 4 no. of 1000Watt amplifier in each tower without redundancy,
considering full tapping for ceiling mount speaker. As requested in pre-bid queires
14 Bill of Quantities Section B Item 1.2a Kindly comply to technical specification and N+1 to be considered.
please confirm the Speaker tapping to quote suitable amplifiers. Please clarify
whether additional amplifier also to be considered for redundancy.
CABLES & ACCESSORIES FOR FAS
Bill of Quantities Section C Item 1.1 &
15 Line item 1.1 and 1.2. Can we quote for ABC FRLS PVC insulated cable instead of FRLS to be considered.Refer Section 3 Bill of Quantities R2
1.2
ATC fire survival XLPE cable.
CABLES & ACCESSORIES FOR PA SYSTEM
Bill of Quantities Section C Item 1.1 &
16 Line item 1.4. Can we quote for ABC FRLS PVC insulated cable instead of ATC fire FRLS to be considered.Refer Section 3 Bill of Quantities R2
1.4
survival XLPE cable.
We feel this item is not required. Please confirm as touch screen paging
17 Bill of Quantities Section B Item 1.8 Required with license expansion.
microphone is already considered in section B item 1.7
As per the tender BOQ, no. of devices is less compared to the loops considered for
18 Bill of Quantities Section A Item 1.1 fire alarm control panel. Please confirm on optimizing the loops as per the Ok
capacity of system proposed.
Kindly comply to technical specification. Tapping to be considered as per
19 Bill of Quantities Section B Item 1.2a Please confirm tapping of speakers to consider amplifier quantity accordingly.
required DB level.
20 Bill of Quantities Section B Item 1.2a Please confirm can we consider non-EN amplifiers with EN54 controllers. Ok, can be considered
21 Bill of Quantities Section B Item 1.7 Can we consider non-touch EN54 paging station, request you to please confirm. Ok, Can be considered
22 Bill of Quantities Section A Item 1.2 Request you to confirm the quantity of repeater panel. Quantity updated in revised BOQ.Refer Section 3 Bill of Quantities R2
Simplex can be considered. Panel must be integrated with existing FACP
23 List of Approved Makes We understand Simplex make of FAS is approved here.
installed in Phase 1A
With Simplex, we can optimize and downsize the FAS panel. Hence 10 loop fire
24 Bill of Quantities Section A Item 1.1 ok
panel can suffice for each tower as we can have 250 devices in any building.
Hooter and sounder sits on a separate Nac circuit in Simplex. Hence we can
Electronic type Hooters Cum Strobe is addressable and there is no
25 Bill of Quantities Section A Item 1.10 downsize the qty of monitor modules. Please share the break up monitor modules
separate module considered in the BOQ
used for Sounders.
Since majority of detectors shall be installed in the office area with controlled
26 General Kindly comply to technical specification.
environment, can smoke detectors be proposed instead of multicriteria.
Please confirm if telephone jack shall be addressed or not. We can propose zone
Telephone Jack must be addressable as per the specification. Zone /
27 Bill of Quantities Section A Item 1.12 wise/floor wise indication instead of each having every telephone jack
Floor wise indication not required
addressable
28 Bill of Quantities Section A Item 1.2 We suggest to go with additional Repeater panel for status, reset will be required ok, 1 NRP to be considered
Kindly share the following details of products installed in Tower 1 & 2
FAS - Honeywell (XLS Series)
29 General
- Fire Alarm make & series PAS - Honeywell (X-DCS : Digital Integrated System Manager)
- PA system make and series
As per pre-bid reply, we have quoted panel for the detector & devices capacity in
BOQ considering additional 15% spare.
30 General Ok
Hardwired integration with existing FAS system is considered.
We have considered total 16 Nos of 1x 500 watt amplifier / 8 Nos of 2x500 watt
amplifier against this line item. Please consider.
31 Bill of Quantities Section B Item 1.1a Ok
It was discussion during meeting that speakers tapping to be selected considering
75 db @10ft voice for speaker.
Only BMS software with integrated FAS GUI software found at site.

32 Bill of Quantities Section B Item 1.8 Only FAS GUI based soft integration with existing BMS is required. PA to be X-Smart (Sytem Management Software) considered for PAS
integrated with FAS via modules. Which required to be considered in this line
item. No PA software is present in existing towers.
Our detector comes with 3 programmed sensitivity settings.
33 General Ok
It was accepted by Employer
The specification provided in Hooter cum strobe line items seems more of
34 Bill of Quantities Section A Item 1.10 speaker. We like to inform that hooter as a standard comes with 85 / 90 dBA Ok
rating. It was accepted by Employer
We will quote UL listed beam detector of Fireray / Honeywell system sensor make.
35 Bill of Quantities Section A Item 1.13 Ok. Beam detector must be compatible with the FACP
It was accepted by Employer

We will be providing standard wall mounted speakers. Have same specification as


36 General ceiling speakers however the speaker to be Box & wall mounted type. Kindly comply to technical specification.
In existing site, only 6W ceiling and 20 watt wall mounted are present.
We havent found 6 watt wall mount speaker. We would request you to provide
37 General Existing model installed at site is L-PWP06A (Honeywell Make)
model of 6 watt wall mount speaker if any installed at site for comparision.

During site visit we observed that the BMS are security system at site is partly
commissioned.
yes, integration with proper workability is in your scope. While
In continuation to the same, we would like to clarify that the responsibility of
integration if any product damage or found any error in the existing
integration of new system with existing software will be in our scope for which we
38 General system, will be the responsible to correct the same and make the system
will take support of respective OEMs. However, we would require some support
good in workability condition.software handling & maintaining further
of existing vendor in terms of availability of access of complete system. Further,
will be in the appointed contractor's scope.
the responsibility of maintaining DLP of existing system will remain with existing
vendor only.

We have Quoted Below Makes


FIre Panel & devices - Tender mentions Notifier , However , Honeywell XLS3000 as
approved in Query response .
PA- Honeywell Integrated Voice Evacuation with Non UL & Non EN Honeywell
Speakers as confirmed in Query respsone .
Cable Tray - MEM as approved & installed in Phase-1
39 List of Approved Makes Ok
Hooter & Response Indicator - Honeywell System Sensor
Rack - Valrack
Field Sensors - Not approved here . Greystone As approved & installed in T1&T2.
Ultrasonic Level Transmitter - Not approved here . Scientific Device s approved &
installed in T1&T2 .
Panic Switch - SCHUTZ

In each Tower there is total 1443 detectors given in the BOQ and the loop capacity
of the panel is 159 detectors and 159 devices per loop. As per the tender
specification "each loop shall be provided with 15% spare capacity". So
40 Bill of Quantities Section A Item 1.1 Ok
considering 15% spare in each loop, to connect 1443 detectors 11 loop panel is
required. So We have considered 1 Nos 10 Loop & 1 Nos 2 Loop Non Expandable
Panel For the same which is suitable for the same . Please confirm .

Bill of Quantities Section A Item 1.3 & As the BOQ Qty for this is zero , so we understand , Graphics & Server For the
41 Ok
1.4 same will be integrated to existing T1 & T2 .
42 Bill of Quantities Section A Item 1.7 We have Quoted For Rate of Rise Temperature Heat Detetctor. Kindly comply to technical specification.
We have considered Dual Action Push Pull Type Convenstional Manual Call Point
43 Bill of Quantities Section A Item 1.8 with Monitor Module , suitable For the Same. Push Pull Type is better than Break Kindly comply to technical specification / Quote as per existing make
Glass Type in terms of Durability ,usablity & maintaince ..
We have considered Honeywell System Sensor Make SYS-HS Hooter cum Strobe
with Control Module which is externally Powered by reputed Micropwer Make
44 Bill of Quantities Section A Item 1.10 Non UL 24V PSU . One PSU will cater 4-5 Hooters . We understand , Customer to Ok
provide UPS power near all PSU , so battery backup for the same is not considered
.
We have considered Honeywelll System Sensor make Conventional Beam
Detetctor with Monitor Module suitable For the same .. As distance is not
45 Bill of Quantities Section A Item 1.13 Ok
mentioned so we have considered 70 Mtr supported Beam Detetcor. Testing Kit is
already available in existing phase . Additional not Required .
We understand necessary cables to be considered in Cable Qty in Sr No C-a1.1. So
46 Bill of Quantities Section A Item 1.17 Ok
we have not considered any Cable price in this line item .
47 Bill of Quantities Section B item 1.10 a We have considered Fire Integrated Digital PA with Non UL & NON EN Speakers . Kindly comply to technical specification.
As per Speaker Wattage count with 20% Spare we have considered 7 Nos of
Amplifier & 1 backup as N+1 Amplfier redundacy . 1 nos 42U rack also considered
48 Bill of Quantities Section B item 1.12 a Kindly comply to technical specification.
in each tower with same as per BOQ .. As we have Quoted 500W amplifers so PA
BOQ SR NO B: 1.12 b & c not required , hence not quoted .
As confirmed in the Query Resposne , We have quoted Honeywell make 6W Non
49 Bill of Quantities Section B item 1.3 UL -Non EN Ceiling Speaker with Metal backbox suitable for the same . Please OK
confirm.
As confirmed in the Query Resposne , We have quoted Honeywell make 6W Non
50 Bill of Quantities Section B item 1.4 OK
UL -Non EN ABS wall Mount Speaker with suitable for the same . Pls confirm.
We have Quoted the same Models approved & installed in the exiting phase T1 &
T2. 20W unidirectional projected loudspeaker, which hasa sturdy aluminum
51 Bill of Quantities Section B item 1.5 OK
enclosure finished in unobtrusive white color with ABS Front . The loudspeaker is
CE and RoHS complied.
We have Quoted the same Models approved & installed in the exiting phase T1 &
52 Bill of Quantities Section B item 1.7 OK
T2

BOQ Qty for this is 2 , but the BOQ description mentions to be integrated with
exiting PC graphics in Main Fire Command Center . That’s why PC in Sr No 1.9 is
kept Zero .
53 Bill of Quantities Section B item 1.8 Kindly comply to technical specification.
One Software can cater 20 DCS controllers , existing Phase has 11 Nos of DCS &
this has only 2 . Which is sufficent to integrate with existing software in command
center .. hence we have not Quoted For this line item as not required .

We have Quoted Same Specs & Make model as approved & installed in the T1 &
Bill of Quantities Section C item 1.1 &
54 T2 .. Please share the running meter Qty .. Now we have considered 12 Meter per Qty provided in running mtrs. Refer Section 3 Bill of Quantities R2
1.2
device as standard . Pls confirm .
We have Quoted Same Specs & Make model as approved & installed in the T1 &
Bill of Quantities Section C item 1.1 &
55 T2 .. Please share the running meter Qty .. Now we have considered 20 Meter per Qty provided in running mtrs. Refer Section 3 Bill of Quantities R2
1.3
speaker as standard . Pls confirm .
56 General We have Considered Same JB appoved & installed in T1 & T2 . Ok
Any kind of Civil works, core cutting, wall chasing not in Honeywell scope.
57 General Ok
Hoenywell to coordinate with Civil vendor for the same .

Commercial Bid Submission - On or before 5.00pm on 29th June 2023


Complied
MASTERFLEXO CABLE PRIVATE LIMITED

DIMENSIONAL DRAWING
Cable Description :
600/1000 V, 2C x 1.5mm², TCu/GMT/ XLPE/OSCR/LSZH/GSWA/LSZH: FIRE SURVIVAL
Stranded (Class 2) non-compacted circular Annealed Tinned Copper Conductor & Over Glass mica tape lapped, Extruded XLPE insulation,
Two cores laid up together, Overall Aluminium Mylar tape screening alongwith ATC drain wire 0.5 sq. mm (7-strand) in continous contact with
aluminium side & Extruded - Inner layer LSZH, Galvanised Steel round wire single layer armouring, & Outer layer LSZH compound sheathed
Fire Survival cable constructed generally as per IS:7098 (Part 1), BS: 7846, BS: 6387 & client specification.

Conductor : 1.5 sq. mm


Stranded Class 2 non-compact Circular Tinned Copper
Approx. dia. 1.6 mm
Fire Protection
Glass Mica Tape
Thickness - 0.1 mm (approx)

Insulation:
Extruded (XLPE)
Thickness - 0.7 mm (nom)

Fillers and Binder - Non-hygroscopic


Polypropylene fillers as applicable

Overall Screen -
Aluminium Mylar Tape

Drain Wire - Annealed Tinned Copper(ATC)


drain Wire 0.5 mm2 (7/0.3mm)

Inner sheath:
Extruded LSZH compound,
Thickness - 0.3mm (min)

Armouring: Galvanized Steel round wire


Diameter - 0.9 ± 0.05 mm

Outer Sheath:
Extruded LSZH compound,
1) Schematic colour only for representation not to match product. Thickness - 1.24 mm (min)
2) Binder tape/s shall be provided where ever applicable/required.
3) Non-hygroscopic fillers shall be provided wherever required.
4) Overall shield shall be Aluminium backed by mylar tape with 25% overlap and 100% coverage.minimum shield
thickness shall be 0.024 mm.Drain wire shall be 0.5 sq.mm. (7/0.3) Multistrand tinned annealed copper conductor.

Cable Technical Data: Conductor Electrical Data:


1) Approx. overall cable diameter : 14.3 ± 2 mm 1) Conductor DC resistance at 20 °C Ω/Km
2) Approx. cable weight : 358 kg/km 12.2 (max)
3) Maximum pulling force (N) when pulled by pulling eye 2) Conductor AC resistance at 90 °C Ω/Km
a) Copper Conductor cable 210 N 15.6 (max)
3) Conductor short circuit rating
4) Cable minimum bending radius (mm) 0.21 kA for 1 sec.
a) During Installation = 240 mm (15 x OD) 4) Metal Screen earth fault rating (if applicable)
not applicable

Masterflexo Cable Pvt. Ltd.,


Prepared : R. P. Scale: Not to scale
Approved : S. S. Drawing No.: 1 kV/2C x 1.5 Sq. mm - FS FP-120
Date: 10-11-2023 Rev.: 00
MASTERFLEXO CABLE PRIVATE LIMITED

DATA SHEETS FOR XLPE COPPER FIRE SURVIVAL FP-120 CABLE ARMOURED

S.No. Description cores x sq.mm 2C x 1.5

1 GENERAL
Name of Manufacture M/s MASTERFLEXO CABLES PVT. LTD.,
Brand Name MASTERFLEX
Cable Type/Code TCu/GMT/ XLPE/OSCR/LSZH/GSWA/LSZH : FIRE SURVIVAL
Voltage Grade 650/1100 volts
Standards Applicable IS:7098 (Part I) 1988, BS: 7846 & BS: 6387, IS:5831-1984, IS:8130-1984, IS:3975
2 CONDUCTOR
Material Stranded Non-Compacted Circular Annealed Tinned Copper Conductor as per Class-2 of IS:8130-2013
Cross Sectional Area sq.mm. 1.5
No. of Strands nos 7
Dia.of each strand (before stranding) mm 0.53
Max.C.R.@ 20° C. ohms/km 12.2
Fire Survival Tape Mica tape helically applied with 100% coverage and 25% overlap
Overall diameter over FS tape (appx) 1.9 ± 0.2
3 INSULATION
Material Extruded XLPE as per IS 7098-1/88 (latest)
Thickness (Nom.) mm 0.7
Dia. Over insulation mm 3.4 ± 0.2
CONDUCTOR TEMPERATURE
Rated 90 Deg .C.
During short circuit 250 Deg. C.
Cabled core laid up overall shielded with Aluminium backed Mylar tape (0.024 mm min thickness) helically wrapped with 25 %
4 OVERALL SHIELDING overlap & 100% coverage, ATC Drain wire of 0.5 sq. mm(7/0.3 -strands) under Aluminium Mylar / Polyster tape in continuous
contact with Aluminium side of the tape
5 INNER SHEATH
Material Extruded LSZH Compound
Thickness (Min.) mm 0.3
Colour Black
6 ARMOUR
Material Galvanised steel round wire as per IS : 3975
Size mm 0.9 ± 0.05
7 OUTER SHEATH
Material Extruded LSZH Compound
Thickness (Minimum) mm 1.24
Colour RED
Approx.Overall dia of cable mm 14.3
Tolerance on overall dia +/- 2 mm
Approx. wt of cable in gm/mtr 358
8 LSZH Properties
oxygen Index at room temperature 32 min. as per ASTM-D-2863
Temperature Index. Min. 250 deg.c. as per ASTM-D-2863
Smoke density Rating 60% max. as per ASTM-D-2843
Acid Gas Generation 0.5% max. as per IEC-754-1
Flamability test as per IS:7098 Pt.1
Buring of sample after removal of flame max 60 sec. & Uncharred protion min. 50 mm
& IS 10810 Pt. 53
Circuit integrity Fire survival test As per BS; 7846 Category A, suitable to sustain @ 950 ⁰C for 120 minutes.
9 ELECTRICAL DATA
A.C. resistance at 90 deg C Ohms/km 15.6
Short circuit current rating KA 0.21
Approx Capacitance µF/km 0.17
Approx. Reactance at 50Hz Ohms/km 0.1113
Approx. impedance at 50Hz Ohms/km 15.6
10 Current Rating
In ground @ 30 deg.C 33
In Air @ 40 deg.C (ambient) 29
11 Core indentification Red & Black
12 Drum Length 1drum x 1000 mtr.
Tolerance (%) +/- 5
13 Printing/Embossing MASTERFLEXO CABLE ELECTRIC XLPE SHIELDED 1100V 2C x 1.5 SQ MM FS FP-120 BS 6387 GENERALLY IS: 7098 PT1 INDIA 2023

14 Min. Bending radius 15 x OD


15 Sequential Marking Shall be provided at every interval of one meter
Cables are conforming to IS: 7098 (Part I)1988, BS: 5308 PT1 & BS: 7846
FOR MASTERFLEXO CABLE PRIVATE LIMITED