PA Cable TDS - R1
PA Cable TDS - R1
Proposed Material
3 Copy of the related drawings
(Specification/BOQ)
2c x 1.5 sq mm Fire Survival armored cable
Justification of Alternative
11 License of Manufacturer
Material
IGBC/USGBC Compliance
Name 12
Approval
Concrete Mix Design (Applicable
Signature 13
only for Concrete Submittal)
Date 14 Others
We do certify that the material submitted herewith has been reviewed in details and in accordance with the Contract Documents (BOQ,
Specification)except as otherwise stated here above.
Contractor Reply -
Please refer attached Fire Survival Cable TDS for Approval.
Note(1): Client’s/ Engineer’s approval is for conformance with information given and design concept expressed in Contract Documents. Approval does not authorize changes to
Contract Documents. Client’s/ Engineer’s approval does not relieve the Contractor from his contractual obligation to ensure conformance to all Contract Documents. Any deviations,
to the Contract Documents found subsequent to Client’s/ Engineer’s approval are to be corrected by the Contractor at no extra Cost/Time to the Employer.
4 Project Head
1.1 Supplying, installing, testing and commissioning of FRLS cables 2 core 1.5 Sqmm armored
cable for fire detection and alarm system. Armoured cables as per BS standard . Cable should
be RED in color, Cables shall be estimated per device basis as per the drawings. Cabling for
response indicator/ Input & Output modules to field equipment/ power shall not be considered Rmt 23237 23237 46473
seperately as device. The quoted rate shall be inclusive of suitable saddles spacers,
hardware,fire rated junction/Back boxes & Glands for termination etc. complete as per
specifcation.
1.2 Supplying, installing, testing and commissioning of FRLS armored cables 18 AWG,2 paired (4
nos conductor ) armored Sheilded twin twisted pairs ATC cable for fire detection and alarm
system. Armored cables as per BS standards. The quoted rate shall be inclusive of suitable Mtrs. 300 300 600
saddles spacers, hardware,fire rated junction boxes/Back & Glands for termination etc.
complete as per specifcation.
1.3 Supplying, installing, testing and commissioning of 2 mm thick GI trunking with cover of the
following sizes complete with angle iron supports/hanging arrangement etc
b. 50 x 450 x 50 Mtrs. RO
d. 50 x 150 x 50 Mtrs. RO
1.4 Supplying, installing, testing and commissioning of FRLS armored cables 2c x 1.5 sq mm
armored cable for fire detection and alarm system . Armored cables as per BS standards.
Cables shall be estimated per Speaker basis as per the drawings.The quoted rate shall be RMT 10260 10260 20520
inclusive of suitable saddles spacers, hardware,fire rated junction/Back boxes & Glands for
termination etc. complete as per specifcation.
c supply installation testing commissioning of 25mm Heavy duty PVC Conduit including chase
cutting in wall and finishing, complete as per specifcation. RM 400 400 800
Contractor is free to select any of the approved makes listed as long as the makes comply with the
specification and performance requirements given elsewhere in the tender documents.
Once Proposed and approved, the Contractor shall use the same makes throughout the Projects
Ateis - Switzerland
Bosch
Integrated digital audio amplifier to be
GE
1 integrated with Digital voice control in the
Honeywell Notifire
fire panel
NETRACK
WALLRACK
Ateis - Switzerland
Bosch
2 Speakers wall mounted - 6W
GE
Honeywell Notifire
Ateis - Switzerland
Bosch
3 Speakers ceiling mounted - 6W
GE
Honeywell Notifire
Ateis - Switzerland
Announcement console complete with
Bosch
4 microphone and Minimum 2 Zone
GE
selection.
Honeywell Notifire
PHILIPS
Integrated music source consisting of DVD
AHUJA
5 player (should be capable of playing
SONY
MP3,VCD,DVD).
BOSCH
Batra Henlay
Caliplast
2C x 1.5 sq.mm PVC sheathed copper Lappkabel
conductor 1100 volts grade armoured Neolex
6
FRLS cable (from Audio amplifiers to First Polycab
speaker Rolex
RR Kabel
Technoflex
AKG
16-gauge 25 mm dia MS Conduits with BEC
7
Accessories. NIC
Wimco
Birla-3M
Raychem
8 LT Jointing Kit / Termination
REPL
Safe Kit
Baliga Lighting
Cable Glands Double Compression with
9 Comet
earthing links
Cosmos
STR-26
Sl.No Product Description Tender Approved Makes
Control Well
10 PVC Glands
Lapp
Comet
Cosmos
11 Bi-metallic Cable Lug
Hax Brass (Copper Alloy India)
Anchor
Lapp Kabel
Havells
PVC insulated copper conductor stranded
12 L&T
flexible wires (HFFR) -
Polycab
Rallison Cables
R R Kabel
AKG
13 Metallic / GI Conduit (ISI approved) BEC
Vimco
STR-27
Sl.No Product Description Tender Approved Makes
Amar Raja
BCH
Exide
22 Sealed Maintenance Free Batteries
Global (Rocket)
Hitachi
Shinkobe
Emerson
APC-MGE
23 UPS Socomec
GE
EATON
Indiana
MK (raceway)
Cable Trays (Factory Fabricated) /
25 OBO Bettermann
Raceways
Profab
Techno Fab
ABB (T Max)
Larsen & Toubro (D- Sine)
26 Moulded Case Circuit Breaker (MCCB)
Schneider Electric (Compact NSX/ NS)
Siemens (3VL)
ABB
Hager (L & T)
27 Motor Protection Circuit Breaker(MPCB)
Schneider Electric
Siemens
ABB
Hager (L&T)
28 Miniature Circuit Breakers (MCB)
Schneider Electric (Multi 9)
Siemens
STR-28
C. LIST OF MAKES FA SYSTEM
Sl.No Product Description Tender Approved Makes
Edwards EST3
Honeywell Esser 3000
Intelligent and electronically addressable
1 Johnson IFC 3030/IFC 640
photoelectric smoke detector
Notifier
Siemens Fire Finder series
Edwards EST3
Intelligent and electronically addressable, rate Honeywell Esser 3000
2 of rise cum fixed temperature thermistor type Johnson IFC 3030/IFC 640
heat detector Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
Intelligent and electronically addressable
3 Johnson IFC 3030/IFC 640
smoke cum heat detector (Multi sensor)
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
4 Fault Isolator Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
5 Addressable control relay modules Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
6 Addressable monitoring module Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
7 Addressable Single action Manual Call Points Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Edwards EST3
Round speaker (should be directly
Honeywell Esser 3000
interfaced/connected with Fire panel for
10 Johnson IFC 3030/IFC 640
Emergency Voice Evacuation System Ceiling
Notifier
mounting arrangement (2 watts)
Siemens Fire Finder series
STR-34
Sl.No Product Description Tender Approved Makes
Edwards EST3
Round speaker (should be directly
Honeywell Esser 3000
interfaced/connected with Fire panel for
11 Johnson IFC 3030/IFC 640
Emergency Voice Evacuation System Wall
Notifier
/Column mounting arrangement (2 watts)
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
2-way communication Addressable Fire
12 Johnson IFC 3030/IFC 640
Fighter's Telephone Jack
Notifier
Siemens Fire Finder series
Edwards EST3
Honeywell Esser 3000
13 2-way communication Fire Fighter's Handset Johnson IFC 3030/IFC 640
Notifier
Siemens Fire Finder series
Honeywell
Johnson
14 Response indicator unit.
Schneider
Siemens
D-LINK
15 Layer switch Cisco
Netgear
Molex
Panduit
16 Optic Fibre Communication Cable 6 core R&M
Systimax
TYCO AMP
Batra Henlay
Caliplast
Lapp kabel
Copper, multi strand, ATC, Mylar Taped Neolex
17
shielded armoured cable Polycab
Rolex
RR Kabel
Technoflex
Batra Henlay
Caliplast
Lappkabel
Neolex
32 Armoured power cables
Polycab
Rolex
RR Kabel
Technoflex
Batra Henlay
Caliplast
Lappkabel
Neolex
18 LAN cable. (Cat- 6)
Polycab
Rolex
RR Kabel
Technoflex
STR-35
Sl.No Product Description Tender Approved Makes
Birla-3M
Raychem
19 LT Jointing Kit / Termination
REPL
Safe Kit
Baliga Lighting
Cable Glands Double Compression with
20 Comet
earthing links
Cosmos
Control Well
21 PVC Glands
Lapp
Comet
Cosmos
22 Bi-Metallic Cable Lug
Hax Brass (Copper Alloy India)
Anchor
Lapp Kabel
Havells
PVC insulated copper conductor stranded
23 L&T
flexible wires (HFFR) -
Polycab
Rallison Cables
R R Kabel
AKG
24 Metallic / GI Conduit (ISI approved) BEC
Vimco
PLICA India Pvt. Ltd.
25 Lead Coated Flexible GI Conduit
Flexicon
AKG
BEC
D Plast
26 PVC Conduit & Accessories (ISI approved) Dimond
Duraline
Polypack
Precision
ABB Lumina/ Classic
Anchor (Roma)
Crabtree
27 Switch & Socket
Legrand (Mosaic)
Siemens
Wipro (North-West)
Connect Well
Elmex
28 Terminal Blocks
Wago
29 Industrial Socket
Clipsal
Gewiss
29.a Splash Proof Neptune Balls
ELCON-PCE
Schneider Electric
STR-36
Sl.No Product Description Tender Approved Makes
BCH
29.b Metal Clad
MDS
ABB
BCH
GE Power Control
30 Timer Larsen & Toubro
MDS Legrand
Schneider Electric
Siemens
Amar Raja
BCH
Exide
31 Sealed Maintenance Free Batteries
Global (Rocket)
Hitachi
Shinkobe
Emerson
APC-MGE
32 UPS Socomec
GE
EATON
Indiana
MK (raceway)
Maheshwari Electricals
OBO Bettermann
33 Cable Trays (Factory Fabricated) / Raceways Profab
Pushpak
Techno Fab
Gripple
ABB (T Max)
Larsen & Toubro (D-Sine)
34 Moulded Case Circuit Breaker (MCCB)
Schneider Electric (Compact NSX/ NS)
Siemens (3VL)
ABB
Hager (L & T)
35 Motor Protection Circuit Breaker(MPCB)
Schneider Electric
Siemens
ABB
Hager (L&T)
36 Miniature Circuit Breakers (MCB)
Schneider Electric (Multi 9)
Siemens
STR-37
Addendum 2 - Fire Alarm & Public Address System Works for TRIL IT City Tower 3 & 4
Sl.No Reference Queries Clarification
Fire Alarm & Public Address System
1 General Only BMS Integration with FAS has been considered in our offer, please confirm Ok
Quoted for Conventional Hooter cum strobe with Control module and power
2 Bill of Quantities Section A Item 1.10 supply as addressable Hooter Cum strobe is not available in the Edwards make. Ok, Control module to be consider for each hooter for addressing.
Please confirm.
We have proposed System Sensor(By Honeywell) Response indicator. Please
3 Bill of Quantities Section A Item 1.17 OK
confirm.
As per the Pre-bid clarification and given schematic the FACP panels in Tower-3
and Tower-4 are interconnected, but the required cable for connectiing both the
4 General Refer Section 3 Bill of Quantities R2, Section-C- Line Item a -1.2
panels is not given in the BOQ. Please provide the cable with qty to propose.
Please clarify.
32 Bill of Quantities Section B Item 1.8 Only FAS GUI based soft integration with existing BMS is required. PA to be X-Smart (Sytem Management Software) considered for PAS
integrated with FAS via modules. Which required to be considered in this line
item. No PA software is present in existing towers.
Our detector comes with 3 programmed sensitivity settings.
33 General Ok
It was accepted by Employer
The specification provided in Hooter cum strobe line items seems more of
34 Bill of Quantities Section A Item 1.10 speaker. We like to inform that hooter as a standard comes with 85 / 90 dBA Ok
rating. It was accepted by Employer
We will quote UL listed beam detector of Fireray / Honeywell system sensor make.
35 Bill of Quantities Section A Item 1.13 Ok. Beam detector must be compatible with the FACP
It was accepted by Employer
During site visit we observed that the BMS are security system at site is partly
commissioned.
yes, integration with proper workability is in your scope. While
In continuation to the same, we would like to clarify that the responsibility of
integration if any product damage or found any error in the existing
integration of new system with existing software will be in our scope for which we
38 General system, will be the responsible to correct the same and make the system
will take support of respective OEMs. However, we would require some support
good in workability condition.software handling & maintaining further
of existing vendor in terms of availability of access of complete system. Further,
will be in the appointed contractor's scope.
the responsibility of maintaining DLP of existing system will remain with existing
vendor only.
In each Tower there is total 1443 detectors given in the BOQ and the loop capacity
of the panel is 159 detectors and 159 devices per loop. As per the tender
specification "each loop shall be provided with 15% spare capacity". So
40 Bill of Quantities Section A Item 1.1 Ok
considering 15% spare in each loop, to connect 1443 detectors 11 loop panel is
required. So We have considered 1 Nos 10 Loop & 1 Nos 2 Loop Non Expandable
Panel For the same which is suitable for the same . Please confirm .
Bill of Quantities Section A Item 1.3 & As the BOQ Qty for this is zero , so we understand , Graphics & Server For the
41 Ok
1.4 same will be integrated to existing T1 & T2 .
42 Bill of Quantities Section A Item 1.7 We have Quoted For Rate of Rise Temperature Heat Detetctor. Kindly comply to technical specification.
We have considered Dual Action Push Pull Type Convenstional Manual Call Point
43 Bill of Quantities Section A Item 1.8 with Monitor Module , suitable For the Same. Push Pull Type is better than Break Kindly comply to technical specification / Quote as per existing make
Glass Type in terms of Durability ,usablity & maintaince ..
We have considered Honeywell System Sensor Make SYS-HS Hooter cum Strobe
with Control Module which is externally Powered by reputed Micropwer Make
44 Bill of Quantities Section A Item 1.10 Non UL 24V PSU . One PSU will cater 4-5 Hooters . We understand , Customer to Ok
provide UPS power near all PSU , so battery backup for the same is not considered
.
We have considered Honeywelll System Sensor make Conventional Beam
Detetctor with Monitor Module suitable For the same .. As distance is not
45 Bill of Quantities Section A Item 1.13 Ok
mentioned so we have considered 70 Mtr supported Beam Detetcor. Testing Kit is
already available in existing phase . Additional not Required .
We understand necessary cables to be considered in Cable Qty in Sr No C-a1.1. So
46 Bill of Quantities Section A Item 1.17 Ok
we have not considered any Cable price in this line item .
47 Bill of Quantities Section B item 1.10 a We have considered Fire Integrated Digital PA with Non UL & NON EN Speakers . Kindly comply to technical specification.
As per Speaker Wattage count with 20% Spare we have considered 7 Nos of
Amplifier & 1 backup as N+1 Amplfier redundacy . 1 nos 42U rack also considered
48 Bill of Quantities Section B item 1.12 a Kindly comply to technical specification.
in each tower with same as per BOQ .. As we have Quoted 500W amplifers so PA
BOQ SR NO B: 1.12 b & c not required , hence not quoted .
As confirmed in the Query Resposne , We have quoted Honeywell make 6W Non
49 Bill of Quantities Section B item 1.3 UL -Non EN Ceiling Speaker with Metal backbox suitable for the same . Please OK
confirm.
As confirmed in the Query Resposne , We have quoted Honeywell make 6W Non
50 Bill of Quantities Section B item 1.4 OK
UL -Non EN ABS wall Mount Speaker with suitable for the same . Pls confirm.
We have Quoted the same Models approved & installed in the exiting phase T1 &
T2. 20W unidirectional projected loudspeaker, which hasa sturdy aluminum
51 Bill of Quantities Section B item 1.5 OK
enclosure finished in unobtrusive white color with ABS Front . The loudspeaker is
CE and RoHS complied.
We have Quoted the same Models approved & installed in the exiting phase T1 &
52 Bill of Quantities Section B item 1.7 OK
T2
BOQ Qty for this is 2 , but the BOQ description mentions to be integrated with
exiting PC graphics in Main Fire Command Center . That’s why PC in Sr No 1.9 is
kept Zero .
53 Bill of Quantities Section B item 1.8 Kindly comply to technical specification.
One Software can cater 20 DCS controllers , existing Phase has 11 Nos of DCS &
this has only 2 . Which is sufficent to integrate with existing software in command
center .. hence we have not Quoted For this line item as not required .
We have Quoted Same Specs & Make model as approved & installed in the T1 &
Bill of Quantities Section C item 1.1 &
54 T2 .. Please share the running meter Qty .. Now we have considered 12 Meter per Qty provided in running mtrs. Refer Section 3 Bill of Quantities R2
1.2
device as standard . Pls confirm .
We have Quoted Same Specs & Make model as approved & installed in the T1 &
Bill of Quantities Section C item 1.1 &
55 T2 .. Please share the running meter Qty .. Now we have considered 20 Meter per Qty provided in running mtrs. Refer Section 3 Bill of Quantities R2
1.3
speaker as standard . Pls confirm .
56 General We have Considered Same JB appoved & installed in T1 & T2 . Ok
Any kind of Civil works, core cutting, wall chasing not in Honeywell scope.
57 General Ok
Hoenywell to coordinate with Civil vendor for the same .
DIMENSIONAL DRAWING
Cable Description :
600/1000 V, 2C x 1.5mm², TCu/GMT/ XLPE/OSCR/LSZH/GSWA/LSZH: FIRE SURVIVAL
Stranded (Class 2) non-compacted circular Annealed Tinned Copper Conductor & Over Glass mica tape lapped, Extruded XLPE insulation,
Two cores laid up together, Overall Aluminium Mylar tape screening alongwith ATC drain wire 0.5 sq. mm (7-strand) in continous contact with
aluminium side & Extruded - Inner layer LSZH, Galvanised Steel round wire single layer armouring, & Outer layer LSZH compound sheathed
Fire Survival cable constructed generally as per IS:7098 (Part 1), BS: 7846, BS: 6387 & client specification.
Insulation:
Extruded (XLPE)
Thickness - 0.7 mm (nom)
Overall Screen -
Aluminium Mylar Tape
Inner sheath:
Extruded LSZH compound,
Thickness - 0.3mm (min)
Outer Sheath:
Extruded LSZH compound,
1) Schematic colour only for representation not to match product. Thickness - 1.24 mm (min)
2) Binder tape/s shall be provided where ever applicable/required.
3) Non-hygroscopic fillers shall be provided wherever required.
4) Overall shield shall be Aluminium backed by mylar tape with 25% overlap and 100% coverage.minimum shield
thickness shall be 0.024 mm.Drain wire shall be 0.5 sq.mm. (7/0.3) Multistrand tinned annealed copper conductor.
DATA SHEETS FOR XLPE COPPER FIRE SURVIVAL FP-120 CABLE ARMOURED
1 GENERAL
Name of Manufacture M/s MASTERFLEXO CABLES PVT. LTD.,
Brand Name MASTERFLEX
Cable Type/Code TCu/GMT/ XLPE/OSCR/LSZH/GSWA/LSZH : FIRE SURVIVAL
Voltage Grade 650/1100 volts
Standards Applicable IS:7098 (Part I) 1988, BS: 7846 & BS: 6387, IS:5831-1984, IS:8130-1984, IS:3975
2 CONDUCTOR
Material Stranded Non-Compacted Circular Annealed Tinned Copper Conductor as per Class-2 of IS:8130-2013
Cross Sectional Area sq.mm. 1.5
No. of Strands nos 7
Dia.of each strand (before stranding) mm 0.53
Max.C.R.@ 20° C. ohms/km 12.2
Fire Survival Tape Mica tape helically applied with 100% coverage and 25% overlap
Overall diameter over FS tape (appx) 1.9 ± 0.2
3 INSULATION
Material Extruded XLPE as per IS 7098-1/88 (latest)
Thickness (Nom.) mm 0.7
Dia. Over insulation mm 3.4 ± 0.2
CONDUCTOR TEMPERATURE
Rated 90 Deg .C.
During short circuit 250 Deg. C.
Cabled core laid up overall shielded with Aluminium backed Mylar tape (0.024 mm min thickness) helically wrapped with 25 %
4 OVERALL SHIELDING overlap & 100% coverage, ATC Drain wire of 0.5 sq. mm(7/0.3 -strands) under Aluminium Mylar / Polyster tape in continuous
contact with Aluminium side of the tape
5 INNER SHEATH
Material Extruded LSZH Compound
Thickness (Min.) mm 0.3
Colour Black
6 ARMOUR
Material Galvanised steel round wire as per IS : 3975
Size mm 0.9 ± 0.05
7 OUTER SHEATH
Material Extruded LSZH Compound
Thickness (Minimum) mm 1.24
Colour RED
Approx.Overall dia of cable mm 14.3
Tolerance on overall dia +/- 2 mm
Approx. wt of cable in gm/mtr 358
8 LSZH Properties
oxygen Index at room temperature 32 min. as per ASTM-D-2863
Temperature Index. Min. 250 deg.c. as per ASTM-D-2863
Smoke density Rating 60% max. as per ASTM-D-2843
Acid Gas Generation 0.5% max. as per IEC-754-1
Flamability test as per IS:7098 Pt.1
Buring of sample after removal of flame max 60 sec. & Uncharred protion min. 50 mm
& IS 10810 Pt. 53
Circuit integrity Fire survival test As per BS; 7846 Category A, suitable to sustain @ 950 ⁰C for 120 minutes.
9 ELECTRICAL DATA
A.C. resistance at 90 deg C Ohms/km 15.6
Short circuit current rating KA 0.21
Approx Capacitance µF/km 0.17
Approx. Reactance at 50Hz Ohms/km 0.1113
Approx. impedance at 50Hz Ohms/km 15.6
10 Current Rating
In ground @ 30 deg.C 33
In Air @ 40 deg.C (ambient) 29
11 Core indentification Red & Black
12 Drum Length 1drum x 1000 mtr.
Tolerance (%) +/- 5
13 Printing/Embossing MASTERFLEXO CABLE ELECTRIC XLPE SHIELDED 1100V 2C x 1.5 SQ MM FS FP-120 BS 6387 GENERALLY IS: 7098 PT1 INDIA 2023