TECHNICAL DATASHEET
GALAXY - V 250 GX
GALAXY “GX” MAIN DATA
Continuous power (PRP)
245.0 (kVA)
Continuous power (PRP)
196.0 (kW)
Stand-by power (LTP)
265.0 (kVA)
Stand-by power (LTP)
212.0 (kW)
Voltage • Frequency • Power 460V •60Hz • 0.8 cosφ
Factor
DIMENSIONS AND WEIGHT
Width 1350 mm
For illustrative purposes only
Length 3770 mm
Height 2270 mm
ENGINE
Weight 3070 kg
Engine brand VOLVO-PENTA
Engine model TAD840GE
Cylinders 6 ALTERNATOR
Speed 1800 r.p.m. Alternator brand STAMFORD
Cubic capacity 7.70 l Alternator model UCI274H
Air intake Turbocharged P.R.P. Power 245.0 kVA
Standard voltage 24 Vdc L.T.P. Power 265.0 kVA
Optional voltage Vdc Connection Series star
Sae 2-11½ Phases 3PH+N
BMEP 2000 kPa Winding 12 terminals
Winding 311
Cooling Water
Terminal Number 12 nr.
Flywheel P.R.P. Power 229.0 kW
IP Protection 23
Flywheel Stand-by Power 252.0 kW
Electronic regulator AS440
Fuel Cons. at 100% (L.T.P.) 63.2 l/h
Precision 1.0 ±%
Fuel Cons. at 100% (P.R.P) 58.2 l/h
Fuel Cons. at 75% (P.R.P.) 43.8 l/h BASEFRAME
Fuel Cons. at 50% (P.R.P.) 29.6 l/h Model GV121
Fuel Cons. at 25% (P.R.P.) 17.1 l/h Standard tank 500 l
Electronic regulator Standard Optional tank 0 l
Precision class G3 Oversized tank* 0 l
Oil quantity 27.0 l
CANOPY & SILENCER
Engine Antifreeze capacity 17.0 l
Canopy model GV121
Radiator type Tropical
Silencer model MSR/a 100
Heat from radiator 163.0 kW
Silencer outlet diameter 114.0 mm
Heat from exhaust 192.0 kW
Standard reference conditions temperature 25°C, altitude 100m asl, relative humidity 30%,
Heat from radiation 0.0 kW atmospheric pressure 100 kPa (1 bar), power factor 0.8 lag, balanced load - non
distortional. Fuel consumption is nominal and refers to specific weight 0,850kg/l. Sound
Exhaust temperature 539 °C power values refer to free field conditions: the installation site may influence the values.
Dimensions, weights and other specifications contained in the technical data sheet and
Cooling air flow 360.00 m³/min related attachments are nominal, subject to tolerances and refer to the model with standard
equipment; any optional and additional equipment/accessories can modify weight,
Combustion air flow 16.00 m³/min dimensions, performance.
P.R.P. Prime Power-Continuous power at variable load: The power that a genset can
Exhaust gas flow 0.00 m³/min supply in continuous service at a variable load for an unlimited number of hours per year
while respecting the maintenance intervals established in the environmental conditions
TA Luft Not available stated by the Manufacturer. according to ISO8528-1. The average power supplied over time
and any applicable overload must be less than the percentages stated by the Manufacturer.
TA Luft/2 Not available L.T.P. Limited-time running power-Limited power: The maximum power that a genset
can supply for a limited time respecting the maintenance intervals established in the
environmental conditions stated by the Manufacturer according to ISO 8528-1.The number
EPA Not available
of hours per year is stated by the Manufacturer. Overload is not permitted.
Stage Not available
The data contained in this document is nominal and refers to the standard equipped model and is not binding. Visa S.p.A. reserves the
right to revise the information without notice per our policy of continuous product development and improvement.
VISA S.p.A. - ITALY- CERTIFIED ISO 9001-2015 e ISO 14001-2015 - www.visa.it