0% found this document useful (0 votes)
27 views34 pages

Q Series QnU CPU Ethernet Driver How To Connect HMI GP Pro EX and CPU Mitsubishi Mit - Qnue

The document is a manual for the Mitsubishi Electric Q Series QnU CPU Ethernet Driver, detailing connection procedures for external devices and displays. It includes sections on system configuration, device selection, communication settings, and setup items, with specific examples and notes for proper configuration. The manual emphasizes the importance of matching settings between the display and external devices to ensure successful communication.

Uploaded by

Thanh Baron
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views34 pages

Q Series QnU CPU Ethernet Driver How To Connect HMI GP Pro EX and CPU Mitsubishi Mit - Qnue

The document is a manual for the Mitsubishi Electric Q Series QnU CPU Ethernet Driver, detailing connection procedures for external devices and displays. It includes sections on system configuration, device selection, communication settings, and setup items, with specific examples and notes for proper configuration. The manual emphasizes the importance of matching settings between the display and external devices to ensure successful communication.

Uploaded by

Thanh Baron
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

Mitsubishi Electric Corporation

Q Series QnU CPU


Ethernet Driver

1 System Configuration....................................................................................................... 3
2 External Devices Selection .............................................................................................. 8
3 Communication Settings .................................................................................................. 9
4 Setup Items .................................................................................................................... 15
5 Supported Devices......................................................................................................... 19
6 Device Code and Address Code.................................................................................... 27
7 Error Messages.............................................................................................................. 33

1
Q Series QnU CPU Ethernet Driver

Introduction
This manual describes how to connect the Display and the External Device (target PLC).
In this manual, the connection procedure is described in the sections identified below:

1 System Configuration
 "1 System Configuration" (page 3)
This section lists the types of External
Devices and SIO that you can connect.

2 External Devices Selection


 "2 External Devices Selection" (page 8)
Select a model (series) of the External
Device and its connection method.

3 Communication Settings
 "3 Communication Settings" (page 9)
This section shows setting examples for
communicating between the Display and
the External Device.

4 Setup Items
 "4 Setup Items" (page 15)
This section describes communication
setup items on the Display.
Set the Display's communication settings
in GP Pro-EX or in offline mode.

Operation

GP-Pro EX Device/PLC Connection Manual 2


Q Series QnU CPU Ethernet Driver

1 System Configuration

The system configuration in the case when the External Device and the Display are connected is shown.

Setting
Series CPU Link I/F SIO Type
Example

Q03UDECPU
Q04UDEHCPU Setting
Q06UDEHCPU Ethernet (UDP) Example 1
Q10UDEHCPU (page 9)
Q13UDEHCPU
Q20UDEHCPU Ethernet connector on the
Q26UDEHCPU CPU unit
Q03UDVCPU
Q04UDVCPU Setting
Q06UDVCPU Ethernet (TCP) Example 2
Q13UDVCPU (page 12)
Q26UDVCPU

Q03UDCPU Setting
Q04UDHCPU Ethernet (UDP) Example 1
Q06UDHCPU Ethernet connector on (page 9)
Q10UDHCPU Universal Model built-in
MELSEC-Q
Q13UDHCPU Ethernet port QCPU*1 Setting
Series Q20UDHCPU Ethernet (TCP) Example 2
Q26UDHCPU (page 12)

Setting
Q02CPU Ethernet (UDP) Example 1
Q02HCPU Ethernet connector on (page 9)
Q06HCPU Universal Model built-in
Q12HCPU Ethernet port QCPU*2 Setting
Q25HCPU Ethernet (TCP) Example 2
(page 12)

Setting
Ethernet (UDP) Example 1
Ethernet connector on (page 9)
Q172DCPU
Universal Model built-in
Q173DCPU
Ethernet port QCPU*3 Setting
Ethernet (TCP) Example 2
(page 12)
*1 Since the Universal Model QCPU (Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q10UDHCPU,
Q13UDHCPU, Q20UDHCPU, Q26UDHCPU) cannot be directly connected to the Display, use it with
a Multi CPU System.
*2 Since the High Performance model QCPU (Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU)
cannot be directly connected to the Display, use it with a Multi CPU System.
*3 Since the motion CPU (Q172DCPU, Q173DCPU) cannot be directly connected to the Display, use it
with a Multi CPU System.

GP-Pro EX Device/PLC Connection Manual 3


Q Series QnU CPU Ethernet Driver

 Connection Configuration

• Use Straight cables for Ethernet cables.


Crossing cables can also be used for connecting the External Device with the Display directly
using an Ethernet cable.

• 1:1 Connection
<HUB Connection>

<Direct Connection>

• 1:n Connection

GP-Pro EX Device/PLC Connection Manual 4


Q Series QnU CPU Ethernet Driver

• n:1 Connection

• For UDP communication with drivers (Ver.1.12.02 or later), make settings so that two or more
Display units will not start communication all at once.
If communication starts all at once, the communication processing load becomes large and as a
result, communication cannot be made normally.
Please check the followings.

When starting the system, start the External Device and then start the Display.
When starting the Display, make the following settings. When restarting or resetting the external
device during operation, be sure to turn off all Displays once.
• When starting all Displays at a time:
Adjust [Start Time] in [Display Unit] of the GP-Pro EX so that the setting time can be different
in each Display.
• When starting the Displays one by one:
Start from the Displays orderly whose [Start Time] setting is shorter in [Display Unit] of the GP-
Pro EX.

GP-Pro EX Device/PLC Connection Manual 5


Q Series QnU CPU Ethernet Driver

• n:m Connection

• For UDP communication with drivers (Ver.1.12.02 or later), make settings so that two or more
Displays units will not start communication all at once.
If communication starts all at once, the communication processing load becomes large and as a
result, communication cannot be made normally.
Please check the followings.

When starting the system, start the External Device and then start the Display.
When starting the Display, make the following settings. When restarting or resetting the external
device during operation, be sure to turn off all Displays once.
• When starting all Displays at a time:
Adjust [Start Time] in [Display Unit] of the GP-Pro EX so that the setting time can be different
in each Display.
• When starting the Displays one by one:
Start from the Displays orderly whose [Start Time] setting is shorter in [Display Unit] of the GP-
Pro EX.

GP-Pro EX Device/PLC Connection Manual 6


Q Series QnU CPU Ethernet Driver

• Multi-CPU System

• For the CPU unit numbers, the number "1" is assigned to the CPU slot, and any subsequent
units are aligned to the right and assigned "2", "3", "4", in order.
• The multi-CPU system enables you to access a CPU that is not directly connected.
For External Devices that can be used in a multi-CPU system, refer to the External Device
manual.

GP-Pro EX Device/PLC Connection Manual 7


Q Series QnU CPU Ethernet Driver

2 External Devices Selection

Select the External Device to be connected to the Display.

Setup Items Setup Description


Select the maker of the External Device to be connected. Select "Mitsubishi Electric
Maker
Corporation".
Select a model (series) of the External Device to be connected and connection method.
Select "Q Series QnU CPU Ethernet".
Series In System configuration, check to make sure the external device to which you are
connecting is supported in "Q Series QnU CPU Ethernet".
 "1 System Configuration" (page 3)
Check this option when you synchronize the system data area of Display and the device
(memory) of External Device. When synchronized, you can use the ladder program of
External Device to switch the display or display the window on the display.
Cf. GP-Pro EX Reference Manual Appendix "LS Area (Direct Access Method
Use System Area Area)"
This can also be set in GP-Pro EX or in the Display's offline mode.
Cf. GP-Pro EX Reference Manual "Display Unit (System Area) Settings Guide"
Cf. Maintenance/Troubleshooting Manual "Main Unit - System Area Settings"
Port Select the Display port to be connected to the External Device.

GP-Pro EX Device/PLC Connection Manual 8


Q Series QnU CPU Ethernet Driver

3 Communication Settings

Examples of communication settings of the Display and the External Device, recommended by Pro-face, are
shown.

3.1 Setting Example 1


 GP-Pro EX Settings
 Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

• When directly connecting an External Device (1:1 connection) using the cross cable, you
need to set 6 (sec) or more for [Timeout].
• In the case of "n:1" or "n:m" connection, you need to set 3 (sec) or more for [Timeout] and
2 or more for [Retry].
• When communication is made from the Display before the initialization processing in the
External Device is completed, the communication error occurs to the Display. In this case,
adjust the time in [Timeout].
When the motion CPU is used in the multiple CPU system especially, adjust [Timeout] to
10 (sec) or more.

GP-Pro EX Device/PLC Connection Manual 9


Q Series QnU CPU Ethernet Driver

 Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the External Device and click [Settings] . To connect multiple External Devices, from
[Device-Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.

 Notes
• Check with the network administrator about the IP address.
• Be sure not to duplicate IP addresses on the same network.
• Set the IP address of the External Device under [Individual Device Settings].
• You need to set the IP address of the Display in its offline mode.

GP-Pro EX Device/PLC Connection Manual 10


Q Series QnU CPU Ethernet Driver

 External Device Settings


Use the ladder software (GX-Developer Ver.8.68W or later) for the External Device communication settings.
For QUDVCPU, use GX Works2 1.95Z or later.
Refer to your External Device manual for details.

1 Start up the ladder software.


2 From the [Project] menu, select [New project] to display the [New Project] dialog box.
3 Select the External Device you want to use from [PLC Type], and then click [OK].
4 Double-click [PLC Parameter] in the tree view to display the [Q parameter setting] dialog box.
5 Select the [Built-in Ethernet port] tab.
6 Enter "192.168.0.1" in [IP address].
7 Click [Open settings] to display the [Built-in Ethernet port open setting] dialog box.
8 Set each item as follows:
Protocol Open Method
UDP MELSOFT connection

9 Click [End].

10 Click [End] in the [Q parameter setting] dialog box.

11 Transfer the communication settings to the External Device.

This completes the External Device setup.

 Notes
• Check with the network administrator about the IP address.
• Be sure not to duplicate IP addresses on the same network.

GP-Pro EX Device/PLC Connection Manual 11


Q Series QnU CPU Ethernet Driver

3.2 Setting Example 2


 GP-Pro EX Settings
 Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

• When directly connecting an External Device (1:1 connection) using the cross cable, you
need to set 6 (sec) or more for [Timeout].
• In the case of "n: 1" or "n:m" connection, you need to set 3 (sec) or more for [Timeout].
• When communication is made from the Display before the initialization processing in the
External Device is completed, the communication error occurs to the Display. In this case,
adjust the time in [Timeout].
When the motion CPU is used in the multiple CPU system especially, adjust [Timeout] to
10 (sec) or more.

GP-Pro EX Device/PLC Connection Manual 12


Q Series QnU CPU Ethernet Driver

 Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the External Device and click [Settings] . To connect multiple External Devices, from
[Device-Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.

 Notes
• Check with the network administrator about the IP address.
• Be sure not to duplicate IP addresses on the same network.
• Set the IP address of the External Device under [Individual Device Settings].
• You need to set the IP address of the Display in its offline mode.

GP-Pro EX Device/PLC Connection Manual 13


Q Series QnU CPU Ethernet Driver

 External Device Settings


Use the ladder software (GX-Developer Ver.8.68W or later) for the External Device communication settings.
For QUDVCPU, use GX Works2 1.95Z or later.
Refer to your External Device manual for details.

1 Start up the ladder software.


2 From the [Project] menu, select [New project] to display the [New Project] dialog box.
3 Select the External Device you want to use from [PLC Type], and then click [OK].
4 Double-click [PLC Parameter] in the tree view to display the [Q parameter setting] dialog box.
5 Select the [Built-in Ethernet port] tab.
6 Enter "192.168.0.1" in [IP address].
7 Click [Open settings] to display the [Built-in Ethernet port open setting] dialog box.
8 Set each item as follows:
Protocol Open Method
TCP MELSOFT connection

9 Click [End].

10 Click [End] in the [Q parameter setting] dialog box.

11 Transfer the communication settings to the External Device.

This completes the External Device setup.

 Notes
• Check with the network administrator about the IP address.
• Be sure not to duplicate IP addresses on the same network.

GP-Pro EX Device/PLC Connection Manual 14


Q Series QnU CPU Ethernet Driver

4 Setup Items

Set up the Display's communication settings in GP Pro-EX or in the Display's offline mode.
The setting of each parameter must match that of the External Device.
"3 Communication Settings" (page 9)
• You need to set the IP address of the Display in its offline mode.

Cf. Maintenance/Troubleshooting Guide "Ethernet Settings"

4.1 Setup Items in GP-Pro EX


 Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Setup Items Setup Description


Use an integer from 1024 to 65534 to enter the port No. of the Display. If you check [Auto],
the port No. is automatically set.
Port No.
• The [Auto] option can be set only when you select "Ethernet (TCP)" under [Connecting
Method].
Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the response
Timeout
from the External Device.
In case of no response from the External Device, use an integer from 0 to 255 to enter how
Retry
many times the Display retransmits the command.
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving packets
Wait To Send
to transmitting next commands.

GP-Pro EX Device/PLC Connection Manual 15


Q Series QnU CPU Ethernet Driver

 Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the External Device and click [Settings] . To connect multiple External Devices, from
[Device-Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.

Setup Items Setup Description


Set the IP address of the External Device.

IP Address
• Check with the network administrator about the IP address.
• Be sure not to duplicate IP addresses on the same network.

GP-Pro EX Device/PLC Connection Manual 16


Q Series QnU CPU Ethernet Driver

4.2 Setup Items in Offline Mode

• Refer to the Maintenance/Troubleshooting manual for information on how to enter offline


mode or about the operation.

Cf. Maintenance/Troubleshooting Guide "Offline Mode"

 Communication Settings
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings] in offline mode.
Touch the External Device you want to set from the displayed list.

Setup Items Setup Description


Set the Port No. of the Display.
With the UDP connection, the entered port No. is assigned regardless of whether you select
[Fixed] or [Auto].
Port No.
With the TCP connection, select either [Fixed] or [Auto]. If you select [Fixed], use an
integer from 1024 to 65534 to enter the port No. of the Display. If you select [Auto], the
port No. is automatically assigned regardless of the entered value.
Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
Timeout
response from the External Device.
In case of no response from the External Device, use an integer from 0 to 255 to enter how
Retry
many times the Display retransmits the command.
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
Wait To Send
packets to transmitting next commands.

GP-Pro EX Device/PLC Connection Manual 17


Q Series QnU CPU Ethernet Driver

 Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings]. Touch the
External Device you want to set from the displayed list, and touch [Device].

Setup Items Setup Description


Select the External Device to set. Device/PLC name is the title of the External Device set
Device/PLC Name
with GP-Pro EX. (Initial value [PLC1])
Set the IP address of the External Device.

IP Address
• Check with the network administrator about the IP address.
• Be sure not to duplicate IP addresses on the same network.

GP-Pro EX Device/PLC Connection Manual 18


Q Series QnU CPU Ethernet Driver

5 Supported Devices

Range of supported device address is shown in the table below. Please note that the actually supported range of
the devices varies depending on the External Device to be used. Please check the actual range in the manual of
your External Device.
Enter the External Device address in the dialog box below.

1 3

1. Unit number Use an integer from 1 to 4 to enter the unit number of the CPU with which to communicate.
To access a CPU that is directly connected, as in a single CPU system, select "0".
2. Device Select a device.
3. Address Set the address.

GP-Pro EX Device/PLC Connection Manual 19


Q Series QnU CPU Ethernet Driver

5.1 MELSEC Q (Universal Model) Series


: This address can be specified as system data area.

32
Device Bit Address Word Address Remarks
bits

Input Relay X0000-X1FFF X0000-X1FF0

Output Relay Y0000-Y1FFF Y0000-Y1FF0


*1
M00000-M32767 M00000-M32752
Internal Relay
*2
M00000-M61439 M00000-M61424

Special Relay SM0000-SM2047 SM0000-SM2032

Latch Relay L00000-L32767 L00000-L32752

Annunciator F00000-F32767 F00000-F32752

Edge Relay V00000-V32767 V00000-V32752


*1
S0000-S8191 S0000-S8176
Step Relay
*2
S00000-S16383 S00000-S16368

B0000-B7FFF B0000-B7FF0 *1
Link Relay
B0000-BEFFF B0000-BEFF0 *2

Special Link Relay SB0000-SB7FFF SB0000-SB7FF0


*1
TS00000-TS25023 ---
Timer (Contact)
TS00000-TS32767 --- *2

*1
TC00000-TC25023 ---
Timer (Coil)
TC00000-TC32767 --- *2

*1
SS00000-SS25023 ---
Retentive Timer (Contact)
*2
SS00000-SS32767 ---
*1
SC00000-SC25023 ---
Retentive Timer (Coil)
*2
SC00000-SC32767 ---
*1
CS00000-CS25023 ---
Counter (Contact)
CS00000-CS32767 --- *2

*1
CC00000-CC25023 ---
Counter (Coil)
*2
CC00000-CC32767 ---

--- TN00000-TN25023 *1
Timer (Current Value)
*2
--- TN00000-TN32767
*1
Retentive Timer (Current --- SN00000-SN25023
Value) --- SN00000-SN32767 *2

Continued on next page.

GP-Pro EX Device/PLC Connection Manual 20


Q Series QnU CPU Ethernet Driver

32
Device Bit Address Word Address Remarks
bits
*1
--- CN00000-CN25023
Counter (Current Value)
*2
--- CN00000-CN32767

Data Register/ *4
--- D0000000-D4910079
Extended Data Register*3

Special Register --- SD0000-SD2047

Link Register/
--- W000000-W4AEBFF
Extended Link Register*5
*1
--- SW0000-SW6DFF
Special Link Register
--- SW0000-SW6FFF *2

File Register (Normal) --- R00000-R32767

ZR0000000-
File Register (Serial) ---
ZR4849663

--- 0R00000-0R32767

--- 1R00000-1R32767

File Register --- 2R00000-2R32767


(0R to 31R)*6 : : :

--- 30R00000-30R32767

--- 31R00000-31R32767

U3E0-10000-
---
U3E0-24335

U3E1-10000-
---
Common device for Multiple U3E1-24335
CPU*7 U3E2-10000-
---
U3E2-24335

U3E3-10000-
---
U3E3-24335
*1 For the universal model QCPU with a serial number whose first 5 digits is less than "10042" .
*2 For the universal model QCPU with a serial number whose first 5 digits is "10042" or more.
*3 Extended data register can be used in the case of the universal model QCPU with a serial number whose
first 5 digits is less than "09042".
*4 You can set the multi-CPU system in the system data area as well.
*5 Extended link register can be used in the case of the universal model QCPU with a serial number whose
first 5 digits is less than "09042".
*6 Set the block number at the beginning of the device name. This is a device notation compatible with GP-
Pro/PBIII for Windows. When you specify a new device, we recommend using the file register (serial).
*7 For the Multi CPU System configuration, the available points should be as follows:
2 CPUs: 14k points or less
3 CPUs: 13k points or less
4 CPUs: 12k points or less

GP-Pro EX Device/PLC Connection Manual 21


Q Series QnU CPU Ethernet Driver

• The address notation varies depending on the unit number you select.
(Example) When "0" is selected for the unit number:
D 0010
Address
Device

(Example) When "1" is selected for the unit number:


1 / D 0010
Address
Device
Unit number

• For system data area, refer to the GP-Pro EX Reference Manual.

Cf. GP-Pro EX Reference Manual Appendix "LS Area (Direct Access Method Area)"

• Please refer to the precautions on manual notation for icons in the table.
 "Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual 22


Q Series QnU CPU Ethernet Driver

5.2 MELSEC Q (High Performance Model) Series


: This address can be specified as system data area.

32
Device Bit Address Word Address Remarks
bits

Input Relay X0000-X1FFF X0000-X1FF0

Output Relay Y0000-Y1FFF Y0000-Y1FF0

Internal Relay M00000-M32767 M00000-M32752

Special Relay SM0000-SM2047 SM0000-SM2032

Latch Relay L00000-L32767 L00000-L32752

Annunciator F00000-F32767 F00000-F32752

Edge Relay V00000-V32767 V00000-V32752

Step Relay S0000-S8191 S0000-S8176

Link Relay B0000-B7FFF B0000-B7FF0

Special Link Relay SB000-SB7FF SB000-SB7F0

Timer (Contact) TS00000-TS23087 ---

Timer (Coil) TC00000-TC23087 ---

Retentive Timer (Contact) SS00000-SS23087 ---

Retentive Timer (Coil) SC00000-SC23087 ---

Counter (Contact) CS00000-CS23087 ---

Counter (Coil) CC00000-CC23087 ---

Timer (Current Value) --- TN00000-TN23087

Retentive Timer (Current


--- SN00000-SN23087
Value)

Counter (Current Value) --- CN00000-CN23087

Data Register --- D00000-D25983 *1

Special Register --- SD0000-SD2047

Link Register --- W0000-W657F

Special Link Register --- SW000-SW7FF

File Register (Normal) --- R00000-R32767

ZR0000000-
File Register (Serial) ---
ZR1042431

Continued on next page.

GP-Pro EX Device/PLC Connection Manual 23


Q Series QnU CPU Ethernet Driver

32
Device Bit Address Word Address Remarks
bits

--- 0R00000-0R32767

--- 1R00000-1R32767

File Register --- 2R00000-2R32767


(0R to 31R)*2 : : :

--- 30R00000-30R32767

--- 31R00000-31R26623
*1 You can set the multi-CPU system in the system data area as well.
*2 Set the block number at the beginning of the device name. This is a device notation compatible with GP-
Pro/PBIII for Windows. When you specify a new device, we recommend using the file register (serial).

• The address notation varies depending on the unit number you select.
(Example) When "0" is selected for the unit number:
D 0010
Address
Device

(Example) When "1" is selected for the unit number:


1 / D 0010
Address
Device
Unit number

• For system data area, refer to the GP-Pro EX Reference Manual.

Cf. GP-Pro EX Reference Manual Appendix "LS Area (Direct Access Method Area)"

• Please refer to the precautions on manual notation for icons in the table.

 "Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual 24


Q Series QnU CPU Ethernet Driver

5.3 Q Series Motion Controller


: This address can be specified as system data area.

32
Device Bit Address Word Address Remarks
bits

Input Relay X0000-X1FFF X0000-X1FF0

Output Relay Y0000-Y1FFF Y0000-Y1FF0

Internal Relay M00000-M08191 M00000-M08176

Special Relay SM0000-SM2255 SM0000-SM2240

Annunciator F00000-F02047 F00000-F02032

Link Relay B0000-B1FFF B0000-B1FF0

Data Register --- D0000000-D0008191

Special Register --- SD0000-SD2255

Link Register --- W0000-W1FFF

U3E0-10000-
---
U3E0-24335

U3E1-10000-
---
Common device for Multiple U3E1-24335
CPU*1 U3E2-10000-
---
U3E2-24335

U3E3-10000-
---
U3E3-24335

%MR00000-
Motion Register (#)*2 ---
%MR12287*3
*1 For the Multi CPU System configuration, the available points should be as follows:
2 CPUs: 14k points or less
3 CPUs: 13k points or less
4 CPUs: 12k points or less
*2 No. 2 to No. 4 can be allocated to the motion CPU.
*3 Device name with motion CPU is #.

GP-Pro EX Device/PLC Connection Manual 25


Q Series QnU CPU Ethernet Driver

• The address notation varies depending on the unit number you select.
(Example) When "0" is selected for the unit number:
D 0010
Address
Device

(Example) When "1" is selected for the unit number:


1 / D 0010
Address
Device
Unit number

• For system data area, refer to the GP-Pro EX Reference Manual.

Cf. GP-Pro EX Reference Manual Appendix "LS Area (Direct Access Method Area)"

• Please refer to the precautions on manual notation for icons in the table.
 "Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual 26


Q Series QnU CPU Ethernet Driver

6 Device Code and Address Code

Use device code and address code when you set "Device Type & Address" for the address type of the data display
or other devices.

Device Code
Device Device Name Address Code
(HEX)

X 0080

1/X 0180
Value of word address divided
Input Relay 2/X 0280
by 0x10
3/X 0380

4/X 0480

Y 0081

1/Y 0181
Value of word address divided
Output Relay 2/Y 0281
by 0x10
3/Y 0381

4/Y 0481

M 0082

1/M 0182
Value of word address divided
Internal Relay 2/M 0282
by 16
3/M 0382

4/M 0482

SM 0083

1/SM 0183
Value of word address divided
Special Relay 2/SM 0283
by 16
3/SM 0383

4/SM 0483

L 0084

1/L 0184
Value of word address divided
Latch Relay 2/L 0284
by 16
3/L 0384

4/L 0484

Continued on next page.

GP-Pro EX Device/PLC Connection Manual 27


Q Series QnU CPU Ethernet Driver

Device Code
Device Device Name Address Code
(HEX)

F 0085

1/F 0185
Value of word address divided
Annunciator 2/F 0285
by 16
3/F 0385

4/F 0485

V 0086

1/V 0186
Value of word address divided
Edge Relay 2/V 0286
by 16
3/V 0386

4/V 0486

S 0087

1/S 0187
Value of word address divided
Step Relay 2/S 0287
by 16
3/S 0387

4/S 0487

B 0088

1/B 0188
Value of word address divided
Link Relay 2/B 0288
by 0x10
3/B 0388

4/B 0488

SB 0089

1/SB 0189
Value of word address divided
Special Link Relay 2/SB 0289
by 0x10
3/SB 0389

4/SB 0489

TN 0060

1/TN 0160

Timer (Current Value) 2/TN 0260 Word address

3/TN 0360

4/TN 0460

Continued on next page.

GP-Pro EX Device/PLC Connection Manual 28


Q Series QnU CPU Ethernet Driver

Device Code
Device Device Name Address Code
(HEX)

SN 0062

1/SN 0162
Retentive Timer (Current
2/SN 0262 Word address
Value)
3/SN 0362

4/SN 0462

CN 0061

1/CN 0161

Counter (Current Value) 2/CN 0261 Word address

3/CN 0361

4/CN 0461

D 0000

1/D 0100
Data Register /
2/D 0200 Word address
Extended Data Register
3/D 0300

4/D 0400

SD 0001

1/SD 0101

Special Register 2/SD 0201 Word address

3/SD 0301

4/SD 0401

W 0002

1/W 0102
Link Register /
2/W 0202 Word address
Extended Link Register
3/W 0302

4/W 0402

SW 0003

1/SW 0103

Special Link Register 2/SW 0203 Word address

3/SW 0303

4/SW 0403

Continued on next page.

GP-Pro EX Device/PLC Connection Manual 29


Q Series QnU CPU Ethernet Driver

Device Code
Device Device Name Address Code
(HEX)

R 000F

1/R 010F

File Register (Normal) 2/R 020F Word address

3/R 030F

4/R 040F

ZR 000E

1/ZR 010E

File Register (Serial) 2/ZR 020E Word address

3/ZR 030E

4/ZR 040E

Continued on next page.

GP-Pro EX Device/PLC Connection Manual 30


Q Series QnU CPU Ethernet Driver

Device Code
Device Device Name Address Code
(HEX)

0R 0010

1/0R 0110

2/0R 0210 Word address

3/0R 0310

4/0R 0410

1R 0011

1/1R 0111

2/1R 0211 Word address

3/1R 0311

4/1R 0411

2R 0012

1/2R 0112

File Register 2/2R 0212 Word address


(0R to 31R) 3/2R 0312

4/2R 0412

: : :

30R 002E

1/30R 012E

2/30R 022E Word address

3/30R 032E

4/30R 042E

31R 002F

1/31R 012F

2/31R 022F Word address

3/31R 032F

4/31R 042F

2/%MR 0234

Motion Register (#) 3/%MR 0334 Word address

4/%MR 0434

Continued on next page.

GP-Pro EX Device/PLC Connection Manual 31


Q Series QnU CPU Ethernet Driver

Device Code
Device Device Name Address Code
(HEX)

U3E0- 0035

1/U3E0- 0135

2/U3E0- 0235

3/U3E0- 0335

4/U3E0- 0435

U3E1- 0036

1/U3E1- 0136

2/U3E1- 0236

3/U3E1- 0336

Common device for 4/U3E1- 0436


Word address
Multiple CPU U3E2- 0037

1/U3E2- 0137

2/U3E2- 0237

3/U3E2- 0337

4/U3E2- 0437

U3E3- 0038

1/U3E3- 0138

2/U3E3- 0238

3/U3E3- 0338

4/U3E3- 0438

GP-Pro EX Device/PLC Connection Manual 32


Q Series QnU CPU Ethernet Driver

7 Error Messages

Error messages are displayed on the Display screen as follows: "No. : Device Name: Error Message (Error
Occurrence Area)". Each description is shown below.

Item Description
No. Error number
Name of the External Device where an error has occurred. Device/PLC name is the title of
Device Name
the External Device set with GP Pro-EX. (Initial value [PLC1])
Error Message Displays messages related to an error that has occurred.
Displays the IP address or device address of the External Device where an error has
occurred, or error codes received from the External Device.

Error Occurrence Area


• IP addresses are displayed as "IP address (Decimal): MAC address (Hex)".
• Device addresses are displayed as "Address: Device address".
• Received error codes are displayed as "Decimal [Hex]".

Display Examples of Error Messages


"RHAA035: PLC1: Error has been responded for device write command (Error Code: 2[02H])"

• Refer to your External Device manual for details on received error codes.
• Refer to "Display-related errors" in "Maintenance/Troubleshooting Guide" for details on the
error messages common to the driver.

 Error Messages Unique to the External Device


Error No. Error Message Description
(Node Name): The specified CPU unit could not be Appears if you access a CPU
RHxx128
accessed (Address: Device Address) number that is not assigned.

GP-Pro EX Device/PLC Connection Manual 33


Q Series QnU CPU Ethernet Driver

GP-Pro EX Device/PLC Connection Manual 34

You might also like