MR-JE InstructionManual 030128-B
MR-JE InstructionManual 030128-B
MR-JE-_A
SERVO AMPLIFIER
MR-JE-A SERVOAMPLIFIER
MODEL INSTRUCTIONMANUAL
MODEL
CODE 1CW706
B
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310
To use the equipment correctly, do not attempt to install, operate, maintain, or inspect the equipment until
you have read through this Instruction Manual, Installation guide, and appended documents carefully. Do not
use the equipment until you have a full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Note that the CAUTION level may lead to a serious consequence according to conditions.
Please follow the instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols.
Indicates what must not be done. For example, "No Fire" is indicated by .
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this Instruction Manual, keep it accessible to the operator.
A- 1
1. To prevent electric shock, note the following
WARNING
Before wiring and inspections, turn off the power and wait for 15 minutes or more until the charge lamp
turns off. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp
is off or not, always confirm it from the front of the servo amplifier.
Ground the servo amplifier and servo motor securely.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it
may cause an electric shock.
Do not operate switches with wet hands. Otherwise, it may cause an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric
shock.
To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo
amplifier to the protective earth (PE) of the cabinet.
When using an earth-leakage current breaker (RCD), select the type B.
To avoid an electric shock, insulate the connections of the power supply terminals.
A- 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a malfunction, injury,
electric shock, etc.
When the product has been stored for an extended period of time, contact your local sales office.
When handling the servo amplifier, be careful about the edged parts such as corners of the servo
amplifier.
The servo amplifier must be installed in a metal cabinet.
When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used
for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our
products. Please take necessary precautions to ensure that remaining materials from fumigant do not
enter our products, or treat packaging with methods other than fumigation (heat method). Additionally,
disinfect and protect wood from insects before packing products.
A- 3
(2) Wiring
CAUTION
Before removing the CNP1 connector of MR-JE-40A to MR-JE-100A, disconnect the lead wires of the
regenerative resistor from the CNP1 connector.
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly.
Do not install a power capacitor, surge killer, or radio noise filter (optional FR-BIF) on the servo amplifier
output side.
To avoid a malfunction, connect the wires to the correct phase terminals (U, V, and W) of the servo
amplifier and servo motor.
Connect the servo amplifier power output (U, V, and W) to the servo motor power input (U, V, and W)
directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.
Servo amplifier Servo motor Servo amplifier Servo motor
U U
U U
V V
V M V M
W W
W W
The connection diagrams in this instruction manual are shown for sink interfaces, unless stated
otherwise.
The surge absorbing diode installed to the DC relay for control output should be fitted in the specified
direction. Otherwise, the emergency stop and other protective circuits may not operate.
Servo amplifier Servo amplifier
24 V DC 24 V DC
DOCOM DOCOM
Control output RA
Control output RA
signal signal
For sink output interface For source output interface
When the cable is not tightened enough to the terminal block, the cable or terminal block may generate
heat because of the poor contact. Be sure to tighten the cable with specified torque.
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a
malfunction.
A- 4
(4) Usage
CAUTION
When it is assumed that a hazardous condition may occur due to a power failure or product malfunction,
use a servo motor with an external brake to prevent the condition.
Do not disassemble, repair, or modify the equipment.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off in order to prevent a
sudden restart. Otherwise, it may cause an accident.
Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic
interference may be given to the electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break it.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be
used for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor
are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety,
install a stopper on the machine side.
Servo motor
RA
B 24 V DC
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
Provide an adequate protection to prevent unexpected restart after an instantaneous power failure.
A- 5
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn
without covers and safety guards. When the equipment is operated, the covers and safety guards must
be installed as specified. Operation must be performed in accordance with this Instruction Manual.
DISPOSAL OF WASTE
Please dispose a servo amplifier and other options according to your local laws and regulations.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier may malfunction when the
EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Write to the EEP-ROM due to device changes
You must have this Instruction Manual and the following manuals to use this servo. Ensure to prepare
them to use the servo safely.
Relevant manuals
Wires mentioned in this Instruction Manual are selected based on the ambient temperature of 40 ˚C.
A- 6
CONTENTS
1.1 Summary........................................................................................................................................... 1- 1
1.2 Function block diagram..................................................................................................................... 1- 2
1.3 Servo amplifier standard specifications ............................................................................................ 1- 4
1.4 Combinations of servo amplifiers and servo motors ........................................................................ 1- 5
1.5 Function list....................................................................................................................................... 1- 5
1.6 Model designation............................................................................................................................. 1- 7
1.7 Structure ........................................................................................................................................... 1- 8
1.7.1 Parts identification...................................................................................................................... 1- 8
1.8 Configuration including peripheral equipment ................................................................................. 1-10
2. INSTALLATION 2- 1 to 2- 6
1
3.9 Interfaces ......................................................................................................................................... 3-50
3.9.1 Internal connection diagram...................................................................................................... 3-50
3.9.2 Detailed explanation of interfaces............................................................................................. 3-52
3.9.3 Source I/O interfaces ................................................................................................................ 3-56
3.10 Servo motor with an electromagnetic brake .................................................................................. 3-57
3.10.1 Safety precautions .................................................................................................................. 3-57
3.10.2 Timing chart ............................................................................................................................ 3-58
3.11 Grounding ...................................................................................................................................... 3-61
4. STARTUP 4- 1 to 4-36
5. PARAMETERS 5- 1 to 5-44
2
5.1.2 Gain/filter setting parameters ([Pr. PB_ _ ]) ............................................................................... 5- 2
5.1.3 Extension setting parameters ([Pr. PC_ _ ]) .............................................................................. 5- 3
5.1.4 I/O setting parameters ([Pr. PD_ _ ]) ......................................................................................... 5- 5
5.1.5 Extension setting 2 parameters ([Pr. PE_ _ ])............................................................................ 5- 6
5.1.6 Extension setting 3 parameters ([Pr. PF_ _ ])............................................................................ 5- 7
5.2 Detailed list of parameters ................................................................................................................ 5- 8
5.2.1 Basic setting parameters ([Pr. PA_ _ ])...................................................................................... 5- 8
5.2.2 Gain/filter setting parameters ([Pr. PB_ _ ]) .............................................................................. 5-17
5.2.3 Extension setting parameters ([Pr. PC_ _ ]) ............................................................................. 5-28
5.2.4 I/O setting parameters ([Pr. PD_ _ ]) ........................................................................................ 5-38
5.2.5 Extension setting 2 parameters ([Pr. PE_ _ ])........................................................................... 5-42
5.2.6 Extension setting 3 parameters ([Pr. PF_ _ ])........................................................................... 5-43
8. TROUBLESHOOTING 8- 1 to 8-28
3
8.2 Remedies for alarms......................................................................................................................... 8- 6
8.3 Remedies for warnings .................................................................................................................... 8-24
9. DIMENSIONS 9- 1 to 9- 6
4
1. FUNCTIONS AND CONFIGURATION
1.1 Summary
The Mitsubishi general-purpose AC servo MELSERVO-JE series have limited functions with keeping high
performance based on MELSERVO-J4 series.
The servo amplifier has position, speed, and torque control modes. In the position control mode, the
maximum pulse train of 4 Mpulses/s is supported. Further, it can perform operation with the control modes
switched, e.g. position/speed control, speed/torque control and torque/position control. Hence, it is
applicable to a wide range of fields, not only precision positioning and smooth speed control of machine tools
and general industrial machines but also line control and tension control.
With one-touch tuning and real-time auto tuning, you can automatically adjust the servo gains according to
the machine.
The tough drive function, drive recorder function, and preventive maintenance support function strongly
support machine maintenance.
The servo amplifier has a USB communication interface. Therefore, you can connect the servo amplifier to
the personal computer with MR Configurator2 installed to perform the parameter setting, test operation, gain
adjustment, and others.
The MELSERVO-JE series servo motor equipped with an incremental encoder whose resolution is 131072
pulses/rev will enable a high-accuracy positioning.
1- 1
1. FUNCTIONS AND CONFIGURATION
P+ C Servo motor
Diode Dynamic
stack Relay (Note 1) brake circuit
MCCB MC L1 U U
(Note 2) U
V V
Power L2 Current
+ encoder M
supply U U
Regene-
L3 rative W W
TR
CHARGE
lamp
RA B1
Electromagnetic
24 V DC B brake
B2
Control
circuit
Base Voltage Current
CN2
power Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command encoder
input Model Model
position speed
control control
Virtual
motor
DI/O control
Analog Servo-on Personal
(two channel) Input command pulse. computer
Analog monitor Start
(two channel) Malfunction, etc USB
Note 1. The built-in regenerative resistor is not provided for MR-JE-10A and MR-JE-20A.
2. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open.
For the power supply specifications, refer to section 1.3.
1- 2
1. FUNCTIONS AND CONFIGURATION
CHARGE
lamp
Cooling fan RA B1
Electromagnetic
24 V DC B brake
B2
Control
circuit
Base Voltage Current
CN2
power Overcurrent
amplifier detection protection detection
Encoder
Position Virtual
command encoder
input Model Model
position speed
control control
Virtual
motor
DI/O control
Analog Servo-on Personal
(two channel) Input command pulse. computer
Analog monitor Start
(two channel) Malfunction, etc USB
1- 3
1. FUNCTIONS AND CONFIGURATION
1- 4
1. FUNCTIONS AND CONFIGURATION
The following table lists the functions of this servo. For details of the functions, refer to each section
indicated in the detailed explanation field.
Detailed
Function Description
explanation
Section 3.2.1
Position control mode This servo is used as a position control servo. Section 3.6.1
Section 4.2
Section 3.2.2
Speed control mode This servo is used as a speed control servo. Section 3.6.2
Section 4.3
Section 3.2.3
Torque control mode This servo is used as a torque control servo. Section 3.6.3
Section 4.4
Position/speed control switch Using an input device, control can be switched between position control and speed
Section 3.6.4
mode control.
Speed/torque control switch Using an input device, control can be switched between speed control and torque
Section 3.6.5
mode control.
Torque/position control switch Using an input device, control can be switched between torque control and position
Section 3.6.6
mode control.
High-resolution encoder of 131072 pulses/rev is used for the encoder of the servo
High-resolution encoder
motor compatible with the MELSERVO-JE series.
You can switch gains during rotation and during stop, and can use an input device to
Gain switching function Section 7.2
switch gains during operation.
Advanced vibration
This function suppresses vibration at the arm end or residual vibration. Section 7.1.5
suppression control II
Servo amplifier detects mechanical resonance and sets filter characteristics
Adaptive filter II Section 7.1.2
automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo system response is
Low-pass filter Section 7.1.4
increased.
Analyzes the frequency characteristic of the mechanical system by simply connecting
Machine analyzer function an MR Configurator2 installed personal computer and servo amplifier.
MR Configurator2 is necessary for this function.
This function provides better disturbance response in case low response level that
Robust filter [Pr. PE41]
load to motor inertia ratio is high for such as roll send axes.
Slight vibration suppression
Suppresses vibration of ±1 pulse produced at a servo motor stop. [Pr. PB24]
control
[Pr. PA06]
Electronic gear Input pulses can be multiplied by 1/10 to 4000.
[Pr. PA07]
S-pattern
acceleration/deceleration time Speed can be increased and decreased smoothly. [Pr. PC03]
constant
Automatically adjusts the gain to optimum value if load applied to the servo motor
Auto tuning Section 6.3
shaft varies.
Used when the built-in regenerative resistor of the servo amplifier does not have
Regenerative option Section 11.2
sufficient regenerative capability for the regenerative power generated.
1- 5
1. FUNCTIONS AND CONFIGURATION
Detailed
Function Description
explanation
Alarm history clear Alarm history is cleared. [Pr. PC18]
Output signal selection ST1 (Forward rotation start), ST2 (Reverse rotation start), and SON (Servo-on) and [Pr. PD03] to
(device settings) other input device can be assigned to any pins. [Pr. PD20]
Output signal selection The output devices including MBR (Electromagnetic brake interlock) can be assigned [Pr. PD24] to
(device settings) to certain pins of the CN1 connector. [Pr. PD28]
Output signal (DO) forced Output signal can be forced on/off independently of the servo status.
Section 4.5.8
output Use this function for checking output signal wiring, etc.
Command pulse selection Command pulse train form can be selected from among three different types. [Pr. PA13]
Section 3.6.1
(5)
Torque limit Servo motor torque can be limited to any value.
[Pr. PA11]
[Pr. PA12]
Section 3.6.3
(3)
Speed limit Servo motor speed can be limited to any value.
[Pr. PC05] to
[Pr. PC11]
Status display Servo status is shown on the 5-digit, 7-segment LED display. Section 4.5.3
External I/O signal display On/off statuses of external I/O signals are shown on the display. Section 4.5.7
Voltage is automatically offset to stop the servo motor if it does not come to a stop
Automatic VC offset Section 4.5.4
when VC (Analog speed command) or VLA (Analog speed limit is 0 V.
Alarm code output If an alarm has occurred, the corresponding alarm number is outputted in 3-bit code. Chapter 8
Jog operation, positioning operation, motor-less operation, DO forced output, and
Test operation mode program operation Section 4.5.9
MR Configurator2 is required for the positioning operation and program operation.
[Pr. PC14],
Analog monitor output Servo status is outputted in terms of voltage in real time.
[Pr. PC15]
Using a personal computer, you can perform the parameter setting, test operation,
MR Configurator2 Section 11.4
monitoring, and others.
Gain adjustment is performed just by one click on a certain button on MR
One-touch tuning Section 6.2
Configurator2 or operation section.
This function makes the equipment continue operating even under the condition that
an alarm occurs.
Tough drive function Section 7.3
The tough drive function includes two types: the vibration tough drive and the
instantaneous power failure tough drive.
This function continuously monitors the servo status and records the status transition
before and after an alarm for a fixed period of time. You can check the recorded data
on the drive recorder window on MR Configurator2 by clicking the "Graph" button.
Drive recorder function However, the drive recorder will not operate on the following conditions. [Pr. PA23]
1. You are using the graph function of MR Configurator2.
2. You are using the machine analyzer function.
3. [Pr. PF21] is set to "-1".
You can check the cumulative energization time and the number of on/off times of the
Servo amplifier life diagnosis inrush relay. This function gives an indication of the replacement time for parts of the
function servo amplifier including a capacitor and a relay before they malfunction.
MR Configurator2 is necessary for this function.
This function calculates the power running energy and the regenerative power from
Power monitoring function the data in the servo amplifier such as speed and current. Power consumption and
others are displayed on MR Configurator2.
From the data in the servo amplifier, this function estimates the friction and vibrational
component of the drive system in the equipment and recognizes an error in the
Machine diagnosis function
machine parts, including a ball screw and bearing.
MR Configurator2 is necessary for this function.
1- 6
1. FUNCTIONS AND CONFIGURATION
(2) Model
The following describes what each block of a model name indicates.
General-purpose interface
Series
Rated output
Symbol Rated output [kW]
10 0.1
20 0.2
40 0.4
70 0.75
100 1
200 2
300 3
1- 7
1. FUNCTIONS AND CONFIGURATION
1.7 Structure
(2) Display
Section
(1) The 5-digit, 7-segment LED shows the servo status
4.5
(3) and the alarm number.
Operation section
Used to perform status display, diagnostic, alarm,
and parameter setting operations. Push the "MODE"
and "SET" buttons at the same time for 3 s or more
(7) to switch to the one-touch tuning mode.
Side Used to change the mode.
(4) Section
Used to change the 4.5
(2) display or data in each Section
mode.
6.2
Used to set data.
1- 8
1. FUNCTIONS AND CONFIGURATION
(8)
(5) To the one-touch tuning
mode
(9)
USB communication connector (CN3) Section
(3)
Connect with the personal computer. 11.4
Bottom I/O signal connector (CN1) Section
(10) Digital I/O signal, analog input signal, and analog 3.2
(4)
monitor output are connected. Section
3.4
Encoder connector (CN2) Section
(5)
Used to connect the servo motor encoder. 3.4
Power connector (CNP1) Section
Input power supply and regenerative option are 3.1
(6)
connected. Section
3.3
Rating plate Section
(7)
1.6
Servo motor power connector (CNP2) Section
Connect the servo motor. 3.1
(8)
Section
3.3
Charge lamp
(9) When the main circuit is charged, this will light up.
While this lamp is lit, do not reconnect the cables.
Protective earth (PE) terminal Section
Grounding terminal 3.1
(10)
Section
3.3
1- 9
1. FUNCTIONS AND CONFIGURATION
POINT
Equipment other than the servo amplifier and servo motor are optional or
recommended products.
RS T
(Note 1)
Power
supply
Personal
Molded-case computer
circuit breaker MR Configurator2
CN3
(Note 2)
Magnetic
contactor
(MC)
CN1
Power factor
improving AC
reactor Junction terminal block
(FR-HAL)
Line noise
filter
(FR-BSF01) CN2
L1
L2
L3
U Servo motor
V
W
Note 1. A 1-phase 200 V AC to 240 V AC power supply may be used with the servo amplifier of MR-JE-70A or less. For 1-phase 200 V
AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open. For the power supply specifications, refer to section
1.3.
2. Depending on the power supply voltage and operation pattern, bus voltage can decrease. This can shift the mode to the
dynamic brake deceleration during forced stop deceleration. When dynamic brake deceleration is not required, slow the time to
turn off the magnetic contactor.
1 - 10
1. FUNCTIONS AND CONFIGURATION
Molded-case
circuit breaker
Personal
computer
(Note 2) MR Configurator2
Magnetic CN3
contactor
(MC)
Power factor
improving AC
reactor
(FR-HAL)
Line noise
filter
(FR-BSF01)
CN1
L1
L2 Junction terminal block
L3
U
V
W
CN2
Servo motor
1 - 11
1. FUNCTIONS AND CONFIGURATION
MEMO
1 - 12
2. INSTALLATION
2. INSTALLATION
2- 1
2. INSTALLATION
MR-JE-40A to MR-JE-100A have a regenerative resistor on their back face. The regenerative resistor
generates heat of 100 ˚C higher than the ambient temperature. Please fully consider heat dissipation,
installation position, etc. when mounting it.
40 mm
or more
Servo
amplifier Wiring allowance
80 mm
or more
10 mm 10 mm
or more or more Top
Bottom
40 mm
or more
2- 2
2. INSTALLATION
POINT
Close mounting is possible for all capacity type of MR-JE servo amplifiers.
Leave a large clearance between the top of the servo amplifier and the cabinet walls, and install a
cooling fan to prevent the internal temperature of the cabinet from exceeding the environment.
When mounting the servo amplifiers closely, leave a clearance of 1 mm between the adjacent servo
amplifiers in consideration of mounting tolerances. In this case, keep the ambient temperature within
0 ˚C to 45 ˚C or use the servo amplifier with 75% or less of the effective load ratio.
Cabinet Cabinet
30 mm 30 mm 30 mm Top
or more or more or more
Bottom
40 mm or more 40 mm or more
(2) Others
When using heat generating equipment such as the regenerative option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
(1) When drilling in the cabinet, prevent drill chips and wire fragments from entering the servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the cabinet or
a cooling fan installed on the ceiling.
(3) When installing the cabinet in a place where toxic gas, dirt and dust exist, conduct an air purge (force
clean air into the cabinet from outside to make the internal pressure higher than the external pressure) to
prevent such materials from entering the cabinet.
2- 3
2. INSTALLATION
(1) The way of clamping the cable must be fully examined so that bending stress and cable's own weight
stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, and
brake) with having some slack from the connector connection part of the servo motor to avoid putting
stress on the connector connection part. Use the optional encoder cable within the bending life range.
Use the power supply and brake wiring cables within the bending life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner or
stamped by workers or vehicles.
(4) For installation on a machine where the servo motor moves, the flexing radius should be made as large
as possible. Refer to section 10.4 for the bending life.
Before starting maintenance and/or inspection, turn off the power and wait for 15
minutes or more until the charge lamp turns off. Otherwise, an electric shock may
occur. In addition, when confirming whether the charge lamp is off or not, always
WARNING confirm it from the front of the servo amplifier.
To avoid an electric shock, only qualified personnel should attempt inspections.
For repair and parts replacement, contact your local sales office.
Do not perform insulation resistance test on the servo amplifier. Otherwise, it may
CAUTION cause a malfunction.
Do not disassemble and/or repair the equipment on customer side.
(1) Check for loose terminal block screws. Retighten any loose screws.
(2) Check the cables and the like for scratches or cracks. Inspect them periodically according to operating
conditions especially when the servo motor is movable.
(3) Check that the connector is securely connected to the servo amplifier.
(4) Check that the wires are not coming out from the connector.
(6) Check for unusual noise generated from the servo amplifier.
2- 4
2. INSTALLATION
Service lives of the following parts are listed below. However, the service life vary depending or operating
methods and environment. If any fault is found in the parts, they must be replaced immediately regardless of
their service lives. For parts replacement, please contact your local sales office.
Part name Life guideline
Smoothing capacitor 10 years
Number of power-on and forced stop times
Relay
by EM1 (Forced stop 1): 100,000 times
50,000 hours to 70,000 hours (7 years to 8
Cooling fan
years)
(2) Relays
Contact faults will occur due to contact wear arisen from switching currents. Relays will reach the end of
their lives depending on their power supply capacity when the number of power-on times and number of
forced stop times by EM1 (Forced stop 1) are 100,000 times in total.
2- 5
2. INSTALLATION
MEMO
2- 6
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Otherwise, an electric shock may occur. In addition, when
confirming whether the charge lamp is off or not, always confirm it from the front
of the servo amplifier.
Ground the servo amplifier and servo motor securely.
WARNING Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, it may cause an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it
may cause an electric shock.
To avoid an electric shock, insulate the connections of the power supply
terminals.
Control output RA
Control output RA
signal signal
For sink output interface For source output interface
3- 1
3. SIGNALS AND WIRING
Always connect a magnetic contactor between the power supply and the power
supply (L1, L2, and L3) of the servo amplifier, in order to configure a circuit that
shuts down the power supply on the side of the servo amplifier’s power supply. If
a magnetic contactor is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.
Use ALM (Malfunction) to switch power off. Not doing so may cause a fire when a
regenerative transistor malfunctions or the like may overheat the regenerative
resistor.
Before removing the CNP1 connector from MR-JE-40A to MR-JE-100A,
disconnect the lead wires of the regenerative resistor from the CNP1 connector.
CAUTION Not doing so may break the lead wires of the regenerative resistor.
Check the servo amplifier model, and then input proper voltage to the servo
amplifier power supply. If input voltage exceeds the upper limit of the
specification, the servo amplifier will break down.
The servo amplifier has a built-in surge absorber (varistor) to reduce noise and to
suppress lightning surge. The varistor can break down due to its aged
deterioration. To prevent a fire, use a molded-case circuit breaker or fuse for input
power supply.
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo
amplifier may cause a malfunction.
POINT
EM2 has the same function as EM1 in the torque control mode.
Connect the 1-phase 200 V AC to 240 V AC power supply to L1 and L3. One of
the connecting destinations is different from MR-E Super Series Servo
Amplifier's. When using MR-JE as a replacement for MR-E Super, be careful not
to connect the power to L2.
Configure the wirings so that the power supply is shut off and SON (Servo-on) is turned off after deceleration
to a stop due to an alarm occurring, enabled servo forced stop, etc. A molded-case circuit breaker (MCCB)
must be used with the input cables of the main circuit power supply.
3- 2
3. SIGNALS AND WIRING
(Note 7)
CN2 (Note 2) Encoder
Encoder cable
(Note 6)
Power CN1
supply
Forced stop 2 EM2 CN1
(Note 3) 24 V DC (Note 8)
Servo-on SON DOCOM
Note 1. MR-JE-40A to MR-JE-100A have a built-in regenerative resistor. (factory-wired) When using the regenerative option,
refer to section 11.2.
2. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "HF-KN/HF-SN Servo
Motor Instruction Manual".
3. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
4. For connecting servo motor power wires, refer to "HF-KN/HF-SN Servo Motor Instruction Manual".
5. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the power supply voltage and operation pattern, bus voltage can decrease.
This can shift the mode to the dynamic brake deceleration during forced stop deceleration. When dynamic brake
deceleration is not required, slow the time to turn off the magnetic contactor.
6. Configure a circuit to turn off EM2 when the power is turned off to prevent an unexpected restart of the servo amplifier.
7. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However,
they can be configured by one.
3- 3
3. SIGNALS AND WIRING
POINT
Connect the 1-phase 200 V AC to 240 V AC power supply to L1 and L3. One of
the connecting destinations is different from MR-E Super Series Servo
Amplifier's. When using MR-JE as a replacement for MR-E Super, be careful not
to connect the power to L2.
OFF
ON
MC
(Note 7)
CN2 (Note 2) Encoder
Encoder cable
(Note 6)
Power CN1
supply
Forced stop 2 EM2 CN1
(Note 3) 24 V DC (Note 8)
Servo-on SON DOCOM
Note 1. MR-JE-40A and MR-JE-70A have a built-in regenerative resistor. (factory-wired) When using the regenerative option,
refer to section 11.2.
2. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "HF-KN/HF-SN Servo
Motor Instruction Manual".
3. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
4. For connecting servo motor power wires, refer to "HF-KN/HF-SN Servo Motor Instruction Manual".
5. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the power supply voltage and operation pattern, bus voltage can decrease.
This can shift the mode to the dynamic brake deceleration during forced stop deceleration. When dynamic brake
deceleration is not required, slow the time to turn off the magnetic contactor.
6. Configure a circuit to turn off EM2 when the power is turned off to prevent an unexpected restart of the servo amplifier.
7. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However,
they can be configured by one.
3- 4
3. SIGNALS AND WIRING
(3) MR-JE-200A/MR-JE-300A
OFF
ON
MC
(Note 7)
CN2 (Note 2) Encoder
Encoder cable
(Note 6)
Power CN1
supply
Forced stop 2 EM2 CN1
(Note 3) 24 V DC (Note 8)
Servo-on SON DOCOM
Note 1. Always connect between P+ and D terminals. (factory-wired) When using the regenerative option, refer to section 11.2.
2. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "HF-KN/HF-SN Servo
Motor Instruction Manual".
3. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
4. For connecting servo motor power wires, refer to "HF-KN/HF-SN Servo Motor Instruction Manual".
5. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the power supply voltage and operation pattern, bus voltage can decrease.
This can shift the mode to the dynamic brake deceleration during forced stop deceleration. When dynamic brake
deceleration is not required, slow the time to turn off the magnetic contactor.
6. Configure a circuit to turn off EM2 when the power is turned off to prevent an unexpected restart of the servo amplifier.
7. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However,
they can be configured by one.
3- 5
3. SIGNALS AND WIRING
10 m or less (Note 7)
(Note 11) CN1
Power supply
(Note 3, 5) Forced stop 2 EM2 42 (Note 7)
CN1
Servo-on SON 15
26 MO1 Analog monitor 1
Reset RES 19 ± 10 V DC
Forward rotation 30 LG
LSP 43
(Note 5) stroke end 29 MO2 Analog monitor 2
Reverse rotation 24 V DC (Note 4) LSN 44 ± 10 V DC
stroke end
DICOM 21
0 V to +10 V Plate SD
Analog torque limit TLA 27
+10 V/maximum torque 2 m or less
LG 28
SD Plate
2 m or less
Personal
(Note 9) computer
MR Configurator2
CN3
USB cable (option)
+ (Note 1)
3- 6
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 300 mA. 300 mA is the value applicable
when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) that gives the current value necessary for the interface. The illustration of the 24 V DC power supply is divided
between input signal and output signal for convenience. However, they can be configured by one.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end) (normally closed contact).
6. ALM (Malfunction) turns on in normal alarm-free condition (normally closed contact). When this signal is switched off (at
occurrence of an alarm), the output of the programmable controller should be stopped by the sequence program.
7. The pins with the same signal name are connected in the servo amplifier.
8. This length applies to the command pulse train input in the differential line driver type. It is 2 m or less in the open-collector
type.
9. Use SW1DNC-MRC2-E. (Refer to section 11.4.)
10. This connection is not necessary for LD75D and QD75D. However, to enhance noise immunity, it is recommended to connect
LG of servo amplifier and control common depending on the positioning module.
11. Configure a circuit to turn off EM2 when the power is turned off to prevent an unexpected restart of the servo amplifier.
12. Plus and minus of the power of source interface are the opposite of those of sink interface.
13. CLEAR and CLEARCOM of source interface are interchanged to sink interface.
14. When a command cable malfunctions due to disconnection or noise, a position mismatch can occur. To avoid position
mismatch, it is recommended that Encoder A-phase pulse and Encoder B-phase pulse be checked.
3- 7
3. SIGNALS AND WIRING
POINT
For notes, refer to (1) (a) in this section.
Servo amplifier
24 V DC (Note 4, 12) (Note 7)
Positioning module CN1 24 V DC (Note 4, 12)
LD75D/QD75D (Note 7)
47 DOCOM (Note 2)
CN1
(Note 14) DICOM 20 48 ALM RA1 Malfunction (Note 6)
CLEAR 13 DOCOM 46
(Note 13)
CLEARCOM 14 CR 41 23 ZSP RA2 Zero speed detection
RDYCOM 12 24 INP RA3 In-position
READY 11 RD 49
PULSE F+ 15 PP 10 10 m or less
PULSE F- 16 PG 11
4 LA Encoder A-phase pulse
PULSE R+ 17 NP 35 (differential line driver)
5 LAR
PULSE R- 18 NG 36
6 LB Encoder B-phase pulse
PG0 9 LZ 8 (differential line driver)
7 LBR
PG0 COM 10 LZR 9
Control common
(Note 10) LG 3
34 LG Control common
SD Plate
33 OP Encoder Z-phase pulse
Plate SD (open collector)
10 m or less (Note 8)
2 m or less
10 m or less (Note 7)
(Note 11) CN1
Power supply
(Note 3, 5) Forced stop 2 EM2 42 (Note 7)
CN1
Servo-on SON 15
26 MO1 Analog monitor 1
Reset RES 19 ± 10 V DC
Forward rotation 30 LG
LSP 43
(Note 5) stroke end 29 MO2 Analog monitor 2
Reverse rotation 24 V DC (Note 4, 12) LSN 44 ± 10 V DC
stroke end
DICOM 21
0 V to +10 V Plate SD
Analog torque limit TLA 27
+10 V/maximum torque 2 m or less
LG 28
SD Plate
2 m or less
Personal
(Note 9) computer
MR Configurator2
CN3
USB cable (option)
+ (Note 1)
3- 8
3. SIGNALS AND WIRING
(2) When you use a positioning module FX3U-_ _MT/ES (For sink I/O interface)
2 m or less (Note 8)
Programmable controller
FX3U-_ _MT/ES (Note 11)
(Note 15)
S/S
24 V Servo amplifier
0V (Note 7)(Note 7)
L CN1 CN1
Programmable 24 V DC 24 V DC (Note 4)
controller (Note 4) DICOM 20 47 DOCOM
power supply (Note 2)
N OPC 12
DOCOM 46 48 ALM RA1 Malfunction (Note 6)
Y000 PP 10 23 ZSP RA2 Zero speed detection
(Note 12) COM1
Y010 NP 35 10 m or less
COM3
8 LZ Encoder Z-phase pulse
9 LZR (differential line driver)
Y004 CR 41
4 LA Encoder A-phase pulse
(Note 13) COM2 (differential line driver)
5 LAR
6 LB Encoder B-phase pulse
X___ INP 24 (differential line driver)
7 LBR
34 LG Control common
X___ RD 49
Plate SD
(Note 14) X000 OP 33
LG 3
SD Plate
10 m or less (Note 7)
(Note 10) CN1
Power supply
(Note 3, 5) Forced stop 2 EM2 42 (Note 7)
CN1
Servo-on SON 15
26 MO1 Analog monitor 1
Reset RES 19 ± 10 V DC
30 LG
Forward rotation LSP 43
(Note 5) stroke end 29 MO2 Analog monitor 2
Reverse rotation 24 V DC (Note 4) LSN 44 ± 10 V DC
stroke end DICOM 21
0 V to +10 V Plate SD
Analog torque limit TLA 27
+10 V/maximum torque 2 m or less
LG 28
SD Plate
2 m or less
Personal
(Note 9) computer
MR Configurator2
CN3
USB cable (option)
+ (Note 1)
3- 9
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 300 mA. 300 mA is the value applicable
when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) that gives the current value necessary for the interface. The illustration of the 24 V DC power supply is divided
between input signal and output signal for convenience. However, they can be configured by one.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end) (normally closed contact).
6. ALM (Malfunction) turns on in normal alarm-free condition (normally closed contact). When this signal is switched off (at
occurrence of an alarm), the output of the programmable controller should be stopped by the sequence program.
7. The pins with the same signal name are connected in the servo amplifier.
8. Connect them within 2 m because of open-collector type.
9. Use SW1DNC-MRC2-E. (Refer to section 11.4.)
10. Configure a circuit to turn off EM2 when the power is turned off to prevent an unexpected restart of the servo amplifier.
11. Select the number of I/O points of the programmable controller depending on your system.
12. It will be COM0 for FX3U-16MT/ES.
13. It will be COM4 for FX3U-16MT/ES.
14. Select it within X000 to X007.
15. When a command cable malfunctions due to disconnection or noise, a position mismatch can occur. To avoid position
mismatch, it is recommended that Encoder A-phase pulse and Encoder B-phase pulse be checked.
3 - 10
3. SIGNALS AND WIRING
47 DOCOM
(Note 2)
10 m or less
(Note 7) 48 ALM RA1 Malfunction (Note 6)
(Note 11) CN1
Power supply
(Note 3, 5) Forced stop 2 EM2 42 23 ZSP RA2 Zero speed detection
Servo-on SON 15 24 SA RA3 Speed reached
Forward rotation start ST1 19
Reverse rotation start ST2 41 49 RD RA4 Ready
Forward rotation LSP 43
(Note 5) stroke end LSN 44
10 m or less
Reverse rotation
stroke end
DICOM 20 8 LZ Encoder Z-phase pulse
24 V DC (Note 4) DICOM 21 9 LZR (differential line driver)
Plate SD
2 m or less
(Note 1)
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 300 mA. 300 mA is the value applicable
when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) that gives the current value necessary for the interface. The illustration of the 24 V DC power supply is divided
between input signal and output signal for convenience. However, they can be configured by one.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end) (normally closed contact).
6. ALM (Malfunction) turns on in normal alarm-free condition (normally closed contact).
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD03], [Pr. PD11], [Pr. PD13], [Pr. PD17],
and [Pr. PD19]. (Refer to section 3.6.1 (5).)
9. Use SW1DNC-MRC2-E. (Refer to section 11.4.)
10. Use an external power supply when inputting a negative voltage.
11. Configure a circuit to turn off EM2 when the power is turned off to prevent an unexpected restart of the servo amplifier.
12. Plus and minus of the power of source interface are the opposite of those of sink interface.
3 - 11
3. SIGNALS AND WIRING
POINT
For notes, refer to (1) in this section.
Servo amplifier
(Note 7)
CN1 24 V DC (Note 4, 12)
46 DOCOM
47 DOCOM
(Note 2)
10 m or less
(Note 7) 48 ALM RA1 Malfunction (Note 6)
(Note 11) CN1
Power supply
(Note 3, 5) Forced stop 2 EM2 42 23 ZSP RA2 Zero speed detection
Servo-on SON 15 24 SA RA3 Speed reached
Forward rotation start ST1 19
Reverse rotation start ST2 41 49 RD RA4 Ready
Forward rotation LSP 43
(Note 5) stroke end LSN 44
10 m or less
Reverse rotation
stroke end DICOM 20 8 LZ Encoder Z-phase pulse
24 V DC (Note 4, 12) DICOM 21 9 LZR (differential line driver)
Plate SD
2 m or less
(Note 1)
3 - 12
3. SIGNALS AND WIRING
POINT
EM2 has the same function as EM1 in the torque control mode.
47 DOCOM
(Note 2)
10 m or less
(Note 6) 48 ALM RA1 Malfunction (Note 6)
(Note 9) CN1
Power supply
(Note 3) Forced stop 2 EM2 42 23 ZSP RA2 Zero speed detection
Servo-on SON 15 49 RD RA3 Ready
Forward rotation start RS1 41
Reverse rotation start RS2 19 10 m or less
DICOM 20
8 LZ Encoder Z-phase pulse
24 V DC (Note 4) DICOM 21
9 LZR (differential line driver)
-8 V to +8 V 4 LA Encoder A-phase pulse
Analog torque command TC 27 (differential line driver)
±8 V/maximum torque 5 LAR
LG 28
6 LB Encoder B-phase pulse
-10 V to +10 V VLA 2 7 LBR (differential line driver)
(Note 8) Analog speed limit
0 to ±10 V/rated speed Control common
SD Plate 34 LG
2 m or less
33 OP Encoder Z-phase pulse
Personal Plate SD (open collector)
(Note 7)
MR Configurator2 computer 2 m or less
CN3
USB cable (option) (Note 6)
+ CN1
26 MO1 Analog monitor 1
± 10 V DC
30 LG
29 MO2 Analog monitor 2
± 10 V DC
Plate SD
2 m or less
(Note 1)
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 300 mA. 300 mA is the value applicable
when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) that gives the current value necessary for the interface. The illustration of the 24 V DC power supply is divided
between input signal and output signal for convenience. However, they can be configured by one.
5. ALM (Malfunction) turns on in normal alarm-free condition (normally closed contact).
6. The pins with the same signal name are connected in the servo amplifier.
7. Use SW1DNC-MRC2-E. (Refer to section 11.4.)
8. Use an external power supply when inputting a negative voltage.
9. Configure a circuit to turn off EM2 when the power is turned off to prevent an unexpected restart of the servo amplifier.
10. Plus and minus of the power of source interface are the opposite of those of sink interface.
3 - 13
3. SIGNALS AND WIRING
POINT
For notes, refer to (1) in this section.
Servo amplifier
(Note 6)
CN1 24 V DC (Note 4, 10)
46 DOCOM
47 DOCOM
(Note 2)
10 m or less
(Note 6) 48 ALM RA1 Malfunction (Note 5)
(Note 9) CN1
Power supply 23 ZSP RA2 Zero speed detection
(Note 3) Forced stop 2 EM2 42
Servo-on SON 15 49 RD RA3 Ready
Forward rotation start RS1 41
Reverse rotation start RS2 19 10 m or less
DICOM 20
8 LZ Encoder Z-phase pulse
24 V DC (Note 4, 10) DICOM 21 (differential line driver)
9 LZR
-8 V to +8 V 4 LA Encoder A-phase pulse
Analog torque command TC 27 (differential line driver)
±8 V/maximum torque 5 LAR
LG 28
6 LB Encoder B-phase pulse
-10 V to +10 V VLA 2 7 LBR (differential line driver)
(Note 8) Analog speed limit Control common
0 to ±10 V/rated speed
SD Plate 34 LG
2 m or less
33 OP Encoder Z-phase pulse
Personal Plate SD (open collector)
(Note 7)
MR Configurator2 computer 2 m or less
CN3
USB cable (option) (Note 6)
+ CN1
26 MO1 Analog monitor 1
± 10 V DC
30 LG
29 MO2 Analog monitor 2
± 10 V DC
Plate SD
2 m or less
(Note 1)
3 - 14
3. SIGNALS AND WIRING
POINT
For the layout of connector and terminal block, refer to chapter 9 DIMENSIONS.
Connection target
Symbol Description
(application)
Supply the following power to L1, L2, and L3. For 1-phase 200 V AC to 240 V AC,
connect the power supply to L1 and L3. Leave L2 open.
1) MR-JE-100A or less
MR-JE-10A to MR-JE-100A do not have D.
When using a servo amplifier built-in regenerative resistor, connect P+ and C.
(factory-wired)
MR-JE-10A and MR-JE-20A do not have a built-in regenerative resistor.
When using a regenerative option, disconnect wires of P+ and C for the built-in
Regenerative regenerative resistor. And then connect wires of the regenerative option to P+
P+/C/D
option and C.
2) MR-JE-200A or more
When using a servo amplifier built-in regenerative resistor, connect P+ and D.
(factory-wired)
When using a regenerative option, disconnect P+ and D, and connect the
regenerative option to P+ and C.
Refer to section 11.2 for details.
Connect them to the servo motor power supply (U, V, and W). Connect the servo
Servo motor amplifier power output (U, V, and W) to the servo motor power input (U, V, and W)
U/V/W
power output directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a
malfunction.
This is for manufacturer adjustment.
N- Leave this open.
MR-JE-10A to MR-JE-100A do not have N-.
Protective earth Connect it to the grounding terminal of the servo motor and to the protective earth
(PE) (PE) of the cabinet for grounding.
3 - 15
3. SIGNALS AND WIRING
POINT
The voltage of analog monitor output, output signal, etc. may be unstable at
power-on.
2) The servo amplifier receives the SON (Servo-on) 2.5 s to 3.5 s after the power supply is switched
on. Therefore, when SON (Servo-on) is switched on simultaneously with the power supply, the
base circuit will switch on in about 2.5 s to 3.5 s, and the RD (Ready) will switch on in further
about 5 ms, making the servo amplifier ready to operate. (Refer to (2) of this section.)
3) When RES (Reset) is switched on, the base circuit is shut off and the servo motor shaft coasts.
(2.5 s to 3.5 s)
ON
Power supply
OFF
ON
Base circuit
OFF
10 ms 10 ms 95 ms
ON
SON (Servo-on)
OFF 95 ms
ON
RES (Reset)
OFF
5 ms 10 ms 5 ms 10 ms 5 ms 10 ms
ON
RD (Ready)
OFF
3 - 16
3. SIGNALS AND WIRING
POINT
For the wire sizes used for wiring, refer to section 11.5.
To wire to CNP1 and CNP2, use servo amplifier power connectors packed with the amplifier or optional
connectors (refer to section 11.1.1).
(1) Connector
(a) MR-JE-10A to MR-JE-100A
Servo amplifier
CNP1
(b) MR-JE-200A/MR-JE-300A
Servo amplifier
CNP1
CNP2
3 - 17
3. SIGNALS AND WIRING
Stripped length
You can also use a ferrule to connect with the connectors. The following shows references to select
ferrules according to wire sizes.
Ferrule model (Phoenix Contact) Crimp terminal
Servo amplifier Wire size
For one For two (Phoenix Contact)
MR-JE-10A to AWG 16 AI1.5-10BK AI-TWIN2×1.5-10BK
MR-JE-100A AWG 14 AI2.5-10BU
AWG 16 AI1.5-10BK AI-TWIN2×1.5-10BK CRIMPFOX-ZA3
MR-JE-200A to
AWG 14 AI2.5-10BU AI-TWIN2×2.5-10BU
MR-JE-300A
AWG 12 AI4-10GY
3 - 18
3. SIGNALS AND WIRING
POINT
The pin assignment of the connectors are as viewed from the cable connector
wiring section.
For the CN1 connector, securely connect the external conductor of the shielded
cable to the ground plate and fix it to the connector shell.
Screw
Cable
Screw
Ground plate
The servo amplifier front view shown is that of the MR-JE-40A or less. Refer to chapter 9 DIMENSIONS for
the appearances and connector layouts of the other servo amplifiers.
1 26
2 27
3 28
4 29
5 30
6 31
7 32
8 33
9 34
10 35
11 36
12 37
13 38
14 39
CN2
15 40
2 6 10 16 41
LG 4 8 17 42
MRR MDR
18 43
1 5 9
P5 3 7 19 44
MR MD 20 45
21 46
This is a connector of 3M. 22 47
The frames of the CN1 connector
are connected to the protective earth 23 48
terminal in the servo amplifier. 24 49
25 50
3 - 19
3. SIGNALS AND WIRING
The device assignment of CN1 connector pins changes depending on the control mode. For the pins
which are given parameters in the related parameter column, their devices will be changed using those
parameters.
(Note 1) (Note 2) I/O signals in control modes
Pin No. Related parameter
I/O P P/S S S/T T T/P
1
2 I -/VC VC VC/VLA VLA VLA/-
3 LG LG LG LG LG LG
4 O LA LA LA LA LA LA
5 O LAR LAR LAR LAR LAR LAR
6 O LB LB LB LB LB LB
7 O LBR LBR LBR LBR LBR LBR
8 O LZ LZ LZ LZ LZ LZ
9 O LZR LZR LZR LZR LZR LZR
10 I PP PP/- -/PP
11 I PG PG/- -/PG
12 OPC OPC/- -/OPC
13
14
15 I SON SON SON SON SON SON Pr. PD03/Pr. PD04
16
17
18
19 I RES RES/ST1 ST1 ST1/RS2 RS2 RS2/RES Pr. PD11/Pr. PD12
20 DICOM DICOM DICOM DICOM DICOM DICOM
21 DICOM DICOM DICOM DICOM DICOM DICOM
22
23 O ZSP ZSP ZSP ZSP ZSP ZSP Pr. PD24
24 O INP INP/SA SA SA/- -/INP Pr. PD25
25
26 O MO1 MO1 MO1 MO1 MO1 MO1 Pr. PC14
(Note 3) (Note 3) (Note 3) (Note 3)
27 I TLA TC
TLA TLA TLA/TC TC/TLA
28 LG LG LG LG LG LG
29 O MO2 MO2 MO2 MO2 MO2 MO2 Pr. PC15
30 LG LG LG LG LG LG
31
32
33 O OP OP OP OP OP OP
34 LG LG LG LG LG LG
35 I NP NP/- -/NP
36 I NG NG/- -/NG
37
38
39
40
41 I CR CR/ST2 ST2 ST2/RS1 RS1 RS1/CR Pr. PD13/Pr. PD14
42 I EM2 EM2 EM2 EM2 EM2 EM2
43 I LSP LSP LSP LSP/- -/LSP Pr. PD17/Pr. PD18
44 I LSN LSN LSN LSN/- -/LSN Pr. PD19/Pr. PD20
45
3 - 20
3. SIGNALS AND WIRING
For the I/O interfaces (symbols in I/O division column in the table), refer to section 3.9.2. In the control mode
field of the table
P: position control mode, S: speed control mode, T: torque control mode Torque control mode
: devices used with initial setting status, : devices used by setting [Pr. PA04] and [Pr. PD03] to [Pr.
PD28]
The pin numbers in the connector pin No. column are those in the initial status.
3 - 21
3. SIGNALS AND WIRING
Control
Connector I/O
Device Symbol Function and application mode
pin No. division
P S T
Reset RES CN1-19 Turn on RES for more than 50 ms to reset the alarm. DI-1
Some alarms cannot be deactivated by RES (Reset). Refer to section 8.1.
Turning RES on in an alarm-free status shuts off the base circuit. The base
circuit is not shut off when " _ _ 1 _ " is set in [Pr. PD30].
This device is not designed to make a stop. Do not turn it on during
operation.
Forward rotation LSP CN1-43 To start operation, turn on LSP and LSN. Turn it off to bring the motor to a DI-1
stroke sudden stop and make it servo-locked.
end Setting [Pr. PD30] to " _ _ _ 1" will enable a slow stop.
Set [Pr. PD01] as indicated below to switch on the signals (keep terminals
connected) automatically in the servo amplifier.
Status
[Pr. PD01]
LSP LSN
Automatic
_4__
on
Automatic
_8__
on
Automatic Automatic
_C__
on on
When LSP or LSN turns off, [AL. 99 Stroke limit warning] occurs, and WNG
(Warning) turns on. When using WNG, enable it by setting [Pr. PD24], [Pr.
PD25] and [Pr. PD28].
External torque TL Turning off TL will enable [Pr. PA11 Forward torque limit] and [Pr. PA12 DI-1
limit selection Reverse torque limit], and turning on it will enable TLA (Analog torque
limit). For details, refer to section 3.6.1 (5).
Internal torque TL1 To select [Pr. PC35 Internal torque limit 2], enable TL1 with [Pr. PD03] to DI-1
limit selection [Pr. PD20]. For details, refer to section 3.6.1 (5).
Forward rotation ST1 This is used to start the servo motor. DI-1
start The following shows the directions.
Reverse rotation ST2 If both ST1 and ST2 are switched on or off during operation, the servo
start motor will be decelerated to a stop according to the [Pr. PC02] setting and
servo-locked.
When " _ _ _1" is set in [Pr. PC23], the servo motor is not servo-locked
after deceleration to a stop.
3 - 22
3. SIGNALS AND WIRING
Control
Connector I/O
Device Symbol Function and application mode
pin No. division
P S T
Forward rotation RS1 This is used to select a servo motor torque generation directions. DI-1
selection The following shows the torque generation directions.
3 - 23
3. SIGNALS AND WIRING
Control
Connector I/O
Device Symbol Function and application mode
pin No. division
P S T
Proportion PC Turn PC on to switch the speed amplifier from the proportional integral type DI-1
control to the proportional type.
If the servo motor at a stop is rotated even one pulse due to any external
factor, it generates torque to compensate for a position shift. When the
servo motor shaft is to be locked mechanically after positioning completion
(stop), switching on the PC (Proportion control) upon positioning
completion will suppress the unnecessary torque generated to compensate
for a position shift.
When the shaft is to be locked for a long time, switch on the PC
(Proportion control) and TL (External torque limit selection) at the same
time to make the torque less than the rated by TLA (Analog torque limit).
Clear CR CN1-41 Turn CR on to clear the position control counter droop pulse on its leading DI-1
edge. The pulse width should be 10 ms or longer.
The delay amount set in [Pr. PB03 Position command
acceleration/deceleration time constant] is also cleared. When " _ _ _1 " is
set to [Pr. PD32], the pulses are always cleared while CR is on.
Electronic gear CM1 The combination of CM1 and CM2 enables you to select four different DI-1
selection 1 electronic gear numerators set in the parameters.
Gain switching CDP Turn on CDP to use the values of [Pr. PB29] to [Pr. PB36] and [Pr. PB56] DI-1
to [Pr. PB60] as the load to motor inertia ratio and gain values.
3 - 24
3. SIGNALS AND WIRING
Control
Connector I/O
Device Symbol Function and application mode
pin No. division
P S T
Control switching LOP «Position/speed control switching mode» DI-1 Refer to
This is used to select the control mode in the position/speed control Function
switching mode. and
application.
(Note) Control
LOP mode
0 Position
1 Speed
Note. 0: Off
1: On
(Note) Control
LOP mode
0 Speed
1 Torque
Note. 0: Off
1: On
(Note) Control
LOP mode
0 Torque
1 Position
Note. 0: Off
1: On
Second STAB2 The device allows selection of the acceleration/deceleration time constant DI-1
acceleration/ at servo motor rotation in the speed control mode or torque control mode.
deceleration The s-pattern acceleration/deceleration time constant is always uniform.
selection
(Note) Acceleration/deceleration time
STAB2 constant
0 Pr. PC01 Acceleration time
constant
Pr. PC02 Deceleration time
constant
1 Pr. PC30 Acceleration time
constant 2
Pr. PC31 Deceleration time
constant 2
Note. 0: Off
1: On
3 - 25
3. SIGNALS AND WIRING
OFF level 1)
Forward 70 r/min 3)
rotation 2) 20 r/min
direction ON level (Hysteresis width)
50 r/min
[Pr. PC17]
Servo motor 0 r/min
speed
[Pr. PC17]
Reverse ON level
rotation -50 r/min
20 r/min
direction OFF level (Hysteresis width)
-70 r/min 4)
ZSP ON
(Zero speed OFF
detection)
ZSP will turn on when the servo motor is decelerated to 50 r/min (at 1)),
and will turn off when the servo motor is accelerated to 70 r/min again (at
2)).
ZSP will turn on when the servo motor is decelerated again to 50 r/min (at
3)), and will turn off when the servo motor speed has reached -70 r/min (at
4)).
The range from the point when the servo motor speed has reached on
level, and ZSP turns on, to the point when it is accelerated again and has
reached off level is called hysteresis width.
Hysteresis width is 20 r/min for this servo amplifier.
Electromagnetic MBR When using the device, set operation delay time of the electromagnetic DO-1
brake interlock brake in [Pr. PC16].
When a servo-off status or alarm occurs, MBR will turn off.
Warning WNG When warning has occurred, WNG turns on. When a warning is not DO-1
occurring, turning on the power will turn off WNG after 2.5 s to 3.5 s.
3 - 26
3. SIGNALS AND WIRING
Control
Connector I/O
Device Symbol Function and application mode
pin No. division
P S T
Alarm code ACD0 (CN1-24) To use these signals, set " _ _ _ 1" in [Pr. PD34]. DI-1
This signal is outputted when an alarm occurs.
ACD1 (CN1-23) When an alarm is not occurring, respective ordinary signals are outputted.
For details of the alarm codes, refer to chapter 8.
ACD2 (CN1-49) When you select alarm code output while MBR or ALM is selected for
CN1-23, CN1-24, or CN1-49 pin, [AL. 37 Parameter error] will occur.
Variable gain CDPS CDPS turns on during gain switching. DO-1
selection
During tough MTTR When a tough drive is enabled in [Pr. PA20], activating the instantaneous DO-1
drive power failure tough drive will turn on MTTR.
3 - 27
3. SIGNALS AND WIRING
3 - 28
3. SIGNALS AND WIRING
POINT
Adjust the logic of a positioning module and command pulse as follows.
Q series/L series positioning module
Command pulse logic setting
Signal type Q series/L series positioning MR-JE-_A servo amplifier
module Pr. 23 setting [Pr. PA13] setting
Positive logic Positive logic (_ _ 0 _)
Open-collector type
Negative logic Negative logic (_ _ 1 _)
Positive logic (Note) Negative logic (_ _ 1 _)
Differential line driver type
Negative logic (Note) Positive logic (_ _ 0 _)
Note. For Q series and L series, the logic means N-side waveform. Therefore, reverse the input
pulse logic of the servo amplifier.
24 V DC OPC
DOCOM
Approx.
PP 1.2 kΩ
Approx.
NP 1.2 kΩ
(Note)
SD
3 - 29
3. SIGNALS AND WIRING
The following section explains about the case where the negative logic and the forward/reverse
rotation pulse trains are set to "_ _ 1 0" in [Pr. PA13].
PG
(Note) Approximately
NP 100Ω
NG
SD
The following example shows that an input waveform has been set to the negative logic and
forward/reverse rotation pulse trains by setting "_ _ 1 0" in [Pr. PA13]. The waveforms of PP, PG,
NP, and NG are based on LG.
Forward rotation
pulse train
PP
PG
Reverse rotation
pulse train
NP
NG
3 - 30
3. SIGNALS AND WIRING
Alarm
Alarm
No alarm
In-position range
Droop pulses
ON
INP (In-position)
OFF
(3) RD (Ready)
ON
SON (Servo-on)
OFF
Alarm
Alarm
No alarm 100 ms
or shorter 10 ms or shorter 10 ms or shorter
ON
RD (Ready)
OFF
Note. 0: Off
1: On
3 - 31
3. SIGNALS AND WIRING
If the torque limit is canceled during servo-lock, the servo motor may suddenly
CAUTION rotate according to position deviation in respect to the command position.
Torque
A relation between the applied voltage of TLA (Analog torque limit) and the torque limit value of the
servo motor is as follows. Torque limit values will vary about 5% relative to the voltage depending on
products. At the voltage of less than 0.05 V, torque may vary as it may not be limited sufficiently.
Therefore, use this function at the voltage of 0.05 V or more.
DICOM
0 V to +10 V
±5% TLA
LG
SD
0
0 0.05
TLA applied voltage [V]
TLA applied voltage vs. torque limit value Connection example
Note. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
3 - 32
3. SIGNALS AND WIRING
Note. 0: Off
1: On
3 - 33
3. SIGNALS AND WIRING
The following table indicates the rotation direction according to ST1 (Forward rotation start) and ST2
(Reverse rotation start) combination.
(Note 1) Input device (Note 2) Rotation direction
VC (Analog speed command)
ST2 ST1 Internal speed command
Polarity: + 0V Polarity: -
Stop Stop Stop Stop
0 0
(servo-lock) (servo-lock) (servo-lock) (servo-lock)
0 1 CCW Stop CW CCW
1 0 CW (no servo-lock) CCW CW
Stop Stop Stop Stop
1 1
(servo-lock) (servo-lock) (servo-lock) (servo-lock)
Note 1. 0: Off
1: On
2. If the torque limit is canceled during servo-lock, the servo motor may suddenly rotate according to position deviation in respect
to the command position.
ST1
(Note)
24 V DC ST2
DICOM
-10 V to +10 V
VC
LG
SD
Note. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
3 - 34
3. SIGNALS AND WIRING
Note. 0: Off
1: On
You can change the speed during rotation. To accelerate/decelerate, set acceleration/deceleration
time constant in [Pr. PC01] or [Pr. PC02].
When the internal speed commands are used to command a speed, the speed does not vary with
the ambient temperature.
ST1 or ST2 ON
OFF
SA (Speed reached) ON
OFF
3 - 35
3. SIGNALS AND WIRING
Maximum torque
CW direction
Reverse rotation
(CW)
Generated torque command values will vary about 5% relative to the voltage depending on products.
The torque may vary if the voltage is low (-0.05 V to 0.05 V) and the actual speed is close to the limit
value. In such a case, increase the speed limit value.
The following table indicates the torque generation directions determined by RS1 (Forward rotation
selection) and RS2 (Reverse rotation selection) when TC (Analog torque command) is used.
(Note) Input device Rotation direction
TC (Analog torque command)
RS2 RS1
Polarity: + 0V Polarity: -
0 0 Torque is not generated. Torque is not generated.
CCW CW
(Forward rotation in (Reverse rotation in
0 1 power running power running
mode/reverse rotation in mode/forward rotation in
regenerative mode) regenerative mode)
Torque is not generated.
CW CCW
(Reverse rotation in (Forward rotation in
1 0 power running power running
mode/forward rotation in mode/reverse rotation in
regenerative mode) regenerative mode)
1 1 Torque is not generated. Torque is not generated.
Note. 0: Off
1: On
RS1
(Note)
24 V DC RS2
DICOM
TC
-8 V to 8 V
LG
SD
Note. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
3 - 36
3. SIGNALS AND WIRING
Maximum torque
Torque
[Pr. PC38]
offset range
-9999 mV to 9999 mV
0 8 (-8)
TC applied voltage [V]
The following table indicates the limit direction according to RS1 (Forward rotation selection) and
RS2 (Reverse rotation selection) combination.
(Note) Input device Speed limit direction
VLA (Analog speed limit)
RS1 RS2 Internal speed command
Polarity: + Polarity: -
1 0 CCW CW CCW
0 1 CW CCW CW
Note. 0: Off
1: On
3 - 37
3. SIGNALS AND WIRING
-10 V to +10 V
VLA
LG
SD
Note. 0: Off
1: On
When the internal speed limits 1 to 7 are used to limit a speed, the speed does not vary with the
ambient temperature.
3 - 38
3. SIGNALS AND WIRING
Set " _ _ _ 1" in [Pr. PA01] to switch to the position/speed control switching mode.
Note. 0: Off
1: On
You can switch the control mode in the zero speed status. To ensure safety, switch modes after the
servo motor has stopped. When position control mode is switched to speed control mode, droop pulses
will be reset.
If LOP is switched on/off at the speed higher than the zero speed, the control mode cannot be changed
regardless of the speed. The following shows a switching timing chart.
Position control Speed control Position control
mode mode mode
Zero speed
Servo motor speed level
ZSP ON
(Zero speed detection) OFF
LOP ON
(Control switching) (Note) (Note)
OFF
Note. When ZSP is not turned on, the control mode is not switched even if LOP is turned
on/off. After LOP is turned on/off, even if ZSP is turned on, the control mode is not
switched.
3 - 39
3. SIGNALS AND WIRING
ST1
(Note)
24 V DC ST2
DICOM
-10 V to +10 V
VC
LG
SD
Note. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
Note. 0: Off
1: On
You can change the speed during rotation. Acceleration/deceleration is performed with the setting
values of [Pr. PC01] and [Pr. PC02].
When the internal speed commands 1 to 7 are used to command a speed, the speed does not vary
with the ambient temperature.
3 - 40
3. SIGNALS AND WIRING
Set " _ _ _ 3" in [Pr. PA01] to switch to the speed/torque control switching mode.
Note. 0: Off
1: On
The control mode may be switched at any time. The following shows a switching timing chart.
Speed control Torque control Speed control
mode mode mode
LOP ON
(Control switching) OFF
Note. When ST1 (Forward rotation start) and ST2 (Reverse rotation start) are switched off
as soon as a mode is switched to the speed control, the servo motor comes to a stop
according to the deceleration time constant. A shock may occur at switching control
modes.
3 - 41
3. SIGNALS AND WIRING
-10 V to +10 V
VLA
LG
SD
Note. 0: Off
1: On
When the internal speed command 1 is used to command a speed, the speed does not vary with the
ambient temperature.
3 - 42
3. SIGNALS AND WIRING
Set " _ _ _ 5" in [Pr. PA01] to switch to the torque/position control switching mode.
Note. 0: Off
1: On
You can switch the control mode in the zero speed status. To ensure safety, switch modes after the
servo motor has stopped. When position control mode is switched to torque control mode, droop pulses
will be reset.
If LOP is switched on/off at the speed higher than the zero speed, the control mode cannot be changed
regardless of the speed. The following shows a switching timing chart.
Position control Torque control Position control
mode mode mode
Zero speed
Servo motor level
speed
10 V
TC (Analog
torque command)
0V
ON
ZSP (Zero
speed detection) OFF
ON
LOP (Note) (Note)
(Control switching) OFF
Note. When ZSP is not turned on, the control mode is not switched even if LOP is turned
on/off. After LOP is turned on/off, even if ZSP is turned on, the control mode is not
switched.
3 - 43
3. SIGNALS AND WIRING
POINT
When alarms not related to the forced stop function occur, control of motor
deceleration can not be guaranteed. (Refer to chapter 8.)
In the torque control mode, the forced stop deceleration function is not available.
When EM2 is turned off, dynamic brake will start to stop the servo motor after forced stop deceleration.
During this sequence, the display shows [AL. E6 Servo forced stop warning].
During normal operation, do not use EM2 (Forced stop 2) to alternate stop and drive. The the servo amplifier
life may be shortened.
24 V DC
DICOM
(Note)
Forced stop 2 EM2
Note. This diagram shows sink I/O interface. For source I/O interface, refer to section
3.9.3.
3 - 44
3. SIGNALS AND WIRING
POINT
When LSP/LSN is turned on during a forced stop deceleration, the motor will
stop depending on the setting of [Pr. PD30] as follows.
[Pr. PD30] Stop system
___0 Switching to sudden stop
___1 Continuing forced stop deceleration
When EM2 (Forced stop 2) turns off, the motor will decelerate according to [Pr. PC51 Forced stop
deceleration time constant]. Once the motor speed is below [Pr. PC17 Zero speed] after completion of
the deceleration command, base power is cut and the dynamic brake activates.
ON
EM2 (Forced stop 2)
OFF (Enabled)
Dynamic brake
Ordinary Forced stop +
operation deceleration Electromagnetic brake
Rated speed
[Pr. PC51]
Base circuit ON
(Energy supply to
the servo motor) OFF
MBR ON
(Electromagnetic OFF (Enabled)
brake interlock)
3 - 45
3. SIGNALS AND WIRING
The base circuit shut-off delay time function is used to prevent vertical axis from dropping at a forced stop
(EM2 goes off) or alarm occurrence due to delay time of the electromagnetic brake. Use [Pr. PC16] to set
the delay time between completion of EM2 (Forced stop 2) or activation of MBR (Electromagnetic brake
interlock) due to an alarm occurrence, and shut-off of the base circuit.
Base circuit ON
(Energy supply to
the servo motor) OFF
[Pr. PC16]
MBR ON
(Electromagnetic
brake interlock) OFF (Enabled)
(2) Adjustment
While the servo motor is stopped, turn off EM2 (Forced stop 2), adjust the base circuit shut-off delay
time in [Pr. PC16], and set the value to approximately 1.5 times of the smallest delay time in which the
servo motor shaft does not freefall.
3 - 46
3. SIGNALS AND WIRING
The vertical axis freefall prevention function avoids machine damage by pulling up the shaft slightly like the
following case.
When the servo motor is used for operating vertical axis, the servo motor electromagnetic brake and the
base circuit shut-off delay time function avoid dropping axis at forced stop. However, the functions may not
avoid dropping axis a few μm due to the backlash of the servo motor electromagnetic brake.
The vertical axis freefall prevention function is enabled with the following conditions.
Other than "0" is set to [Pr. PC54 Vertical axis freefall prevention compensation amount].
The servo motor speed decelerates lower than the value of zero speed by turning off EM2 (Forced stop
2) or by an alarm occurrence.
The base circuit shut-off delay time function is enabled.
EM2 (Forced stop 2) turned off or an alarm occurred while the servo motor speed is zero speed or less.
Base circuit ON
(Energy supply to
the servo motor) OFF
MBR ON Set the base circuit shut-off delay time. ([Pr. PC16])
(Electromagnetic
brake interlock) OFF (Enabled)
(2) Adjustment
Set the freefall prevention compensation amount in [Pr. PC54].
While the servo motor is stopped, turn off the EM2 (Forced stop 2). Adjust the base circuit shut-off
delay time in [Pr. PC16] in accordance with the travel distance ([Pr. PC54). Adjust it considering the
freefall prevention compensation amount by checking the servo motor speed, torque ripple, etc.
(1) The forced stop function is not available for alarms that activate the dynamic brake when the alarms
occur.
(2) When an alarm that activates the dynamic brake during forced stop deceleration occurs, the braking
distance until the servo motor stops will be longer than that of normal forced stop deceleration without
the dynamic brake.
3 - 47
3. SIGNALS AND WIRING
When an alarm has occurred, remove its cause, make sure that the operation
CAUTION signal is not being input, ensure safety, and reset the alarm before restarting
operation.
POINT
In the torque control mode, the forced stop deceleration function is not available.
To deactivate an alarm, cycle the power, push the "SET" button in the current alarm window, or cycle the
RES (Reset) However, the alarm cannot be deactivated unless its cause is removed.
POINT
To enable the function, set "2 _ _ _ (initial value)" in [Pr. PA04].
0 r/min
Controller command is ignored.
Base circuit ON
(Energy supply to
the servo motor) OFF
Servo amplifier
display No alarm Alarm No.
MBR ON
(Electromagnetic
brake interlock) OFF
ON (no alarm)
ALM (Malfunction)
OFF (alarm)
Note. The model speed command is a speed command generated in the servo amplifier for forced stop deceleration
of the servo motor.
3 - 48
3. SIGNALS AND WIRING
0 r/min
Base circuit ON
(Energy supply to
the servo motor) OFF
Servo amplifier
display No alarm Alarm No.
Operation delay time of the electromagnetic brake
MBR ON
(Electromagnetic
brake interlock) OFF
ON (no alarm)
ALM (Malfunction)
OFF (alarm)
3.8.2 When you do not use the forced stop deceleration function
POINT
To disable the function, set "0 _ _ _" in [Pr. PA04].
The operation status during an alarm is the same as section 3.8.1 (2).
3 - 49
3. SIGNALS AND WIRING
3.9 Interfaces
The following diagram is for sink I/O interface when command pulse train input is differential line driver type.
Servo amplifier
(Note 1)
CN1 P S T
(Note 1) (Note 4) 24 V DC
Approx. 46 DOCOM
P S T CN1 6.2 kΩ
SON SON SON 15 47 DOCOM
RES ST1 RS2 19
(Note 3) 23 ZSP ZSP ZSP RA
CR ST2 RS1 41
(Note 3)
EM2 42 24 INP SA
Approx.
LSP LSP 43 6.2 kΩ 48 ALM
LSN LSN 44
(Note 4) OPC RD
12 49 RD RD RA
24 V DC
DICOM 20
DICOM 21 Approx. Approx.
(Note 2) 100 Ω 1.2 kΩ
PP 10
PG 11 Approx. Approx.
100 Ω 1.2 kΩ
NP 35
NG 36
Isolated
(Note 1)
CN1 P S T
4 LA
5 LAR
6 LB Differential line
driver output
7 LBR (35 mA or less)
8 LZ
(Note 1)
9 LZR
P S T CN1
33 OP Open-collector
VC VLA 2 34 LG output
3 - 50
3. SIGNALS AND WIRING
Note 1. P: position control mode, S: speed control mode, T: torque control mode
2. This is for the differential line driver pulse train input. For the open-collector pulse train input, connect as follows.
DOCOM 46
24 V DC OPC 12
DICOM 20
DOCOM 47
PP 10
PG 11
NP 35
NG 36
3. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
4. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
can be configured by one.
3 - 51
3. SIGNALS AND WIRING
This section provides the details of the I/O signal interfaces (refer to the I/O division in the table) given in
section 3.5. Refer to this section and make connection with the external device.
If polarity of diode is
reversed, servo amplifier
will malfunction.
ALM Load
etc.
DOCOM
(Note) 24 V DC ± 10%
300 mA
Note. If the voltage drop (maximum of 2.6 V) interferes with the relay operation, apply high
voltage (maximum of 26.4 V) from external source.
3 - 52
3. SIGNALS AND WIRING
Am26LS31 or equivalent SD
VOH: 2.5 V
VOL: 0.5 V
tc tLH
tF
NP NG
DOCOM
SD
3 - 53
3. SIGNALS AND WIRING
tc tLH
tF
NP
OP OP
Photocoupler
LG LG
SD SD
150 Ω
LG
SD SD
3 - 54
3. SIGNALS AND WIRING
2) Output pulse
Servo motor CCW rotation
LA Time cycle (T) is determined by the settings of
[Pr. PA15] and [Pr. PC19].
LAR T
LB
LBR
/2
LZ
LZR
400 s or more
OP
VC etc.
Approx.
LG 10 kΩ
SD
MO1
(MO2)
Output voltage: ±10 V (Note)
Maximum output current: 1 mA
LG Resolution: 10 bits or equivalent
3 - 55
3. SIGNALS AND WIRING
DICOM
Approximately DC 24 V ± 10%
5 mA 300 mA
VCES 1.0 V
ICEO 100 A
If polarity of diode is
reversed, servo amplifier
will malfunction.
ALM Load
etc.
DOCOM
(Note) 24 V DC ± 10%
300 mA
Note. If the voltage drop (maximum of 2.6 V) interferes with the relay operation, apply high
voltage (maximum of 26.4 V) from external source.
3 - 56
3. SIGNALS AND WIRING
Servo motor
RA
B U 24 V DC
The electromagnetic brake is provided for holding purpose and must not be used
for ordinary braking.
Before operating the servo motor, be sure to confirm that the electromagnetic
brake operates properly.
Do not use the 24 V DC interface power supply for the electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
Otherwise, it may cause a malfunction.
POINT
Refer to "HF-KN/HF-SN Servo Motor Instruction Manual" for specifications such
as the power supply capacity and operation delay time of the electromagnetic
brake.
Refer to "HF-KN/HF-SN Servo Motor Instruction Manual" for the selection of a
surge absorber for the electromagnetic brake.
Note the following when the servo motor with an electromagnetic brake is used.
1) The brake will operate when the power (24 V DC) turns off.
2) The status is base circuit shut-off during RES (Reset) on. When you use the motor in vertical axis
system, use MBR (Electromagnetic brake interlock).
B2
Note 1. Create the circuit in order to shut off by interlocking with the emergency stop switch.
2. Do not use the 24 V DC interface power supply for the electromagnetic brake.
3 - 57
3. SIGNALS AND WIRING
(2) Setting
(a) Enable MBR (Electromagnetic brake interlock) with [Pr. PD03] to [Pr. PD20].
(b) In [Pr. PC16 Electromagnetic brake sequence output], set the time delay (Tb) from electromagnetic
brake operation to base circuit shut-off at a servo-off as in the timing chart in section 3.10.2 (1).
POINT
To enable the function, set "2 _ _ _ (initial value)" in [Pr. PA04].
Coasting
Servo motor speed 0 r/min
Approx. 95 ms Tb
ON
Base circuit
OFF
Approx. 95 ms Operation delay time of
MBR ON the electromagnetic brake
(Electromagnetic (Note 1)
brake interlock) OFF
ON
SON (Servo-on)
OFF
(Note 3)
3 - 58
3. SIGNALS AND WIRING
POINT
In the torque control mode, the forced stop deceleration function is not available.
(Note 2)
Model speed command 0
and equal to or less than
Servo motor speed zero speed
0 r/min
Base circuit ON
(Energy supply to
the servo motor) OFF
ON
EM2 (Forced stop 2)
OFF
MBR ON
(Electromagnetic (Note 1)
brake interlock) OFF
ON (no alarm)
ALM (Malfunction)
OFF (alarm)
MBR ON
(Electromagnetic (Note 2)
OFF
brake interlock)
Operation delay time of
No alarm the electromagnetic brake
Alarm
[AL.10 Undervoltage] Alarm
ON
Power supply
OFF
3 - 59
3. SIGNALS AND WIRING
(2) When you do not use the forced stop deceleration function
POINT
To disable the function, set "0 _ _ _" in [Pr. PA04].
Disabled (ON)
EM1 (Forced stop)
Enabled (OFF)
3 - 60
3. SIGNALS AND WIRING
3.11 Grounding
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on
the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to di/dt
and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB(NA)67310).
Cabinet
Servo amplifier Servo motor
CN2
MCCB MC
L1
Line filter
(Note) Encoder
Power L2
supply
L3
U U
V V M
W W
CN1
Programmable
controller
Outer
box
Protective earth (PE)
Note. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open. For the power
supply specifications, refer to section 1.3.
3 - 61
3. SIGNALS AND WIRING
MEMO
3 - 62
4. STARTUP
4. STARTUP
Do not operate the switches with wet hands. Otherwise, it may cause an electric
WARNING shock.
Before starting operation, check the parameters. Improper settings may cause
some machines to operate unexpectedly.
The servo amplifier heat sink, regenerative resistor, servo motor, etc. may be hot
CAUTION while power is on or for some time after power-off. Take safety measures, e.g.
provide covers, to avoid accidentally touching the parts (cables, etc.) by hand.
During operation, never touch the rotor of the servo motor. Otherwise, it may
cause injury.
When switching power on for the first time, follow this section to make a startup.
Surrounding environment check Check the surrounding environment of the servo amplifier and servo motor.
(Refer to section 4.1.3.)
Parameter setting Set the parameters as necessary, such as the used operation mode and
regenerative option selection. (Refer to chapter 5, and sections 4.2.4, 4.3.4,
and 4.4.4.)
Test operation of the servo motor For the test operation, with the servo motor disconnected from the machine
alone in test operation mode
and operated at the speed as low as possible, check whether the servo
motor rotates correctly. (Refer to sections 4.2.3, 4.3.3, and 4.4.3.)
Test operation of the servo motor For the test operation with the servo motor disconnected from the machine
alone by commands
and operated at the speed as low as possible, give commands to the servo
amplifier and check whether the servo motor rotates correctly.
Test operation with the servo motor After connecting the servo motor with the machine, check machine motions
and machine connected
with sending operation commands from the controller.
Gain adjustment Make gain adjustment to optimize the machine motions. (Refer to chapter 6.)
Actual operation
Stop Stop giving commands and stop operation. Other conditions that stop the
servo motor are mentioned in sections 4.2.2, 4.3.2, and 4.4.2.
4- 1
4. STARTUP
2) The power supplied to the servo amplifier should not be connected to the power outputs (U, V,
and W). Doing so will fail the connected servo amplifier and servo motor.
3) The grounding terminal of the servo motor is connected to the PE terminal of the servo amplifier.
Servo amplifier Servo motor
4) The CN2 connector of the servo amplifier should be connected to the encoder of the servo motor
securely using the encoder cable.
4- 2
4. STARTUP
(b) A voltage exceeding 24 V DC is not applied to the pins of the CN1 connector.
(c) Between SD and DOCOM of the CN1 connector should not be shorted.
Servo amplifier
CN1
DOCOM
SD
(b) The encoder cable should not be used in excess of its bending life. (Refer to section 10.4.)
(2) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
4- 3
4. STARTUP
Make a startup in accordance with section 4.1. This section provides descriptions specific to the position
control mode.
(1) Power-on
Switch power on in the following procedure. Always follow this procedure at power-on.
(2) Power-off
1) Make sure that a command pulse train is not input.
4.2.2 Stop
If any of the following situations occurs, the servo amplifier suspends the running of the servo motor and
brings it to a stop. Refer to section 3.10 for the servo motor with an electromagnetic brake.
Operation/command Stopping condition
Switch off SON (Servo-on). The base circuit is shut off and the servo motor coasts.
Alarm occurrence The servo motor decelerates to a stop with the command. With some alarms,
however, the dynamic brake operates to bring the servo motor to a stop. (Refer to
chapter 8.)
EM2 (Forced stop 2) off The servo motor decelerates to a stop with the command. [AL. E6 Servo forced stop
warning] occurs. EM2 has the same function as EM1 in the torque control mode.
Refer to section 3.5 for EM1.
LSP (Forward rotation stroke end) off, LSN It will bring the motor to a sudden stop and make it servo-locked. It can be run in the
(Reverse rotation stroke end) off opposite direction.
4- 4
4. STARTUP
Before starting actual operation, perform test operation to make sure that the machine operates normally.
Refer to section 4.2.1 for how to power on and off the servo amplifier.
Test operation of the servo motor In this step, confirm that the servo amplifier and servo motor operate
alone in JOG operation of test
operation mode normally.
With the servo motor disconnected from the machine, use the test operation
mode and check whether the servo motor correctly rotates at the slowest
speed. Refer to section 4.5.9 for the test operation mode.
Test operation of the servo motor In this step, confirm that the servo motor correctly rotates at the slowest
alone by commands
speed under the commands from the controller.
Make sure that the servo motor rotates in the following procedure.
1) Switch on EM2 (Forced stop 2) and SON (Servo-on). When the servo
amplifier is put in a servo-on status, RD (Ready) switches on.
2) Switch on LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end).
3) When a pulse train is input from the controller, the servo motor starts
rotating. Give a low speed command at first and check the rotation
direction, etc. of the servo motor. If the machine does not operate in the
intended direction, check the input signal.
Test operation with the servo motor In this step, connect the servo motor with the machine and confirm that the
and machine connected
machine operates normally under the commands from the controller.
Make sure that the servo motor rotates in the following procedure.
1) Switch on EM2 (Forced stop 2) and SON (Servo-on). When the servo
amplifier is put in a servo-on status, RD (Ready) switches on.
2) Switch on LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end).
3) When a pulse train is input from the controller, the servo motor starts
rotating. Give a low speed command at first and check the operation
direction, etc. of the machine. If the machine does not operate in the
intended direction, check the input signal. In the status display, check for
any problems of the servo motor speed, command pulse frequency, load
ratio, etc.
4- 5
4. STARTUP
POINT
The following encoder cables are of four-wire type. When using any of these
encoder cables, set [Pr. PC22] to "1 _ _ _" to select the four-wire type. Incorrect
setting will result in [AL. 16 Encoder initial communication error 1].
MR-EKCBL30M-L
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
In the position control mode, the servo amplifier can be used by merely changing the basic setting
parameters ([Pr. PA _ _ ]) mainly.
As necessary, set other parameters.
Start actual operation after confirmation of normal operation by test operation and completion of the
corresponding parameter settings. Perform a home position return as necessary.
4- 6
4. STARTUP
POINT
Using the optional MR Configurator2, you can refer to reason for rotation failure,
etc.
The following faults may occur at start-up. If any of such faults occurs, take the corresponding action.
(1) Troubleshooting
No. Start-up sequence Fault Investigation Possible cause Reference
1 Power on LED is not lit. Not improved even if CN1 and 1. Power supply voltage fault
LED flickers. CN2 connectors are disconnected. 2. The servo amplifier is
malfunctioning.
Improved when CN1 connector is Power supply of CN1 cabling is
disconnected. shorted.
Improved when CN2 connector is 1. Power supply of encoder
disconnected. cabling is shorted.
2. Encoder is malfunctioning.
Alarm occurs. Refer to chapter 8 and remove cause. Chapter 8
2 Switch on SON Alarm occurs. Refer to chapter 8 and remove cause. Chapter 8
(Servo-on). Servo motor shaft is 1. Check the display to see if the 1. SON (Servo-on) is not input. Section
not servo-locked. servo amplifier is ready to (wiring mistake) 4.5.7
(Servo motor shaft is operate. 2. 24 V DC power is not
free.) 2. Check the external I/O signal supplied to DICOM.
indication (section 4.5.7) to see
if SON (Servo-on) is on.
3 Input command Servo motor does not Check the cumulative command 1. Wiring mistake Section
pulse (test rotate. pulse on the status display (a) For open collector pulse 4.5.3
operation). (section 4.5.3). train input, 24 V DC power
is not supplied to OPC.
(b) LSP and LSN are not on.
2. Pulse is not input from the
controller.
Mistake in setting of [Pr. PA13]. Chapter
Servo motor run in 1. Mistake in wiring to controller. 5
reverse direction. 2. Mistake in setting of [Pr.
PA14].
4 Gain adjustment Rotation ripples (speed Make gain adjustment in the Gain adjustment fault Chapter
fluctuations) are large following procedure. 6
at low speed. 1. Increase the auto tuning
response level.
2. Repeat acceleration and
deceleration several times to
complete auto tuning.
Large load inertia If the servo motor may be driven Gain adjustment fault Chapter
moment causes the with safety, repeat acceleration 6
servo motor shaft to and deceleration several times to
oscillate side to side. complete auto tuning.
5 Cyclic operation Position shift occurs Confirm the cumulative command Pulse counting error, etc. due to (2) of
pulses, cumulative feedback noise. this
pulses and actual servo motor section
position.
4- 7
4. STARTUP
Cause C
(c) Cumulative feedback pulses
When a position shift occurs, check (a) output pulse counter Q, (b) cumulative command pulse P, (c)
cumulative feedback pulse C, and (d) machine stop position M in the above diagram.
Also, Causes A, B, and C indicate the causes of position mismatch. For example, Cause A indicates that
noise entered the wiring between the controller and servo amplifier, causing command input pulses to be
miscounted.
In a normal status without position shift, there are the following relationships.
131072
P• =C
FBP [Pr. PA05]
1) When Q ≠ P
Noise entered the pulse train signal wiring between the controller and servo amplifier, causing
command input pulses to be miscounted. (Cause A)
Make the following check or take the following measures.
Check how the shielding is done.
Change the open collector type to the differential line driver type.
Run wiring away from the power circuit.
Install a data line filter. (Refer to section 11.9 (2) (a).)
Change the [Pr. PA13 Command pulse input form] setting.
4- 8
4. STARTUP
CMX
2) When P • ≠C
CDV
During operation, SON (Servo-on), LSP (Forward rotation stroke end), or LSN (Reverse rotation
stroke end) was switched off; or CR (Clear) or RES (Reset) was switched on. (Cause C)
3) When C • Δℓ ≠ M
Mechanical slip occurred between the servo motor and machine. (Cause B)
Make a startup in accordance with section 4.1. This section provides the methods specific to the speed
control mode.
(1) Power-on
Switch power on in the following procedure. Always follow this procedure at power-on.
2) Make sure that ST1 (Forward rotation start) and ST2 (Reverse rotation start) are off.
(2) Power-off
1) Switch off ST1 (Forward rotation start) and ST2 (Reverse rotation start).
4.3.2 Stop
If any of the following situations occurs, the servo amplifier suspends the running of the servo motor and
brings it to a stop.
Refer to section 3.10 for the servo motor with an electromagnetic brake.
Operation/command Stopping condition
Switch off SON (Servo-on). The base circuit is shut off and the servo motor coasts.
Alarm occurrence The servo motor decelerates to a stop with the command. With some alarms,
however, the dynamic brake operates to bring the servo motor to a stop. (Refer to
chapter 8.)
EM2 (Forced stop 2) off The servo motor decelerates to a stop with the command. [AL. E6 Servo forced stop
warning] occurs. EM2 has the same function as EM1 in the torque control mode.
Refer to section 3.5 for EM1.
LSP (Forward rotation stroke end) off, LSN It will bring the motor to a sudden stop and make it servo-locked. It can be run in the
(Reverse rotation stroke end) off opposite direction.
Simultaneous on or off of ST1 (Forward The servo motor is decelerated to a stop.
rotation start) and ST2 (Reverse rotation
start)
4- 9
4. STARTUP
Before starting actual operation, perform test operation to make sure that the machine operates normally.
Refer to section 4.3.1 for how to power on and off the servo amplifier.
Test operation of the servo motor In this step, confirm that the servo amplifier and servo motor operate
alone in JOG operation of test
operation mode normally.
With the servo motor disconnected from the machine, use the test operation
mode and check whether the servo motor correctly rotates at the slowest
speed. Refer to section 4.5.9 for the test operation mode.
Test operation of the servo motor In this step, confirm that the servo motor correctly rotates at the slowest
alone by commands
speed under the commands from the controller.
Make sure that the servo motor rotates in the following procedure.
1) Switch on EM2 (Forced stop 2) and SON (Servo-on). When the servo
amplifier is put in a servo-on status, RD (Ready) switches on.
2) Switch on LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end).
3) When VC (Analog speed command) is input from the controller and ST1
(Forward rotation start) or ST2 (Reverse rotation start) is switched on,
the servo motor starts rotating. Give a low speed command at first and
check the rotation direction, etc. of the servo motor. If the machine does
not operate in the intended direction, check the input signal.
Test operation with the servo In this step, connect the servo motor with the machine and confirm that the
motor and machine connected
machine operates normally under the commands from the controller.
Make sure that the servo motor rotates in the following procedure.
1) Switch on EM2 (Forced stop 2) and SON (Servo-on). When the servo
amplifier is put in a servo-on status, RD (Ready) switches on.
2) Switch on LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end).
3) When VC (Analog speed command) is input from the controller and ST1
(Forward rotation start) or ST2 (Reverse rotation start) is switched on,
the servo motor starts rotating. Give a low speed command at first and
check the operation direction, etc. of the machine. If the machine does
not operate in the intended direction, check the input signal. In the status
display, check for any problems of the servo motor speed, load ratio, etc.
4 - 10
4. STARTUP
POINT
The following encoder cables are of four-wire type. When using any of these
encoder cables, set [Pr. PC22] to "1 _ _ _" to select the four-wire type. Incorrect
setting will result in [AL. 16 Encoder initial communication error 1].
MR-EKCBL30M-L
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
When using this servo in the speed control mode, change [Pr. PA01] setting to select the speed control
mode. In the speed control mode, the servo can be used by merely changing the basic setting parameters
([Pr. PA _ _ ]) and extension setting parameters ([Pr. PC _ _ ]) mainly.
As necessary, set other parameters.
4 - 11
4. STARTUP
Start actual operation after confirmation of normal operation by test operation and completion of the
corresponding parameter settings.
POINT
Using the optional MR Configurator2, you can refer to reason for rotation failure,
etc.
The following faults may occur at start-up. If any of such faults occurs, take the corresponding action.
No. Start-up sequence Fault Investigation Possible cause Reference
1 Power on LED is not lit. Not improved even if CN1 and 1. Power supply voltage fault
LED flickers. CN2 connectors are 2. The servo amplifier is
disconnected. malfunctioning.
Improved when CN1 connector is Power supply of CN1 cabling is
disconnected. shorted.
Improved when CN2 connector is 1. Power supply of encoder
disconnected. cabling is shorted.
2. Encoder is malfunctioning.
Alarm occurs. Refer to chapter 8 and remove cause. Chapter 8
2 Switch on SON Alarm occurs. Refer to chapter 8 and remove cause. Chapter 8
(Servo-on). Servo motor shaft is 1. Check the display to see if the 1. SON (Servo-on) is not input. Section
not servo-locked. servo amplifier is ready to (wiring mistake) 4.5.7
(Servo motor shaft is operate. 2. 24 V DC power is not supplied
free.) 2. Check the external I/O signal to DICOM.
indication (section 4.5.7) to
see if SON (Servo-on) is on.
3 Switch on ST1 Servo motor does not Call the status display (section Analog speed command is 0 V. Section
(Forward rotation rotate. 4.5.3) and check the input 4.5.3
start) or ST2 voltage of VC (Analog speed
(Reverse rotation command).
start). Call the external I/O signal LSP, LSN, ST1, and ST2 are off. Section
display (section 4.5.7) and check 4.5.7
the on/off status of the input
signal.
Check the internal speed Set value is 0. Section
commands 1 to 7 ([Pr. PC05] to 5.2.3
[Pr. PC11]).
Check the forward rotation Torque limit level is too low as Section
torque limit ([Pr. PA11]) and the compared to the load torque. 5.2.1
reverse rotation torque limit ([Pr.
PA12]).
When TLA (Analog torque limit) Torque limit level is too low as Section
is usable, check the input voltage compared to the load torque. 4.5.3
on the status display.
4 - 12
4. STARTUP
Make a startup in accordance with section 4.1. This section provides the methods specific to the torque
control mode.
(1) Power-on
Switch power on in the following procedure. Always follow this procedure at power-on.
2) Make sure that RS1 (Forward rotation selection) and RS2 (Reverse rotation selection) are off.
(2) Power-off
1) Switch off RS1 (Forward rotation selection) or RS2 (Reverse rotation selection).
4.4.2 Stop
If any of the following situations occurs, the servo amplifier suspends the running of the servo motor and
brings it to a stop. Refer to section 3.10 for the servo motor with an electromagnetic brake.
Operation/command Stopping condition
Switch off SON (Servo-on). The base circuit is shut off and the servo motor coasts.
Alarm occurrence The servo motor decelerates to a stop with the command. With some alarms,
however, the dynamic brake operates to bring the servo motor to a stop. (Refer to
chapter 8.)
EM2 (Forced stop 2) off This stops the servo motor with the dynamic brake. [AL. E6 Servo forced stop
warning] occurs. EM2 has the same function as EM1 in the torque control mode.
Refer to section 3.5 for EM1.
Simultaneous on or off of RS1 (Forward The servo motor coasts.
rotation selection) and RS2 (Reverse rotation
selection)
4 - 13
4. STARTUP
Before starting actual operation, perform test operation to make sure that the machine operates normally.
Refer to section 4.4.1 for how to power on and off the servo amplifier.
Test operation of the servo motor In this step, confirm that the servo amplifier and servo motor operate
alone in JOG operation of test
operation mode normally.
With the servo motor disconnected from the machine, use the test operation
mode and check whether the servo motor correctly rotates at the slowest
speed. Refer to section 4.5.9 for the test operation mode.
Test operation of the servo In this step, confirm that the servo motor correctly rotates at the slowest
motor alone by commands
speed under the commands from the controller.
Make sure that the servo motor rotates in the following procedure.
2) When TC (Analog speed command) is input from the controller and RS1
(Forward rotation start) or RS2 (Reverse rotation start) is switched on,
the servo motor starts rotating. Give a low torque command at first and
check the rotation direction, etc. of the servo motor. If the machine does
not operate in the intended direction, check the input signal.
Test operation with the servo In this step, connect the servo motor with the machine and confirm that the
motor and machine connected
machine operates normally under the commands from the controller.
Make sure that the servo motor rotates in the following procedure.
2) When TC (Analog speed command) is input from the controller and RS1
(Forward rotation start) or RS2 (Reverse rotation start) is switched on,
the servo motor starts rotating. Give a low torque command at first and
check the operation direction, etc. of the machine. If the machine does
not operate in the intended direction, check the input signal. In the status
display, check for any problems of the servo motor speed, load ratio, etc.
4 - 14
4. STARTUP
POINT
The following encoder cables are of four-wire type. When using any of these
encoder cables, set [Pr. PC22] to "1 _ _ _" to select the four-wire type. Incorrect
setting will result in [AL. 16 Encoder initial communication error 1].
MR-EKCBL30M-L
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
When using this servo in the torque control mode, change [Pr. PA01] setting to select the torque control
mode. In the torque control mode, the servo can be used by merely changing the basic setting parameters
([Pr. PA _ _ ]) and extension setting parameters ([Pr. PC _ _ ]) mainly.
As necessary, set other parameters.
Start actual operation after confirmation of normal operation by test operation and completion of the
corresponding parameter settings.
4 - 15
4. STARTUP
POINT
Using the optional MR Configurator2, you can refer to reason for rotation failure,
etc.
The following faults may occur at start-up. If any of such faults occurs, take the corresponding action.
No. Start-up sequence Fault Investigation Possible cause Reference
1 Power on LED is not lit. Not improved even if CN1 and 1. Power supply voltage fault
LED flickers. CN2 connectors are 2. The servo amplifier is
disconnected. malfunctioning.
Improved when CN1 connector is Power supply of CN1 cabling is
disconnected. shorted.
Improved when CN2 connector is 1. Power supply of encoder
disconnected. cabling is shorted.
2. Encoder is malfunctioning.
Alarm occurs. Refer to chapter 8 and remove cause. Chapter 8
2 Switch on SON Alarm occurs. Refer to chapter 8 and remove cause. Chapter 8
(Servo-on). Servo motor shaft is Call the external I/O signal 1. SON (Servo-on) is not input. Section
free. display (section 4.5.7) and check (wiring mistake) 4.5.7
the on/off status of the input 2. 24 V DC power is not supplied
signal. to DICOM.
3 Switch on RS1 Servo motor does not Call the status display (section Analog torque command is 0 V. Section
(Forward rotation rotate. 4.5.3) and check the input 4.5.3
start) or RS2 voltage of TC (Analog torque
(Reverse rotation command).
start). Call the external I/O signal RS1 and RS2 are off. Section
display (section 4.5.7) and check 4.5.7
the on/off status of the input
signal.
Check the internal speed limit 1 Set value is 0. Section
to 7 ([Pr. PC05] to [Pr. PC11]). 5.2.3
Check the analog torque Torque command level is too low Section
command maximum output ([Pr. as compared to the load torque. 5.2.3
PC13]) value.
Check the forward rotation Set value is 0. Section
torque limit ([Pr. PA11]) and the 5.2.1
reverse rotation torque limit ([Pr.
PA12]).
4 - 16
4. STARTUP
4.5.1 Summary
The MR-JE-A servo amplifier has the display section (5-digit, 7-segment LED) and operation section (4
pushbuttons) for servo amplifier status display, alarm display, parameter setting, etc. Push the "MODE" and
"SET" buttons at the same time for 3 s or more to switch to the one-touch tuning mode.
The operation section and display data are described below.
4 - 17
4. STARTUP
Press the "MODE" button once to shift to the next display mode. Refer to section 4.5.3 and later for the
description of the corresponding display mode.
To refer to and set the gain/filter parameters, extension setting parameters and I/O setting parameters,
enable them with [Pr. PA19 Parameter writing inhibit].
Display mode transition Initial screen Function Reference
Servo status display. Section
appears at power-on. 4.5.3
Status display (Note)
Note. When the axis name is set to the servo amplifier using MR Configurator2, the axis name is displayed and the servo status is then
displayed.
4 - 18
4. STARTUP
The servo status during operation is shown on the 5-digit, 7-segment LED display. Press the "UP" or
"DOWN" button to change display data as desired. When the required data is selected, the corresponding
symbol is displayed. Press the "SET" button to display that data. At only power-on, however, data appears
after the symbol of the status display selected in [Pr. PC36] has been shown for 2 s.
4 - 19
4. STARTUP
11252 pulses
Cumulative feedback
pulses
-12566 pulses
Lit
4 - 20
4. STARTUP
4 - 21
4. STARTUP
4 - 22
4. STARTUP
Sequence
Ready
Indicates that the servo was switched on after
completion of initialization and the servo
amplifier is ready to operate.
Drive recorder enabled
When an alarm occurs in the status, the drive
recorder will operate and write the status of
occurrence.
Drive recorder disabled
Drive recorder enabled/disabled display The drive recorder will not operate on the
following conditions.
1. You are using the graph function of MR
Configurator2.
2. You are using the machine analyzer
function.
3. [Pr. PF21] is set to "-1".
This Indicates the on/off status of external I/O
signal.
External I/O signal display Refer to section 4.5.7. The upper segments correspond to the input
signals and the lower segments to the output
signals.
This allows digital output signal to be
switched on/off forcibly.
Output signal (DO) forced output
For details, refer to section 4.5.8.
4 - 23
4. STARTUP
Note. Even if Automatic VC offset is performed and 0 V is input, the servo motor may not completely stop due to an internal error. To
completely stop the servo motor, switch off ST1 or ST2.
4 - 24
4. STARTUP
The current alarm, past alarm history and parameter error are displayed. The lower 2 digits on the display
indicate the alarm number that has occurred or the parameter number in error.
Name Display Description
Indicates no occurrence of an alarm.
Current alarm
Indicates the occurrence of [AL. 33.1 Main
circuit voltage error].
Flickers at alarm occurrence.
4 - 25
4. STARTUP
(2) Even during alarm occurrence, the other screen can be viewed by pressing the button in the operation
area. At this time, the decimal point in the fourth digit remains flickering.
(3) For any alarm, remove its cause and clear it in any of the following methods. (Refer to chapter 8 for the
alarms that can be cleared.)
[Pr. PA01] [Pr. PB01] [Pr. PC01] [Pr. PD01] [Pr. PE01] [Pr. PF01]
[Pr. PA02] [Pr. PB02] [Pr. PC02] [Pr. PD02] [Pr. PE02] [Pr. PF02]
UP
DOWN
[Pr. PA31] [Pr. PB63] [Pr. PC79] [Pr. PD47] [Pr. PE63] [Pr. PF47]
[Pr. PA32] [Pr. PB64] [Pr. PC80] [Pr. PD48] [Pr. PE64] [Pr. PF48]
4 - 26
4. STARTUP
4 - 27
4. STARTUP
POINT
The I/O signal settings can be changed using the I/O setting parameters [Pr.
PD03] to [Pr. PD28].
The on/off states of the digital I/O signals connected to the servo amplifier can be confirmed.
(1) Operation
The display screen at power-on. Using the "MODE" button, display the diagnostic screen.
Input signal
Always lit
Output signals
The LED segment corresponding to the pin is lit to indicate on, and is extinguished to indicate off.
The signals corresponding to the pins in the respective control modes are indicated below.
4 - 28
4. STARTUP
4 - 29
4. STARTUP
4 - 30
4. STARTUP
POINT
When the servo system is used in a vertical lift application, turning on MBR
(Electromagnetic brake interlock) by the DO forced output after assigning it to
connector CN1 will release the electromagnetic brake, causing a drop. Take
drop preventive measures on the machine side.
Output signals can be switched on/off forcibly independently of the servo status. This function is used for
output signal wiring check, etc. This operation must be performed in the servo off state by turning off SON
(Servo-on).
Operation
The display screen at power-on. Using the "MODE" button, display the diagnostic screen.
4 - 31
4. STARTUP
The test operation mode is designed for checking servo operation. Do not use it
CAUTION for actual operation.
If the servo motor operates unexpectedly, use EM2 (Forced stop 2) to stop it.
POINT
MR Configurator2 is required to perform positioning operation.
Test operation cannot be performed if SON (Servo-on) is not turned off.
4 - 32
4. STARTUP
POINT
When performing JOG operation, turn on EM2, LSP and LSN. LSP and LSN can
be set to automatic on by setting [Pr. PD01] to " _ C _ _ ".
JOG operation can be performed when there is no command from the controller.
(a) Operation
The servo motor rotates while holding down the "UP" or the "DOWN" button. The servo motor stops
rotating by releasing the button. The operation condition can be changed using MR Configurator2.
The initial operation condition and setting range for operation are listed below.
Item Initial setting Setting range
0 to permissible instantaneous
Speed [r/min] 200
speed
Acceleration/deceleration
1000 0 to 50000
time constant [ms]
If the USB cable is disconnected during JOG operation using the MR Configurator2, the servo motor
decelerates to a stop.
4 - 33
4. STARTUP
POINT
MR Configurator2 is required to perform positioning operation.
Turn on EM2 (forced stop 2) when performing positioning operation.
Positioning operation can be performed when there is no command from the controller.
(a) Operation
m)
n)
g)
a)
b)
c)
d)
e)
f)
l)
h)
i)
j) k)
4 - 34
4. STARTUP
To perform continuous operation with the repeat pattern and dwell time settings, which are set
by referring to the above table, click the check box of "Make the aging function enabled".
k) Forced stop
Click the "Forced stop" button during servo motor rotation to make a sudden stop.
This button is enabled during servo motor rotation.
l) Operation status
The operation status during the repeat operation, and the number of operations are displayed
m) Axis No.
Axis No. in operation is displayed.
4 - 35
4. STARTUP
4 - 36
5. PARAMETERS
5. PARAMETERS
POINT
To enable a parameter whose symbol is preceded by *, turn off the power for 1 s
or more after setting and turn it on again. However, the time will be longer
depending on a setting value of [Pr. PF25 SEMI-F47 function - Instantaneous
power failure detection time (instantaneous power failure tough drive - detection
time)] when "SEMI-F47 function selection (instantaneous power failure tough
drive selection)" is enabled in [Pr. PA20].
The symbols in the control mode column mean as follows.
P: Position control mode
S: Speed control mode
T: Torque control mode
5- 1
5. PARAMETERS
5- 2
5. PARAMETERS
5- 3
5. PARAMETERS
5- 4
5. PARAMETERS
5- 5
5. PARAMETERS
5- 6
5. PARAMETERS
5- 7
5. PARAMETERS
POINT
Set a value to each "x" in the "Setting digit" columns.
5- 8
5. PARAMETERS
PA05 The servo motor rotates based on set command input pulses. 10000
*FBP To enable the parameter value, select "Number of command input pulses per
Number of revolution (1 _ _ _)" of "Electronic gear selection" in [Pr. PA21].
command
input pulses Setting range: 1000 to 1000000
per revolution
5- 9
5. PARAMETERS
Encoder
Always set the electronic gear with servo-off state to prevent unexpected operation
due to improper setting.
5 - 10
5. PARAMETERS
5 - 11
5. PARAMETERS
Setting range: 1 to 40
PA10 Set an in-position range per command pulse. 100
INP To change it to the servo motor encoder pulse unit, set [Pr. PC24]. [pulse]
In-position
range Setting range: 0 to 65535
PA11 You can limit the torque generated by the servo motor. Set the parameter referring 100.0
TLP section 3.6.1 (5). [%]
Forward The larger value of [Pr. PA11 Forward rotation torque limit] or [Pr. PA12 Reverse
rotation rotation torque limit] will be the maximum output voltage (8 V).
torque limit Set the parameter on the assumption that the maximum torque is 100 [%]. The
parameter is for limiting the torque of the servo motor in the CCW power running or
CW regeneration. Set this parameter to "0.0" to generate no torque.
5 - 12
5. PARAMETERS
PP
A-phase pulse PP
train
_ _ 1 2h
B-phase pulse
train NP
Forward rotation PP
pulse train
_ _ 0 0h
Reverse rotation
pulse train NP
Positive logic
PP
_ _ 0 1h Signed pulse train
NP L
H
A-phase pulse PP
train
_ _ 0 2h
B-phase pulse
train NP
Arrows in the table indicate the timing of importing pulse trains. A-phase pulse train and B-phase pulse train are
imported after they have been multiplied by 4.
5 - 13
5. PARAMETERS
Setting range: 0, 1
PA15 Set the encoder output pulses from the servo amplifier by using the number of 4000
*ENR output pulses per revolution, dividing ratio, or electronic gear ratio. (after [pulse/
Encoder multiplication by 4) rev]
output pulses To set a numerator of the electronic gear, select "A-phase/B-phase pulse electronic
gear setting (_ _ 3 _)" of "Encoder output pulse setting selection" in [Pr. PC19].
The maximum output frequency is 4.6 Mpulses/s. Set the parameter within this
range.
5 - 14
5. PARAMETERS
PA20 Alarms may not be avoided with the tough drive function depending on the situations of the power supply and load
*TDS fluctuation.
Tough drive You can assign MTTR (During tough drive) to pins CN1-23, CN1-24, and CN1-49 with [Pr. PD24], [Pr. PD25], and [Pr.
setting PD28].
_ _ _ x For manufacturer setting 0h
_ _ x _ Vibration tough drive selection 0h
0: Disabled
1: Enabled
Selecting "1" enables to avoid occurring [AL. 10 Undervoltage] using the electrical
energy charged in the capacitor in the servo amplifier in case that an instantaneous
power failure occurs during operation. In [Pr. PF25 SEMI-F47 function -
Instantaneous power failure detection time (instantaneous power failure tough drive -
detection time)], set the time until the occurrence of [AL. 10.1 Voltage drop in the
power].
When the parameter is enabled, the power should be off for the setting value of [Pr.
PF25] + 1.5 s or more before cycling the power to enable a parameter whose symbol
is preceded by "*".
x___ For manufacturer setting 0h
5 - 15
5. PARAMETERS
When you select the standard mode or low response mode, "Vibration suppression
control 2" is not available.
When you select the 3 inertia mode, the feed forward gain is not available.
Before changing the control mode during the 3 inertia mode or low response mode,
stop the motor.
__x_ For manufacturer setting 0h
_x__ 0h
x___ 0h
PA25 Set a permissible value of overshoot amount for one-touch tuning as a percentage of 0
OTHOV the in-position range. [%]
One-touch However, setting "0" will be 50%.
tuning -
Overshoot
permissible
level
PA26 ___x Torque limit function selection at instantaneous power failure 0h
*AOP5 0: Disabled
Function 1: Enabled
selection A-5 Selecting "1" for this digit will limit torques to save electric energy when an
instantaneous power failure occurs during operation and will make [AL. 10
Undervoltage] less likely to occur.
The torque limit function at instantaneous power failure is enabled when "SEMI-F47
function selection (instantaneous power failure tough drive selection)" in [Pr. PA20]
is "Enabled (_ 1 _ _)".
__x_ For manufacturer setting 0h
_x__ 0h
x___ 0h
5 - 16
5. PARAMETERS
Synchronizing
encoder
Start
Servo motor
Servo amplifier
Without time
constant setting
With time
Servo motor constant setting
speed
ON t
OFF
Start
5 - 17
5. PARAMETERS
PB08 This is used to set the gain of the position loop. 37.0
PG2 Set this parameter to increase the position response to level load disturbance. [rad/s]
Position loop Increasing the setting value will also increase the response level to the load
gain disturbance but will be liable to generate vibration and/or noise.
The setting of the parameter will be the automatic setting or manual setting
depending on the [Pr. PA08] setting. Refer to the following table for details.
5 - 18
5. PARAMETERS
5 - 19
5. PARAMETERS
5 - 20
5. PARAMETERS
PB19 Set the vibration frequency for vibration suppression control 1 to suppress low- 100.0
VRF11 frequency machine vibration. [Hz]
Vibration When "Vibration suppression control 1 tuning mode selection" is "Automatic setting
suppression (_ _ _ 1)" in [Pr. PB02], this parameter will be set automatically. Set manually for
control 1 - "Manual setting (_ _ _ 2)". Refer to section 7.1.5 for details.
Vibration
frequency Setting range: 0.1 to 300.0
PB20 Set the resonance frequency for vibration suppression control 1 to suppress low- 100.0
VRF12 frequency machine vibration. [Hz]
Vibration When "Vibration suppression control 1 tuning mode selection" is "Automatic setting
suppression (_ _ _ 1)" in [Pr. PB02], this parameter will be set automatically. Set manually for
control 1 - "Manual setting (_ _ _ 2)". Refer to section 7.1.5 for details.
Resonance
frequency Setting range: 0.1 to 300.0
PB21 Set a damping of the vibration frequency for vibration suppression control 1 to 0.00
VRF13 suppress low-frequency machine vibration.
Vibration When "Vibration suppression control 1 tuning mode selection" is "Automatic setting
suppression (_ _ _ 1)" in [Pr. PB02], this parameter will be set automatically. Set manually for
control 1 - "Manual setting (_ _ _ 2)". Refer to section 7.1.5 for details.
Vibration
frequency Setting range: 0.00 to 0.30
damping
PB22 Set a damping of the resonance frequency for vibration suppression control 1 to 0.00
VRF14 suppress low-frequency machine vibration.
Vibration When "Vibration suppression control 1 tuning mode selection" is "Automatic setting
suppression (_ _ _ 1)" in [Pr. PB02], this parameter will be set automatically. Set manually for
control 1 - "Manual setting (_ _ _ 2)". Refer to section 7.1.5 for details.
Resonance
frequency Setting range: 0.00 to 0.30
damping
PB23 ___x Shaft resonance suppression filter selection 0h
VFBF Select the shaft resonance suppression filter.
Low-pass 0: Automatic setting
filter selection 1: Manual setting
2: Disabled
When you select "Enabled (_ _ _ 1)" of "Machine resonance suppression filter 4
selection" in [Pr. PB49], the shaft resonance suppression filter is not available.
__x_ Low-pass filter selection 0h
Select the low-pass filter.
0: Automatic setting
1: Manual setting
2: Disabled
_x__ For manufacturer setting 1h
x___ 0h
5 - 21
5. PARAMETERS
5 - 22
5. PARAMETERS
5 - 23
5. PARAMETERS
5 - 24
5. PARAMETERS
5 - 25
5. PARAMETERS
5 - 26
5. PARAMETERS
5 - 27
5. PARAMETERS
0 r/min Time
[Pr. PC01] setting [Pr. PC02] setting
For example for the servo motor of 3000 r/min rated speed, set 3000 (3s) to increase
speed from 0 r/min to 1000 r/min in 1 second.
5 - 28
5. PARAMETERS
Servo motor
speed
0 r/min
Time
STC STA STC STC STB STC
2000000 2000000
for acceleration or by for deceleration.
STA STB
(Example) At the setting of STA 20000, STB 5000 and STC 200, the actual arc part
times are as follows.
5 - 29
5. PARAMETERS
5 - 30
5. PARAMETERS
5 - 31
5. PARAMETERS
A-phase A-phase
1
B-phase B-phase
5 - 32
5. PARAMETERS
Setting
Filtering time [ms]
value
0 0
1 0.444
2 0.888
3 1.777
4 3.555
5 7.111
5 - 33
5. PARAMETERS
5 - 34
5. PARAMETERS
Note 1. It is for the speed control mode. It will be the analog speed limit voltage in
the torque control mode.
2. It is for the torque control mode. It will be the analog torque limit voltage in
the speed control mode and position control mode.
3. Travel distance from power on is displayed by counter value.
_x__ Status display at power-on in corresponding control mode 0h
0: Depends on the control mode
5 - 35
5. PARAMETERS
5 - 36
5. PARAMETERS
0 r/min
[Pr. PC51]
[Precautions]
If the servo motor torque is saturated at the maximum torque during forced stop
deceleration because the set time is too short, the time to stop will be longer than
the set time constant.
[AL. 50 Overload alarm 1] or [AL. 51 Overload alarm 2] may occur during forced
stop deceleration, depending on the set value.
After an alarm that leads to a forced stop deceleration, if an alarm that does not
lead to a forced stop deceleration occurs or if the power supply is cut, dynamic
braking will start regardless of the deceleration time constant setting.
5 - 37
5. PARAMETERS
0
Initial value
Signal name
BIN HEX
0
0
0
SON (Servo-on) 0
0
Initial value
Signal name
BIN HEX
PC (Proportional control) 0
TL (External torque limit selection) 0
0
0
0
Initial value
Signal name
BIN HEX
0
0
0
LSP (Forward rotation stroke end) 0
LSN (Reverse rotation stroke end) 0
BIN 0: Use for an external input signal.
BIN 1: Automatic on
5 - 38
5. PARAMETERS
Note 1. P: position control mode, S: speed control mode, T: torque control mode
The diagonal lines indicate manufacturer settings. Never change the setting.
2. When assigning LOP (Control switching), assign it to the same pin in all control modes.
5 - 39
5. PARAMETERS
Note. P: position control mode, S: speed control mode, T: torque control mode
5 - 40
5. PARAMETERS
5 - 41
5. PARAMETERS
ON
WNG
OFF
ON
0 ALM
OFF
Warning occurrence
ON
WNG
OFF
ON
1 ALM
OFF
Warning occurrence
5 - 42
5. PARAMETERS
Servo motor
speed 0 r/min
Operation pattern
Reverse rotation
direction
Setting range: 0 to
permissible speed
5 - 43
5. PARAMETERS
MEMO
5 - 44
6. NORMAL GAIN ADJUSTMENT
POINT
In the torque control mode, you do not need to make gain adjustment.
Before making gain adjustment, check that your machine is not being operated
at maximum torque of the servo motor. If operated over maximum torque, the
machine may vibrate and may operate unexpectedly. In addition, make gain
adjustment with a safety margin considering characteristic differences of each
machine. It is recommended that generated torque during operation is under
90% of the maximum torque of the servo motor.
The following table shows the gain adjustment modes that can be set on a single servo amplifier. For gain
adjustment, first execute "Auto tuning mode 1". If you are not satisfied with the result of the adjustment,
execute "Auto tuning mode 2" and "Manual mode" in this order.
6- 1
6. NORMAL GAIN ADJUSTMENT
Start
No
Yes
No Error handling No
Finished normally? is possible? Auto tuning mode 1
Yes
Yes
Adjustment OK?
No
Yes
Adjustment OK?
No No
Adjustment OK?
Yes
Adjustment OK?
No
Manual mode
End
This section explains the functions and adjustment using the servo amplifier with MR Configurator2.
Function Description Adjustment
Machine analyzer With the machine and servo motor coupled, You can grasp the machine resonance
the characteristic of the mechanical system frequency and determine the notch
can be measured by giving a random frequency of the machine resonance
vibration command from a personal suppression filter.
computer to the servo and measuring the
machine response.
6- 2
6. NORMAL GAIN ADJUSTMENT
You can execute the one-touch tuning with MR Configurator2 or push buttons. The following parameters are
set automatically with one-touch tuning.
Start
Rotate the servo motor by an external controller, etc. (The one-touch tuning cannot be performed if the
Operation servo motor is not operating.)
Select a response mode (high mode, basic mode, and low mode) in the one-touch tuning window of
Response mode selection MR Configurator2.
Push the start button to start one-touch tuning. Push it during motor driving.
One-touch tuning execution When one-touch tuning is completed normally, the parameters described in table 6.1 will be set
automatically.
End
6- 3
6. NORMAL GAIN ADJUSTMENT
Start
Rotate the servo motor by an external controller, etc. (The one-touch tuning cannot be performed if the
Operation servo motor is not operating.)
Select the initial screen ("AUTO") of the one-touch tuning with the "MODE" button during motor
One-touch tuning start
driving. Push the "SET" button for 2 s or more during displaying "AUTO" to switch to the response
mode selection ("AUTO."). Push the "MODE" and "SET" buttons at the same time for 3 s or more to
switch to the response mode selection ("AUTO.") without going through the initial screen of the one-
touch tuning ("AUTO").
The initial value of response mode is "AUTO." (basic mode). As necessary, push the "UP" or "DOWN"
Response mode selection button to select "AUTO.H" (high mode) or "AUTO.L" (low mode).
Push the "SET" button to start one-touch tuning. Push the "SET" button during servo motor driving.
One-touch tuning execution
When one-touch tuning is completed normally, the parameters described in table 6.1 will be set
automatically.
End
6- 4
6. NORMAL GAIN ADJUSTMENT
6- 5
6. NORMAL GAIN ADJUSTMENT
Arm robot
General machine
tool conveyor
Precision working
machine
Inserter
Mounter
Bonder
High response
6- 6
6. NORMAL GAIN ADJUSTMENT
POINT
For equipment in which overshoot during one-touch tuning is in the permissible
level of the in-position range, changing the value of [Pr. PA25 One-touch tuning
- Overshoot permissible level] will shorten the settling time and improve the
response.
After the response mode is selected in (a), pushing the start button during driving will start one-touch
tuning. If the start button is pushed while the motor stops, "C 0 0 2" or "C 0 0 4" will be displayed at
status in error code. (Refer to table 6.2 of (1) (d) of this section for error codes.)
During processing of one-touch tuning, the status will be displayed in the progress window as
follows. One-touch tuning will be finished at 100%.
Completing the one-touch tuning starts writing tuning parameters to the servo amplifier. "0 0 0 0" is
displayed at status in error code. In addition, settling time and overshoot amount will be displayed in
"Adjustment result" after adjustment.
6- 7
6. NORMAL GAIN ADJUSTMENT
6- 8
6. NORMAL GAIN ADJUSTMENT
When clearing one-touch tuning is completed, the following window will be displayed. (returning to
initial value)
6- 9
6. NORMAL GAIN ADJUSTMENT
POINT
Push the "MODE" and "SET" buttons at the same time for 3 s or more to switch
to the response mode selection ("AUTO.") without going through the initial
screen of the one-touch tuning ("AUTO").
6 - 10
6. NORMAL GAIN ADJUSTMENT
POINT
For equipment in which overshoot during one-touch tuning is in the permissible
level of the in-position range, changing the value of [Pr. PA25 One-touch tuning
- Overshoot permissible level] will shorten the settling time and improve the
response.
After the response mode is selected in (a), pushing the "SET" button will start one-touch tuning.
One-touch tuning in
progress
Complete
Completing the one-touch tuning will start writing the auto-tuned parameters to the servo
amplifier.
The one-touch tuning mode can be stopped by pushing the "SET" button regardless of
displayed item.
2 s interval The stop symbol and error code "C 000" (cancel during tuning) will be displayed by turns
with 2 s interval.
Error code
6 - 11
6. NORMAL GAIN ADJUSTMENT
If an error occurs during the one-touch tuning, the tuning will be forcibly terminated and the
stop symbol and error code from "C 001" to "C 00F" will be displayed by turns with 2 s
interval.
2 s interval
Error code
Check the error cause referring table 6.2 of (1) (d) of this section.
If an alarm occurs during tuning, one-touch tuning will be forcibly terminated and the alarm
No. will be displayed.
Alarm display
If a warning occurs during tuning, the alarm No. of the warning will be displayed.
When the warning is one which continue the motor driving, the one-touch tuning will be
continued.
6 - 12
6. NORMAL GAIN ADJUSTMENT
1) Push the "MODE" button to switch to the initial screen "AUTO" of the one-touch tuning.
2) Select the clear mode or back mode with the "UP" or "DOWN" button.
One-touch tuning clear mode selection
Auto mode
Clear mode
UP DOWN
Back mode
(2) The one-touch tuning cannot be executed while an alarm or warning which withholds the motor driving is
occurring.
(3) You can execute the one-touch tuning during the following test operation modes marked by "○".
Test operation mode
How to one-touch tuning Output signal (DO) forced Positioning Motor-less Program
JOG operation
output operation operation operation
MR Configurator2
Push buttons
6 - 13
6. NORMAL GAIN ADJUSTMENT
The servo amplifier has a real-time auto tuning function which estimates the machine characteristic (load to
motor inertia ratio) in real time and automatically sets the optimum gains according to that value. This
function permits ease of gain adjustment of the servo amplifier.
POINT
The auto tuning mode 1 may not be performed properly if all of the following
conditions are not satisfied.
Time to reach 2000 r/min is the acceleration/deceleration time constant of 5 s
or less.
Speed is 150 r/min or higher.
The load to motor inertia ratio is 100 times or less.
The acceleration/deceleration torque is 10% or more of the rated torque.
Under operating conditions which will impose sudden disturbance torque during
acceleration/deceleration or on a machine which is extremely loose, auto tuning
may not function properly, either. In such cases, use the auto tuning mode 2 or
manual mode to make gain adjustment.
6 - 14
6. NORMAL GAIN ADJUSTMENT
Load moment
Automatic setting of inertia
Encoder
Command + Loop gain +
PG1, PG2, Current
control M
- VG2, VIC -
Load to motor
Gain table inertia ratio
estimation section
Switch Speed feedback
When a servo motor is accelerated/decelerated, the load to motor inertia ratio estimation section always
estimates the load to motor inertia ratio from the current and speed of the servo motor. The results of
estimation are written to [Pr. PB06 Load to motor inertia ratio]. These results can be confirmed on the status
display screen of the MR Configurator2.
If you have already known the value of the load to motor inertia ratio or failed to estimate, set "Gain
adjustment mode selection" to "Auto tuning mode 2 (_ _ _ 2)" in [Pr. PA08] to stop the estimation (turning off
the switch in above diagram), and set the load to motor inertia ratio ([Pr. PB06]) manually.
From the preset load to motor inertia ratio ([Pr. PB06]) value and response ([Pr. PA09]), the optimum loop
gains are automatically set on the basis of the internal gain table.
The auto tuning results are saved in the EEP-ROM of the servo amplifier every 60 minutes since power-on.
At power-on, auto tuning is performed with the value of each loop gain saved in the EEP-ROM being used
as an initial value.
POINT
If sudden disturbance torque is imposed during operation, the load to motor
inertia ratio may be misestimated temporarily. In such a case, set "Gain
adjustment mode selection" to "Auto tuning mode 2 (_ _ _ 2)" in [Pr. PA08] and
then set the correct load to motor inertia ratio in [Pr. PB06].
When any of the auto tuning mode 1 and auto tuning mode settings is changed
to the manual mode 2 setting, the current loop gains and load to motor inertia
ratio estimation value are saved in the EEP-ROM.
6 - 15
6. NORMAL GAIN ADJUSTMENT
Since auto tuning is enabled before shipment from the factory, simply running the servo motor automatically
sets the optimum gains that match the machine. Merely changing the response level setting value as
required completes the adjustment. The adjustment procedure is as follows.
Acceleration/deceleration repeated
No
Yes
Set [Pr. PA08] to "_ _ _ 2" and set
[Pr. PB06 Load to motor inertia ratio]
manually.
Acceleration/deceleration repeated
No
Requested performance
satisfied?
Yes
6 - 16
6. NORMAL GAIN ADJUSTMENT
Set the response of the whole servo system by [Pr. PA09]. As the response level setting is increased, the
track ability and settling time for a command decreases, but a too high response level will generate vibration.
Hence, make setting until desired response is obtained within the vibration-free range.
If the response level setting cannot be increased up to the desired response because of machine resonance
beyond 100 Hz, filter tuning mode selection in [Pr. PB01] or machine resonance suppression filter in [Pr.
PB13] to [Pr. PB16], and [Pr. PB46] to [Pr. PB51] may be used to suppress machine resonance.
Suppressing machine resonance may allow the response level setting to increase. Refer to section 7.1.1 and
7.1.2 for settings of the adaptive tuning mode and machine resonance suppression filter.
[Pr. PA09]
Machine characteristic Machine characteristic
Setting value Guideline for Setting value Guideline for
Response machine resonance Response machine resonance
frequency [Hz] frequency [Hz]
1 Low response 2.7 21 Middle response 67.1
2 3.6 22 75.6
3 4.9 23 85.2
4 6.6 24 95.9
5 10.0 25 108.0
6 11.3 26 121.7
7 12.7 27 137.1
8 14.3 28 154.4
9 16.1 29 173.9
10 18.1 30 195.9
11 20.4 31 220.6
12 23.0 32 248.5
13 25.9 33 279.9
14 29.2 34 315.3
15 32.9 35 355.1
16 37.0 36 400.0
17 41.7 37 446.6
18 47.0 38 501.2
19 52.9 39 571.5
20 Middle response 59.6 40 High response 642.7
6 - 17
6. NORMAL GAIN ADJUSTMENT
If you are not satisfied with the adjustment of auto tuning, you can make simple manual adjustment with
three parameters.
POINT
If machine resonance occurs, filter tuning mode selection in [Pr. PB01] or
machine resonance suppression filter in [Pr. PB13] to [Pr. PB16] and [Pr. PB46]
to [Pr. PB51] may be used to suppress machine resonance. (Section 7.1.1,
7.1.2)
6 - 18
6. NORMAL GAIN ADJUSTMENT
2000 to 3000
Speed integral compensation setting [ms] ≥
Speed loop gain/(1 + Load to motor inertia ratio)
6 - 19
6. NORMAL GAIN ADJUSTMENT
2000 to 3000
Speed integral compensation setting [ms] ≥
Speed loop gain/(1 + Load to motor inertia ratio)
6 - 20
6. NORMAL GAIN ADJUSTMENT
6 - 21
6. NORMAL GAIN ADJUSTMENT
The 2 gain adjustment mode is used to match the position loop gains of the axes when performing the
interpolation operation of servo motors of two or more axes for an X-Y table or the like. In this mode,
manually set the model loop gain that determines command track ability. Other parameters for gain
adjustment are set automatically.
6 - 22
6. NORMAL GAIN ADJUSTMENT
POINT
Set the same value in [Pr. PB07 Model loop gain] for the axis used in 2 gain
adjustment mode.
Speed [r/min]
Position command frequency = × Encoder resolution (number of pulses per servo motor
60
revolution)
6 - 23
6. NORMAL GAIN ADJUSTMENT
MEMO
6 - 24
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
The functions given in this chapter need not be used normally. Use them if you
are not satisfied with the machine status after making adjustment in the methods
in chapter 6.
Load
[Pr. PB48] [Pr. PB50]
[Pr. PB49] Machine [Pr. PE41] Machine
resonance resonance
suppression suppression Encoder
filter 4 filter 5
[Pr. PB17] PWM M
Shaft
resonance
suppression Robust filter Servo motor
filter
POINT
The machine resonance suppression filter is a delay factor for the servo system.
Therefore, vibration may increase if you set an incorrect resonance frequency or
set notch characteristics too deep or too wide.
If the frequency of machine resonance is unknown, decrease the notch
frequency from higher to lower ones in order. The optimum notch frequency is
set at the point where vibration is minimal.
A deeper notch has a higher effect on machine resonance suppression but
increases a phase delay and may increase vibration.
A deeper notch has a higher effect on machine resonance suppression but
increases a phase delay and may increase vibration.
The machine characteristic can be grasped beforehand by the machine analyzer
on MR Configurator2. This allows the required notch frequency and notch
characteristics to be determined.
If a mechanical system has a natural resonance point, increasing the servo system response level may
cause the mechanical system to produce resonance (vibration or unusual noise) at that resonance
frequency. Using the machine resonance suppression filter and adaptive tuning can suppress the resonance
of the mechanical system. The setting range is 10 Hz to 4500 Hz.
7- 1
7. SPECIAL ADJUSTMENT FUNCTIONS
(1) Function
The machine resonance suppression filter is a filter function (notch filter) which decreases the gain of
the specific frequency to suppress the resonance of the mechanical system. You can set the gain
decreasing frequency (notch frequency), gain decreasing depth and width.
mechanical system
Response of
Machine resonance point
Frequency
characteristics
Notch width
Notch
Notch depth
Frequency
Notch frequency
7- 2
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameter
(a) Machine resonance suppression filter 1 ([Pr. PB13] and [Pr. PB14])
Set the notch frequency, notch depth and notch width of the machine resonance suppression filter 1
([Pr. PB13] and [Pr. PB14])
When you select "Manual setting (_ _ _ 2)" of "Filter tuning mode selection" in [Pr. PB01], the setting
of the machine resonance suppression filter 1 is enabled.
(b) Machine resonance suppression filter 2 ([Pr. PB15] and [Pr. PB16])
To use this filter, select "Enabled (_ _ _ 1)" of "Machine resonance suppression filter 2 selection" in
[Pr. PB16].
How to set the machine resonance suppression filter 2 ([Pr. PB15] and [Pr. PB16]) is the same as for
the machine resonance suppression filter 1 ([Pr. PB13] and [Pr. PB14]).
(c) Machine resonance suppression filter 3 ([Pr. PB46] and [Pr. PB47])
To use this filter, select "Enabled (_ _ _ 1)" of "Machine resonance suppression filter 3 selection" in
[Pr. PB47].
How to set the machine resonance suppression filter 3 ([Pr. PB46] and [Pr. PB47]) is the same as for
the machine resonance suppression filter 1 ([Pr. PB13] and [Pr. PB14]).
(d) Machine resonance suppression filter 4 ([Pr. PB48] and [Pr. PB49])
To use this filter, select "Enabled (_ _ _ 1)" of "Machine resonance suppression filter 4 selection" in
[Pr. PB49]. However, enabling the machine resonance suppression filter 4 disables the shaft
resonance suppression filter.
How to set the machine resonance suppression filter 4 ([Pr. PB48] and [Pr. PB49]) is the same as for
the machine resonance suppression filter 1 ([Pr. PB13] and [Pr. PB14]).
(e) Machine resonance suppression filter 5 ([Pr. PB50] and [Pr. PB51])
To use this filter, select "Enabled (_ _ _ 1)" of "Machine resonance suppression filter 5 selection" in
[Pr. PB51]. However, enabling the robust filter ([Pr. PE41: _ _ _ 1]) disables the machine resonance
suppression filter 5.
How to set the machine resonance suppression filter 5 ([Pr. PB50] and [Pr. PB51]) is the same as for
the machine resonance suppression filter 1 ([Pr. PB13] and [Pr. PB14]).
7- 3
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
The machine resonance frequency which adaptive filter II (adaptive tuning) can
respond to is about 100 Hz to 2.25 kHz. As for the resonance frequency out of
the range, set manually.
When adaptive tuning is executed, vibration sound increases as an excitation
signal is forcibly applied for several seconds.
When adaptive tuning is executed, machine resonance is detected for a
maximum of 10 s and a filter is generated. After filter generation, the adaptive
tuning mode automatically shifts to the manual setting.
Adaptive tuning generates the optimum filter with the currently set control gains.
If vibration occurs when the response setting is increased, execute adaptive
tuning again.
During adaptive tuning, a filter having the best notch depth at the set control
gain is generated. To allow a filter margin against machine resonance, increase
the notch depth in the manual setting.
Adaptive vibration suppression control may provide no effect on a mechanical
system which has complex resonance characteristics.
(1) Function
Adaptive filter II (adaptive tuning) is a function in which the servo amplifier detects machine vibration for
a predetermined period of time and sets the filter characteristics automatically to suppress mechanical
system vibration. Since the filter characteristics (frequency, depth) are set automatically, you need not
be conscious of the resonance frequency of a mechanical system.
mechanical system
mechanical system
Response of
Response of
Frequency Frequency
Notch depth
Notch depth
Frequency Frequency
Notch frequency Notch frequency
When machine resonance is large and When machine resonance is small and
frequency is low frequency is high
(2) Parameter
Select how to set the filter tuning in [Pr. PB01 Adaptive tuning mode (adaptive filter II)].
[Pr. PB01]
0 0 0
Filter tuning mode selection
Setting
value Filter tuning mode selection Automatically set parameter
0 Disabled
1 Automatic setting PB13/PB14
2 Manual setting
7- 4
7. SPECIAL ADJUSTMENT FUNCTIONS
Adaptive tuning
Operation
No
Yes
Yes
Has vibration or unusual
noise been resolved?
No
Factor
Decrease the response until vibration Using the machine analyzer, set the The response has increased to the machine limit.
or unusual noise is resolved. filter manually. The machine is too complicated to provide the
optimum filter.
End
7- 5
7. SPECIAL ADJUSTMENT FUNCTIONS
(1) Function
When a load is mounted to the servo motor shaft, resonance by shaft torsion during driving may
generate a mechanical vibration at high frequency. The shaft resonance suppression filter suppresses
the vibration.
When you select "Automatic setting", the filter will be set automatically on the basis of the motor you use
and the load to motor inertia ratio. The disabled setting increases the response of the servo amplifier for
high resonance frequency.
(2) Parameter
Set "Shaft resonance suppression filter selection" in [Pr. PB23].
[Pr. PB23]
0 1 0
Shaft resonance suppression filter selection
0: Automatic setting
1: Manual setting
2: Disabled
To set [Pr. PB17 Shaft resonance suppression filter] automatically, select "Automatic setting".
To set [Pr. PB17 Shaft resonance suppression filter] manually, select "Manual setting". The setting
values are as follows.
7- 6
7. SPECIAL ADJUSTMENT FUNCTIONS
(1) Function
When a ball screw or the like is used, resonance of high frequency may occur as the response level of
the servo system is increased. To prevent this, the low-pass filter is enabled for a torque command as
the initial value. The filter frequency of the low-pass filter is automatically adjusted to the value in the
following equation.
VG2
Filter frequency ([rad/s]) = × 10
1 + GD2
To set [Pr. PB18] manually, select "Manual setting (_ _ 1 _)" of "Low-pass filter selection" in [Pr. PB23].
(2) Parameter
Set "Low-pass filter selection" in [Pr. PB23].
[Pr. PB23]
0 1 0
Low-pass filter selection
0: Automatic setting
1: Manual setting
2: Disabled
POINT
The function is enabled when "Gain adjustment mode selection" in [Pr. PA08] is
"Auto tuning mode 2 (_ _ _ 2)", "Manual mode (_ _ _ 3)", or "2 gain adjustment
mode 2 (_ _ _ 4)".
The machine resonance frequency supported in the vibration suppression
control tuning mode is 1.0 Hz to 100.0 Hz. As for the vibration out of the range,
set manually.
Stop the servo motor before changing the vibration suppression control-related
parameters. Otherwise, it may cause an unexpected operation.
For positioning operation during execution of vibration suppression control
tuning, provide a stop time to ensure a stop after vibration damping.
Vibration suppression control tuning may not make normal estimation if the
residual vibration at the servo motor side is small.
Vibration suppression control tuning sets the optimum parameter with the
currently set control gains. When the response setting is increased, set vibration
suppression control tuning again.
When using the vibration suppression control 2, set "_ _ _ 1" in [Pr. PA24].
7- 7
7. SPECIAL ADJUSTMENT FUNCTIONS
(1) Function
Vibration suppression control is used to further suppress load-side vibration, such as work-side vibration
and base shake. The servo motor-side operation is adjusted for positioning so that the machine does not
vibrate.
Position
Position
Servo motor side Servo motor side
Load side Load side
t t
Vibration suppression: off (normal) Vibration suppression control: on
When the advanced vibration suppression control II ([Pr. PB02 Vibration suppression control tuning
mode]) is executed, the vibration frequency at load side is automatically estimated to suppress machine
side vibration two times at most.
In the vibration suppression control tuning mode, this mode shifts to the manual setting after the
positioning operation is performed the predetermined number of times. For manual setting, adjust the
vibration suppression control 1 with [Pr. PB19] to [Pr. PB22] and vibration suppression control 2 with [Pr.
PB52] to [Pr. PB55].
(2) Parameter
Set [Pr. PB02 Vibration suppression control tuning mode (advanced vibration suppression control II)].
When you use a vibration suppression control, set "Vibration suppression control 1 tuning mode
selection". When you use two vibration suppression controls, set "Vibration suppression control 2 tuning
mode selection" in addition.
[Pr. PB02]
0 0
Vibration suppression control 1 tuning mode
Setting Vibration suppression control 1
value tuning mode selection Automatically set parameter
_ _ _ 0 Disabled
_ _ _ 1 Automatic setting PB19/PB20/PB21/PB22
_ _ _ 2 Manual setting
_ _ 0 _ Disabled
_ _ 1 _ Automatic setting PB52/PB53/PB54/PB55
_ _ 2 _ Manual setting
7- 8
7. SPECIAL ADJUSTMENT FUNCTIONS
Operation
No
Yes
Stop operation.
Resume operation.
No
End
7- 9
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
When load-side vibration does not show up in servo motor-side vibration, the
setting of the servo motor-side vibration frequency does not produce an effect.
When the anti-resonance frequency and resonance frequency can be confirmed
using the machine analyzer or external equipment, do not set the same value
but set different values to improve the vibration suppression performance.
A vibration suppression control effect is not produced if the relation between the
[Pr. PB07 Model loop gain] value and vibration frequency is as follows.
Measure work-side vibration and device shake with the machine analyzer or external measuring
instrument, and set the following parameters to adjust vibration suppression control manually.
Vibration suppression Vibration suppression
Setting item
control 1 control 2
Vibration suppression control - Vibration
[Pr. PB19] [Pr. PB52]
frequency
Vibration suppression control - Resonance
[Pr. PB20] [Pr. PB53]
frequency
Vibration suppression control - Vibration
[Pr. PB21] [Pr. PB54]
frequency damping
Vibration suppression control - Resonance
[Pr. PB22] [Pr. PB55]
frequency damping
Step 1. Select "Manual setting (_ _ _ 2)" of "Vibration suppression control 1 tuning mode selection" or
"Manual setting (_ _ 2 _)" of "Vibration suppression control 2 tuning mode selection" in [Pr.
PB02].
7 - 10
7. SPECIAL ADJUSTMENT FUNCTIONS
Step 2. Set "Vibration suppression control - Vibration frequency" and "Vibration suppression control -
Resonance frequency" as follows.
(a) When a vibration peak can be confirmed with machine analyzer using MR Configurator2, or external
equipment.
Vibration suppression control 2 -
Vibration frequency
(anti-resonance frequency)
[Pr. PB52]
Vibration suppression control 2 -
Resonance frequency
[Pr. PB53]
Gain characteristics
1 Hz 300 Hz
Resonance of more than
Vibration suppression control 1 - 300 Hz is not the target of control.
Vibration frequency Vibration suppression control 1 -
(anti-resonance frequency) Resonance frequency
[Pr. PB19] [Pr. PB20]
Phase
-90 deg.
(b) When vibration can be confirmed using monitor signal or external sensor
t t
Step 3. Fine-adjust "Vibration suppression control - Vibration frequency damping" and "Vibration
suppression control - Resonance frequency damping".
7 - 11
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
By using the advanced vibration suppression control II and the command notch
filter, the load-side vibration of three frequencies can be suppressed.
The frequency range of machine vibration, which can be supported by the
command notch filter, is between 4.5 Hz and 2250 Hz. Set a frequency close to
the machine vibration frequency and within the range.
When [Pr. PB45 Command notch filter] is changed during the positioning
operation, the changed setting is not reflected. The setting is reflected
approximately 150 ms after the servo motor stops (after servo-lock).
(1) Function
Command notch filter has a function that lowers the gain of the specified frequency contained in a
position command. By lowering the gain, load-side vibration, such as work-side vibration and base
shake, can be suppressed. Which frequency to lower the gain and how deep to lower the gain can be
set.
Position
Position
7 - 12
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameter
Set [Pr. PB45 Command notch filter] as shown below. For the command notch filter setting frequency,
set the closest value to the vibration frequency [Hz] at the load side.
[Pr. PB45]
0
Notch depth Command notch filter setting frequency
Setting Depth Setting Frequency Setting Frequency Setting Frequency
value [dB] value [Hz] value [Hz] value [Hz]
0 -40.0 00 Disabled 20 70 40 17.6
1 -24.1 01 2250 21 66 41 16.5
2 -18.1 02 1125 22 62 42 15.6
3 -14.5 03 750 23 59 43 14.8
4 -12.0 04 562 24 56 44 14.1
5 -10.1 05 450 25 53 45 13.4
6 -8.5 06 375 26 51 46 12.8
7 -7.2 07 321 27 48 47 12.2
8 -6.0 08 281 28 46 48 11.7
9 -5.0 09 250 29 45 49 11.3
A -4.1 0A 225 2A 43 4A 10.8
B -3.3 0B 204 2B 41 4B 10.4
C -2.5 0C 187 2C 40 4C 10.0
D -1.8 0D 173 2D 38 4D 9.7
E -1.2 0E 160 2E 37 4E 9.4
F -0.6 0F 150 2F 36 4F 9.1
10 140 30 35.2 50 8.8
11 132 31 33.1 51 8.3
12 125 32 31.3 52 7.8
13 118 33 29.6 53 7.4
14 112 34 28.1 54 7.0
15 107 35 26.8 55 6.7
16 102 36 25.6 56 6.4
17 97 37 24.5 57 6.1
18 93 38 23.4 58 5.9
19 90 39 22.5 59 5.6
1A 86 3A 21.6 5A 5.4
1B 83 3B 20.8 5B 5.2
1C 80 3C 20.1 5C 5.0
1D 77 3D 19.4 5D 4.9
1E 75 3E 18.8 5E 4.7
1F 72 3F 18.2 5F 4.5
You can switch gains with the function. You can switch gains during rotation and during stop, and can use an
input device to switch gains during operation.
7.2.1 Applications
(1) You want to increase the gains during servo-lock but decrease the gains to reduce noise during rotation.
(2) You want to increase the gains during settling to shorten the stop settling time.
(3) You want to change the gains using an input device to ensure stability of the servo system since the
load to motor inertia ratio varies greatly during a stop (e.g. a large load is mounted on a carrier).
7 - 13
7. SPECIAL ADJUSTMENT FUNCTIONS
The control gains, load to motor inertia ratio, and vibration suppression control settings are changed
according to the conditions selected by [Pr. PB26 Gain switching function] and [Pr. PB27 Gain switching
condition].
CDP
[Pr. PB26]
Input device (CDP)
Command pulse +
frequency -
Droop pulses +
-
Changing
Model speed +
-
CDL Comparator
[Pr. PB27]
GD2 VRF11
[Pr. PB06] [Pr. PB19]
Enabled Enabled
GD2B GD2 value VRF11B VRF11 value
[Pr. PB29] [Pr. PB33]
PG1 VRF12
[Pr. PB07] [Pr. PB20]
Enabled Enabled
PG1B PG1 value VRF12B VRF12 value
[Pr. PB60] [Pr. PB34]
PG2 VRF13
[Pr. PB08] [Pr. PB21]
Enabled Enabled
PG2B PG2 value VRF13B VRF13 value
[Pr. PB30] [Pr. PB35]
VG2 VRF14
[Pr. PB09] [Pr. PB22]
Enabled Enabled
VG2B VG2 value VRF14B VRF14 value
[Pr. PB31] [Pr. PB36]
VIC VRF21
[Pr. PB10] [Pr. PB52]
Enabled Enabled
VICB VIC value VRF21B VRF21 value
[Pr. PB32] [Pr. PB56]
VRF22
[Pr. PB53]
Enabled
VRF22B VRF22 value
[Pr. PB57]
VRF23
[Pr. PB54]
Enabled
VRF23B VRF23 value
[Pr. PB58]
VRF24
[Pr. PB55]
Enabled
VRF24B VRF24 value
[Pr. PB59]
7 - 14
7. SPECIAL ADJUSTMENT FUNCTIONS
7.2.3 Parameter
When using the gain switching function, always select "Manual mode (_ _ _ 3)" of "Gain adjustment mode
selection" in [Pr. PA08 Auto tuning mode]. The gain switching function cannot be used in the auto tuning
mode.
7 - 15
7. SPECIAL ADJUSTMENT FUNCTIONS
7 - 16
7. SPECIAL ADJUSTMENT FUNCTIONS
(c) [Pr. PB29 Load to motor inertia ratio after gain switching]
Set the load to motor inertia ratio after gain switching. If the load to motor inertia ratio does not
change, set it to the same value as [Pr. PB06 Load to motor inertia ratio].
(d) [Pr. PB30 Position loop gain after gain switching], [Pr. PB31 Speed loop gain after gain switching],
and [Pr. PB32 Speed integral compensation after gain switching]
Set the values of after switching position loop gain, speed loop gain and speed integral
compensation.
(e) Vibration suppression control after gain switching ([Pr. PB33] to [Pr. PB36]/[Pr. PB56] to [Pr.
PB59])/[Pr. PB60 Model loop gain after gain switching]
The gain switching vibration suppression control and model loop gain are used only with input device
(CDP) on/off.
You can switch the vibration frequency, resonance frequency, vibration frequency damping,
resonance frequency damping, and model loop gain of the vibration suppression control 1 and
vibration suppression control 2.
7 - 17
7. SPECIAL ADJUSTMENT FUNCTIONS
63.4%
Before-switching gain
Gain switching
CDT = 100 ms
7 - 18
7. SPECIAL ADJUSTMENT FUNCTIONS
(a) Setting
Parameter Symbol Name Setting value Unit
PB06 GD2 Load to motor inertia ratio 4.00 [Multiplier]
PB08 PG2 Position loop gain 120 [rad/s]
PB09 VG2 Speed loop gain 3000 [rad/s]
PB10 VIC Speed integral compensation 20 [ms]
PB29 GD2B Load to motor inertia ratio after 10.00 [Multiplier]
gain switching
PB30 PG2B Gain switching position loop gain 84 [rad/s]
PB31 VG2B Gain switching speed loop gain 4000 [rad/s]
PB32 VICB Speed integral compensation after 50 [ms]
gain switching
PB26 CDP Gain switching selection 0003
(switching by droop pulses)
PB27 CDL Gain switching condition 50 [pulse]
PB28 CDT Gain switching time constant 100 [ms]
Command pulses
+CDL
Droop pulses
0
[pulse] -CDL
After-switching gain
63.4%
Before-switching gain
Gain switching
CDT = 100 ms
7 - 19
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
Set enable/disable of the tough drive function with [Pr. PA20 Tough drive
setting]. (Refer to section 5.2.1.)
This function makes the equipment continue operating even under the condition that an alarm occurs.
This function prevents vibration by resetting a filter instantaneously when machine resonance occurs due to
varied vibration frequency caused by machine aging.
To reset the machine resonance suppression filters with the function, [Pr. PB13 Machine resonance
suppression filter 1] and [Pr. PB15 Machine resonance suppression filter 2] should be set in advance.
Set [Pr. PB13] and [Pr. PB15] as follows.
The vibration tough drive function operates when a detected machine resonance frequency is within ±30%
for a value set in [Pr. PB13 Machine resonance suppression filter 1] or [Pr. PB15 Machine resonance
suppression filter 2].
To set a detection level of the function, set sensitivity in [Pr. PF23 Vibration tough drive - Oscillation
detection level].
POINT
Resetting [Pr. PB13] and [Pr. PB15] by the vibration tough drive function is
performed constantly. However, the number of write times to the EEPROM is
limited to once per hour.
The vibration tough drive function does not reset [Pr. PB46 Machine resonance
suppression filter 3], [Pr. PB48 Machine resonance suppression filter 4], and [Pr.
PB50 Machine resonance suppression filter 5].
The vibration tough drive function does not detect a vibration of 100 Hz or less.
7 - 20
7. SPECIAL ADJUSTMENT FUNCTIONS
The following shows the function block diagram of the vibration tough drive function.
The function detects machine resonance frequency and compare it with [Pr. PB13] and [Pr. PB15], and reset
a machine resonance frequency of a parameter whose set value is closer.
Parameter that is
Filter Setting parameter Precaution reset with vibration
tough drive function
Machine resonance PB01/PB13/PB14 The filter can be set automatically with PB13
suppression filter 1 "Filter tuning mode selection" in [Pr.
PB01].
Machine resonance PB15/PB16 PB15
suppression filter 2
Machine resonance PB46/PB47
suppression filter 3
Machine resonance PB48/PB49 Enabling the filter disables the shaft
suppression filter 4 resonance suppression filter.
The shaft resonance suppression filter is
enabled for the initial setting.
Machine resonance PB50/PB51 The setting of this filter is disabled while
suppression filter 5 you use the robust filter.
The robust filter is disabled for the initial
setting.
Load
[Pr. PB48] [Pr. PB50]
[Pr. PB49] Machine [Pr. PE41] Machine
resonance resonance
suppression suppression Encoder
filter 4 filter 5
[Pr. PB17] PWM M
Shaft
resonance
suppression Robust filter Servo motor
filter
7 - 21
7. SPECIAL ADJUSTMENT FUNCTIONS
The instantaneous power failure tough drive function avoids [AL. 10 Undervoltage] even when an
instantaneous power failure occurs during operation. When the instantaneous power failure tough drive
activates, the function will increase the immunity to instantaneous power failures using the electrical energy
charged in the capacitor in the servo amplifier and will change an alarm level of [AL. 10 Undervoltage]
simultaneously. The [AL. 10.1 Voltage drop in the power] detection time for the power supply can be
changed by [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection time (instantaneous power
failure tough drive - detection time)]. In addition, [AL.10.2 Bus voltage drop] detection level for the bus
voltage is changed automatically.
POINT
MBR (Electromagnetic brake interlock) will not turn off during the instantaneous
power failure tough drive.
Selecting "Enabled (_ _ _ 1)" for "Torque limit function selection at
instantaneous power failure" in [Pr. PA26] will limit torques to save electric
energy when an instantaneous power failure occurs during operation and will
make [AL. 10 Undervoltage] less likely to occur.
When the load of instantaneous power failure is large, the undervoltage alarm
([AL. 10.2]) caused by the bus voltage drop may occur regardless of the set
value of [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection
time (instantaneous power failure tough drive - detection time)].
7 - 22
7. SPECIAL ADJUSTMENT FUNCTIONS
(1) Instantaneous power failure time > [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection
time (instantaneous power failure tough drive - detection time)]
The alarm occurs when the instantaneous power failure time exceeds [Pr. PF25 SEMI-F47 function -
Instantaneous power failure detection time (instantaneous power failure tough drive - detection time)].
MTTR (During tough drive) turns on after the instantaneous power failure is detected.
MBR (Electromagnetic brake interlock) turns off when the alarm occurs.
Instantaneous power failure time
ON
Power supply
OFF
[Pr. PF25]
Bus voltage
Undervoltage level
(158 V DC)
ALM ON
(Malfunction) OFF
WNG ON
(Warning) OFF
MTTR ON
(During tough drive) OFF
MBR ON
(Electromagnetic OFF
brake interlock)
ON
Base circuit
OFF
7 - 23
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Instantaneous power failure time < [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection
time (instantaneous power failure tough drive - detection time)]
Operation status differs depending on how bus voltage decrease.
(a) When the bus voltage decreases lower than 158 V DC within the instantaneous power failure time
[AL. 10 Undervoltage] occurs when the bus voltage decrease lower than 158 V DC regardless of the
enabled instantaneous power failure tough drive.
Instantaneous power failure time
ON
Power supply
OFF
[Pr. PF25]
Bus voltage
Undervoltage level
(158 V DC)
ALM ON
(Malfunction) OFF
WNG ON
(Warning) OFF
MTTR ON
(During tough drive) OFF
MBR ON
(Electromagnetic
brake interlock) OFF
ON
Base circuit
OFF
7 - 24
7. SPECIAL ADJUSTMENT FUNCTIONS
(b) When the bus voltage does not decrease lower than 158 V DC within the instantaneous power
failure time
The operation continues without alarming.
Instantaneous power failure time
ON
Power supply
OFF
[Pr. PF25]
Bus voltage
Undervoltage level
(158 V DC)
ALM ON
(Malfunction) OFF
WNG ON
(Warning) OFF
MTTR ON
(During tough drive) OFF
MBR ON
(Electromagnetic
brake interlock) OFF
ON
Base circuit
OFF
7 - 25
7. SPECIAL ADJUSTMENT FUNCTIONS
MEMO
7 - 26
8. TROUBLESHOOTING
8. TROUBLESHOOTING
POINT
As soon as an alarm occurs, turn SON (Servo-on) off and interrupt the power.
When an error occurs during operation, the corresponding alarm or warning is displayed. If any alarm or
warning has occurred, refer to section 8.2 or 8.3 and take the appropriate action. When an alarm occurs,
ALM will turn off.
To output alarm codes, set [Pr. PD34] to "_ _ _ 1". Alarm codes are outputted by on/off of bit 0 to bit 2.
Warnings ([AL. 91] to [AL. F3]) do not have alarm codes. The alarm codes in the following table will be
outputted when they occur. The alarm codes will not be outputted in normal condition.
After its cause has been removed, the alarm can be deactivated in any of the methods marked ○ in the
alarm deactivation column. Warnings are automatically canceled after the cause of occurrence is removed.
For the alarms and warnings in which "SD" is written in the stop method column, the servo motor stops with
the dynamic brake after forced stop deceleration. For the alarms and warnings written "DB" in the stop
method column, the servo motor stops with the dynamic brake without forced stop deceleration.
10 0 1 0 Undervoltage
10.2 Bus voltage drop SD
12.1 RAM error 1 DB
12.2 RAM error 2 DB
12 0 0 0 Memory error 1 (RAM)
12.4 RAM error 4 DB
12.5 RAM error 5 DB
13.1 Clock error 1 DB
13 0 0 0 Clock error
13.2 Clock error 2 DB
14.1 Control process error 1 DB
14.2 Control process error 2 DB
14.3 Control process error 3 DB
14.4 Control process error 4 DB
14.5 Control process error 5 DB
14 0 0 0 Control process error
14.6 Control process error 6 DB
14.7 Control process error 7 DB
14.8 Control process error 8 DB
14.9 Control process error 9 DB
14.A Control process error 10 DB
Memory error 2 15.1 EEP-ROM error at power on DB
15 0 0 0
(EEP-ROM) 15.2 EEP-ROM error during operation DB
8- 1
8. TROUBLESHOOTING
16.1 DB
data error 1
Encoder initial communication - Receive
16.2 DB
data error 2
Encoder initial communication - Receive
16.3 DB
data error 3
Encoder initial communication -
16.5 DB
Transmission data error 1
Encoder initial communication -
16.6 DB
Transmission data error 2
Encoder initial communication -
16.7 DB
Encoder initial Transmission data error 3
16 1 1 0
communication error 1 Encoder initial communication - Process
16.A DB
error 1
Encoder initial communication - Process
16.B DB
error 2
Encoder initial communication - Process
16.C DB
error 3
Encoder initial communication - Process
16.D DB
error 4
Encoder initial communication - Process
16.E DB
error 5
Encoder initial communication - Process
16.F DB
error 6
17.1 Board error 1 DB
17 0 0 0 Board error 17.3 Board error 2 DB
17.4 Board error 3 DB
Memory error 3 19.1 FLASH-ROM error 1 DB
19 0 0 0
(FLASH-ROM) 19.2 FLASH-ROM error 2 DB
Servo motor combination
1A 1 1 0 1A.1 Servo motor combination error DB
error
Encoder initial
1E 1 1 0 1E.1 Encoder malfunction DB
communication error 2
Encoder initial
1F 1 1 0 1F.1 Incompatible encoder DB
communication error 3
Encoder normal communication - Receive
20.1 DB
data error 1
Encoder normal communication - Receive
20.2 DB
data error 2
Encoder normal communication - Receive
20.3 DB
data error 3
Encoder normal communication -
20.5 DB
Encoder normal Transmission data error 1
20 1 1 0
communication error 1 Encoder normal communication -
20.6 DB
Transmission data error 2
Encoder normal communication -
20.7 DB
Transmission data error 3
Encoder normal communication - Receive
20.9 DB
data error 4
Encoder normal communication - Receive
20.A DB
data error 5
21.1 Encoder data error 1 DB
21.2 Encoder data update error DB
Encoder normal 21.3 Encoder data waveform error DB
21 1 1 0
communication error 2 21.5 Encoder hardware error 1 DB
21.6 Encoder hardware error 2 DB
21.9 Encoder data error 2 DB
8- 2
8. TROUBLESHOOTING
24.1 DB
detection circuit
24 1 0 0 Main circuit error
Ground fault detected by software
24.2 DB
detection function
8- 3
8. TROUBLESHOOTING
Note 1. Leave for about 30 minutes of cooling time after removing the cause of occurrence.
2. Stop method indicates as follows:
DB: Stop with dynamic brake
SD: Forced stop deceleration
3. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB using [Pr. PA04].
4. To cancel the alarm, turn off the power and check that the 5-digit, 7-segment LED display is off, and then turn on the power.
8- 4
8. TROUBLESHOOTING
Note 1. Leave for about 30 minutes of cooling time after removing the cause of occurrence.
2. Stop method indicates as follows:
DB: Stop with dynamic brake
SD: Forced stop deceleration
3. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB using [Pr. PA04].
4. Quick stop or slow stop can be selected using [Pr. PD30].
8- 5
8. TROUBLESHOOTING
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate
CAUTION the alarm before restarting operation. Otherwise, it may cause injury.
As soon as an alarm occurs, make the Servo-off status and interrupt the power.
POINT
When any of the following alarms has occurred, do not cycle the power
repeatedly to restart. Doing so will cause a malfunction of the servo amplifier
and servo motor. Remove its cause and allow about 30 minutes for cooling
before resuming the operation.
[AL. 30 Regenerative error] [AL. 45 Main circuit device overheat]
[AL. 46 Servo motor overheat] [AL. 50 Overload 1]
[AL. 51 Overload 2]
Remove the cause of the alarm in accordance with this section. Use MR Configurator2 to refer to the cause
of alarm occurrence.
Alarm No.: 10 or less Name: Undervoltage
The power supply voltage dropped.
Alarm content
The bus voltage dropped.
Display Detail name Cause Check method Check result Action
10.1 Voltage drop in (1) The connection of the Check the power It has a failure. Connect it correctly.
the power power connector has a connector.
failure. It has no failure. Check (2).
(2) Power supply voltage is Check if the voltage of The voltage is lower than Review the voltage of
low. the power supply is 160 160 V AC. the power supply.
V AC or lower. The voltage is higher Check (3).
than 160 V AC.
(3) An instantaneous power Check if the power has a It has a problem. Review the power.
failure has occurred for problem.
longer time than the
specified time. The time
will be 60 ms when [Pr.
PA20] is "_ 0 _ _". The
time will be the value set
in [Pr. PF25] when [Pr.
PA20] is "_ 1 _ _".
10.2 Bus voltage (1) The connection of the Check the power It has a failure. Connect it correctly.
drop power connector has a connector.
It has no failure. Check (2).
failure.
(2) Power supply voltage is Check if the voltage of The voltage is lower than Increase the power
low. the power supply is 160 160 V AC. supply voltage.
V AC or lower. The voltage is higher Check (3).
than 160 V AC.
(3) The alarm has occurred Check that the bus The voltage is less than Increase the acceleration
during acceleration. voltage during 200 V DC. time constant. Or
acceleration is 200 V DC increase the power
or more. supply capacity.
The voltage is 200 V DC Check (4).
or more.
(4) The servo amplifier is Check the bus voltage The voltage of the power Replace the servo
malfunctioning. value. supply is 160 V AC or amplifier.
more, and the bus
voltage is less than 200
V DC.
8- 6
8. TROUBLESHOOTING
8- 7
8. TROUBLESHOOTING
8- 8
8. TROUBLESHOOTING
8- 9
8. TROUBLESHOOTING
8 - 10
8. TROUBLESHOOTING
8 - 11
8. TROUBLESHOOTING
8 - 12
8. TROUBLESHOOTING
(2) Something near the Check the noise, ground It has a failure. Take countermeasures
device caused it. fault, ambient against its cause.
temperature, etc.
8 - 13
8. TROUBLESHOOTING
8 - 14
8. TROUBLESHOOTING
8 - 15
8. TROUBLESHOOTING
8 - 16
8. TROUBLESHOOTING
8 - 17
8. TROUBLESHOOTING
8 - 18
8. TROUBLESHOOTING
8 - 19
8. TROUBLESHOOTING
8 - 20
8. TROUBLESHOOTING
8 - 21
8. TROUBLESHOOTING
8 - 22
8. TROUBLESHOOTING
8 - 23
8. TROUBLESHOOTING
POINT
When any of the following alarms has occurred, do not cycle the power of the
servo amplifier repeatedly to restart. Doing so will cause a malfunction of the
servo amplifier and servo motor. If the power of the servo amplifier is switched
off/on during the alarms, allow more than 30 minutes for cooling before
resuming operation.
[AL. 91 Servo amplifier overheat warning] [AL. E0 Excessive regeneration
warning]
[AL.E1 Overload warning 1] [AL.EC Overload warning 2]
If [AL. E6] or [AL. E9] occurs, the amplifier will be the servo-off status. If any other warning occurs, operation
can be continued but an alarm may take place or proper operation may not be performed.
Remove the cause of warning according to this section. Use MR Configurator2 to refer to the cause of
warning occurrence.
Alarm No.: 91 Name: Servo amplifier overheat warning
Alarm content The temperature inside of the servo amplifier reached a warning level.
Display Detail name Cause Check method Check result Action
91.1 Main circuit (1) Ambient temperature of Check the ambient It is over 55 ˚C. Lower the ambient
device overheat the servo amplifier has temperature. temperature.
warning exceeded 55 ˚C. It is less than 55 ˚C. Check (2).
(2) The close mounting is Check the specifications It is out of specifications. Use within the range of
out of specifications. of close mounting. specifications.
8 - 24
8. TROUBLESHOOTING
8 - 25
8. TROUBLESHOOTING
8 - 26
8. TROUBLESHOOTING
8 - 27
8. TROUBLESHOOTING
MEMO
8 - 28
9. DIMENSIONS
9. DIMENSIONS
[Unit: mm]
2.9
50
6
φ6 mounting hole Approx. 80 135
6
CN3
CN1
156
168
CN2
CNP1
PE
6
2-M5 screw
6
P+
C
U
V
W
Approx. 168
156 ± 0.5
PE
Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
9- 1
9. DIMENSIONS
(2) MR-JE-70A/MR-JE-100A
[Unit: mm]
70
22
φ6 mounting hole Approx. 80 185
6
CN3
CN1
156
168
CN2
CNP1
PE
6
6
22 42
3.3
L2
6
L3
P+
C
U
Approx. 168
V
156 ± 0.5
3-M5 screw
PE
Screw size: M4
Tightening torque: 1.2 [N•m]
Approx.
42 ± 0.3
6
Approx. 22 Approx. 6
Mounting hole process drawing
9- 2
9. DIMENSIONS
(3) MR-JE-200A/MR-JE-300A
[Unit: mm]
90
85
φ6 mounting hole 45 Approx. 80 195
CN3 Exhaust
6 CNP1
161
156
168
CN1
CNP2
CN2
6
PE Cooling fan
6 air intake
6 78
L2
6
L3
N-
C
D
Approx. 168
P+
156 ± 0.5
CNP2
U 3-M5 screw
V PE
Screw size: M4
W Tightening torque: 1.2 [N•m]
Approx.
6
9- 3
9. DIMENSIONS
9.2 Connector
[Unit: mm]
E
D
A C
Logo etc, are indicated here.
39.0
23.8
B 12.7
Variable dimensions
Connector Shell kit
A B C D E
10150-3000PE 10350-52F0-008 41.1 52.4 18.0 14.0 17.0
[Unit: mm]
E D
A C F
Logo etc, are indicated here.
39.0
23.8
5.2
B
12.7
Variable dimensions
Connector Shell kit
A B C D E F
10150-3000PE 10350-52A0-008 41.1 52.4 18.0 14.0 17.0 46.5
9- 4
9. DIMENSIONS
[Unit: mm]
39.5
34.8
11.0
22.4
9- 5
9. DIMENSIONS
MEMO
9- 6
10. CHARACTERISTICS
10. CHARACTERISTICS
An electronic thermal is built in the servo amplifier to protect the servo motor, servo amplifier and servo
motor power wires from overloads.
[AL. 50 Overload 1] occurs if overload operation performed is above the electronic thermal protection curve
shown in fig. 10.1. [AL. 51 Overload 2] occurs if the maximum current is applied continuously for several
seconds due to machine collision, etc. Use the equipment on the left-side area of the continuous or broken
line in the graph.
For the system where the unbalanced torque occurs, such as a vertical axis system, it is recommended that
the unbalanced torque of the machine be kept at 70% or less of the motor's rated torque.
This servo amplifier has servo motor overload protective function. (The servo motor overload current (full
load current) is set on the basis of 120% rated current of the servo amplifier.)
10 - 1
10. CHARACTERISTICS
1000 1000
Operating Operating
100 100
Operation time [s]
1 1
0.1 0.1
0 50 100 150 200 250 300 320 0 50 100 150 200 250 300 320
(Note) Load ratio [%] (Note) Load ratio [%]
10 - 2
10. CHARACTERISTICS
Table 10.1 Power supply capacity and generated loss per servo motor at rated output
(Note 1) (Note 2) Servo amplifier- Area required
Servo amplifier Servo motor Power supply generated heat [W] for heat
2
capacity [kVA] At rated output With servo-off dissipation [m ]
MR-JE-10A HF-KN13 0.3 25 15 0.5
MR-JE-20A HF-KN23 0.5 25 15 0.5
MR-JE-40A HF-KN43 0.9 35 15 0.7
HF-KN73 1.3 50 15 1.0
MR-JE-70A
HF-SN52 1.0 40 15 0.8
MR-JE-100A HF-SN102 1.7 50 15 1.0
HF-SN152 2.5
MR-JE-200A 90 20 1.8
HF-SN202 3.5
MR-JE-300A HF-SN302 4.8 120 20 2.4
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value is
applicable when the power factor improving AC reactor is not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate
heat generated by the regenerative option, refer to section 11.2.
10 - 3
10. CHARACTERISTICS
P
A= ·········································································································································· (10.1)
K • ΔT
When calculating the heat dissipation area with equation 10.1, assume that P is the sum of all losses
generated in the cabinet. Refer to table 10.1 for heat generated by the servo amplifier. "A" indicates the
effective area for heat dissipation, but if the cabinet is directly installed on an insulated wall, that extra
amount must be added to the cabinet's surface area. The required heat dissipation area will vary with
the conditions in the cabinet. If convection in the cabinet is poor and heat builds up, effective heat
dissipation will not be possible. Therefore, arrangement of the equipment in the cabinet and the use of a
cooling fan should be considered. Table 10.1 lists the cabinet dissipation area for each servo amplifier
(guideline) when the servo amplifier is operated at the ambient temperature of 40 ˚C under rated load.
When air flows along the outer wall of the cabinet, effective heat exchange will be possible, because the
temperature slope inside and outside the cabinet will be steeper.
10 - 4
10. CHARACTERISTICS
POINT
Do not use dynamic brake to stop in a normal operation as it is the function to
stop in emergency.
For a machine operating at the recommended load to motor inertia ratio or less,
the estimated number of usage times of the dynamic brake is 1000 times while
the machine decelerates from the rated speed to a stop once in 10 minutes.
Be sure to enable EM1 (Forced stop 1) after servo motor stops when using EM1
(Forced stop 1) frequently in other than emergency.
Dynamic brake
time constant τ
V0
Machine speed
te Time
V0 JL
Lmax = • te + 1+ ··············································································································· (10.2)
60 JM
10 - 5
10. CHARACTERISTICS
constant [ms]
constant [ms]
15 60
23 43 202
10 40 52
302
5 20
13 152
0 0
0 500 1500 2500 3500 4500 0 500 1000 1500 2000 2500 3000
1000 2000 3000 4000
Speed [r/min] Speed [r/min]
10.3.2 Permissible load to motor inertia when the dynamic brake is used
Use the dynamic brake under the load to motor inertia ratio indicated in the following table. If the ratio is
higher than this value, the dynamic brake may burn. If there is a possibility that the ratio may exceed the
value, contact your local sales office.
The values of the permissible load to motor inertia ratio in the table are the values at the maximum rotation
speed of the servo motor.
Permissible load to
Servo motor
motor inertia ratio [multiplier]
HF-KN13
HF-KN23
HF-KN43
HF-KN73
30
HF-SN52
HF-SN102
HF-SN152
HF-SN202
HF-SN302 16
10 - 6
10. CHARACTERISTICS
The bending life of the cables is shown below. This graph calculated values. Since they are not guaranteed
values, provide a little allowance for these values.
1 × 108 a
5 × 107
1 × 107
5 × 106 a: Long bending life encoder cable
Long bending life motor power cable
Number of bending times
1 × 106
5 × 105
b: Standard encoder cable
Standard motor power cable
Standard electromagnetic brake cable
1 × 105
5 × 104
1 × 104 b
5 × 103
1 × 103
4 7 10 20 40 70 100 200
Bend radius [mm]
The following table indicates the inrush currents (reference data) that will flow when 240 V AC is applied at
the power supply capacity of 2500 kVA and the wiring length of 1 m. Even when you use a 1-phase 200 V
AC power supply with MR-JE-10A to MR-JE-70A, the inrush currents will be the same.
Servo amplifier Inrush currents (A0-P)
MR-JE-10A, MR-JE-20A, 32 A
MR-JE-40A (attenuated to approx. 3 A in 20 ms)
36 A
MR-JE-70A, MR-JE-100A
(attenuated to approx. 7 A in 20 ms)
102 A
MR-JE-200A, MR-JE-300A
(attenuated to approx. 12 A in 20 ms)
Since large inrush currents flow in the power supplies, always use molded-case circuit breakers and
magnetic contactors. (Refer to section 11.6.)
When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an
inrush current, be used.
10 - 7
10. CHARACTERISTICS
MEMO
10 - 8
11. OPTIONS AND PERIPHERAL EQUIPMENT
Before connecting options and peripheral equipment, turn off the power and wait
for 15 minutes or more until the charge lamp turns off. Otherwise, an electric
WARNING shock may occur. In addition, when confirming whether the charge lamp is off or
not, always confirm it from the front of the servo amplifier.
POINT
We recommend using HIV wires to wire the servo amplifiers, options, and
peripheral equipment. Therefore, the recommended wire sizes may differ from
those used for the previous servo amplifiers.
POINT
The IP rating indicated for cables and connectors is their protection against
ingress of dust and raindrops when they are connected to a servo amplifier or
servo motor. If the IP rating of the cable, connector, servo amplifier and servo
motor vary, the overall IP rating depends on the lowest IP rating of all
components.
Please purchase the cable and connector options indicated in this section.
11 - 1
11. OPTIONS AND PERIPHERAL EQUIPMENT
Operation 3)
panel
2)
Servo amplifier
Personal computer
Controller
5)
CN3
CN1
1) (Packed with the
servo amplifier)
(Note) CN2
CNP1
To 24 V DC power supply
for electromagnetic brake Servo motor
Note. Connectors for 1 kW or less. Refer to section 3.3.3 (1) (b) for 2 kW or more.
11 - 2
11. OPTIONS AND PERIPHERAL EQUIPMENT
CNP1 Connector:
09JFAT-SAXGDK-H5.0
(JST)
Applicable wire size: AWG 18 to 14
Insulator OD: to 3.9 mm
Open tool
J-FAT-OT
(JST)
MR-JECNP1-02 Supplied
with servo
amplifiers
of 2 kW
and 3 kW
CNP1 Connector:
07JFAT-SAXGFK-XL
(JST)
Applicable wire size: AWG 16 to 10 Open tool
Insulator OD: to 4.7 mm J-FAT-OT-EXL
(JST)
Servo amplifier MR-JECNP2-02
power connector
CNP2 Connector:
03JFAT-SAXGFK-XL
(JST)
Applicable wire size: AWG 16 to 10
Insulator OD: to 4.7 mm
2) Junction terminal MR-J2M- Junction terminal block connector CN1 connector For
block cable CN1TBL_M Connector: D7950-B500FL Connector: 10150-6000EL junction
Cable length: (3M) Shell kit: 10350-3210-000 terminal
0.5 m, 1 m (3M or equivalent) block
(Refer to section connection
11.3.)
11 - 3
11. OPTIONS AND PERIPHERAL EQUIPMENT
Do not use servo amplifiers with regenerative options other than the combinations
CAUTION specified below.
Otherwise, it may cause a fire.
The power values in the table are resistor-generated powers and not rated powers.
Regenerative power [W]
Servo Built-in (Note)
amplifier MR-RB032 MR-RB12 MR-RB30 MR-RB32
regenerative MR-RB50
[40 Ω] [40 Ω] [13 Ω] [40 Ω]
resistor [13 Ω]
MR-JE-10A 30
MR-JE-20A 30 100
MR-JE-40A 10 30 100
MR-JE-70A 20 30 100 300
MR-JE-100A 20 30 100 300
MR-JE-200A 100 300 500
MR-JE-300A 100 300 500
11 - 4
11. OPTIONS AND PERIPHERAL EQUIPMENT
Use the following method when regeneration occurs continuously in vertical motion applications or when it is
desired to make an in-depth selection of the regenerative option.
Time
Down
Unbalance torque
M t1 t2 t3 t4
tpsa1 tpsd1 tpsa2 tpsd2
Friction
torque 1)
(+)
(Power running)
Generated torque
2) 4) 8)
TF 5)
TU 6)
3)
(Regenerative) 7)
(-)
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative energies.
11 - 5
11. OPTIONS AND PERIPHERAL EQUIPMENT
Inverse efficiency (η): Efficiency including some efficiencies of the servo motor and servo amplifier
when rated (regenerative) torque is generated at rated speed. Since the
efficiency varies with the speed and generated torque, allow for about 10%.
Capacitor charging (Ec): Energy charged into the electrolytic capacitor in the servo amplifier
Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies
by the inverse efficiency to calculate the energy consumed by the regenerative option.
ER [J] = η • Es - Ec
Calculate the power consumption of the regenerative option on the basis of one-cycle operation
period tf [s] to select the necessary regenerative option.
PR [W] = ER/tf
0 0
Regenerative option selection
00: Regenerative option is not used.
For servo amplifier of 200 W, regenerative resistor is not used.
For servo amplifier of 0.4 kW to 3 kW, built-in regenerative resistor is used.
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50 (Cooling fan is required)
11 - 6
11. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
When you use a regenerative option with an MR-JE-40A to MR-JE-100A,
remove the built-in regenerative resistor and wiring from the servo amplifier.
When MR-RB50 is used, a cooling fan is required to cool it. The cooling fan
should be prepared by the customer.
For the wire sizes used for wiring, refer to section 11.5.
A built-in regenerative resistor should not be mounted/removed frequently.
When you remount a built-in regenerative resistor, check the lead wires of the
built-in regenerative resistor for scratches or cracks.
The regenerative option generates heat of 100 ˚C higher than the ambient temperature. Fully consider heat
dissipation, installation position, wires used, etc. before installing the option. For wiring, use flame-resistant
wires or make the wires flame-resistant and keep them away from the regenerative option. Always use
twisted cables of max. 5 m length for connection with the servo amplifier.
5 m or less
Note 1. The built-in regenerative resistor is not provided for MR-JE-10A and MR-JE-20A.
2. Make up a sequence which will switch off the magnetic contactor when abnormal
heating occurs.
G3-G4 contact specifications
Maximum voltage: 120 V AC/DC
Maximum current: 0.5 A/4.8 V DC
Maximum capacity: 2.4 VA
11 - 7
11. OPTIONS AND PERIPHERAL EQUIPMENT
To remove the built-in regenerative resistor mounted on the back of MR-JE-40A to MR-JE-100A, follow
the procedures 1) to 3) with referring the illustration.
1) Disconnect the wirings of the built-in regenerative resistor from the power connector (CNP1).
(Refer to (3) (b) of 3.3.2.)
2) Remove the wirings of the built-in regenerative resistor from the closest position to the power
connector (CNP1) in order. Please pay full attention not to break the wirings.
3) Remove the screw fixing the built-in regenerative resistor and dismount the built-in regenerative
resistor.
(Note)
3)
1)
2)
11 - 8
11. OPTIONS AND PERIPHERAL EQUIPMENT
5 m or less
(Note 1, 2)
Cooling fan
3
Note 1. When using the MR-RB50, forcibly cool it with a cooling fan (1.0 m /min or more,
92 mm × 92 mm).
2. When the ambient temperature is more than 55 °C and the regenerative load ratio
is more than 60% in MR-RB30 and MR-RB32, forcefully cool the air with a cooling
3
fan (1.0 m /min or more, 92 mm × 92 mm). A cooling fan is not required if the
ambient temperature is 35 °C or less. (A cooling fan is required for the shaded
area in the following graph.)
A cooling fan is required.
100
Load ratio [%]
60
A cooling fan is
not required.
0
0 35 55
Ambient temperature [°C]
3. Make up a sequence which will switch off the magnetic contactor when abnormal
heating occurs.
G3-G4 contact specifications
Maximum voltage: 120 V AC/DC
Maximum current: 0.5 A/4.8 V DC
Maximum capacity: 2.4 VA
11 - 9
11. OPTIONS AND PERIPHERAL EQUIPMENT
11.2.5 Dimensions
(1) MR-RB12
[Unit: mm]
TE1 terminal block
G3
φ6 mounting hole
40 G4
Approx. 6
36 P
15 C
2 2
Applicable wire size: 0.2 mm to 2.5 mm (AWG 24 to
12)
Tightening torque: 0.5 to 0.6 [N•m]
5 Mounting screw
156
168
144
Screw size: M5
TE1 Tightening torque: 3.24 [N•m]
6 2
Approx. 20 149
169
(2) MR-RB30/MR-RB32
[Unit: mm]
Terminal block
Cooling fan mounting
screw (2-M4 screw) P
8.5
C
G3
125
82.5
150
142
G4
101.5 82.5
10 90 17 318
100 Mounting screw
335
Screw size: M6
Approx. 30
11 - 10
11. OPTIONS AND PERIPHERAL EQUIPMENT
(3) MR-RB50
[Unit: mm]
Terminal block
Cooling fan mounting
screw (2-M3 screw) P
On opposite side
7 × 14 C
12.5
49 82.5 slotted hole
G3
G4
Mounting screw
Air Screw size: M6
82.5
350
2.3 7
12.5
(4) MR-RB032
[Unit: mm]
TE1 terminal block
φ6 mounting hole G3
30
Approx. 12
Approx. 6
15 G4
P
C
2 2
Applicable wire size: 0.2 mm to 2.5 mm (AWG 24 to
12)
Tightening torque: 0.5 to 0.6 [N•m]
5
156
168
144
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N•m]
TE1
Mass: 0.5 [kg]
12
6 1.6
6
Approx. 20 99
119
11 - 11
11. OPTIONS AND PERIPHERAL EQUIPMENT
(1) Usage
Always use the junction terminal block (MR-TB50) with the option cable (MR-J2M-CN1TBL_M) as a set.
Servo amplifier
CN1
Junction terminal
block cable
(MR-J2M-CN1TBL_M)
Install the junction terminal block cable on the junction terminal block side with the supplied cable clamp
fitting (AERSBAN-ESET). For the use of the cable clamp fitting, refer to section 11.9, (2) (c).
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
1
9
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
2
(3) Dimensions
[Unit: mm]
235
2- 4.5
Approx.
2 50
1 49
25
MITSUBISHI
50
MR-TB50
9
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 3133 35 37 39 41 43 45 47 49
25
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
2.5
244 46.5
11 - 12
11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 13
11. OPTIONS AND PERIPHERAL EQUIPMENT
11.4 MR Configurator2
POINT
For the MR-JE servo amplifier, use MR Configurator2 with software version
1.19V or later.
MR Configurator2 (SW1DNC-MRC2-E) uses the communication function of the servo amplifier to perform
parameter setting changes, graph display, test operation, etc. on a personal computer.
(1) Specifications
Item Description
Project Create/read/save/delete project, system setting, and print
Parameter Parameter setting, axis name setting
Monitor Display all, I/O monitor, and graph
Alarm display, alarm onset data, drive recorder, no motor rotation, system configuration, life
Diagnosis
diagnosis, machine diagnosis
Jog operation, positioning operation, motor-less operation, DO forced output, and program
Test operation
operation, test mode information
Adjustment One-touch tuning, tuning, and machine analyzer
Servo assistant, parameter setting range update, machine unit conversion setting, and help
Others
display
11 - 14
11. OPTIONS AND PERIPHERAL EQUIPMENT
Note 1. Microsoft, Windows, Internet Explorer and Windows Vista are registered trademarks of Microsoft Corporation in the United
States and other countries.
Celeron and Pentium are the registered trademarks of Intel Corporation.
2. On some personal computers, MR Configurator2 may not run properly.
® ® ® ® ® ®
3. When Microsoft Windows 7, Microsoft Windows Vista , or Microsoft Windows XP is used, the following functions cannot
be used.
Windows Program Compatibility mode
Fast User Switching
Remote Desktop
Large Fonts Mode (Display property)
DPI settings other than 96 DPI (Display property)
®
For 64-bit operating system, this software is compatible with Windows 7.
®
4. When Windows 7 is used, the following functions cannot be used.
Windows XP Mode
Windows touch
® ®
5. When using this software with Windows Vista and Windows 7, log in as a user having USER authority or higher.
CN3
11 - 15
11. OPTIONS AND PERIPHERAL EQUIPMENT
POINT
To comply with the UL/CSA standard, use the wires shown in appendix 2 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection conditions of wire size is as follows.
Construction condition: One wire is constructed in the air.
Wiring length: 30 m or shorter
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
1) Power lead
Servo amplifier
Power supply
L1 U
L2 V M
L3 W
Table 11.1 shows examples for using the 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV
wire).
Note 1. The wire size shows applicable size of the servo amplifier connector. For wires
connecting to the servo motor, refer to "HF-KN/HF-SN Servo Motor Instruction
Manual".
2
2. Be sure to use the size of 2 mm when corresponding to UL/CSA standard.
11 - 16
11. OPTIONS AND PERIPHERAL EQUIPMENT
Always use one molded-case circuit breaker and one magnetic contactor with one servo amplifier. When
using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in this
section.
Molded-case circuit breaker (Note 1) Fuse Magnetic
Servo amplifier Voltage Current Voltage contactor
Frame, rated current Class (Note 2)
AC [V] [A] AC [V]
MR-JE-10A
30 A frame 5 A 10
MR-JE-20A
S-N10
MR-JE-40A 30 A frame 10 A 15
S-T10
MR-JE-70A
30 A frame 15 A 20
MR-JE-100A 240 T 300
S-N20 (Note 3)
MR-JE-200A 30 A frame 20 A 40
S-T21
S-N20
MR-JE-300A 30 A frame 30 A 70
S-T21
Note 1. When having the servo amplifier comply with the UL/CSA standard, refer to appendix 2.
2. Use a magnetic contactor with an operation delay time (interval between current being applied to
the coil until closure of contacts) of 80 ms or less.
3. S-N18 can be used when auxiliary contact is not required.
The following shows the advantages of using power factor improving AC reactor.
It improves the power factor by increasing the form factor of the servo amplifier's input current.
It decreases the power supply capacity.
The input power factor is improved to about 80%.
When using power factor improving reactors for two servo amplifiers or more, be sure to connect a power
factor improving reactor to each servo amplifier. If using only one power factor improving reactor, enough
improvement effect of phase factor cannot be obtained unless all servo amplifiers are operated.
Servo amplifier
1-phase 200 V class
FR-HAL
MCCB MC R X
(Note) L1
1-phase
200 V AC to S Y
L2
240 V AC T Z
L3
Note. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave
L2 open.
11 - 17
11. OPTIONS AND PERIPHERAL EQUIPMENT
(2) Dimensions
Terminal layout
R X S Y T Z
4-d mounting hole
(Varnish is removed from front right mounting
hole (face and back side).) (Note 1)
D or less
H
W1 D2
Max. W (Note 2) D1
Fig. 11.1
11 - 18
11. OPTIONS AND PERIPHERAL EQUIPMENT
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and those
radiated by the servo amplifier to cause peripheral equipment to malfunction. Since the servo amplifier is an
electronic device which handles small signals, the following general noise reduction techniques are required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral equipment malfunction due to noises produced by the servo amplifier, noise suppression
measures must be taken. The measures will vary slightly with the routes of noise transmission.
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many
relays which make a large amount of noise) near the servo amplifier and the servo amplifier may
malfunction, the following countermeasures are required.
Provide surge absorbers on the noise sources to suppress noises.
Attach data line filters to the signal cables.
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp
fittings.
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and other
equipment against large exogenous noise and lightning surge, attaching a varistor to the power
input section of the equipment is recommended.
(c) Techniques for noises radiated by the servo amplifier that cause peripheral equipment to malfunction
Noises produced by the servo amplifier are classified into those radiated from the cables connected
to the servo amplifier and its main circuits (input and output circuits), those induced
electromagnetically or statically by the signal cables of the peripheral equipment located near the
main circuit cables, and those transmitted through the power supply cables.
Noises produced
by servo amplifier Noises transmitted in the air Noise radiated directly from servo amplifier Route 1)
11 - 19
11. OPTIONS AND PERIPHERAL EQUIPMENT
5)
7) 7)
2)
7)
Sensor
power
1) supply
Servo
2)
amplifier
Instrument Receiver
3)
8)
6)
4) Sensor
3)
Servo motor M
Noise transmission
Suppression techniques
route
When measuring instruments, receivers, sensors, etc. which handle weak signals and may
malfunction due to noise and/or their signal cables are contained in a cabinet together with the servo
amplifier or run near the servo amplifier, such devices may malfunction due to noises transmitted
through the air. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
1) 2) 3) 2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
3. Avoid wiring the power lines (input/output lines of the servo amplifier) and signal lines side by side
or bundling them together.
4. Insert a line noise filter to the I/O cables or a radio noise filter on the input line.
5. Use shielded wires for the signal and power lines, or put the lines in separate metal conduits.
When the power lines and the signal lines are laid side by side or bundled together, magnetic
induction noise and static induction noise will be transmitted through the signal cables and
malfunction may occur. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
4) 5) 6) 2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
3. Avoid wiring the power lines (input/output lines of the servo amplifier) and signal lines side by side
or bundling them together.
4. Use shielded wires for the signal and power lines, or put the lines in separate metal conduits.
When the power supply of peripheral equipment is connected to the power supply of the servo
amplifier system, noises produced by the servo amplifier may be transmitted back through the power
7) supply cable and the devices may malfunction. The following techniques are required.
1. Install the radio noise filter (FR-BIF) on the power lines (Input lines) of the servo amplifier.
2. Install the line noise filter (FR-BSF01) on the power lines of the servo amplifier.
When the cables of peripheral equipment are connected to the servo amplifier to make a closed loop
8) circuit, leakage current may flow to malfunction the peripheral equipment. If so, malfunction may be
prevented by disconnecting the grounding cable of the peripheral device.
11 - 20
11. OPTIONS AND PERIPHERAL EQUIPMENT
φ13 ± 1
TDK
φ30 ± 1
Product name Lot number
Outline drawing (ZCAT3035-1330)
MC
SK
Relay
Surge killer
Surge killer
Maximum current: not less than two times the drive current of the relay or
the like Diode
11 - 21
11. OPTIONS AND PERIPHERAL EQUIPMENT
cable
40
External conductor
Clamp section diagram
Dimensions
30
L or less 10
B ± 0.3
C
A
6
24 -0.2
0
35
3
24+ 00.3
7
(Note) M4 screw 6 22
35
11
Note. Screw hole for grounding. Connect it to the grounding plate of the cabinet.
11 - 22
11. OPTIONS AND PERIPHERAL EQUIPMENT
Approx. 22.5
as the number of passes increases, but generally four passes
would be appropriate. For the servo motor power lines, passes
must be four times or less. Do not pass the grounding wire
11.25 ± 0.5
through the filter. or the effect of the filter will drop. Approx. 65
Wind the wires by passing through the filter to satisfy the required
φ33
number of passes as shown in Example 1. If the wires are too
thick to wind, use two or more filters to have the required number
of passes as shown in Example 2.
Approx. 65
Place the line noise filters as close to the servo amplifier as
possible for their best performance.
4.5
Example 1
MCCB MC Servo amplifier
Power L1
supply
L2
Line noise L3
filter
(Number of passes: 4)
Example 2
MCCB MC
Power Servo amplifier
supply
L1
Line noise L2
filter L3
11 - 23
11. OPTIONS AND PERIPHERAL EQUIPMENT
Approx. 300
insulate the lead wires that are not used for wiring.
Terminal
block Servo amplifier
MCCB MC
L1 29
Power
supply L2 φ5
42
hole
L3
4
58 29 7
44
Radio noise
filter
[Unit: mm]
(Note)
D T D H T E φd W
Model L
Max. Max. Max. ±1.0 ±0.05 ±1.0
min.
TND20V-431K 6.4 3.3
H
Note. For special purpose items for lead length (L), contact the manufacturer.
W E
L
11 - 24
11. OPTIONS AND PERIPHERAL EQUIPMENT
Rated sensitivity current ≥ 10 • {Ig1 + Ign + Iga + K • (Ig2 + Igm)} [mA]············································· (11.1)
Ig1: Leakage current on the electric channel from the earth-leakage current breaker to the input
terminals of the servo amplifier (Found from Fig. 11.2.)
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo
motor (found from Fig. 11.2.)
Ign: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF)
Iga: Leakage current of the servo amplifier (Found from table 11.3.)
Igm: Leakage current of the servo motor (Found from table 11.2.)
120
Leakage current [mA]
100
80
60
40
20
0
2 5.5 14 38100
3.5 8 22 60 150
30 80
Cable size [mm2]
Fig. 11.2 Example of leakage current per km (lg1, lg2) for CV cable run in metal conduit
11 - 25
11. OPTIONS AND PERIPHERAL EQUIPMENT
NV
Servo amplifier
M Servo motor
MR-JE-40A HF-KN43
5
Ig1 = 20 • = 0.1 [mA]
1000
5
Ig2 = 20 • = 0.1 [mA]
1000
According to the result of calculation, use an earth-leakage current breaker having the rated sensitivity
current (Ig) of 4.0 mA or more.
An earth-leakage current breaker having Ig of 15 mA is used with the NV-SP/SW/CP/CW/HW series.
11 - 26
11. OPTIONS AND PERIPHERAL EQUIPMENT
It is recommended that one of the following filters be used to comply with EN EMC directive. Some EMC
filters have large in leakage current.
Note. A surge protector is separately required to use any of these EMC filters.
MCCB MC
1 4 L1
(Note 1)
Power supply 2 5 L2
3 6 L3
E
(Note 2)
1 2 3 Surge protector
(RSPD-250-U4)
(OKAYA Electric Industries Co., Ltd.)
Note 1. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3.
Leave L2 open.
2. The example is when a surge protector is connected.
11 - 27
11. OPTIONS AND PERIPHERAL EQUIPMENT
(3) Dimensions
(a) EMC filter
HF3010A-UN
[Unit: mm]
3-M4 4-5.5 × 7 3-M4 M4
32 ± 2
110 ± 4
85 ± 2
IN
Approx. 41
258 ± 4
65 ± 4
273 ± 2
288 ± 4
300 ± 5
HF3030A-UN
[Unit: mm]
6-R3.25 length:8
3-M5 3-M5
125 ± 2
140 ± 1
155 ± 2
M4
44 ± 1
70 ± 2
85 ± 1 85 ± 1
210 ± 2 140 ± 2
260 ± 5
11 - 28
11. OPTIONS AND PERIPHERAL EQUIPMENT
5.5 ± 1
11 ± 1
φ4.2 ± 0.5
28.5 ± 1
Resin
Lead
200 +30
0
1 2 3
4.5 ± 0.5
28 ± 1
Case
41 ± 1
11 - 29
11. OPTIONS AND PERIPHERAL EQUIPMENT
MEMO
11 - 30
APPENDIX
This section explains safety of users and machine operators. Please read the section carefully before
mounting the equipment.
Always use the MR-JE servo amplifiers within specifications (voltage, temperature, etc. Refer to section 1.3
for details.). Mitsubishi Electric Co. accepts no claims for liability if the equipment is used in any other way or
if modifications are made to the device, even in the context of mounting and installation.
It takes 15 minutes for capacitor discharging. Do not touch the unit and terminals
WARNING immediately after power off.
App. - 1
APPENDIX
Note 1. Select wire sizes depending on the rated output of the servo motors. The values in the table are sizes based on rated output of
the servo amplifiers.
2. The following shows the PE terminal specifications of the servo amplifier.
Screw size: M4
Tightening torque: 1.2 [N•m]
Recommended crimp terminals: R2-4 (JST)
Crimping tool: YPT-60-21 (JST)
(d) Grounding
To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the
servo amplifier to the protective earth (PE) of the cabinet. Do not connect two grounding cables to
the same protective earth (PE) terminal. Always connect cables to the terminals one-to-one.
If using an earth-leakage current breaker, always ground the protective earth (PE) terminal of the
servo amplifier to prevent an electric shock. Only an RCD (earth-leakage current breaker) of type B
can be used for the power supply side of the product.
PE terminals
PE terminals
App. - 2
APPENDIX
(2) EU compliance
The MR-JE servo amplifiers are designed to comply with the following directions to meet requirements
for mounting, using, and periodic technical inspections: EMC directive (2004/108/EC) and Low-voltage
directive (2006/95/EC).
(a) Installation
The minimum cabinet size is 150% of MR-JE servo amplifier's volume. Also, design the cabinet so
that the ambient temperature in the cabinet is 55 °C or less. The servo amplifier must be installed in
the metal cabinet. For environment, the units should be used in open type (UL 50) and overvoltage
category III or lower. The servo amplifier needs to be installed at or below of pollution degree 2. For
connection, use copper wires.
App. - 3
APPENDIX
App. 2.1.4 General cautions for safety protection and protective measures
Observe the following items to ensure proper use of the MELSERVO MR-JE servo amplifiers.
(1) Only qualified personnel and professional engineers should perform system installation.
(2) When mounting, installing, and using the MELSERVO MR-JE servo amplifier, always observe standards
and directives applicable in the country.
Disposal of unusable or irreparable devices should always occur in accordance with the applicable country-
specific waste disposal regulations. (Example: European Waste 16 02 14)
The devices must be installed in the specified direction. Not doing so may cause
a malfunction.
CAUTION Mount the servo amplifier on a cabinet which meets IP54 in the correct vertical
direction to maintain pollution degree 2.
40 mm
or more 80 mm or longer
for wiring
Servo amplifier
10 mm 10 mm Servo amplifier
or more or more
40 mm
or more
Bottom
App. - 4
APPENDIX
Turn off the molded-case circuit breaker (MCCB) to avoid electrical shocks or
WARNING damages to the product before starting the installation or wiring.
The following shows representative configuration examples to conform to the IEC/EN/UL/CSA standards.
Servo amplifier
(3-phase MCCB MC
230 V AC) L1 L2 L3
or fuse
Power
supply CN1
(3-phase Controller
400 V AC) CN2 Encoder cable
PE
Transformer
(star-connected) U/V/W/PE
Cabinet side
Machine side
Servo motor
Encoder
Servo amplifier
(3-phase MCCB MC
230 V AC) L1 L2 L3
or fuse
Power
supply
(3-phase CN1
400 V AC) Controller
CN2 Encoder cable
PE
Transformer
(star-connected) U/V/W/PE
Cabinet side
Machine side
Servo motor
Encoder
The control circuit connectors described by rectangles are safely separated from the main circuits described
by circles.
The connected motors will be limited as follows.
App. - 5
APPENDIX
The following shows CN1 connector signals as a typical example. Refer to section 3.4 for other connectors.
CN1
1 26
2 27 MO1
3 TLA 28
4 LG 29 LG
LA 5 MO2 30
6 LAR 31 LG
LB 7 32
8 LBR 33
LZ 9 OP 34
10 LZR 35 LG
PP 11 NP 36
12 PG 37 NG
OPC 13 38
14 39
15 40
16 SON 41
17 CR 42
18 43 EM2
19 LSP 44
20 RES 45 LSN
DICOM
21 46
22 DICOM 47 DOCOM
DOCOM
23 48
24 ZSP 49 ALM
INP 25 RD 50
The following shows typical I/O devices. Refer to section 3.5 for other devices.
Input device
Symbol Device Connector Pin No.
SON Servo-on 15
RES Reset 19
CR Clear 41
CN1
EM2 Forced stop 2 42
LSP Forward rotation stroke end 43
LSN Reverse rotation stroke end 44
App. - 6
APPENDIX
Output device
Symbol Device Connector Pin No.
ZSP Zero speed detection 23
INP In-position 24
CN1
ALM Malfunction 48
RD Ready 49
Power supply
Symbol Device Connector Pin No.
DICOM Digital I/F power supply input 20, 21
DOCOM Digital I/F common CN1 46, 47
SD Shield Plate
Do not perform insulation resistance test on the servo amplifier. Otherwise, it may
CAUTION cause a malfunction.
Do not disassemble and/or repair the equipment on customer side.
(1) Check for loose protective earth (PE) terminal screws of the servo amplifier. Retighten any loose screws.
(Tightening torque: 1.2 N•m)
(2) Check servo motor bearings, brake section, etc. for unusual noise.
(3) Check the cables and the like for scratches or cracks. Perform periodic inspection according to
operating conditions.
(4) Check that the connectors are securely connected to the servo motor.
(5) Check that the wires are not coming out from the connector.
(7) Check for unusual noise generated from the servo amplifier.
(8) Check the servo motor shaft and coupling for connection.
App. - 7
APPENDIX
Service lives of the following parts are listed below. However, the service life vary depending or operating
methods and environment. If any fault is found in the parts, they must be replaced immediately regardless of
their service lives. For parts replacement, please contact your local sales office.
Part name Life guideline
Smoothing capacitor (Note) 10 years
Number of power-on times and forced stop times:
Relay
100,000 in total
Cooling fan 50,000 hours to 70,000 hours (7 years to 8 years)
Note. The characteristic of smoothing capacitor is deteriorated due to ripple currents, etc. The life of the capacitor greatly depends on
ambient temperature and operating conditions.
The capacitor will reach the end of its life in 10 years of continuous operation in normal air-conditioned environment (40 ˚C
surrounding air temperature or less).
When you keep or use it, please fulfill the following environment.
Item Environment
Operation [°C] 0 to 55 Class 3K3 (IEC/EN 60721-3-3)
Ambient
Transportation (Note) [°C] -20 to 65 Class 2K4 (IEC/EN 60721-3-2)
temperature
Storage (Note) [°C] -20 to 65 Class 1K4 (IEC/EN 60721-3-1)
Ambient Operation, transportation,
5% to 90 %RH
humidity storage
10 Hz to 57 Hz with constant deviation of 0.075 mm
2
Test values 57 Hz to 150 Hz with constant acceleration of 9.8 m/s (1 g) to IEC/EN 61800-5-1
Vibration (Test Fc of IEC 60068-2-6)
2
load Operation 5.9 m/s (0.6 g)
Transportation (Note) Class 2M3 (IEC/EN 60721-3-2)
Storage Class 1M2 (IEC/EN 60721-3-2)
Pollution degree 2
IP20 (IEC/EN 60529)
IP rating
Open type (UL 50)
Operation, storage 1000 m or less above sea level
Altitude
Transportation 10000 m or less above sea level
App. - 8
APPENDIX
W D
c
a d
App. - 9
APPENDIX
POINT
A voltage of analog monitor output may be irregular at power-on.
(1) Setting
Change the following digits of [Pr. PC14] and [Pr. PC15].
[Pr. PC14]
0 0
Analog monitor 1 output selection
(the signal provided to the output across MO1 and LG)
[Pr. PC15]
0 0
Analog monitor 2 output selection
(the signal provided to the output across MO2 and LG)
[Pr. PC39] and [Pr. PC40] can be used to set the offset voltages to the analog output voltages. Setting
value is -9999 mV to 9999 mV.
Parameter Description Setting range [mV]
This is used to set the offset voltage of MO1
PC39
(Analog monitor 1).
-9999 to 9999
This is used to set the offset voltage of MO2
PC40
(Analog monitor 2).
App. - 10
APPENDIX
(2) Setting
The servo amplifier is factory-set to output the servo motor speed to MO1 (Analog monitor 1) and the
torque to MO2 (Analog monitor 2). The setting can be changed as listed below by setting the [Pr. PC14]
and [Pr. PC15] value.
Refer to (3) for the detection point.
Setting Setting
Output item Description Output item Description
value value
00 Servo motor speed 01 Torque Power running in
CCW direction CCW direction
8 [V] 8 [V]
0 0
Maximum speed Maximum torque
-8 [V] -8 [V]
CW direction Power running in
CW direction
06 Servo motor-side droop CCW direction 07 Servo motor-side droop CCW direction
10 [V] 10 [V]
pulses pulses
(Note 1, 2, 3) (Note 1, 2, 3)
(±10 V/100 pulses) 100 [pulse] (±10 V/1000 pulses) 1000 [pulse]
0 100 [pulse] 0 1000 [pulse]
08 Servo motor-side droop CCW direction 09 Servo motor-side droop CCW direction
10 [V] 10 [V]
pulses pulses
(Note 1, 2, 3) (Note 1, 2, 3)
(±10 V/10000 pulses) 10000 [pulse] (±10 V/100000 pulses) 100000 [pulse]
0 10000 [pulse] 0 100000 [pulse]
0
Maximum speed
0 400 [V]
-8 [V]
CW direction
-10 [V]
App. - 11
APPENDIX
Current
Speed encoder
Command + Position command + Speed + Current
pulse control control control PWM M Servo motor
- - -
Encoder inside
temperature
Current feedback
Encoder
Differen-
tiation
Position feedback
App. - 12
APPENDIX
MR-JE series servo amplifiers are certificated in compliance with Low-voltage directive. The following shows
a certificate by the Certification Body.
Supplementation: Refer to section 1.6 (2) for the models shown in "(see Appendix 1)".
App. - 13
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Data *Manual Number Revision
May. 2013 SH(NA)030128-A First edition
Jul. 2013 SH(NA)030128-B 4. Additional instructions Partially changed.
(3) Transportation and
installation
Section 1.3 Partially changed.
Section 1.6 Partially changed.
Chapter 2 CAUTION is partially changed.
Chapter 3 CAUTION is partially changed.
Section 3.2.1 Partially changed.
Section 3.4 Partially changed.
Section 3.5 Partially changed.
Section 3.6.1 Partially changed.
Section 3.9.1 Partially changed.
Section 3.9.2 Partially changed.
Section 3.9.3 Partially deleted.
Section 5.2.1 Partially added and partially changed in Pr. PA13.
Section 11.3 Partially changed.
Section 11.6 Partially changed.
App. 2 Partially changed.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which
may occur as a result of using the contents noted in this manual.
© 2013 MITSUBISHI ELECTRIC CORPORATION
Country/Region Sales office Tel/Fax
[Term]
The term of warranty for Product is twelve (12) months after your purchase or delivery of the Product to a place designated by you or
eighteen (18) months from the date of manufacture whichever comes first (“Warranty Period”). Warranty period for repaired Product
cannot exceed beyond the original warranty period before any repair work.
[Limitations]
(1) You are requested to conduct an initial failure diagnosis by yourself, as a general rule.
It can also be carried out by us or our service company upon your request and the actual cost will be charged. However, it will not
be charged if we are responsible for the cause of the failure.
(2) This limited warranty applies only when the condition, method, environment, etc. of use are in compliance with the terms and
conditions and instructions that are set forth in the instruction manual and user manual for the Product and the caution label
affixed to the Product.
(3) Even during the term of warranty, the repair cost will be charged on you in the following cases;
(i) a failure caused by your improper storing or handling, carelessness or negligence, etc., and a failure caused by your
hardware or software problem
(ii) a failure caused by any alteration, etc. to the Product made on your side without our approval
(iii) a failure which may be regarded as avoidable, if your equipment in which the Product is incorporated is equipped with a
safety device required by applicable laws and has any function or structure considered to be indispensable according to a
common sense in the industry
(iv) a failure which may be regarded as avoidable if consumable parts designated in the instruction manual, etc. are duly
maintained and replaced
(v) any replacement of consumable parts (battery, fan, smoothing capacitor, etc.)
(vi) a failure caused by external factors such as inevitable accidents, including without limitation fire and abnormal fluctuation of
voltage, and acts of God, including without limitation earthquake, lightning and natural disasters
(vii) a failure generated by an unforeseeable cause with a scientific technology that was not available at the time of the shipment
of the Product from our company
(viii) any other failures which we are not responsible for or which you acknowledge we are not responsible for
4. Exclusion of responsibility for compensation against loss of opportunity, secondary loss, etc.
Whether under or after the term of warranty, we assume no responsibility for any damages arisen from causes for which we are not
responsible, any losses of opportunity and/or profit incurred by you due to a failure of the Product, any damages, secondary
damages or compensation for accidents arisen under a specific circumstance that are foreseen or unforeseen by our company,
any damages to products other than the Product, and also compensation for any replacement work, readjustment, start-up test run
of local machines and the Product and any other operations conducted by you.
SH(NA)030128-B
General-Purpose AC Servo
MR-JE-_A
SERVO AMPLIFIER
MR-JE-A SERVOAMPLIFIER
MODEL INSTRUCTIONMANUAL
MODEL
CODE 1CW706
B
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310