0% found this document useful (0 votes)
10 views8 pages

T002 - Post-Lay Test by Otdr

The document is a request for inspection related to the installation of optical fiber cables for Saudi Aramco's project involving three gas PDMs. It includes details on inspection requirements, testing parameters, and results for optical fiber cable acceptance tests conducted at different wavelengths. The document also contains signatures from relevant personnel and outlines the compliance with project specifications.

Uploaded by

afareenkhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views8 pages

T002 - Post-Lay Test by Otdr

The document is a request for inspection related to the installation of optical fiber cables for Saudi Aramco's project involving three gas PDMs. It includes details on inspection requirements, testing parameters, and results for optical fiber cable acceptance tests conducted at different wavelengths. The document also contains signatures from relevant personnel and outlines the compliance with project specifications.

Uploaded by

afareenkhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

REQUEST FOR INSPECTION - at>"'

Saudi Aramco 6717-ENG (I 1/98) 726-200 (I nspection Department) Ref: SAEP I I 50 & I023 RFINo. 7CP-3GAs-ff~f>l/-iDi 3-k~
Bf 0 1263/020 16 JO Phase Title Tl IREE GAS PDMs IN HSBI I & ARB! FIELD

To: Projects Inspection Un it/ Mr. _ Raz


_-_a_A_h_m_e_d _ D C ivil D Mech. D Plumb.Ill Comms. D Elect. D Other _ _ _ _ _ __

Inspection/monitoring is required on (date) 3 '~fYI pc;oc to 11t'~i1) {;j1aYT1mJi'6YiJ


for the fo llowing location/equipment

Work Permit required: IZJ Yes D No T .


Proj ect Q ua l"1ty Pl an: IZJ Hold Po int D Witness Point

SAPMT representative has verified that the work is ready for CONTRACTOR has verified that the work to be inspected is
inspection and conforms to the project requirements. complete and in compliance with the following specifications:

SAPMTName ~'o ~ SA ES/ SAMS/Other # Q23-QM-ITP-6 I 26


Signature _ ~'~(,IL Date ___--"'
i +\2? \ Q,\
'-'-+- _,___ _ Contractor/Company Subsca7
Telephone z:;::_ Fax _ _ _ _ _ __ QA/QC Name Afarccn khan
QA/QC Signature Date

T ime - - - - -- -

NOTE: lnspector's signature is for receivi ng thi s request only and not for approval or
Distribution: A. O riginal - Project Management B. I st Copy - Inspection C. 2nd Copy - Contractor

Copyright© Saudi Aramco 2009. All rights reserved.


Document Responsibility: Communications Standards Committee SAES-T-634
Issue Date: 2 May 2012
Next Planned Update: 21 February 2016 Telecommunications - Cable Testing and Acceptance
7CP-3GAS-HSBH- 9r; /! 3 -T- (JO"
r - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- -- - - - -- - - - - - - - - - - - - - - - - - - - - - - - - -- 1
I Exhibit 3-0ptical Fiber Cable Acceptance Test Record
OPTICAL FIBER CABLE ACCEPTANCE TEST RECORDS
Area Location: L~ If.SB H go 3 Bl/ER#: 10-01253102016
Page
Date:
2/-M(fflh -;.o),J I
I
(A)
Check One Box: o A.End-to End Fiber Test o B.Splice Loss Data
SPA N NUMBER ' CABLE NUMBER CABLE COUNT
(BJ (C) 24F (D)

FIBER TYPE: WAVELENGTH(nm) MAX.ALLOWABLE LOSS:( db)


¢'.single Mode 1550 0.3dBLkm
(E) (F) (G) I
o B.Multimode WAVELENGTH( nm) MAX.ALLOWABLE LOSS:( db) I
1625 0.4dBLkm
--
A
OFFICE A If!> 811 a~~ OPERATOR'S NAME OFFICE B
_/l..S.f:Jf •Ti" ' (I)
OPERATOR'S NAME

- (H)
-- I
SPLICE LOCATION TYPE TEST SET USED

I
Te& t
B
TYPEOF TESTEQPT. tE~ TEST SET LOCATION TEST SET OPERATOR'S NAME:
OTDR ~DS John D.Gmoes
I
v I
I
COLOR COLOR I
FIBER Attenuation( dB/km) FIBER Attenuation( dB/km) I
(J) (J)
NO. NO.
BUFFER FIBER 1550nm 1625 nm BUFFER FIBER lSSOnm 1625nm
1 Blue o · /&:i.. 0·11s 13 Blue
"· IH ~ 0·11r
2 Oran ge () · 16 lt ()• f~3 14 Orange o· /G:-3 0 • /'1{,
3 Green
" · /S4 o· ft7 15 Gr een 0 . ,~, D·f'j/
4 Brown
o · I !cf:> ,. ,, :J.. 16 Br own o · tfs:l. o· /ttf(
I
5 Gre y O· !.P.3 b·f'th 17 Gr ey o· /f'!> o ·/"fl-.
6 Wh ite t> . IJI~ ~ ·1ttr 18 Whi t e 6 • /$}D () •l°ttJ
7 Red t>• flfV () •/44 19 Red o·J~o I!> · !'I (
8 Black D· /Blt ()1>/9.\ 20 Blac k o • /$1;1 0·1'11
9

10

11
Yellow

V iolet

Pink
"·ltl3
b · ~;2.

b· /BI
t> · t'fL
~. JC/4
() •I'll
I
21

22

23
Yellow

V iolet

Pink
". 17tf
o • /8~
" •19'3
" · , fJ.ct
() .

O•
(~

l'lR-
,
12 Aqua
~
~· rgi., I
() · 19 3 24 A qua
"·/!I " ' /'11 1
Remarks:
~ /J '
..-r- I ~ __./
/

Construction QC Inspector QC Supervisor PID Representative PMT Representative


Representative
Name
Sign

Date
[~ES Co I
Project THREE GAS PDMs Cabl e Number : HSBH 80-83 , HSBH TP-2
Contract No : Bl-10-01263-02016 Cable Length : 4.824 KM
Cable Manufacturer : NEXAN Cable Type 24 Fiber SM G.6520
Year Manufactured : Maximum Total loss 0.40 db/km
Test Date : 04-March-2021 Test Equipment : EXFO FTB-1
Test Wavelength : 1625nm

POST-LAY TEST BY OTDR


Tota l. Loss Total. Loss Total. Loss Total. Loss
Fibre No. Color I 1625nm Fibre No. Color 1625nm Fibre No. Color 1625nm Fibre No. Color 1625nm
(dB/ Km) (dB I Km) (dB/ Km) (dB I Km)

BLUE 0.195 13 BLUE 0.195

ORANGE 0.193 14 ORANGE 0.196

3 GREEN 0.197 15 GREEN 0.191

4 BROWN 0.192 16 BROWN 0.198

5 SLATE 0.196 17 SLATE 0.196

6 WHITE 0.195 18 WHITE 0.194

7 RED 0.194 19 RED 0.195

8 BLACK 0. 195 20 BLACK 0.197

9 YE LLOW 0.196 21 YELLOW 0.189

10 VIO LET 0.194 22 VIOLET 0.191

11 PINK 0.191 23 PINK 0.198

12 AQUA 0.193 24 AQUA 0.199

Maximum allowable attenuation per KM at 162Snm (Max. Attn.) = 0.40dB/km

Tested By: John Dale Gomez Witnessed by: AF;,(Ml ~


Slgnot"'e<is£ S Signature :
~ ~-

Route: HSBH 80-83 To HSBH TP-2 (A TO B) Test by OTDR at 1625nm


I PESCO I

Project : THREE GAS PDMs Cable Number : HSBH 80-83 , HSBH TP-2
Contract No : Bl-10-01263-02016 Cable Length : 4.824 KM
Cable Manufacturer : NEXAN Cable Type : 24 Fiber SM G.6520
Year Manufactured : Maximum Total loss : 0.30db/km
Test Date : 04-March-2021 Te st Equipment : EXFO FTB-1
Test Wavelength : 1550nm

POST-LAY TEST BY OTDR


Total. Loss Total. Loss Total . Loss Total. Loss
Fibre No. Color 1550nm Fibre No. Color 1550nm Fibre No. Color 1550nm Fibre No. Color 1550nm
(dB/ Km) (dB/ Km) (dB/ Km) (dB/Km)
1 BLUE 0.182 13 BLUE 0.182
2 ORANGE 0.184 14 ORANGE 0.183
3 GREEN 0.184 15 GREEN 0.181
4 BROWN 0.180 16 BROWN 0.182
s SLATE 0.183 17 SLATE 0.183
6 WHITE 0.182 18 WHITE 0.180
7 REO 0.180 19 RED 0.180
8 BLACK 0.184 20 BLACK 0.181
9 YELLOW 0.183 21 YELLOW 0.178
10 VIOLET 0.182 22 VIOLET 0.182
11 PINK 0.181 23 PINK 0.183
12 AQUA 0.184 24 AQUA 0.181

Maximum allowable attenuation per KM at 1550nm (Max. Attn.)= 0.30 dB/km

A~ rf"~ ~
Tested By: John Dale Gomez Witnessed by:

s;goatu<e' ~ Signature:
v~ti
\.. \ ~
- J \'
Route: HSBH 80-83 To HSBH TP-2 (A TO B) Test by OTDR at lSSOnm
OTDR Report
General Information
Filename: Fiber1 .trc
Test date: 3/4/2021 Customer: ARAMCO
Test time: 3:03:14 PM Company: SUBSEA 7
Cable ID: HSBH 80-83,TP-2 Fiber ID: Fiber1
Job ID: B1-10-01263-02016
Comments: POST LAY TEST

Locations
Location A Location B
Location HSBH TP-2 HSBH TP-2
Operator JOHN DALE GOMEZ
Model FTB-730-2348-EA
Serial number 785227
Calibration date 3/6/2015 (UTC)

Results
Span length: 4.8248 km Average loss: 0.195 dB/km Injection level: 17.5 dB
Span loss: 0.941 dB Average splice loss:
Span ORL: <25.57 dB Maximum splice loss:

Graph

1625 (9 J.Jm)
35

3()

25

co
-0

10

•:l+----~----~---~---~----~-_.Ulllll.I.
{) 4

Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 0.0000 -75.6 0.000
Section 4.8248 0.941 0 .195 0.941
Reflective 2 4.8248 >-24.0 0.941

Test Parameters
A -. B
Wavelength (nm) 1625 (9 µm)
Range (km) 10.0000
Pulse (ns) 30
Duration (s) 10

EXFO Signature: - - - - - - - - - - - - - - Date: 3/4/2021 Page 1of 4


OTDR Report
Test Settings
A-+ B
IOR 1.468734
Backscatter (dB) -82.59
Helix factor(%) 0.00
Splice loss detection threshold (dB) 0.100
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

EXFO Signature: - - - -- - - -- - - - -- Date: 3/4/2021 Page 2 of 4


OTDR Report
General Information
Filename: Fiber1 .trc
Test date: 3/4/2021 Customer: ARAMCO
Test time: 3:03:26 PM Company: SUBSEA 7
Cable ID: HSBH 80-83,TP-2 Fiber ID: Fiber1
Job ID: Bl- 10-01263-02016
Comments: POST LAY TEST

Locations
Location A Location B
Location HSBH TP-2 HSBH TP-2
Operator JOHN DALE GOMEZ
Model FTB-730-234B-EA
Serial number 785227
Calibration date 3/6/2015 (UTC)

Res ults
Span length: 4.8236 km Average loss: 0.182 dB/km Injection level: 18.4 dB
Span loss: 0.877 dB Average splice loss:
Span ORL: 27.75 dB Maximum splice loss:

Graph

1550 (9 J.Jm)
35

lO

2.5

10

Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 0.0000 -74.4 0.000
Section 4.8236 0.877 0.182 0.877
Reflective 2 4 .8236 -26.5 0.877

Test Parameters
A -+ B
Wavelength (nm) 1550 (9 µm)
Range (km) 10.0000
Pulse (ns) 30
Duration (s) 10

EXFO S ignature: - - - - - - - - - - - - - - Date: 3/4/2021 Page 3 of 4


OTDR Report
Test Settings
A -+ B
IOR 1.468325
Backscatter (dB) -81.87
Helix factor(%) 0.00
Splice loss detection threshold (dB) 0. 100
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

EXFO Signature: - - - - - - - - - - - - -- Date: 3/4/2021 Page 4 of 4