NHX Series 48v Inverter User Manual-Nfi
NHX Series 48v Inverter User Manual-Nfi
2. Safety 2
2.1. Important Safety Instructions 2
3. Introduction 7
3.1. Basic features 7
3.2. System Diagram 7
3.4. Dimension 12
3.5. Terminals of PV inverter 13
4. Technical Parameters 15
4.1. Inverter specification 15
5. Installation 17
5.1. Check for Physical Damage 17
5.3. Mounting 17
6. Electrical Connection 21
6.1. PV connection 21
9. LCD Operation 41
9.1. Control Panel 41
9.4. Setting 44
“Note” provides tips that are valuable for the optimal operation of our
inverter.
2. Safety
2.1. Important Safety Instructions
Danger!
(5) Children should be supervised to ensure that they do not play with the
appliance.
Caution!
(7) During operation, the upper lid of the enclosure and the enclosure body
may become hot.
Caution!
(10)Do not stay closer than 20 cm to inverter for any length of time.
Note!
(12)Comply with the local requirements for grounding the PV modules and the
PV generator. It is recommends connecting the generator frame and other
electrically conductive surfaces in a manner which ensures continuous
conduction and ground these in order to have optimal protection of system
and persons.
Warning
Warning
Warning
● Please keep the user manual properly. When operating equipment, in addition to
following the general precautions in this document, follow the specific safety
instructions. We will not be liable for any consequence caused by the violation of the
safety operation regulations and design, production, and usage standards.
● Accessories only together with the inverter shipment are recommended here.
Otherwise may result in a risk of fire, electric shock, or injury to person.
● Make sure that existing wiring is in good condition and that wire is not undersized.
Do not disassemble any parts of inverter which are not mentioned in installation
guide. It contains no user-serviceable parts. See Warranty for instructions on
obtaining service. Attempting to service the inverter yourself may result in a risk of
electric shock or fire and will void your warranty.
● Keep away from flammable, explosive materials to avoid fire disaster.
● The installation place should be away from humid or corrosive substance.
● Authorized service personnel must use insulated tools when installing or working with
this equipment.
● Never touch either the positive or negative pole of PV connecting device. Strictly
prohibit touching both of them at the same time.
● The unit contains capacitors that remain charged to a potentially lethal voltage after
the MAINS, battery and PV supply has been disconnected.
● Hazardous voltage will present for up to 5 minutes after disconnection from power
supply.
● CAUTION-RISK of electric shock from energy stored in capacitor. Never operate on
the inverter couplers, the MAINS cables, Battery cables, PV cables or the PV generator
when power is applied. After switching off the PV, battery and Mains, always wait for
5 minutes to let the intermediate circuit capacitors discharge before unplugging DC,
battery in plug and MAINS couplers.
● When accessing the internal circuit of inverter, it is very important to wait 5 minutes
before operating the power circuit or demounting the electrolyte capacitors inside the
device. Do not open the device before hand since the capacitors require time
sufficiently discharge!
● Surge protection devices (SPDs) for PV installation.
Warning
(18)The grid connected inverter is not fitted with SPDs in both PV input
side and MAINS side.
● Lightning will cause a damage either from a direct strike or from surges due to a
nearby strike.
● Induced surges are the most likely cause of lightning damage in majority or
installations, especially in rural areas where electricity is usually provided by long
overhead lines. Surge may be included on both the PV array conduction and the AC
cables leading to the building.
● Specialists in lightning protection should be consulted during the end use application.
Using appropriate external lightning protection, the effect of a direct lightning strike
into a building can be mitigated in a controlled way, and the lightning current can be
discharged into the ground.
● Installation of SPDs to protect the inverter against mechanical damage and excessive
stress include a surge arrester in case of a building with external lightning protection
system (LPS) when separation distance is kept.
● To protect the DC system, surge suppression device (SPD type2) should be fitted at
the inverter end of the DC cabling and at the array located between the inverter and
the PV generator, if the voltage protection level (VP) of the surge arresters is greater
than 1100V, an additional SPD type 3 required for surge protection for electrical
devices.
● To protect the AC system, surge suppression devices (SPD type2) should be fitted at
the main incoming point of AC supply (at the consumers cutout), located between the
inverter and the meter/distribution system;
● All DC cables should be installed to provide as short a run as possible, and positive
and negative cables of the string or main DC supply should be bundled together.
Avoiding the creation of loops in the system.
● Spark gap devices are not suitable to be used in DC circuits once conducting, they
won’t stop conducting until the voltage across their terminals is typically more than
30 volts.
⮚ Anti-Islanding Effect
Islanding effect is a special phenomenon that grid-connected PV system still supply
power to the nearby grid when the voltage loss is happened in the power system. It is
dangerous for maintenance personnel and the public.
Hybrid series inverter provide Active Frequency Drift(AFD) to prevent islanding effect.
Warning
Incorrect grounding can cause physical injury, death or equipment malfunction and
increase electromagnetic.
This symbol indicates that you should wait at least 5 mins after disconnecting the
inverter from the utility grid and from the PV panel before touching any inner live
parts.
Keep dry! The package/product must be protected from excessive humidity and
Fragile - The package/product should be handled carefully and never be tipped over
or slung.
Caution! Failure to observe a warning indicated in this manual may result in injury!
3. Introduction
3.1. Basic features
Hybrid Series is a high-quality inverter which can convert solar energy to AC energy
and store energy into battery.
The inverter can be used to optimize self-consumption, store in the battery for future
use or feed in to public grid. Work mode depends on PV energy and user’s preference. It
can provide power for emergency use during the grid lost by using the energy from
battery and inverter (generated from PV).
Note!
(21)Please control the home loads, and make sure it’s within the “BACK-UP
output rating” under BACK-UP mode, otherwise the inverter will shut down
with an “overload fault” warning.
(22)Please confirm with the mains grid operator whether there is any special
regulations for grid connection.
11
All switches and RCD devices in the figure are for reference only, and the specific
installation shall be subject to local regulations.
Note!
(23)Please control the home loads, and make sure it’s within the “BACK-UP
output rating” under BACK-UP mode, otherwise the inverter will shut down
with an “overload fault” warning.
(24)Please confirm with the mains grid operator whether there is any special
regulations for grid connection.
12
Note!
(26)If the CT connector is improperly connected, the inverter cannot read the
data correctly, so that the relevant working conditions cannot be realized
normally.
13
3.3. Work Modes
Inverter provides multiple work modes based on different requirements.
14
In addition to the above three basic modes, there is also an “Advanced Mode”.
Please refer to Chapter 13 for details.
3.4. Dimension
15
3.5. Terminals of PV inverter
Object Description
A DC switch
B BAT input
C WiFi
D CAN1/CAN2/RS485/BMS485,BMSCAN/CTL1/CTL2/Type-c upgrade
E PV1~PV4 input
F Generator
G Grid
H BACK-UP1 output
I PE
J BACK-UP2 output
K LCD
L RSD button
Warning!
16
* Port Function
CAN1/CAN2: Communication interface for connecting inverters.
RS485: Read the internal data of inverter.
BMS-485/ BMS-CAN: BMS communication for lithium batteries.
CT L1/CT L2: For external grid side CT to detect current size.
TYPE-C UPDATE: Update machine software locally on PC via USB-A port.
17
4. Technical Parameters
4.1. Inverter specification
PV Input Data
NO.MPPT Tracker 4
AC Output Data(On-Grid)
Output Voltage Range 110-120/220-240V split phase, 208V(2/3 phase), 230V(1 phase)
AC Output Data(Back-Up)
Efficiency
Protection
18
Battery reverse Polarity YES
General Data
Weight 41kg
Display LCD
Grid connection standards IEEE 1547, IEEE 2030.5, Hawaii Rule 14H, Rule 21 Phase I,II,III
19
5. Installation
5.1. Check for Physical Damage
Make sure the inverter is intact during transportation. If there is any visible damage,
such as cracks, please contact your dealer immediately.
Object Description
A Inverter
B Expansion screws and pan-head screws
C CT (Inner radius 16mm)
D WiFi module (optional)
E GPRS module (optional)
F User manual
G CT (Inner radius 35mm / OPTIONAL)
5.3. Mounting
⮚ Installation Precaution
Inverter is designed for outdoor installation (IP 65). Make sure the installation site
meets the following conditions:
⮚ Space Requirement
Position Min.size
Left 300mm
Right 300mm
Top 500mm
Bottom 500mm
Front 1000mm
21
⮚ Mounting
Tools required for installation.
Installation tools: crimping pliers for binding post and RJ45, screwdriver, manual
wrench etc..
Step 1: Drill 4 holes in the wall according to the following distance dimensions,
50~60mm depth. Then use a proper hammer to fit the expansion bolt into the holes.
Step 2: Lift up the inverter and align the hole of the inverter with the expansion bolt,
fix the inverter on the wall.
Step 3: Tighten the nut of expansion bolt, and install an anti-theft lock on DC switch
of the inverter.
22
Step 4: Remove the cover screws by Allen Wrench and remove the cover . Remove
the waterproof cover by a flat blade screwdriver. Wiring box conduit plugs, Conduit plugs
are provided for 1 inch conduit fittings. If used conduit fitting is not 1 inch, an appropriate
conduit adaptor should be used.
23
6. Electrical Connection
6.1. PV connection
Hybrid can be connected in series with 4-strings PV modules for 5kW, 8kW and 10kw.
Select PV modules with excellent function and reliable quality. Open-circuit voltage of
module arrays connected in series should be <Max. DC input voltage; operating voltage
should be conformed to MPPT voltage range.
Warning!
(28)PV module voltage is very high, which already achieve dangerous voltage
range, please comply with electric safety rules when connecting.
Note!
(32)In order to save cable and reduce the DC loss, we suggest to install the
inverter near PV modules.
Step1. Wiring.
1.1 Choose the 12 AWG wire to connect with the cold-pressed terminal.
1.2 Remove 18mm of insulation from the end of wire.
18mm
12AWG
Step2. Cross the PV cables through the PV port, Connect PV cables to PV terminals.
Connect PV cables to PV terminals.
24
6.2. Grid Connection (GEN connection)
Step1. Check the grid voltage.
1. Check the grid voltage and compare with the permissive voltage range (Please refer
to technical data).
2. Disconnect the circuit board from all the phases and secure against re-connection.
Step2. Grid cables choose
Use the right pin terminal from the accessory box. Press the connectors on cable
conductor core tightly.
Step3. Choose the wire to connect with the cold-pressed terminal. (Remove
18mm of insulation from the end of wire.)
18mm
Step4. Cross the Grid cables through the grid port, Connect Grid cables to Grid
terminals.
Generator
(GEN)
Grid
25
down
1) For inverter, the standard PV installation typically consists of the connection of the
inverter with both panels and batteries. In case of systems not connected to the
batteries, the Back-Up function is strongly not advised to use. It shall not cover the
standard warranty and be liable for any consequences arising from users not following
this instruction.
2) Hybrid inverters are able to supply over load output at its "Back-Up". For details please
refer to the technical parameters of inverter. And the inverter has self-protection
dreading at high ambient temperature.
3) For complicated application, or Special load, please contact after-sales.
PV1
BAT
PV2
Hybrid Inverter
DG
Meter CT1 PE
L1
L2
N CT2
PE
`
LOAD1 LOAD2
GRID
E-BAR
Note!
(33)In case of discrepancies between wiring mode of local policy and the
operation guide above, especially for the wiring of neutral line, grounding
and RCD, please contact us before any operation!
Note: The absence of AC breaker on back-up side will lead to inverter damage if an
electrical short circuit happens on back-up side.
18mm
Step2. Connect the cables to the BACK-UP:Load1 and Load2 port of the inverter.
Inside the inverter, load2 is connected to load1 through a relay, and the relay
disconnect when the SOC of battery is lower than set value. At this time, the load2 is
powered off and load1 is still powered on. (The total power of Load1 plus Load2 should
not more than the rated BACK-UP power when GRID is off)
Warning!
(34)Make sure the BACK-UP load power rating is within BACK-UP output rating,
otherwise the inverter will shut down with an “over load” warning.
(35)When an “over load” is appeared, adjust the load power to make sure it is
within the BACK-UP output power range, then turn the inverter back on.
(36)For the nonlinear load, please make sure the inrush power should be within
the BACK-UP output power range.
27
6.4. Battery Connection
Charging & discharging system of Hybrid series inverter is designed for 48V lithium
battery.
Before choosing battery, please note the maximum voltage of battery can not exceed
60V and the battery communication should be compatible with Hybrid inverter.
⮚ Battery breaker
Before connecting to battery, please install a no-polarized DC breaker to make sure
inverter can be securely disconnected during maintenance.
When using RS485 protocol, please note that PIN2 must be disconnected!
Note!
(37)The battery communication can only work when the battery BMS is
compatible with the inverter.
28
⮚ Power Connection Battery:
Step1.
Choose the 1 AWG wire and strip the cable to 15mm. Select two O-terminals with an
aperture of M10. Insert the stripping line into the O-terminal and clamp it with a crimping
clamp.
Step2. Cross the battery cable through the battery port. Connect battery cable to
battery terminal
BMS
BATTERY TERMINAL
24.5 N.M
Note!
Cloud
Router
2)WiFi Connection:
Step1. Plug WIFI into “WiFi” port at the bottom of the inverter.
29
Step2. Build the connection between the inverter and router.
Step3. Create a user account online. (Please check the WiFi user manual for more
details).
AC
Meter
WIFI or GPRS
2)GPRS Connection:
Please refer to the Smart Plug user manual for detailed connection
Note!
(38)If CT is not installed or installed reversely, the functions of "Anti -reflux", "Self-
use", "Peak-shift "… will not be realized.
(39)The direction of the arrow on the CT points from this inverter to the GRID.
When connected to single-phase power grid (Europe, Africa, Asia, Australia). Only
30
one CT is provided in the accessories. The RJ45 connector of CT is connected to” CT-L1”,
and the CT is connected to L phase.
When connected to split phase power grid (North America), the accessories provide
two CTS, “CT-L1” network interface is corresponds to L1 phase, and “CT-l2” network
interface is connected to L2 phase.
31
communication board, and the two conductors are respectively connected to DRY1_ 1B
and DRY1_ 1.
At e-stop, the conductor is connected to the back of the contactor.
32
7. Inverter Parallel Guide
7.1. Parallel System Diagram
Multiple inverters can be installed together to deliver more power. When AC loads
are present, all units effectively share the load. The system diagram is as follows.
33
7.1.1. Split Phase (120/240Vac) Parallel Connection Diagram
34
7.1.2. Parallel Connection for 120/208 Three Phase (American Standard)
35
36
7.1.3. Parallel Connection for 230/400 Three Phase
37
7.2. Parallel Communication Cable Connection
For parallel communication, CAT 5 cables are needed. The units should be connected
hand by hand.
When using common batteries, BMS cable needs to be connected to the master unit.
The inverter shares the BMS information by inter-unit parallel communication cable.
Please check the diagram above. The common batteries use is supported on default for
maximizing the system efficiency. The BMS cable should be connected to the master
inverter.
2) Connect the loads of the two inverters together first. It should be noted that the
grid power line and the load line of the two inverters should be roughly the
same length.
3) Make sure the CT Limiter sensor is installed properly. If the load is connected
outside the inverter, user need to choose common ct and make sure the CT ratio is
right (the default 90A ct ratio is 1:1000, no need to change). The common CT is only
needed to be connected to the master inverter. Please install CT on every unit’s
incoming electrical service wires on L1 and L2 (see diagram) when choosing
independent CT.
4) Please check the master and slave’s setting by screen and make sure all the setting
are same.
38
7.4. Parallel System Setting
The parallel setting page can be visited in the following steps in the screen:
Password->Parallel Settings
7.4.1. Setting
Interface Description
This interface shows parallel setting.
39
Note!
(40) If you need to assemble the split phase into three phases, please make
the following settings:
40
8. Generator Use Operation Guide
8.1. Generator Use Diagram
8.1.1. The Generator is connected to the grid port of the inverter. The connecting cable
shall be covered with CT. It is used in some off network situations. The system
diagram is as follows.
8.1.2. The Generator is normally connected to the Generator port. The connecting cable
between the Generator and the inverter does not need to be covered with CT.
The connection line of the power grid port should be connected with CT. The
system diagram is as follows.
41
8.2. Generator Operation Notes
8.2.1. The two wire start signal DRYO_1A and DRYO_1B of the Generator is used to
automatically control the start and stop of the Generator.
8.2.2. Make sure the inverter units software version support Generator function.
Password->Information
8.2.3. When the generator is used in inverter parallel situation, the two wires start
signal is only needed to be connected to the master unit. The wiring and the
setting of the Generator should be exactly same.
42
8.2.4. Please check the diagram above.
Password->Gen Set
8.3.1. Setting
Interface Description
This interface shows Generator setting.
Generator.
(1) When the SOC of battery is lower than the
1.START SOC. setpoint, the Generator drycontact is enabled
(1) STOP SOC and Generator Manual operation is disabled,
the connected Generator will be started.
(2) Charge
(2) When the SOC of battery is higher than the
Current setpoint, the Generator dry contact is
enabled and Generator Manual operation is
4.MAX operating disabled, the connected Generator will be
1. Cooling time stopped (START SOC<STOP SOC).
43
8.3.2. CONTRL
Interface Description
44
9. LCD Operation
45
Display the real-time generator power. Click generator to enter
6 Generator the working status interface of generator, see section for 11.3.6
details.
Users can click Setting to enter the settings interface, see
7 Setting
section 11.4 for details.
lit in green: The inverter is in grid mode.
8
Off: The inverter is in not in grid mode.
9 lit in green: The inverter is in off-grid mode.
Indicator Off: The inverter is in not in off-grid mode.
LED lit in Yellow: The inverter is in Warning .
10
Off: The inverter has no Inverter Warning
lit in red: The inverter is in fault status.
11
Off: The inverter has no errors.
46
9.3.2. PV
①Display the working parameters of the
four channels of PV (PV1, PV2, PV3,
PV4), including real-time voltage, current,
and power. (PV input type can be set in the
settings).
②Display the cumulative charging capacity
of the PV, including daily and total
accumulated energy.
9.3.3. Grid
①Display the working parameters on the
grid, including Frequency, real-time
voltage, real-time current, and real-time
power.
②Accumulated energy from the power grid
to the equipment(Sell) and accumulated
energy from equipment to the power
grid(Buy),including daily and total
accumulated energy.
9.3.4. Battery
②Display battery charging voltage,
charging current, and discharge current.
③Three working states of batteries(from
BMS), including charging, discharging,
and forced charging.
Charge EN:Charge Enable Discharge
EN:Discharge Enable
④Accumulated discharge and charging
capacity of the battery, including daily and
total accumulated energy.
①Display the working parameters of the battery,
including real-time voltage, real-time current, battery
surplus capacity, battery temperature, battery power,
and battery type.
9.3.5. Load
9.3.5.1. Load/Page One
Load
47
①User can click to return to the
previous page, and click to enter the next
page .(not to be repeated later)
②Display the working parameters of the
load, including real-time voltage, current,
and power.
③Accumulated usage of load, including
daily and total accumulated energy.
9.3.6. Generator
Display the working parameters of the
generator,including real-time voltage,
current, and power.
9.4. Setting
9.4.1. Enter Setting
9.4.1.1. Input password
①Users can click on the icon above to
enter device status data (PV, Battery,
Energy Storage Inverter, Load, Grid,
Generator) and return to the Home Page.
②To enter the settings, a password is
required. The default password is 11111.
Click OK to enter the settings interface.
48
Users can click on the icon above to switch
between setting options, machine related
information, and return to the Home Page.
:After modifying the parameters, the user needs to click on this icon to confirm the modification.
②Advanced Mode:
There are four options here: Disable, Sell First Mode, Limited Consumption Mode and Zero Export Mode.
Disable: Only when users selects “Disable”, the three work modes (Self Consumption, Peak Shift, battery
priority) take effect. When the user selects the other three options (Sell First, Limit Consumption, Zero
Export), the three working modes are invalid.
Sell First: First consider selling electricity to the grid. In this mode the anti-reflux setting is automatically
disabled. The users can use this mode to sell back surplus solar power to grid. If time of use is enabled, the
battery power can also be sold to grid.
Limit Consumption: In this mode, the ct limiters are used to sense the grid power flow direction. The hybrid
inverter can be chosen to sell power or not sell power to grid. There is a CT Limit Power parameter available
in this mode. When the battery is needed to discharge to reduced the load consumption, the grid will cover the
parameter set part consumption firstly and the battery discharges energy to makes up the rest part. Other
conditions are similar to SELF CONSUME working mode.
Zero Export:In this mode, the ct limiters should be installed in the input of the inverter’s grid port. The
hybrid inverter will not sell power to grid. The user can use Zero export power parameter to ensure the inverter
won’t feed back power to grid.
③Backup Enable:When the Grid and PV are powered off, Enable the battery to supply power to the load,
default option is enable.
④Sell Enable:It means inverter allowed to generate electricity to the Grid.
⑤Grid Export Limit
Users can click to enter the numerical input interface.(not to be repected)
49
⑥Advanced Settings
Users can click to enter the advanced
settings interface.
There are also some attributes of these mode: Global Grid Charge
Enable, PV Charge Only, Bat Charge On Priority , Time-of-use
Enable and 6 Time-of-use Slots.
Advanced Settings/First Page:
i Time-of-use Enable : There are 6 slots which can be
programmed. If grid charge is enable, the grid is used to power the load and charge the battery to target SOC at
specific bat power attribute value. If selling electricity to the grid enable, the battery will discharge to target
SOC at specific battery power attribute value.
ii Users need to check TOU Enable to enter the work mode of Time-of-use Enable。
50
work
Peak Shift:
①work mode choose “Peak Shift”
②“Grid Export Limit” not work
③sell enable:choose enable
④Advanced Mode: must choose
“disable”
⑤don’t set this part, function not
work
⑥set Peak Shift time
Battery Priority
①work mode choose “Batt Priority”
②“Grid Export Limit” not work
③sell enable: depend on customer,if
want to sell power to grid,pls choose
④Advanced Mode: must choose
“disable”
⑤don’t set this part, function not
work
Advanced Mode:
1. Sell First:Prioritize feed to grid
①work mode choose advanced mode
“sell first”
②sell enable: choose enable
③“Grid Export Limit” not work
④Advanced Setting page:
51
2.Limit Consumption:can feed to
grid,support charge battery within a period
of time
①work mode choose advanced mode
“Limit Consumption”
②sell enable:depend on customer,if
want to sell power to grid,pls choose
③“Grid Export Limit” not work
④Advanced Setting page:
52
If want battery be charged within a
period of time,you can set TOU time
and choose “TOU Enable”.
WORKTIME*
1)The maximum allowable setting time is 24h(one day), It is allowed to set six different charging and
discharging states within 24h.(time1 twice,time2 twice,time3 twice), The inverter runs repeatedly every day
according to the set time.
53
Set time range
00:00 23:59
2) The inverter executes according to the settings of time1, time2 and time3 in the order of time. The following
figure is an example。Different time periods do not overlap.
3)If you want to set a continuous charging time from the first night to the next morning. For example, you
want charge battery form first day 21:00pm to next day 5:00am, divide this time period into two time periods
(21:00~23:59, 00:00~05:00), and select two charging time periods from Time1, Time2 and Time3 and set
them.
54
Charge Curr: This interface is used to select the parallel charging current.
Discharge Cur: Start or disable the parallel function.
9.4.4. Battery Setting
9.4.4.1. Battery type and communications
①Set Battery Type and Battery
Communication method
Users can choose the battery type is
lead-acid battery/lithium battery, and the
battery communication method is
CAN/485.The default option is CAN.
②Users can manually input the value of
charging current and discharge power
limit.
③Battery wake-up :
When the battery is low and the battery relay has been disconnected, the inverter will send instructions to the
battery forcibly sucking relay by BMS, and the inverter will charge.
The default option is disabled. (Partial battery support)
If you want to use this feature, please consult the battery brand supported by the dealer. Use it only when the
battery is too low.
After the battery wakes up successfully, please turn off the function, otherwise it will affect the normal
operation of the machine.
55
9.4.5. Grid Setting
9.4.5.1. Grid setting/Page One
①Energy Storage Inverter use Single Phase,default
option is Single Phase.
②Low Voltage:The input value of Grid low voltage. It
is valid when grid mode choose custom.
High Voltage:The input value of Grid high voltage. It
is valid when grid mode choose custom.
Low Freq:The input value of Grid low frequency. It is
valid when grid mode choose custom.
High Freq:The input value of Grid high voltage. It
is valid when grid mode choose custom.
Grid parameters/page two:
AU:Australia AU-W: Western Australia NZ: New Zealand UK: United Kingdom PK:PAKISTAN
KR:Korea PHI:Philippines CN:China
US:America TSAIL:THAILAND ZA:South africa Custom:User defined
POL:Poland EN50549 VDE4105 ITA:Italy JPN:Japan
56
screen, please contact the distributor if you need to
use them.)
57
to start and stop through the dry contact, waiting time of the Generator to
Please ban dragons. restart after it has reached the running
time. The unit is 0.1 hour.
Gen Manual Mode: If the user wants the
Generator to be controlled manually, Enable Max Operating: It indicates the
it(Manual control enable and automatic longest time Generator can run in one
day, when time is up, the Generator
control enable are mutually exclusive when will be turned off. The value 240
set ). means 24hours in which state the
Gen Manual Start/Stop: The on/off Generator will not be shut down all the
command in manual control mode . time. The unit is 0.1 hour.
Gen Connect To Grid: Connect the
diesel Generator to the grid input port.
Notice:
Please read this manual carefully before using products and keep it in the place where
O&M providers can easily find.
Due to product upgrade and other factors, the content of this manual might change
from time to time. Please take actual product as standard and get latest manual from
www.solarman.cn or sales. Unless other- wise agreed herein, this manual will only be
used as guidance. Any statement, information or suggestion in this manual will not take
58
any form of responsibility.
Without written permission, any content of this document (partly or entirely) cannot
be extracted, copied or transmitted in any form by any company or individual.
Download APP
59
Type 2
Step1: Assemble logger to the inverter communication interface as shown in the
diagram.
The normal operation status of the stick logger, when router connected to
the network normally:
1.Connection to the server succeeded: NET light keeps on after the logger powered
on. 2.Logger running normally: READY light flashes.
3.Connection to the inverter succeeded: COM light keeps on.
10.1.3. Abnormal State Processing
If the data on platform is abnormal when the stick logger is running, please check
the table below and according to the status of indicator lights to complete a simple
troubleshooting. If it still can not be resolved or indicator lights status do not show in the
table below, please contact Customer Support.
(Note: Please using the following table query after power-on for 2mins at least.)
60
10.1.4. Usage methods and notices for Reset button
61
10.1.4.2. Notices for Reset button
10.2.1. Registration
Go to SOLARMAN Smart and register.
Click "Register" and create your account here.
62
SN in the external packaging or on the logger body.
63
Step 2: Connect to AP network
Click "Go to connect" and find the right "AP_XXXXX" network (XXXXX refers to logger
SN). If the password is required, you can find the password on the logger body. Go back
to SOLARMAN Smart APP, after connecting to AP network.
64
If configuration failure occurs, please check the following reason and try it
again.
If you have any technical queries about our products, please contact us and provide
the following information:
1. Product model and serial number of stick logger.
2. Product model and serial number of connected inverter. Thank you for your support
and cooperation!
65
10.3.2. Display Interface
66
10.4. Parameters description
67
L/HFRT If the user needs to use over-frequency and
Fac HF3 Trip 61.50Hz Fac HF3 ClrTime 10.0S under-frequency protection, he can find the
corresponding parameters in the above
Fac HF2 Trip 61.50Hz Fac HF2 ClrTime 10.0S
mobile phone APP interface according to the
Fac HF1 Trip 60.50Hz Fac HF1 ClrTime 300.0S table on the left and set them by himself.
Fac LF1 Trip 59.20Hz Fac LF1 ClrTime 300.0S
Fac LF2 Trip 57.50Hz Fac LF2 ClrTime 10.0S Fac
LF3 Trip 57.50Hz Fac LF3 ClrTime 10.0S
68
11. Advanced Mode Operation Guide
11.1. Advanced Mode Introduction
The hybrid inverter can be programmed to control how and when to use grid
power.The Advanced mode allow management of flexible loads and time-of-use billing.
There are three advanced mode available: Sell First Mode, Limited Consumption
Mode and Zero Export Mode.
PV Charge Only:
69
If user don’t want to use grid to charge the battery in any time, please enable this
attribute.
6 Time-of-use Slots:
There are 6 slots which can be programmed. If grid charge/generator charge is
enable, the grid is used to power the load and charge the battery to target SOC at specific
bat power attribute value.
Interface Description
This interface displays advanced mode settings.
--ADVAN SET-- 1. ->Inverter working mode setting.
2. ->Inverter related function control. See 13.2.3 Advanced
-- >1.Export Options
Settings for details.
2.Advanced settings 3.-> Whether TIME OF USE is enabled ,Time of use setting. See
10.2.4 Time of use for details.
3.TOU Enable 4.-> Used to set the SOC of the switch LOAD 2 (only if the battery
4.Auxload Soc is present).
70
11.2.2. Export Options
Interface Description
On this page, select the advanced mode you need to
--MODE SET-- enable. If selected, the mode will be enabled.
-- > 1.Disable
2.Sell First
3.Limit Consumption
4.Zero Export
Interface Description
1.- >Global control, whether the power grid can charge the
--ADVAN CONTROL-- battery.
-- > 1. Grid Charge Enable 2.- >The battery is charged only by PV, and cannot be charged
by the grid.
2. PV Charge Only 3.- >Battery Priority Charge Enable.
4. Battery First
71
Interface Description
1.->From the start time to the end time, charge the battery
Start: 00:00 with the written Power to the written SOC. If Grid is
enabled(Tick√) , allow the grid to charge.
End: 00:00
2.->In the slot section( SOC), control the grid to charge the
Batt Power: 00.0KW battery.
Grid: √
GEN:
SOC: 0%
SOC off: 0%
72
12. Fault diagnosis and solutions
The inverter is easy to maintain. When you encounter the following problems, please
refer to the Solutions below, and contact the local distributor if the problem remains
unsolved. The following table lists some of the basic problems that may occur during the
actual operation as well as their corresponding basic solutions.
The load power is (1) Check whether the load is in compliance with the
greater than other maximum power of the machine.
power(PV,BAT). (2) Cut off all the power and shut down all the
machines; disconnect the load and plug in to
Over Load 01
restart machines, then check whether the load is
short circuited if the fault has been eliminated.
(3) Contact customer service if error warning
continues.
Bat Low Bat Low capacity (1) Battery Low that setting capacity.(SOC<100%-
04
capacity DOD)
The battery voltage is 1. Checking System Settings, If so, power off and
greater than the restart.
Bat Over Vol 05 Inverter maximum 2. Contact customer service if error warning
voltage. continues.
Gird low vol 06 Grid voltage is (1) Check if the grid is abnormal.
73
abnormal (2) Restart the inverter and wait until it functions
normally.
Grid over vol 07
(3) Contact customer service if error warning
continues.
Grid low freq 08 Grid Frequency is (1) Check if the grid is abnormal.
abnormal.
(2) Restart the inverter and wait until it functions
normally.
Grid overFreq 09 (3) Contact customer service if error warning
continues.
BUS voltage is lower (1) Check the input mode setting is correct.
than normal.
(2) Restart the inverter and wait until it functions
bus under vol 13 normally.
(3) Contact customer service if error warning
continues.
BUS voltage is over (1) Check the input mode setting is correct.
bus over vol 14 maximum value..
(2) Restart the inverter and wait until it functions
normally.
The inverter current (1) Restart the inverter and wait until it functions
exceeds the normal normally.
Inv over cur 15 value.
Battery charge current (1) Restart the inverter and wait until it functions
over than the Inverter normally.
Chg over cur 16 maximum voltage.
Bus voltage instability. (1) Check the input and output mode setting is
correct.
Bus vol osc 17
(2) Restart the inverter and wait until it functions
normally.
Inv under vol 18 INV voltage is (1) Check if the INV voltage is abnormal.
abnormal
(2) Restart the inverter and wait until it functions
normally.
Inv over vol 19 (3) Contact customer service if error warning
continues.
74
INV frequency is (1) Check if the INV frequency is abnormal.
abnormal
(2) Restart the inverter and wait until it functions
InvFreqAbnor 20 normally.
(3) Contact customer service if error warning
continues.
75
The inverter (1) Cut off all the power of the machine and wait
temperature is higher one hour, then turn on the power of the
igbt temp high 21 than the allowed value machine.
Battery temperature is (1) Check the ambient temperature near the battery
low than the allowed to see if it meets the specifications.
bat UnderTemp 24
value.
bus soft fail 32 The inverter may be (1) Restart the inverter and wait until it functions
damaged normally.
inv soft fail 33 (2) Contact customer service if error warning
continues.
bus short 34
inv short 35
76
Bus Relay Fault 38 The inverter may be (1) Restart the inverter and wait until it functions
damaged normally.
Grid Relay Fault 39 (2) Contact customer service if error warning
continues.
EPS rly fault 40
Gfci fault 41
Selftest fail 44
System fault 45
Current DCover 46
Voltage DCover 47
Note: If an error occurs that is not listed in the table, Please Contact customer service.
77