0% found this document useful (0 votes)
11 views8 pages

Modbus PTEC v1 - 5

The document outlines the parameters list for a Master Controller version 1.5, detailing various modbus addresses, variable types, units, and descriptions. It includes information on status registers, input command voltages, temperature and pressure probes, and configuration settings. Each parameter has specific writing requirements, default values, and EEPROM save options.

Uploaded by

rpodolsk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views8 pages

Modbus PTEC v1 - 5

The document outlines the parameters list for a Master Controller version 1.5, detailing various modbus addresses, variable types, units, and descriptions. It includes information on status registers, input command voltages, temperature and pressure probes, and configuration settings. Each parameter has specific writing requirements, default values, and EEPROM save options.

Uploaded by

rpodolsk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

MASTER CONTROLLER v1.

5 (13/05/2016)
Parameters List
LEGEND
* possible only if parameter 1024 equal to 1
N.B: all address has reading modbus function 0x03

address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

0 0 Registry registry num


1 1 Registry registry num
2 2 Registry registry num
3 3 Registry registry num
4 4 Registry registry num
5 5 Registry registry num
6 6 Registry registry num
0xA1 = VRTS ; 0xA2= VRTM; 0xBB =
7 7 Device model ID registry num Ptec; 0xBC = Ptec2
8 8 Firmware version registry num firmware version (es. 10 = 1.0)

9 9 Output voltage (ramp excluded) status % Output voltage within ramp time

bit 6= output 0; bit 5= stop input; bit


4=missing probe; bit 3=config error;
10 A Status register alarm / status num bit 2=overheating; bit 1=klixon; bit
11 B Real output voltage status % output voltage (realtime)

value0= normal reboot; valore1= if


reboot after reset; valore2= modified
12 C Status register 2 status num x value 0 value 3 configuration values by keyboard
0=no error; 1=phase missing;
13 D Alarm status num 3=overheating; 5=config error;
14 E Phase missing errors status num Phase missing errors amount

15 F Overtemperature errors status num Overtemperature errors amount


16 10 Klixon errors status num Klixon errors amount
17 11 Missing probe errors status num Missing probe errors amount
19 13 Working hours status num
20 14 Working days status num
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

Internal temperature (one decimal


21 15 Internal temperature status °C point)
22 16 Input command voltage A1 input % Input 1 rate
23 17 Input command voltage A2 input % Input 2 rate
value with one decimal on the
temperature measured by the probe 1
26 1A Temperature probe 1 status °C (Ex . 246 = 24.6 ° C )
value with one decimal on the
temperature measured by the probe 2
27 1B Temperature probe 2 status °C (Ex . 246 = 24.6 ° C )
value with one decimal on the
pressure measured by the probe 1 (Es.
28 1C Pressure probe 1 status bar 134 = 13,4 bar)
value with one decimal on the
pressure measured by the probe 2 (Es.
29 1D Pressure probe 2 status bar 134 = 13,4 bar)

bit 0=speed limit; bit 1=klixon; bit


2=start/stop; bit 3=heat/cool; bit
30 1E digital I/O status num 5=relay 3; bit 6=relay 2; bit 7=relay 1
0=means no S1 installed; 1=means S1
31 1F Expansion card S1 status num installed

0=means that clock isn't enabled to


set speed limit; 1=means that clock is
32 20 Enable speed limit by clock status num enabled to set speed limit

0=means that is not possible to


calculate cos-phi; 1=means that is
33 21 Fan cos-phi function status num possible acquire cos-phi

write 1 enable writing on other


address and block output voltage.
1024 400 Regulator lock parameter num x value 0 value 1 write 0 re-enable regulation control.
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

operation mode (1=slave, 2=chiller,


1030 406 Operation mode (master, slave) parameter num x* value 1 value 3 3=drycooler) 2 x
write 2 for reset to default values;
1031 407 reset parameter num x* value 1 value 3 write 3 for reboot

(1= if 0..10V); (2= if 4..20mA) (3= if


raziometric 0.5-4.5V) (4= if industrial
1032 408 Input type parameter num x* value 1 value 5 PWM ) (5= if Modbus) 1 x

(=0 no speed
limit )(=1
speed limit
enable by
1033 409 Speed limit status parameter num value 0 value 1 clock alarm) 0
Voltage that replaces V1, when speed
1034 40A V1 limit parameter % x 1038 1035 limit is enable 18 x
Voltage that replaces V2, when speed
1035 40B V2 limit parameter % x 1034 1039 limit is enable 65 x
(0= if disabled )(1= automatic cos-phi
1036 40C cos-phi automatic status parameter num x* value 0 value 1 when reboot) 0 x x
values between 6 and 10 means 0.6 e
1037 40D Cos-phi parameter num x* value 6 value 10 1 8 x
1038 40E min. motor limit parameter % x* value 15 1039 Min. motor voltage value 15 x
1039 40F max. motor limit parameter % x* 1038 value 100 Max. motor voltage value 100 x
time needed to control 0-100%
1040 410 ramp parameter sec x* value 2 value 60 voltage output 5 x

1041 411 Kick start parameter num x* value 0 value 1 (0= no kick start)(1= kick start active) 1 x
suppression voltage range 1 (1= if
1042 412 suppression 1 parameter num x* value 0 value 1 active) 0 x
suppression voltage range 2 (1= if
1043 413 suppression 2 parameter num x* value 0 value 1 active) 0 x
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

suppression voltage range 3 (1= if


1044 414 suppression 3 parameter num x* value 0 value 1 active) 0 x

1045 415 min. limit sop 1 parameter % x* value 0 1046 min.voltage suppression range 1 20 x

1046 416 max limit sop 1 parameter % x* 1045 1047 max. voltage suppression range 1 30 x

1047 417 min. limit sop 2 parameter % x* 1046 1048 min.voltage suppression range 2 40 x

1048 418 max limit sop 2 parameter % x* 1047 1049 max. voltage suppression range 2 50 x

1049 419 min. limit sop 3 parameter % x* 1048 1050 min.voltage suppression range 3 60 x

1050 41A max limit sop 3 parameter % x* 1049 value 100 max. voltage suppression range 3 70 x
(value 1 se
1030=1) -
(value 3 1=fault; 2=hysteresis; 3=from clock
1051 41B Relay 1 config parameter num x* value 1 altrimenti) setting 1 x

pressure/temperature value below


1052 41C min. limit relay 1 parameter bar/°C x* value 0 1053 wich relay is denergized 265 x
(1063 se
1030=2) -
(value 950 se pressure/temperature value below
1053 41D max limit relay 1 parameter bar/°C x* 1052 1030=3) wich relay is energized 295 x

1054 41E regulation profile parameter num x* value 1 value 2 1= linear profile; 2= axial fans profile 2 x
1057 421 Modbus slave address parameter num x* value 1 value 247 Modbus slave address 1 x x
(1= if 9600bps); (2= if 19200); (3= if
1058 422 baudrate Modbus parameter num x* value 1 value 3 38400) 2 x x

1059 423 Modbus stop bit parameter num x* value 1 value 2 (1= if 1 stop bit); (2= if 2 stop bit) 1 x x
(1= no parity); (2= even parity ); (3=
1060 424 Modbus parity parameter num x* value 1 value 3 odd parity) 1 x x
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

Indicates the time within which the


master must renew his command
1061 425 Modbus timeout parameter sec x* value 1 value 240 regulation 30 x
Maximum pressure value of the probe
1063 427 Full scale value of pressure probe parameter bar x* value 0 value 10000 (Es. 3003=0,0 bar) 500 x

1=probe 1; 2=probe 2; 3=higher


1064 428 input probe priority parameter num x* value 1 value 5 probe; 4= lower probe; 5=automatic 5 x
1065 429 Second operation cycle parameter num x* value 1 value 2 1=direct; 2=reverse 2 x
1066 42A Start contact parameter num x* value 1 value 2 1=close; 2=open 1 x
Pressure P1 of the first cool cycle. (Ex.
1067 42B CO1_P1 parameter bar x value 0 1068 300 = 30.0 bar) 200 x
Pressure P2 of the first cool cycle. (Ex.
1068 42C CO1_P2 parameter bar x 1067 1069 300 = 30.0 bar) 240 x
Pressure P_MAX of the first cool cycle.
1069 42D CO1_PMAX parameter bar x 1068 1070 (Ex. 300 = 30.0 bar) 250 x
Voltage V1 of the first cool pressure
1070 42E CO1_V1 parameter % x 1069 1071 cycle 20 x
Voltage V2 of the first cool pressure
1071 42F CO1_V2 parameter % x 1070 1072 cycle 90 x
Pressure P1 of the second cool cycle.
1072 430 CO2_P1 parameter bar x value 0 1073 (Ex. 300 = 30.0 bar) 200 x
Pressure P2 of the second cool cycle.
1073 431 CO2_P2 parameter bar x 1072 1074 (Ex. 300 = 30.0 bar) 240 x
Pressure P_MAX of the second cool
1074 432 CO2_PMAX parameter bar x 1073 1075 cycle. (Ex. 300 = 30.0 bar) 250 x
Voltage V1 of the second cool
1075 433 CO2_V1 parameter % x 1074 1076 pressure cycle 20 x
Voltage V2 of the second cool
1076 434 CO2_V2 parameter % x 1075 1077 pressure cycle 90 x
Pressure P1 of the heat cycle (Ex. 300
1077 435 HEA_P1 parameter bar x value 0 1078 = 30.0 bar) 70 x
Pressure P2 of the heat cycle (Ex. 300
1078 436 HEA_P2 parameter bar x 1077 1079 = 30.0 bar) 110 x
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

Pressure P_MAX of the heat cycle (Ex.


1079 437 HEA_PMAX parameter bar x 1078 1080 300 = 30.0 bar) 50 x

1080 438 HEA_V1 parameter % x 1079 1081 Voltage V1 of the heat pressure cycle 20 x

1081 439 HEA_V2 parameter % x 1080 1082 Voltage V2 of the heat pressure cycle 90 x
Temperature T1 of the first cool cycle.
1082 43A CO1_T1 parameter °C x value 0 1083 (Ex. 300 = 30.0 °C) 220 x
Temperature T2 of the first cool cycle.
1083 43B CO1_T2 parameter °C x 1082 1084 (Ex. 300 = 30.0 °C) 280 x
Temperature T_MAX of the first cool
1084 43C CO1_TMAX parameter °C x 1083 value 1950 cycle. (Ex. 300 = 30.0 °C) 290 x
Voltage V1 of the first cool
1085 43D CO1_T_V1 parameter % x 1084 1086 temperature cycle 20 x
Voltage V2 of the first cool
1086 43E CO1_T_V2 parameter % x 1085 1087 temperature cycle 90 x
Temperature T1 of the second cool
1087 43F CO2_T1 parameter °C x value 0 1088 cycle. (Ex. 300 = 30.0 °C) 220 x
Temperature T2 of the second cool
1088 440 CO2_T2 parameter °C x 1087 1089 cycle. (Ex. 300 = 30.0 °C) 280 x

Temperature T_MAX of the second


1089 441 CO2_TMAX parameter °C x 1088 value 1950 cool cycle. (Ex. 300 = 30.0 °C) 290 x
Voltage V1 of the second cool
1090 442 CO2_T_V1 parameter % x 1089 1091 temperature cycle 20 x
Voltage V2 of the second cool
1091 443 CO2_T_V2 parameter % x 1090 1092 temperature cycle 90 x
Temperature T1 of the cycle cool. (Ex.
1092 444 HEA_T1 parameter °C x 1091 1093 300 = 30.0 °C) 220 x
Temperature T2 of the cycle cool. (Ex.
1093 445 HEA_T2 parameter °C x 1092 value 1950 300 = 30.0 °C) 240 x
Temperature T_MAX of the cycle cool.
1094 446 HEA_TMAX parameter °C x value 0 1092 (Ex. 300 = 30.0 °C) 210 x
Voltage V1 of the heat temperature
1095 447 HEA_T_V1 parameter % x 1036 1093 cycle 20 x
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

Voltage V2 of the heat temperature


1096 448 HEA_T_V2 parameter % x 1037 1094 cycle 90 x

offset value for temperature sensor 1


1097 449 offset temp 1 parameter °C x* value -50 value +50 calibration (Es. -34=-3,4 °C) 0 x

offset value for temperature sensor 2


1098 44A offset temp 2 parameter °C x* value -50 value +50 calibration (Es. -34=-3,4 °C) 0 x

(value 1 if
1030=1) - 0=off; 1=fault; 2=hysteresis; 3=from
1099 44B Relay 2 config parameter num x* value 0 (value 4 else) clock setting; 4=partialization load 2 x

pressure/temperature value below


1100 44C min. limit relay 2 parameter bar/°C x* value 0 1101 wich relay 2 is denergized 265 x
(1063 if
1030=2) -
(value 950 if pressure/temperature value below
1101 44D max limit relay 2 parameter bar/°C x* 1100 1030=3) wich relay 2 is energized 295 x

(value 1 if
1030=1) - 0=off; 1=fault; 2=hysteresis; 3=from
1102 44E Relay 3 config parameter num x* value 0 (value 4 else) clock setting; 4=partialization load 0 x

pressure/temperature value below


1103 44F min. limit relay 3 parameter bar/°C x* value 0 1104 wich relay 3 is denergized 265 x
(1063 if
1030=2) -
(value 950 if pressure/temperature value below
1104 450 max limit relay 3 parameter bar/°C x* 1103 1030=3) wich relay 3 is energized 295 x
variable bandwidth (= 0 if not active)
1105 451 variable bandwith parameter num x* value 0 value 1 (= 1 if active) 1 x
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?

variation of the band every 5°C of the


deviation from the reference ambient
1106 452 percentage bandwidth variation parameter % x* value 20 value 65 temperature (25°C) 25 x

value with one decimal on the


temperature measured by the
1107 453 external probe temperature stato °C external probe (Ex . 246 = 24.6 ° C )
value for the temperature threshold
external probe partialization below which the partialization is
1108 454 threshold parameter °C x* value 0 value 15 enabled 10 x

value for the temperature threshold


below which the wet hysteresis relay
1109 455 wet threshold parameter °C x* value -10 value 40 doesn't energize 27 x

Hexadecimal example (with CRC)

Read request of A1 command (address 0x16)


01 03 00 16 00 01 65 CE request
01 03 02 00 35 78 53 reply (A1=0x35=53%)

Write request for change value of adjustment ramp (0x410)


01 06 04 00 00 01 49 3a write 1 on address 0x400
01 06 04 00 00 01 49 3a received confirm as reply
01 06 04 10 00 06 09 3d write 6 on address 0x401 (ramp time)
01 06 04 10 00 06 09 3d received confirm as reply
01 06 04 00 00 00 88 fa write 0 on address 0x400
01 06 04 00 00 00 88 fa received confirm as reply