Modbus PTEC v1 - 5
Modbus PTEC v1 - 5
5 (13/05/2016)
Parameters List
LEGEND
* possible only if parameter 1024 equal to 1
N.B: all address has reading modbus function 0x03
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?
9 9 Output voltage (ramp excluded) status % Output voltage within ramp time
(=0 no speed
limit )(=1
speed limit
enable by
1033 409 Speed limit status parameter num value 0 value 1 clock alarm) 0
Voltage that replaces V1, when speed
1034 40A V1 limit parameter % x 1038 1035 limit is enable 18 x
Voltage that replaces V2, when speed
1035 40B V2 limit parameter % x 1034 1039 limit is enable 65 x
(0= if disabled )(1= automatic cos-phi
1036 40C cos-phi automatic status parameter num x* value 0 value 1 when reboot) 0 x x
values between 6 and 10 means 0.6 e
1037 40D Cos-phi parameter num x* value 6 value 10 1 8 x
1038 40E min. motor limit parameter % x* value 15 1039 Min. motor voltage value 15 x
1039 40F max. motor limit parameter % x* 1038 value 100 Max. motor voltage value 100 x
time needed to control 0-100%
1040 410 ramp parameter sec x* value 2 value 60 voltage output 5 x
1041 411 Kick start parameter num x* value 0 value 1 (0= no kick start)(1= kick start active) 1 x
suppression voltage range 1 (1= if
1042 412 suppression 1 parameter num x* value 0 value 1 active) 0 x
suppression voltage range 2 (1= if
1043 413 suppression 2 parameter num x* value 0 value 1 active) 0 x
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?
1045 415 min. limit sop 1 parameter % x* value 0 1046 min.voltage suppression range 1 20 x
1046 416 max limit sop 1 parameter % x* 1045 1047 max. voltage suppression range 1 30 x
1047 417 min. limit sop 2 parameter % x* 1046 1048 min.voltage suppression range 2 40 x
1048 418 max limit sop 2 parameter % x* 1047 1049 max. voltage suppression range 2 50 x
1049 419 min. limit sop 3 parameter % x* 1048 1050 min.voltage suppression range 3 60 x
1050 41A max limit sop 3 parameter % x* 1049 value 100 max. voltage suppression range 3 70 x
(value 1 se
1030=1) -
(value 3 1=fault; 2=hysteresis; 3=from clock
1051 41B Relay 1 config parameter num x* value 1 altrimenti) setting 1 x
1054 41E regulation profile parameter num x* value 1 value 2 1= linear profile; 2= axial fans profile 2 x
1057 421 Modbus slave address parameter num x* value 1 value 247 Modbus slave address 1 x x
(1= if 9600bps); (2= if 19200); (3= if
1058 422 baudrate Modbus parameter num x* value 1 value 3 38400) 2 x x
1059 423 Modbus stop bit parameter num x* value 1 value 2 (1= if 1 stop bit); (2= if 2 stop bit) 1 x x
(1= no parity); (2= even parity ); (3=
1060 424 Modbus parity parameter num x* value 1 value 3 odd parity) 1 x x
MASTER CONTROLLER v1.5 (13/05/2016)
Parameters List
address HEX Variables Type Unit WRITING address or address or description default need EEPROM
for address (modbus min value max value value REBOOT save
request function 0x06 reference reference after
(base 0) or 0x10) write
function?
1080 438 HEA_V1 parameter % x 1079 1081 Voltage V1 of the heat pressure cycle 20 x
1081 439 HEA_V2 parameter % x 1080 1082 Voltage V2 of the heat pressure cycle 90 x
Temperature T1 of the first cool cycle.
1082 43A CO1_T1 parameter °C x value 0 1083 (Ex. 300 = 30.0 °C) 220 x
Temperature T2 of the first cool cycle.
1083 43B CO1_T2 parameter °C x 1082 1084 (Ex. 300 = 30.0 °C) 280 x
Temperature T_MAX of the first cool
1084 43C CO1_TMAX parameter °C x 1083 value 1950 cycle. (Ex. 300 = 30.0 °C) 290 x
Voltage V1 of the first cool
1085 43D CO1_T_V1 parameter % x 1084 1086 temperature cycle 20 x
Voltage V2 of the first cool
1086 43E CO1_T_V2 parameter % x 1085 1087 temperature cycle 90 x
Temperature T1 of the second cool
1087 43F CO2_T1 parameter °C x value 0 1088 cycle. (Ex. 300 = 30.0 °C) 220 x
Temperature T2 of the second cool
1088 440 CO2_T2 parameter °C x 1087 1089 cycle. (Ex. 300 = 30.0 °C) 280 x
(value 1 if
1030=1) - 0=off; 1=fault; 2=hysteresis; 3=from
1099 44B Relay 2 config parameter num x* value 0 (value 4 else) clock setting; 4=partialization load 2 x
(value 1 if
1030=1) - 0=off; 1=fault; 2=hysteresis; 3=from
1102 44E Relay 3 config parameter num x* value 0 (value 4 else) clock setting; 4=partialization load 0 x