Module : 315Wp
No. of Module : 144 Nos.
DC Capacity : 45.36 kWp
1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3
18 18 18 18 18 18 18 18
STRING-1
STRING-2
STRING-3
STRING-4
STRING-5
STRING-6
STRING-7
STRING-8
Cable 1Cx4Sqmm
Cu. XLPO
Inverter-50kW
DC Rated Voltage -610V
MPPT Range -480 to 800
Max. DC -950V
DC SPD type II (In-Built)
Inverter-1
Placement-As Per Site
Cable 4C+1C x 35Sqmm
Cu. XLPE (1.1kV)
Solar ACDB
(Location-Roof/Ground)
AC SPD type II SPD
MFM MFM METER
AC LT Cl-0.5s
CT 75/5A, Cl-0.5s
SOLAR ON
MCCB
SOLAR O/G MCCB 4P
100A
with OL,SC & EF protection
R Y B
EFR
Cable 4C x 35Sqmm
Cu XLPE (1.1kV)
Incomer
EXISTING HT 11kV, Cl. 0.5S
METER (To be replaced by Net meter)
Existing LT Panel
(LT Panel Room)
800Amp
Solar Metering Panel-
near existing Main Panel BUS BAR
R Y B
BREAKER
SOLAR METER (MAIN METER)
SPARE
M
Current Transformer LT Bi-directional
75/5A, Cl: 0.5s Trivector Meter -AC Cl-0.5s
M SOLAR METER (CHECK METER)
Current Transformer LT Bi-directional
75/5A, Cl: 0.5s MF Energy Meter -AC Cl-0.5s INJECTION
MCCB
THROUGH SPARE BREAKER
100A
OR AS PER SITE
(RATING OF BREAKER/BUSBAR SHALL
BE EQUAL OR HIGHER THAN SOLAR O/G
MCCB)
Note: Specifications, cable sizing, current rating, etc.
for all components shown in SLD can change in case AZURE SITE ID NR-UK-MBD-063
of change in DC capacity. LEGENDS
System Details:- No . 8, Ground Floor, Local Shoping Complex,
= MODULE Madangir, Pushp Vihar, New Delhi - 110 062.
S.N. DESCRIPTION QTY
144 Nos. = INVERTER CLIENT AZURE POWER FORTY FOUR PVT. LTD.
1. No. of Modules
2. DC Capacity 45.36 kWp SPD = METER PROJECT REMCL-46MW
3. No of Inverters 1 Nos DRAWN IRSS TITLE:-
M = METER SINGLE LINE DIAGRAM
4. AC Capacity 50 kW CHECKED ALAUDIN
= MCCB
5. Incomer Feeder Rating 800 A 4P APPROVED M. AHMED PROJECT NO: DRAWING NO. REV. 00
6. Fault Current Rating 25 kA = MCB SCALE N.T.S APFF/SPP/REMCL NR-UK-MBD-063/DCE/02 SHEET 1 OF 1
7. Spare Feeder Rating N/A
DG Sync (Y/N) (If Yes, Rating) 250 kVA,415V = EARTHING 1. All rights reserved. This drawing contains proprietary information which is protected by copyright. No part of this drawing
8. may be reproduced, translated protected by copyright. No part of this drawing may be reproduced, translated in computer
language, or transmitted in any form whatsoever without the prior written consent of Azure Power India Pvt. Ltd.