Float valve balanced type
Series J2 10
Balanced float valve with diaphragm actuated.
Descriptif
• Performances:
- Balanced type valve,
- Progressive operation without friction,
- Low head loss.
• Design:
- Compactness,
- PEHD float,
- Fully epoxy coated.
• No adjustment required.
• Maintenance-free.
• WRAS approved model on request.
Technical data
• Range: DN 40 to 250.
• Max working pressure: 10 bar.
• Max working temperature: +1° to 65° C.
•F
lange drilling ISO PN 10 according to standards EN 1092-2
and ISO 7005-2 (ISO PN 16 for PN 16 execution for DN 200 and 250).
Options
• Ductile iron made.
• 316 L stainless steel float.
• Altitude setting.
• Bottom installation kit.
• PN 16.
Applications
• Control of top water level in reservoirs and storage tanks:
- Drinking water networks.
- Fire protection.
- Irrigation.
- High rise building.
BAYARD - Series J2 10 - PPHT01-04-056D-EN
Float valve balanced type 2
Operation
A high resistance diaphragm balanced design with direct float The slight remaining pressure tending to open the valve
and lever action compensates 90 % of the effect of the pressure 10 %), prevents vibrations and damps down the effects of
on the main valve, with no risk of rubbing or sticking. Hence, rapid operations. The high lever-arm demultiplication factor
the valves operating action is very smooth and only requires a results in the device being highly insensitive to oscillations
relatively small float and mechanical parts. on the water surface. The device is simple, robust, and
requires no ajustement.
B
Item Designation Qty Materials Standards C
3 2 9 11 8 13 12
1 Body 1 Cast iron/EN-GJL-250 EN 1561 14
2 Cover or bonnet 1 Cast iron/EN-GJL-250 EN 1561
3 Stem 1 Stainless steel 420F /X29CrS13 EN 10088
A
4 Diaphragm 1 Textile reinforced elastomer 4
5 Sealing disk 1 Polyurethane/PUR
6 Link 1 Galvanized steel/S235-JR EN 10025
7 Lower lever 1 Galvanized cast/EN-GJMB-350-10 EN 1562
8 Float lever 2 Galvanized steel /S235-JR EN 10025
9 Pin split pin 2 Stainless steel 304L/X2CrNi 18-09 EN 10088
10 Pin split pin 1 Stainless steel 304L/X2CrNi 18-09 EN 10088
11 Pin split pin washers 2 Stainless steel 304L/X2CrNi 18-09 EN 10088
12 Float 1 PEHD
13 Threaded insert 1 Stainless steel 316L/X2CrNiMo17-12-2 EN 10088
1 9 10 5 7 6
14 Bolts s/DN Steel with anticorrosion coating D
DN A B C D H H’ E Weight
mm mm mm mm mm mm mm kg
Standard nstallation
40 108 1490 115 380 250 950 190 21
E
H
50 108 1490 115 380 250 950 190 22
H’
60 108 1490 115 380 250 950 190 22
65 108 1490 115 380 250 950 190 23
3 to 4 DN
80* 128 1550 150 380 270 1050 210 30 L : 1m
100 128 1550 150 380 270 1050 210 31
125 159 2020 180 435 350 1200 230 48
Bottom installation
150 159 2020 180 435 350 1200 230 51
200 230 2310 270 435 400 1500 285 126
H’
250 230 2310 270 435 400 1500 285 130
* DN 80 drilling 4 or 8 holes
Mounting
Check that the emplacement provided for in the wall of the Distance H’ (lever-arm swing) must be respected.
reservoir coincides with the table (especially with respect to If the working pressure is greater than 1 bar, we strongly
distance E, for which only a tolerance of ± 20 mm should be recommend the installation of a stilling well (PVC, steel,
allowed). iron, concrete, asbestos) as shown in figure below.
Before positionning the device, thoroughly flush the The function of this tube is to eliminate too great a
pipeline. The lever arm and float are delivered in kit-form. disturbance of the water-surface upon closing the valve.
For installation at the bottom of the reservoir, use
the complementary kit consisting of: a 4 m stainless steel
chain, two attaching clamps and two hook pieces.
Recommended flow rate / sizing Altitude setting option
Two cases to choose the diameter according to the flow rate: Only for DN 40 to 100, 25 mm step setting.
- When inlet pressure is low (≤ 1 bar) we recommend to size 1273
the float valve according to case 1. Head loss in the fully open
valve will be about 2 m WC.
- When inlet pressure is high, float valves be sized according to
case 2. Head loss will be about 5 m WC.
Setting of 334 to 934
There is a progressive variation in flow rate with respect to the
water-level, from the point where the device is fully open (H’) to
the valve being closed (H) (see Mounting figure).
Flow rates in l/s
DN 40 50 60/65 80 100 125 150 200 250
Case 1 2 3 4 7.5 12 18.5 26.5 47 74
Case 2 3 5 7 12.5 20 31 44 78.5 123
The technical data and performance can be modified
BAYARD without prior notice depending on the technical
Tél. + 33 (0)4 37 44 24 24 - www.bayard.fr evolution.
BAYARD - Series J2 10 - PPHT01-04-056D-EN