PMC-550D Catalogue (20241112S)
PMC-550D Catalogue (20241112S)
www.cet-global.com
PMC-550D LV Motor Protection Relay A Total Solution for LV Motors
Protection Schemes
Electric Fault Protection: Short Circuit, Ground Fault, Residual
Current, LOP, Negative Sequence, MTA Failure, Insulation
Resistance, Thermal Resistance (PTC or NTC), Overvoltage,
Undervoltage, Imbalance, Phase Reversal, etc.
Mechanical Protection: Jam, Long Start, Thermal Overload,
PMC-550D Motor Protection Relay seamlessly Overload, Under Power, Interlock, tE Time, CB Failure, Thermo.,
Block When Start
integrates motor protection, control, tempera-
ture monitoring, and insulation monitoring with a
modular design. Featuring extensive I/O options,
Inputs & Outputs
including 10xDI, 5xDO, 2xRS-485 ports, 1x Analog Digital Input
Standard 10 channels, either externally wetted @ 220VAC/DC
Output, and 1x Residual Current Input, the relay
or internally wetted @ 24VDC based on the model option
offers flexibility and expandability, its modular selected
design allows easy expansion, connecting a Optional 2 additional channels if PMC-KT module is equipped,
standalone HMI module for monitoring and con- dry contact, with 24VDC internally wetted
Status Input or Control Input
trol, a PMC-KT module for additional 6xNTC,
2xDI, and 1xDO for temperature monitoring and Digital Output
Standard 5 channels
I/O control, and a PMC-KR module for ground
Optional one additional channel Form C contact output if the
fault insulation monitoring. The relay supports PMC-KT module is connected
Modbus RTU/PROFIBUS, with PROFIBUS-DP Control and Status Indication
available as an option. Equipped with a robust Analog Output
power supply, it ensures uninterrupted operation 4-20 mA programmable analog output to display the propor-
for 30 seconds during power interruptions. tional DC signal on an external analog meter or DCS system
Selectable analog quantity such as 3-phase Current, Total kW,
These versatile features make the relay suitable
IR and 3I0
for diverse industrial needs.
Optional NTC Input
Motor Start 6 channels NTC Thermistor Input via PMC-KT module for critical
components, such as switches and contactors inside PDU
The PMC-5500D offers generic motor control functions
compartment for long-term operation
like Direct-On-Line, Forward-Reverse and Two-Speed Start
control. It also provides advanced motor starting schemes
to reduce high starting and surge currents to prevent
troublesome voltage dips on the main supply and transient
Communication Options
Standard optically isolated 2xRS-485 port
torque effects in mechanical systems. Use the PMC-550D
Optional 1xPROFIBUS DP port via either DB9 terminal or 3
to facilitate the motor ON/OFF sequence control.
position terminal block and 1xRS-485 port (Modbus RTU)
Applications Optional 1xPROFIBUS DP port either via DB9 terminal or 3
Direct-On-Line Start position terminal block and 1xRS-485 port (either Modbus RTU
Forward-Reverse Start or PROFIBUS DP)
Two-Speed Start Optional 2x10/100BaseT Ethernet port (supporting Modbus
Reduce-Voltage Start (including Star-Delta Start, Auto-Transformer TCP, PROFINET and SNTP) and 1xRS-485 port
Start and Resistance Start)
System Integration
Motor Protection The PMC-550D is supported by CET’s PMC-EasyConfig. In
Electric motors have distinct electrical and mechanical addition, it can be easily integrated into other 3rd party
operation limits. Exceeding these limits may lead to issues Automation or SCADA system because of its multiple commu-
such as mechanical vibration, stoppage, thermal damage, nication ports supporting Modbus RTU and PROFIBUS DP
and ultimately, motor failure. protocol.
PMC-550D LV Motor Protection Relay A Total Solution for LV Motors
Terminal Diagrams
L/+ N/- GND DIC DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 D+/B D-/A L/+ N/- GND DIC DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 D+/B D-/A
A F A F
B G B G
H I J H I J
Expansion Expansion
C C
D D
L P2(10/100M) P3(10/100M) NC NC NC
L
D+ D- SH
K1 M M
K3
P2(RS-485) NC
N N
E E
O O
VA NC VB NC VC NC DO11 D012 DO21 D022 DO31 DO32 DO41 DO42 DO51 DO52 VA NC VB NC VC NC DO11 D012 DO21 D022 DO31 DO32 DO41 DO42 DO51 DO52
L/+ N/- GND DIC DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 D+/B D-/A
A F
B G
A Power Supply H Current Input
H I J
B Chassis Ground I RJ45 connector for remote Display Module (PoE)
RJ45 connector for Expansion Module (PoE)
C LED Indicators J
PMC-KT or PMC-KR (external power source)
C
D Reset Button L Residual Current Input
D E Voltage Input M Analog Output
L F RS-485 Port N Temperature Input
B A DGND
K2 DP
N K1 RS-485 Port K3 10/100BaseT Ethernet Port
E
K2 PROFIBUS DP (either DB9 terminal or 3 position terminal block)
O
VA NC VB NC VC NC DO11 D012 DO21 D022 DO31 DO32 DO41 DO42 DO51 DO52
DIC DI11 DI12 TC11 TC12 TC21 TC22 TC31TC32 L/+ NC N/-
1 1
5
1
PMC-KT PMC-KR
Run Expansion Expansion Run Expansion Expansion
2 2
Comm. 2
Comm.
3 3
4 3
HMI Module
4 5 1 LED Indicators
2 LCD Screen
3 Control Buttons
4 Navigation Buttons
4
Interface
PMC-550D Main Unit Standard Dry contact, internally wetted with 24VDC
Voltage Inputs (VA, VB, VC) Debounce Time 20-9999ms programmable
Standard (Vn) 240VLN/415VLL
TC Input
Range (VLL) 10V to 828V (TC11, TC12, TC21, TC22, TC31, TC32, TC41, TC42, TC51, TC52, TC61, TC62)
Overload 1.2xVn continuous, 2.0xVn for 10s Type NTC
Burden <0.75VA per phase Range 0 to 150 °C
Measurement Category CAT 300VLL
Digital Output (DO61, DO62, DO63)
Frequency 50Hz/60Hz
Type Form C Mechanical Relay
Current Inputs via Plug-in Current Sensor PMC-MTAs (IA, IB, IC, IN) Contact Rating 250VAC/30VDC, 5A
Ie, Rated Motor Current 1A/5A/25A/100A/300A/400A/800A Max. Switching Voltage 277VAC/30VDC
Range 5% to 120% Ie Max. Carrying Current 5A
Overload 2xIe continuous, 10xIe for 10s, 40xIe for 1s Max. Switching Power 1250VA/150W
Burden <0.05VA per phase @ 5A Input Operate Time <10ms
Residual Current Sensor PMC-MIR (·IR, IR) Release Time <10ms
Primary (In) 1A >5,000,000 cycles (Mechanical)
Service Life
Secondary 1V >100,000 cycles (Electrical at rated load)
Internal Clearance/Creepage >6mm (EN61810-1, Pollution Degree 2)
Imax 2In continually
Power Supply (L/+, N/-) Optional PMC-KR Expansion Module
95-250VAC/DC with Enhanced Power Supply (L/+, N/-)
Standard Interface
power supply (ride-through capability) Standard 95-250VAC/DC
Burden <6W Burden <3W
Overvoltage Category OVC 300VLN Insulation Resistance Test (V, G)
Interface
Digital Inputs (DIC, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10) Test Voltage 550VDC/1000VDC
Standard Internally wetted (dry contact) with 24VDC Resistance Range 100kΩ to 100MΩ
Optional Externally wetted with 220VAC/DC
Expansion
Interface
Debounce Time 20-9999ms programmable
Data Transmission RS-485
Relay Outputs
(DO11, DO12, DO21, DO22, DO31, DO32, DO41, DO42, DO51, DO52) Optional PMC-KI Converter Module
DO1 Form B (NC), DO2 Form A (NO) or Voltage Input (1, 2, 3, 4)
Interface
Type
Form B (NC), DO3 to DO5 Form A (NO)
Rated Voltage 110VAC/DC or 220VAC/DC
- DO1 to DO4 DO5 0.45mA (for 110VAC/DC Input)
Rated Current
Contact Rating 250VAC/24VDC, 8A 250VAC/30VDC, 5A or 0.21mA (for 220VAC/DC Input)
Max. Switching Voltage 400VAC/30VDC 277VAC/30VDC Output (5, 6, 7, 8)
Max. Carrying Current 10A 5A Max. Forward Voltage 40V
Max. Switching Power 2000VA/192W 1250VA/150W Max. Forward Current 50mA
Operate Time <10ms <10ms
Environmental Conditions
Release Time <5ms <10ms
Operating Temperature -25°C to 55°C
Mechanical >20,000,000 cycles >5,000,000 cycles
Storage Temperature -25°C to 70°C
Service Life Electrical
>100,000 cycles >100,000 cycles Humidity 5% to 95% non-condensing
(at rated load)
Internal Clearance/Creepage >8mm (EN 61810-1, >6mm (EN 61810-1, Atmospheric Pressure 70kPa to 106kPa
(Safety Insulation < 25VAC) Pollution Degree 3) Pollution Degree 2) Mechanical Characteristics
Analog Output (AO+, AO-) HMI Panel Cutout 54.0x103.0 mm
Load 750 ohms Unit Dimensions 108.0x95.0x122.5 mm
Range 4mA to 20mA IP Rating 40
EMC Compatibility
CE EMC Directive 2014/30/EU (EN 61326: 2021) Standard of Compliance
Immunity Test Safety Requirements
Electrostatic Discharge IEC 61000-4-2: 2009 Level EN 61010-1: 2010 +A1: 2019
CE LVD 2014/35/EU
Radiated Fields IEC 61000-4-3: 2006 +A1: 2008 +A2: 2010 Level EN IEC 61010-2-030: 2021
60
IEC 60255-26: 2013 Class A
on Binary Inputs
Gradual Shut Down/Start-up Tests IEC 60255-26: 2013
Vibration Test (Response/Endurance) IEC 60255-21-1: 1988 Level Main Unit’s 35mm DIN-Rail Installation
Shock Test (Response/Endurance) IEC 60255-21-2 Level
54
Bump Test (Response Endurance) IEC 60255-21-2 Level
Ordering Information
95
35
Language E English
Input Voltage 6 240VLN/415VLL
105
Power Supply A 95-250V AC/DC ±10%, with 30 seconds of ride through
8 5 PMC-MIR-265*103
MTA Model Rated kW Rated Current Hole Ø 1. Additional charges apply for Motor Residual Current Transducers (MIR) and Cables.
2. Connection cables are included with the MIR.
PMC-MTA-1A < 0.4kW 0.2A-1A 10mm 3. The standard cable length for both "Cable" and "Busbar" type MIR is 4m.
PMC-MTA-5A 0.4-2.2kW 1A-5A 10mm Please contact CET.
PMC-MTA-25A 2.2-12.5kW 5A-25A 20mm 4. The Specified Motor Power is based on a 380V system. For other voltage systems,
please use a suitable multiplier based on the actual system voltage (e.g. for a 415V
PMC-MTA-100A 12.5-50kW 25A-100A 30mm
rated motor, multiply the suggested figure by 415/380=1.092).
PMC-MTA-300A 50-150kW 100A-300A 30mm
PMC-MTA-400A-T 120-200kW 240A-400A 55mm
Negative Temeprature Coefficient (NTC) Thermistor
PMC-MTA-800A-T 160-400kW 320A-800A 75mm
Product Code Cable Length B Value
NTC-1041 2m 10000
Current Transducers Accessories
MTA Model Application Range Description 5mm 30mm Dual Wire white Cable (Length=2m/3m/5m/8m)
3-P MTA 3-P Moulded Case 3-Phase MTA can be Pin Terminals in red insulated protective sleeve
Special Cable MTA for PMC-550D connected through this cable
1-P MTA 1-P Moulded Case 3x1-Phase MTA can be
Special Cable MTA for PMC-550D connected through this cable NTC Thermistor 60mm Protective Sleeve
(Insulated by protective sleeve)
1. Additional charges apply for Motor Current Transducers (MTA) and Cables. Note: we also offer insulated NTC Thermistor with a choice of 3m, 5m or 8m cable.
2. The Motor Power mentioned is based on a 380V system. For other voltages,
please use a suitable multiplier based on the actual system voltage (e.g. for a
415V rated motor, multiply the suggested figure by 415/380=1.092).
3. The required type and quantity of MTA Connection Cables must be ordered
separately.
4. The default cable length is 2m, feel free to contact CET for customized cable
lengths.
Our Services
CET has a team of dedicated and proficient Engineering Services personnel
who are ready to provide expert assistance for your system deployment
needs. We are committed in helping our customers create a more secure and
reliable, energy conserving and environmentally friendly electrical power
system. Our team of experts is prepared to provide customized solutions for
your different application needs with timely and efficient services.
Please do not hesitate to contact our sales office or your local representative
for more information.
Email: sales@cet-global.com
Website: www.cet-global.com
V.00 12.11.2024