Conductors & Cables For Electrical Safety & Security
Conductors & Cables For Electrical Safety & Security
TECHNICAL SPECIFICATIONS
SECTION 280513
TABLE OF CONTENTS
SECTION 280513
CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND
SECURITY
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. UTP cabling.
2. Multimode optical fiber cabling.
3. Coaxial cabling.
4. RS-232 cabling.
5. RS-485 cabling.
6. Low-voltage control cabling.
7. Control-circuit conductors.
8. Fire alarm wire and cable.
9. Identification products.
1.3 DEFINITIONS
D. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or
for remote-control and signaling power-limited circuits.
E. Open Cabling: Passing telecommunications cabling through open space (e.g., between the studs
of a wall cavity).
1.For coaxial cable, include the following installation data for each type used:
BIGAR Builders & Developers PLC
Technical Specifications & Methods of
Measurement
CURE CHILDRENS HOSPITAL SECTION - 280513 – Conductors & Cables
For Electronic Safety & Security
Page 3 of 14
A. Qualification Data: For qualified layout technician, installation supervisor, and field inspector.
1. Test optical fiber cable to determine the continuity of the strand end to end. Use [optical
fiber flashlight] [or] [optical loss test set].
2. Test optical fiber cable on reels. Use an optical time domain reflectometer to verify the
cable length and locate cable defects, splices, and connector; include the loss value of
each. Retain test data and include the record in maintenance data.
3. Test each pair of UTP cable for open and short circuits.
A. Do not install conductors and cables that are wet, moisture damaged, or mold damaged.
1. Indications that wire and cables are wet or moisture damaged include, but are not limited
to, discoloration and sagging of factory packing materials.
B. Environmental Limitations: Do not deliver or install UTP, optical fiber, and coaxial cables and
connecting materials until wet work in spaces is complete and dry, and temporary HVAC
system is operating and maintaining ambient temperature and humidity conditions at
occupancy levels during the remainder of the construction period.
PART 2 - PRODUCTS
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in and
NFPA 70, by a qualified testing agency, marked for intended location and application.
2.2 BACKBOARDS
A. UTP Cable Connecting Hardware: IDC type, using modules designed for punch-down caps or
tools. Cables shall be terminated with connecting hardware of the same category or higher.
B. Connecting Blocks: 110-style for Category 5e. Provide blocks for the number of cables
terminated on the block, plus 25 percent spare. Integral with connector bodies, including plugs
and jacks where indicated.
B. Jacket:
A. Cable Connecting Hardware: Meet the Optical Fiber Connector Intermate ability Standards
(FOCIS) specifications of TIA-604-2-B, TIA-604-3-B, and TIA/EIA-604-12. Comply with
TIA/EIA-568-B.3.
1. Quick-connect, simplex and duplex, [Type SC] [Type ST] [Type LC] [Type MT-RJ]
connectors. Insertion loss not more than 0.75 dB.
2. Type SFF connectors may be used in termination racks, panels, and equipment packages.
1. 1.5 sq. mm, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.
2. Double shielded with 100 percent aluminum-foil shield and 60 percent aluminum braid.
3. Jacketed with black PVC or PE.
4. Suitable for indoor installations.
1. 0.6 sq. mm, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.
2. Double shielded with 100 percent aluminum polyester tape and 40 percent aluminum
braid.
3. PVC jacket.
1. 0.6 sq. mm, solid, copper-covered steel conductor; foam fluorinated ethylene propylene
insulation.
2. Double shielded with 100 percent aluminum-foil shield and 65 percent aluminum braid.
3. Copolymer jacket.
G. NFPA and UL Compliance: Coaxial cables shall be listed and labeled by an NRTL acceptable to
authorities having jurisdiction as complying with UL 1655, and with NFPA 70 "Radio and
Television Equipment" and "Community Antenna Television and Radio Distribution" Articles.
Types are as follows:
5. Pairs are cabled on common axis with No. 24 AWG, stranded (7x32) tinned copper
drain wire.
6. Flame Resistance: Comply with UL 1581.
1. Paired, 2 pairs, 0.5 sq. mm, stranded (7x30) tinned copper conductors.
2. Plastic insulation.
3. Individual aluminum foil-polyester tape shielded pairs with 100 percent shield coverage.
4. Plastic jacket.
5. Pairs are cabled on common axis with 0.25 sq. mm, stranded (7x32) tinned copper drain
wire.
6. Flame Resistance: Comply with NFPA 262.
1. Paired, 2 pairs, twisted, 0.25 sq. mm, stranded (7x30) tinned copper conductors.
2. PVC insulation.
3. Unshielded.
4. PVC jacket.
5. Flame Resistance: Comply with UL 1581.
1. Paired, 2 pairs, 0.25 sq. mm, stranded (7x30) tinned copper conductors.
2. Fluorinated ethylene propylene insulation.
3. Unshielded.
4. Fluorinated ethylene propylene jacket.
5. Flame Resistance: NFPA 262, Flame Test.
1. One pair, twisted, 1.5 sq. mm, stranded (19x29) tinned copper conductors.
2. PVC insulation.
3. Unshielded.
4. PVC jacket.
5. Flame Resistance: Comply with UL 1581.
1. One pair, twisted [1.5 sq. mm, stranded (19x29) tinned copper conductors.
2. PVC insulation.
3. Unshielded.
4. PVC jacket.
5. Flame Resistance: Comply with NFPA 262.
A. Class 1 Control Circuits: Stranded copper, Type THHN-THWN, complying with UL 83, in
raceway.
B. Class 2 Control Circuits: Stranded copper, [Type THHN-THWN, complying with UL 83, in
raceway] [power-limited cable, complying with UL 83, concealed in building finishes] [power-
limited tray cable, complying with UL 83, in cable tray] [Type XHHN, complying with UL 44,
in raceway].
C. Class 3 Remote-Control and Signal Circuits: Stranded copper, Type TW or TF, complying with
UL 83.
A. General Wire and Cable Requirements: NRTL listed and labeled as complying with NFPA 70,
Article 760.
B. Signaling Line Circuits: Twisted, shielded pair, not less than 1 sq. mm [size as recommended by
system manufacturer].
1. Circuit Integrity Cable: Twisted shielded pair, NFPA 70, Article 760, Classification CI,
for power-limited fire alarm signal service Type FPL. NRTL listed and labeled as
complying with UL 1424 and UL 2196 for a 2-hour rating.
A. Comply with UL 969 for a system of labeling materials, including label stocks, laminating
adhesives, and inks used by label printers.
A. Testing Agency: Owner will engage a qualified testing agency to evaluate cables.
B. Factory test UTP and optical fiber cables on reels according to TIA/EIA-568-B.1.
D. Factory test multimode optical fiber cables according to TIA-526-14-A and TIA/EIA-568-B.3.
E. Factory sweep test coaxial cables at frequencies from 5 MHz to 1 GHz. Sweep test shall test the
frequency response or attenuation over frequency, of a cable by generating a voltage whose
frequency is varied through the specified frequency range and graphing the results.
F. Cable will be considered defective if it does not pass tests and inspections.
PART 3 - EXECUTION
A. Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems"
for installation of supports for cables.
1. Minimum conduit size shall be 21 mm Control and data transmission wiring shall not
share conduit with other building wiring systems.
2. Comply with requirements in Section 280528 "Pathways for Electronic Safety and
Security."
3. Comply with requirements in Section 260536 "Cable Trays for Electrical Systems."
B. Install cable, concealed in accessible ceilings, walls, and floors when possible.
1. Bundle, lace, and train conductors to terminal points with no excess and without
exceeding manufacturer's limitations on bending radii.
2. Install lacing bars and distribution spools.
3. Separate power-limited and non-power-limited conductors as recommended in writing
by manufacturer.
4. Install conductors parallel with or at right angles to sides and back of enclosure.
5. Connect conductors that are terminated, spliced, or interrupted in any enclosure
associated with intrusion system to terminal blocks.
6. Mark each terminal according to system's wiring diagrams.
7. Make all connections with approved crimp-on terminal spade lugs, pressure-type
terminal blocks, or plug connectors.
D. UTP Cable Installation: Install using techniques, practices, and methods that are consistent with
[Category 5e] [Category 6] rating of components and that ensure [Category 5e] [Category 6]
performance of completed and linked signal paths, end to end.
1. Install outdoor connections in enclosures complying with NEMA 250, Type 4X. Install
corrosion-resistant connectors with properly designed O-rings to keep out moisture.
2. Attach antenna lead-in cable to support structure at intervals not exceeding 915 mm.
G. Open-Cable Installation:
1. Install cabling with horizontal and vertical cable guides in telecommunications spaces
with terminating hardware and interconnection equipment.
2. Suspend copper cable not in a wireway or pathway a minimum of 200 mm above ceilings
by cable supports not more than 1500 mm apart.
3. Cable shall not be run through structural members or in contact with pipes, ducts, or
other potentially damaging items.
2. Install cabling after the flooring system has been installed in raised floor areas.
3. Coil cable shall be neatly coiled not less than 300 mm in diameter below each feed point.
1. Comply with BICSI TDMM and TIA-569-B recommendations for separating unshielded
copper voice and data communication cable from potential EMI sources, including
electrical power lines and equipment.
2. Separation between open communications cables or cables in nonmetallic raceways and
unshielded power conductors and electrical equipment shall be as follows:
4. Separation between cables in grounded metallic raceways and power lines and electrical
equipment located in grounded metallic conduits or enclosures shall be as follows:
5. Separation between Cables and Electrical Motors and Transformers, 5 kVA or HP and
Larger: A minimum of 1200 mm.
6. Separation between Cables and Fluorescent Fixtures: A minimum of 127 mm.
B. Wiring Method: Install wiring in metal raceway according to Section 260533 "Raceways and
Boxes for Electrical Systems."
C. Wiring Method:
1. Cables and raceways used for fire alarm circuits, and equipment control wiring associated
with the fire alarm system, may not contain any other wire or cable.
2. Fire-Rated Cables: Use of 2-hour, fire-rated fire alarm cables, NFPA 70.
3. Signaling Line Circuits: Power-limited fire alarm cables may be installed in the same
cable or raceway as signaling line circuits.
E. Cable Taps: Use numbered terminal strips in junction, pull, and outlet boxes, cabinets, or
equipment enclosures where circuit connections are made.
F. Color-Coding: Color-code fire alarm conductors differently from the normal building power
wiring. Use one color-code for alarm circuit wiring and another for supervisory circuits. Color-
code audible alarm-indicating circuits differently from alarm-initiating circuits. Use different
colors for visible alarm-indicating devices. Paint fire alarm system junction boxes and covers
red.
G. Risers: Install at least two vertical cable risers to serve the fire alarm system. Separate risers in
close proximity to each other with a minimum one-hour-rated wall, so the loss of one riser does
not prevent the receipt or transmission of signals from other floors or zones.
H. Wiring to Remote Alarm Transmitting Device: (25-mm) conduit between the fire alarm control
panel and the transmitter. Install number of conductors and electrical supervision for
connecting wiring as needed to suit monitoring function.
A. 120-V Power Wiring: Install according to Section 260519 "Low-Voltage Electrical Power
Conductors and Cables" unless otherwise indicated.
3.6 CONNECTIONS
A. Comply with requirements in Section 281643 "Perimeter Security Systems" for connecting,
terminating, and identifying wires and cables.
C. Comply with requirements in Section 281300 "Access Control" for connecting, terminating,
and identifying wires and cables.
E. Comply with requirements in Section 284619 "PLC Electronic Detention Monitoring and
Control Systems" for connecting, terminating, and identifying wires and cables.
F. Comply with requirements in Section 283111 "Digital, Addressable Fire-Alarm System for
connecting, terminating, and identifying wires and cables.
G. Comply with requirements in Section 283500 "Refrigerant Detection and Alarm" for
connecting, terminating, and identifying wires and cables.
3.7 FIRESTOPPING
3.8 GROUNDING
A. For communications wiring, comply with J-STD-607-A and with BICSI TDMM, "Grounding,
Bonding, and Electrical Protection" Chapter.
B. For low-voltage wiring and cabling, comply with requirements in Section 260526 "Grounding
and Bonding for Electrical Systems."
3.9 IDENTIFICATION
A. Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply
with requirements for identification specified in Section 260553 "Identification for Electrical
Systems."
A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections.
C. Perform the following tests and inspections with the assistance of a factory-authorized service
representative:
1. Visually inspect UTP and optical fiber cable jacket materials for NRTL certification
markings. Inspect cabling terminations to confirm color-coding for pin assignments, and
inspect cabling connections to confirm compliance with TIA/EIA-568-B.1.
2. Visually inspect cable placement, cable termination, grounding and bonding, equipment
and patch cords, and labeling of all components.
3. Test UTP cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity
between conductors. Test operation of shorting bars in connection blocks. Test cables
after termination but not cross connection.
5. Coaxial Cable Tests: Comply with requirements in Section 274133 "Master Antenna
Television System."
D. Document data for each measurement. Print data for submittals in a summary report that is
formatted using Table 10.1 in BICSI TDMM as a guide, or transfer the data from the
instrument to the computer, save as text files, print, and submit.
E. End-to-end cabling will be considered defective if it does not pass tests and inspections.