This Program is made Possible through the Code Officials Education & Training Fund.
Revenue for the Fund comes from Assessments on Building Permits.
Please turn down cell phones and put pagers on vibrate.
Thank you
Potable Water Supply & Distributio n
Water Required
Structures for Human Occupancy
With plumbing fixtures
Shall be supplied with Potable Water
Potable vs. Nonpotable Water
Potable Definition
Water free from impurities present in amounts sufficient to cause disease or harmful physiological effects and conforming to the bacteriological and chemical quality requirements of the Public Health Service Drinking Water Standards or the regulations of the Public Health Authority having jurisdiction. jurisdiction.
Potable Water Required Section 602.2
To all fixtures supplying water for:
Drinking or Bathing Culinary or Food Processing Medical or Pharmaceutical products
Nonpotable Definition
Water not safe for drinking, personal or culinary utilization.
Definitions
Pollution
An impairment of the quality of the potable water to a degree that does not create a hazard to the public health but that does adversely and unreasonably affect the aesthetic qualities of such potable water for domestic use.
Water Supply vs Distribution
Water Supply System
The water service pipe, water distribution pipes, and the necessary connecting pipes, fittings, control valves and all appurtenances in or adjacent to the structure or premises
Water Service Pipe
The pipe from the water main or other source of potable water supply, or from the meter when the meter is at the public right of way, to the water distribution system of the building served
Water Distribution Pipe
A pipe within the structure or on the premises that conveys water from the water service pipe, or from the meter when the meter is at the structure, to the points of utilization
Water Supply & Distribution
Chapter 6
Protection & Trenching
Section 305 Protection Of Pipes & Plumbing System Components
Freezing & Sewer Depth subject to amendment
With present 48 deep for water 48 servicing piping To the top of the pipe
WATE R SUPPL Y
WATER SERVICE
Water Service Separation
Separation Of Water Service & Building Sewer Section 603.2
Two additions to the Exceptions Material from Table702.2 Water pipe crosses sewer and is sleeved
Five foot horizontally each side of sewer center line
BUILDING SEWER IN SEPARATE TRENCH 5 MINIMUM
Separation of Water Service & Building Sewer
UNEXCAVATED OR COMPACTED EARTH SEPARTING TRENCHES COMMON TRENCH
12 MIN.
WATER SERVICE
BUILDING SEWER
WATER SERVICE IN SEPARATE TRENCH
Appendix E
Sizing of Water Piping System
E101.1.1
Two procedures for water piping sizing
E103.3 Segmented loss method E201.1 Size of water-service mains, branch watermains and risers
Definition
Fixture Unit, Water-Supply Waterw.s.f.u.
A measure of the probable hydraulic demand on the water supply by various types of plumbing fixtures used to size water-piping systems. The waterwaterwatersupply fixture-unit value for a fixtureparticular fixture depends on its volume rate of supply on the time duration of a single supply operation and on the average time between successive operations.
From 2003 IRC definitions
Procedures based upon
Minimum static pressure System head charges
Friction & elevation
Necessary rate of flow
Definition
Drainage Fixture Unit (dfu)
A measure of the probable discharge into the drainage system by various types of plumbing fixtures. The drainage fixture-unit fixturevalue for a particular fixture depends on its volume rate of drainage discharge, on the time duration of a single drainage operation and on the average time between successive operations.
From the 2003 IPC / Chapter 2 Definitions
See next page of Handout for actual Table
Table 604.3
Water Distribution System Design Criteria Required Capacities At Fixture Supply Pipe Outlets
FIXTURE SUPPLY OUTLET SERVING FLOW RATE a GPM
Bathtub 8 Combination Fixture 8 Lavatory 8 Shower, temperature controlled 20 Water closet, tank, one piece 20 4 4
FLOW PRESSURE (psi)
Note: Slide is only a representation of Table 604.3
See next page of Handout for actual Table
Water Supply Connection With Reduced Size Flexible
Supply
Section 604.5
See next page of Handout for actual Table!
Table 604.5
Minimum Sizes Of Fixture Water Supply Pipes
FIXTURE PIPE SIZE (inch) Bathtubs (larger than 60 x 32) 1/2 Drinking fountain 3/8 Sinks, flushing rim
MINIMUM
3/4
Water closet, flush valve Water closet, flushometer tank 3/8
Note: Slide is a representation of Table 604.5
See next page of Handout for actual Table!
Application Sizing Water Service Pipe
Using The Following Information
Piping material
Type L copper
Using Table E103.3(2)
For estimating demand
Convert total building demand to flow rate in gallons
Water closets
Flush tanks
Total fixture demand
30 wsfu
Velocity to be maintained
10 ft / sec
Water service
No elevation change 100 ft water main to meter 90 psi M
Public Water Main
Sizing Water Service Pipe
Using Table E103.3(3)
For estimating demand
Convert total building demand to flow rate in gallons
30 wfsu = 23.3 gpm
Using Figure E103.3(3)
Determine smallest pipe size to convey
23.3 gpm/ velocity no greater than 10ft/sec gpm/
30 wfsu = 23.3 gpm
Sizing Water Service Pipe
Using Table E103.3(3)
For estimating demand
1 pipe @ approximate ly 9 feet per sec velocity
Convert total building demand to flow rate in gallons
30 wfsu = 23.3 gpm
23.3 gpm
Using Figure E103.3(3)
Determine smallest pipe size to convey
23.3 gpm/ velocity no greater than 10ft/sec gpm/
1 inch diameter pipe / @ 23.3 gpm @ 9 feet/ second
Determining Pressure Loss
Using Figure E 103.3(3)
At point of intersection with 1 inch Type L
Draw a vertical line and read/ interpolate
Bottom horizontal reading
23.3 gpm 1 pipe @ approximate ly 9 feet per sec velocity
1 pipe/ 100 100 length = pressure drop of 12 psi
Determining Pressure Loss
Using Figure E 103.3(3)
At point of intersection with 1 inch Type L
Draw a vertical line and read/ interpolate
Bottom horizontal reading 23.3 gpm / 10 ft/sec / 100 ft of 1 inch Type L Copper = pressure drop of 12 psi
Water Supply & Distribution
Tests Section 601.4
Potable water system testing As per
Section 312.5
Water Supply System Test Section 312.5 Test under water pressure
No less than working pressure
Calculate pressure loss
90 psi - 12 psi = 78 psi
Or air test, when other than plastic
Not less than 50 psi
Table 604.4
Water Distribution System Design
General - Section 604.1
Shall conform to accepted engineering practice
Maximum Flow Rates & Consumption For Plumbing Fixtures & Fixture Fittings
PLUMBING FIXTURE OR FIXTURE FITTING
Lavatory, private 60 psi Lavatory, public (metering) metering cycle Lavatory, public (other than metering)
MAXIMUM FLOW RATE OR QUANTITY
2.2 gpm at 0.25 gallon per
System Interconnection - Section 604.2
Provisions shall be made to
Prevent flow between hot and cold water at fixtures and devices
0.5 gpm at 60 psi
NOTE: 1. Slide is a representation of Table 604.4
Booster Systems
Water Pressure Booster System Required - Section 606.5.1
Water pressure insufficient for minimum pressures
Supply shall be supplemented
Support - Section 606.5.2
Water tanks shall be supported as per IBC
See next page of Handout for actual Table!
Pressure Control
Low-Pressure LowCutoff Required on Booster Pumps Low Pressure Section 606.5.5 Cutoff
Installed to prevent creation
Of a negative pressure on the suction
Prevents operation when
Supply pressure at inlet is less than 10psi
See next page of Handout for actual Table!
Valving Requirements
Section 606.1
DWELLIN G UNIT VALVE
MAIN WATER DISTRIBUTION PIPE
WATER SERVICE
STREET, ALLEY OR OTHER RIGHT-OFWAY
See next page of Handout for actual Table!
WATER METER METER VALVE SERVICE VALVE
CURB VALVE ON WATER SUPPLY KEY OPERATED
Shutoff Valves
Location Of Shutoff Valves Section 606.2
To be installed Fixture supply to each plumbing fixture Not bathtub & shower Water supply to each Sillcock & appliance
2-Piece, Full Port, Brass Ball Valves
Access To Valves - Section 606.3
To be provided to all Full open and shutoff valves
Stop Valves With Threaded Ends
Temperature Maintenance
Hot Water Supply System
Access & Identification
Access To Valves Section 606.3
Shall be provided to all required valving
Where Required Section 607.1
Residential Occupancies
Hot water to be supplied to all fixtures Bathing, washing, culinary, cleansing, laundry & building maintenance
Valve Identification Section 606.4
Service & hose bibb valves
Shall be identified
Non-Residential Occupancies Non Hot water to be supplied to all fixtures for culinary, cleansing, laundry, building maintenance Hot or tempered water for bathing & washing
Identification of valves in locations
Not adjacent to fixture
Thermal Expansion & Pressure Control
Fixture Flow
Flow Of Hot Water To Fixtures - Section 607.4
Pressure Reducing Valve Section 607.3.1
Systems up to 2 inch When thermal expansion causes pressure increase downstream Pressure reducing valve
Will ensure system longevity
Fixtures, faucets & diverters to be
Installed and adjusted for flow of hot water
To correspond to the left-hand leftside of the fixture fitting
Exception
Shower & tub mixing valves With hot water flow markings on the device
Water Heaters
Water Heater Labeling Section 501.5
Shall be third party certified
Relief Valves
ANSI Z21.22
Temperature rating of not more than 210 degrees F. Pressure setting not to exceed tank rating Rating not greater than 150 psi
Water Temperature Control In Piping From Tankless Heaters - Section 501.6
Maximum temperature of 140 degrees F.
When used for domestic purposes
Installed within shell of water heater and located within the top 6 inches of the tank
What do you mean that I am defeating its purpose?????
Relief Valve Discharge
Discharge - Section 504.6.1
Full size to safe place Outlet no
Threads, Valves, Tees
Required Pan - Section 504.7
If leakage can cause damage
Install in a galvanized steel pan
Or other approved pan
Potable & Nonpotable Water
Identification Of Potable & Nonpotable Water Section 608.8
Buildings with potable & nonpotable systems
Each system shall be identified
Color & Sizing
Color - Section 608.8.2
Color for piping identification
To be discernable and consistent
Information - Section 608.8.1
Piping identification shall include
Contents, Direction of flow, Hazard Identification to repeat at intervals of every 25 feet
Size - Section 608.8.3
Color field and lettering
To comply with Table 608.8.3
See next page for copy of Table
Table 608.1
Application Of Backflow Preventers
DEVICE APPLICABLE STANDARDS DEGREE OF APPLICATION HAZARD
Air gap fittings for use with plumbing fixtures, appliances & appurtenances
High or Low Hazard
Backsiphonage or backpressure
ASME A112.1.3
Antisiphon-type fill Antisiphonvalves for gravity water closet flush tanks
High hazard
Backsiphonage only
ASME 1002, CSACSAB125
Backflow preventer for carbonated beverage machines
Low hazard
Backpressure or backsiphonage Sizes 1/4-1 1/4inch
ASSE 1022
NOTE: 1. Table shows some of the areas and applications 2. Slide is representative of Table 608.1
See next page of Handout for actual Table!
Backflow Prevention
Protection Against Backflow
Backflow Protection Section 608.13
The following slides are applications of backflow prevention
With everyday application
A means of protection from backflow
Shall be provided
Air Gap Section 608.13.1
Minimum to be measured vertically
From lowest end of a potable water outlet To the flood level rim
Table 608.15.1
Minimum Required Air Gaps
Backflow Protection
Air Gap - Section 608.13.1 Backflow Preventers : Miscellaneous Products : Air Gap Drain
10
Backflow Protection
Reduced Pressure Principle Backflow Preventers - Section 608.13.2 Backflow Preventers : Reduced Pressure Principle
Backflow Protection
Pressure Type Vacuum Breaker - Section 608.13.5
Backflow Prevention
Atmospheric Type Vacuum Breakers - Section 608.13.6
Backflow Prevention
Double Check Valve Assemblies - Section 608.13.7
11
Backflow Preventers : Double Check Valves
Double Check Detector Assembly
Backflow Protection
Spillproof Vacuum Breakers Section 608.13.8
See next page for actual copy of Table!
Measurement From Flood Level Rim To Effective Opening
Backflow Protection
Protection By Vacuum Breaker - Section 608.15.4
When protection is by atmospheric or pressure type vacuum breaker
Critical level is to be set minimum of 6 above 6 The flood level rim
Deck-Mounted & Integral DeckVacuum Breakers Section 608.15.4.1
Install per MFG Installation Instructions
12
Silcocks, Hose Bibbs
:
Backflow Preventers : Vacuum Breakers :
Hose Connections Section 608.15.4.2
Openings with hose connections
Protection to be by Atmospheric or pressure type vacuum breaker or permanently attached Hose connection vacuum breaker
Exceptions
Does not apply to water heater & boiler drains With hose threads Does not apply to water valves for clothes washing machines
Problem we are trying to avoid!!!
Connection To Potable Water System
Beverage Dispensers Section 608.16.1
Connection to carbonated beverage dispenser
Protection to be by a backflow preventer or air gap
Carbon dioxide gas
Is not to affect Piping downstream or the backflow preventer
13
Backflow Preventers : Miscellaneous Products
Dual Check Vacuum Breakers for Vending Machine Water Supply Lines
Boilers & Heat Exchangers
Connection To Boilers Section 608.16.2
To be equipped with
Backflow preventer / intermediate atmospheric vent
Dual Controls (Regulator and Relief Valve)
System with conditioning chemicals
Connection by air gap or reduced pressure principle backflow
Heat Exchangers Section 608.16.3
Essentially Toxic transfer fluid
Separation to be by double-wall doubleconstruction
With air gap open to atmosphere between walls
Nontoxic transfer fluid
Single wall construction may be used
Fire Sprinkler Systems
Connections To Automatic Fire Sprinkler Systems & Standpipe Systems Section 608.16.4 Protection to be obtained from
Double check-valve assembly or checkreduced principle backflow preventer
14
Fire Sprinkler Systems
Additives Or Nonpotable Source Section 608.16.4.1
Systems under continuous pressure containing
Chemical additives or antifreeze To be protected by Reduced pressure principle backflow preventer
Double Check Valve Assemblies, Cast Iron
Wall Hydrant With AntiAntiSiphon, Vacuum Breaker, Automatic Draining
Reduced Pressure Detector Assemblies, Stainless Steel
Reduced Pressure Zone Assemblies, Bronze
Automatic Washers
Water Connection Section 406.2
Water supply to be protected from backflow
Air gap is to be integral with the machine as per ASSE 1007 If installation of backflow preventer is necessary To be installed as per section 608 of this code
Dishwasher Connections
KITCHEN SINK
LOOP REQUIRED PER MANUFACTURERS INSTRUCTIONS
KITCHEN SINK
BRANCH TAILPIECE OF DISHWASHER TAILPIECE TO RECEIVE DISHWASHER WASTE CONNECTION MAY CONNECT DIRECTLY TO FOOD WASTE DISPOSER DISHWASHER
15
Flushing Devices
Flushing Devices Required Section 425.1
Water closet, urinal & trap type plumbing fixture
To be designed & installed to supply water
Bidets
Water Connection Section 408.2
Water supply to be protected
By an air gap or backflow preventer
Fill Valves Section 425.3.1
Flush tanks to be equipped with
Antisiphon fill valve Minimum 1 above 1 overflow
Installation to be in accordance with
Section 608.13
Water Supplies
Individual Water Supplies Section 602.3
To be used when a public water supply is not available Sources - Section 602.3.1
Wells Springs Streams or Cisterns NOTE
For Protection of Individual Water Supplies See Public Health Code / CGS 19a-36 19a-
Individual Water Supplies
Protection Of Individual Water Supplies - Section 608.17 (as amended)
An individual water supply shall be located and constructed so as to be safeguarded against contamination in accordance with the Public Health Code of the State of Connecticut adopted pursuant to Section 19a-36 19aof the Connecticut General Statutes
Water Quality
Individual Water Supplies
Quality to be approved by AHJ
System Disinfection
When Does A System Need To Be Disinfected?
General Section 610.1 New or repaired potable water systems shall be purged of deleterious matter and disinfected prior to utilization. Method of disinfection to be as prescribed by The Health Authority or Water Purveyor having jurisdiction
Disinfection of System Section 602.3.4
To be done after construction or major repair As per section 610 or as prescribed by the Health Authority
Pumps - Section 602.3.5
To be rated for Potable Water transfer
16
System Disinfection
Procedure For Disinfection
When no prescribed method exists
Procedure described in
AWWA C651 or AWWA C652
Piping Material
Water Service Pipe Section 605.3
To conform to
NSF 61 & Table 605.3
Or as described in this section
Pipe to be flushed with clean potable water Water chlorine solution / let stand 24 hr
50 parts per million minimum Or {200 parts per million for 3 hr}
Underground piping standards
To have a minimum pressure rating
Of 160 psi @ 73.4 degrees F
Flush to remove chlorine Repeat if contamination remains
Plastic pipe to terminate within 5 feet
Inside of exterior wall or slab penetration
Table 605.3
Water Service Pipe
MATERIAL
STANDARD
Stainless steel pipe (Type 304/304L)
ASTM A 312; ASTM A 778
Stainless steel pipe (Type 316/316L)
ASTM A 312; ASTM A 778
NOTE: 1. Table is only representative of the two areas within this table 2. Slide is representative of Table 605.3
See page of Handout for actual Table!
Table 605.4 Water Distribution Pipe
MATERIAL STANDARD
Polyethylene/ Aluminum/ Polyethylene (PE-AL-PE) (PE- ALcomposite pipe
ASTM F 1282
Stainless steel pipe (Type 304/304L)
ASTM A 312; ASTM A 778
Stainless steel pipe (Type 316/ 316L) A 778
ASTM A 312; ASTM
NOTE:
1. Table is only representative of the three areas within this table 2. Slide is representative of Table 605.4
See next page of Handout for actual Table!
17
Soil & Ground Water
Table 605.5 Pipe Fittings
MATERIAL STANDARD
Fittings for cross-linked polyethylene (PEX) plastic tubing 1960, ASTM F 2080 ASTM F 1807, ASTM F
Metal (brass) insert fittings for Polyethylene/Aluminum/Polyethyl ene (PE-AL-PE) & Cross-linked Polyethylene/ Aluminum/Polyethylene (PEXAL-PEX)
ASTM F 1974
Stainless steel (Type 304/304L)
ASTM A 312; ASTM A 778
Stainless steel (Type 316/316L)
ASTM A 312; ASTM A 778
NOTE: 1. Table shows four areas of this code 2. Slide is representative of Table 605.5
Additional Elements
Flexible Water Connectors Section 605.6
When exposed to continuous pressure
Shall conform to ASME A112.18.6
Valves - Section 605.7
Valves to be of an approved type
Compatible with system piping
Manufactured Pipe Nipples Section 605.8
To conform to the standards of
Table 605.8
See next page of Handout for actual Table!
Prohibited Joints & Connections
Cement or Concrete Joints
Do not effectively seal
Fittings Not Approved For The Installation
May cause premature failure
Solvent Cement Between Different Types of Plastic
Chemical composition is different
Improper bonding
Saddle Type Fittings
Flow reduction
Possible shifting if subject to impact See next page of Handout for actual Table!
18
Backflow Protection
Devices, Appurtenances, Appliances & Apparatus Section 608.3
Serving special functions
Shall be provided with backflow protection
Inspection And Testing Of Backflow Prevention Assemblies
Section 312.9
Inspection As Per
Sections 312.9.1 & 312.9.2
312.9.1 Inspections / IS DELETED BY 05 CT Supplement
Special Equipment, Water Supply Protection - Section 608.3.1
Hospital fixtures
Shall be protected against backflow
Section 312.9.2 Testing / IS AMENDED BY
05 CT Supplement Test at time of installation Owners responsibility to have tests performed
By properly qualified individuals or agencies
Chemicals & Cross Connection
Chemicals & Other Substances Section 608.5
Substances that produce toxic conditions
Shall not be introduced into the system
Reutilization
Reutilization Prohibited Section 608.9
Cooling and process water
Shall not be returned to the potable water system
Cross-Connection Control - Section Cross608.6
Cross connection is prohibited
Except where approved backflow protective means are installed
Reuse Of Piping - Section 608.10
Piping previously utilized for any purpose
Other than potable water
Not to be used for potable water
Private Water Supplies - Section 608.6.1
Cross connection of
Private to public water supply is prohibited
Hospital Water Service
Section 609.2
Health Care
Hot Water - Section 609.3
To be supplied to all equipment
Temperature shall be as specified by equipment manufacturer
Prohibited Water Closet & Clinical Sink Supply - Section 609.5
Jet or water supplied orifices
Not to be connected with water closet or clinical sink
19
Additional Chapter Sections
Drinking Water Treatment - Section 611
Design Section 611.1
To meet requirements of
NSF 42, 44, 53 or 62
Water Supply & Distribution
Additional Areas Of Concern
Solar Water Service Grounding Pressure Reducing Valves Manifold Systems
Solar Systems Section 612
All construction, installation, alteration & repair
To be in accordance with IMC To comply with ASSE 1017
Solar
Solar Energy Utilization Section 601.2
When used to heat potable water or
Using an independent medium
Water Service For Grounding
Existing Piping Used For Grounding Section 601.3
No replacement of existing with nonmetallic pipe
Until approved means of grounding is provided
It shall not compromise
Cross connection requirements Potable water supply
Reducing Valve or Regulator
Water Pressure Reducing Valve or Regulator - Section 604.8
For water pressure exceeding
80 psi static
Water Hammer
Water Hammer Section 604.9
To be installed
Where quick closing valves are utilized
Install per MFG installation instructions
Installation to reduce pressure in building water distribution
To 80 psi or less
20
Parallel System Manifolds
Parallel Water Distribution System Manifolds - Section 604.10
Hot and cold water manifolds connected in parallel System sizing
As per Table 604.10.1
Total gallons per minute is the demand of all outlets supplied
All individual fixture shutoff valves
Installed at the manifold shall be identified See next page of Handout for actual Table!
Pressure Balancing
Individual Pressure Balancing InInLine Valves for Individual Fixture Fittings Section 604.11
If installed they are to comply with
ASSE 1066
Board Of Health Concerns
Questions Asked By Audience Regarding Well pump wiring and application of the NEC
Installation to be accessible Not to be used alone for substitution of
Balanced pressure, thermostatic or combination shower valves
Well Pump Wiring
2005 National Electrical Code
NFPA 70
Does not breakdown the code into a well wiring section. Numerous sections of the code are used for installation. Complexity being dependent upon application. Such as wiring for a submersible well pump
Well Pump Wiring
Common Wiring Violations
Use of existing water pipe for electrical conduit
Not following code section 110.8
Of the 05 NEC
Use of non-listed piping for nonelectrical wires
Code Section 110.8
Of the 05 NEC
Omission of equipment grounding conductor to the pump
Code Section 250.4(A)3 & (A)5
Of the 05 NEC
21
Wiring Problems
Continuation Of Prior Slide
Failure to bond the well casing
Section 250.4(A)(4)
Of the 05 NEC
QUESTIONS ??
Use of single sleeve to well shaft from building that includes both wires and water pipe
Sections 300.8 and 300.10
Of the 05 NEC
22