Product datasheet
Specifications
Motor circuit breaker, TeSys GV2,
3P, 24-32 A, thermal magnetic,
screw clamp terminals
GV2ME32
Main
Range TeSys Deca
Product name TeSys GV2
Product or component type Motor circuit breaker
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device short name GV2ME
Device application Motor protection
Trip unit technology Thermal-magnetic
Complementary
Poles description 3P
Network type AC
Utilisation category Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-2
Motor power kW 15 kW at 400/415 V AC 50/60 Hz
18.5 kW at 500 V AC 50/60 Hz
22 kW at 690 V AC 50/60 Hz
Breaking capacity 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type Push-button
[In] rated current 32 A
Thermal protection adjustment 24…32 A conforming to IEC 60947-2
range
Magnetic tripping current 537.6 A
[Ith] conventional free air thermal 32 A conforming to IEC 60947-2
current
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand 6 kV conforming to IEC 60947-2
voltage
Phase failure sensitivity Yes conforming to IEC 60947-4-1
Suitability for isolation Yes conforming to IEC 60947-1
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Jul 12, 2025 1
Power dissipation per pole 2.5 W
Mechanical durability 100000 cycles
Electrical durability 100000 cycles for AC-3 at 415 V In
100000 cycles for AC-3e at 415 V In
Rated duty Uninterrupted conforming to IEC 60947-4-1
Connections - terminals Power circuit: screw clamp terminal 2 cable(s) 1…6 mm²solid
Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm²flexible without cable end
Power circuit: screw clamp terminal 2 cable(s) 1…4 mm²flexible with cable end
Tightening torque 1.7 N.m - on screw clamp terminal
Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
Mounting position Horizontal
Vertical
Width 45 mm
Height 89 mm
Depth 78.5 mm
Net weight 0.26 kg
Colour Dark grey
Environment
Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC/EN 60335-2-40:Annex JJ
IEC/EN 60335-1:Clause 30.2
Product certifications CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
IK degree of protection IK04
IP degree of protection IP20 conforming to IEC 60529
Climatic withstand conforming to IACS E10
Ambient air temperature for -40…80 °C
storage
Fire resistance 960 °C conforming to IEC 60695-2-11
Ambient air temperature for -20…60 °C
operation
Mechanical robustness Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz
Operating altitude <= 2000 m
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 9.300 cm
Package 1 Width 4.800 cm
2 Jul 12, 2025
Package 1 Length 8.500 cm
Package 1 Weight 280.000 g
Unit Type of Package 2 S02
Number of Units in Package 2 24
Package 2 Height 15.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 7.022 kg
Unit Type of Package 3 P06
Number of Units in Package 3 384
Package 3 Height 75.000 cm
Package 3 Width 60.000 cm
Package 3 Length 80.000 cm
Package 3 Weight 120.352 kg
Contractual warranty
Warranty 18 months
Jul 12, 2025 3
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) 43
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled cardboard Yes
Packaging without single use plastic No
EU RoHS Directive Compliant with Exemptions
SCIP Number 04104e70-ba29-493c-b2cc-b5837d1f879b
REACh Regulation REACh Declaration
Use Again
Repack and remanufacture
Circularity Profile End of Life Information
Take-back No
The product must be disposed on European Union
WEEE markets following specific waste collection and never end
up in rubbish bins
4 Jul 12, 2025
Product datasheet GV2ME32
Performance Curves
Thermal-Magnetic Tripping Curves for GV2ME and GV2P
Average Operating Times at 20 °C Related to Multiples of the Setting Current
1 3 poles from cold state
2 2 poles from cold state
3 3 poles from hot state
Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))
Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
Jul 12, 2025 5
Product datasheet GV2ME32
1 Maximum peak current
2 24-32 A
3 20-25 A
4 17-23 A
5 13-18 A
6 9-14 A
7 6-10 A
8 4-6.3 A
9 2.5-4 A
10 1.6-2.5 A
11 1-1.6 A
12 Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).
Thermal Limit on Short-Circuit for GV2ME
Thermal Limit in kA2s in the Magnetic Operating Zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
6 Jul 12, 2025
Product datasheet GV2ME32
1 24-32 A
2 20-25 A
3 17-23 A
4 13-18 A
5 9-14 A
6 6-10 A
7 4-6.3 A
8 2.5-4 A
9 1.6-2.5 A
10 1-1.6 A
Jul 12, 2025 7
Product datasheet GV2ME32
Dimensions Drawings
Dimension
GV2ME
(1) Maximum
X1 Electrical clearance = 40 mm for Ue ≤ 690 V
GV2ME●● 89
GV2ME●●3 101
Mounting
GV2ME
On 35 mm rail
c = 78.5 on AM1 DP200 (35 x 7.5)
c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02
On pre-slotted plate AM1 PA
On rails DZ5 MB201
8 Jul 12, 2025
Product datasheet GV2ME32
GV2AF01
Combination GV2ME + TeSys k contactor
GV2AF3
Combination GV2ME + TeSys d contactor
GV2ME + LC1D09…D18 LC1D25 and D32
b 176.4 186.8
c1 94.1 100.4
c 99.6 105.9
GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor
Jul 12, 2025 9
Product datasheet GV2ME32
GV2ME + LC1D09…D18 LC1D25 and D32
b 176.4 186.8
c1 103.1 136.4
c 135.6 141.9
d1 107 107
d 112.5 112.5
GV2ME + GV1L3 (Current Limiter)
X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V
10 Jul 12, 2025
Product datasheet GV2ME32
Connections and Schema
GV2ME•• and GV2RT
Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only
Jul 12, 2025 11
Product datasheet GV2ME32
Technical Illustration
Wiring diagram
GV2ME��
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
REFER TO TECHNICAL DRAWINGS AND DOCUMENTATION FOR COMPLETE INFORMATION.
12 Jul 12, 2025
Product datasheet GV2ME32
Image of product / Alternate images
Alternative
Jul 12, 2025 13
Product datasheet GV2ME32
14 Jul 12, 2025
Product datasheet GV2ME32
Jul 12, 2025 15