NEC Standard Electrical Load Calculation for Single Family Dwellings
(Only for Service Ratings of 120/240V, 225 Amps Max)
Owner: TOMER AVITAL Location: 6744 MULLHOLLAND DR, CA
Total Floor Area of Dwelling (NEC 220.12) 4972 SQFT.
Factor Quantity Volt Amperes
(VA)
“General Lighting”
1. General Lighting (SQFT X 3 VA/SQ FT (Table 220.12) 3 X 4972 sqft. 14916
2. Small Appliance Circuits (1500 VA per circuit) (NEC 1500 X 2 3000
220.52(A)) (minimum 2)
3. Laundry Circuit (1500 VA per circuit) (NEC 220.52(B)) 1500 X 2 3000
4. Total General Lighting Load (Add lines 1, 2 & 3): 20916
5. First 3000 VA @ 100%: 3000
6. Total General Lighting Load – 3000 = 17916 @ 35%= 6271
7. Net General Lighting Load (Per NEC 220.42) (Add lines 5 & 6): 9271
*Fixed Appliances(if insufficient space, use back): YES NO
Garbage Disposal ✔ 1400
Bathroom Fan ✔ 300
Microwave ✔ 1800
Dishwasher ✔ 1500
Other: Refrigerator ✔ 800
Other: Smoke and Carbon Monooxide Detector ✔ 200
Total 6000
8. 3 or less Appliances, Total Appliance VA;
4500
4 or more Appliances, 75% of Total Appliance VA (NEC 220.53):
Nameplate Rating
*Other Loads (including motors, EV charger(s), etc.) YES NO
(VA)
9. Electric Range (8000VA or Nameplate)** ✔
10. HVAC ✔ 14019
11. Electric Oven
12. Electric Dryer (5000 VA minimum)**
13. Electric Vehicle Charger ✔ 0
14. Other: Water Heater (Gas) ✔ 100
15. Other: ✔
16. 25% of largest motor (NEC 430.24) 3504
Total Service Load Volt-Amperes (VA) (Add lines 7, 8 & 9 thru 16) = 32194
Total Service Load Volt-Amperes / 240-volts = 134 Amperes
***Service Rating (Amperes)= 200
* For every “YES” answer, indicate VA rating of equipment
** Nameplate rating must be used if larger
*** Service Rating shall be greater than or equal to the Service load