Load Calculation California

The document outlines the NEC standard electrical load calculation for a single-family dwelling owned by Tomer Avital, located at 6744 Mullholland Dr, CA. It details the total floor area, general lighting load, fixed appliances, and other loads, culminating in a total service load of 32,194 VA, which equates to 134 Amperes. The service rating for the dwelling is noted as 200 Amperes, ensuring it meets the required standards.

Uploaded by

reduanzx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views1 page

Load Calculation California

The document outlines the NEC standard electrical load calculation for a single-family dwelling owned by Tomer Avital, located at 6744 Mullholland Dr, CA. It details the total floor area, general lighting load, fixed appliances, and other loads, culminating in a total service load of 32,194 VA, which equates to 134 Amperes. The service rating for the dwelling is noted as 200 Amperes, ensuring it meets the required standards.

Uploaded by

reduanzx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NEC Standard Electrical Load Calculation for Single Family Dwellings

(Only for Service Ratings of 120/240V, 225 Amps Max)

Owner: TOMER AVITAL Location: 6744 MULLHOLLAND DR, CA

Total Floor Area of Dwelling (NEC 220.12) 4972 SQFT.

Factor Quantity Volt Amperes


(VA)
“General Lighting”
1. General Lighting (SQFT X 3 VA/SQ FT (Table 220.12) 3 X 4972 sqft. 14916
2. Small Appliance Circuits (1500 VA per circuit) (NEC 1500 X 2 3000
220.52(A)) (minimum 2)
3. Laundry Circuit (1500 VA per circuit) (NEC 220.52(B)) 1500 X 2 3000
4. Total General Lighting Load (Add lines 1, 2 & 3): 20916
5. First 3000 VA @ 100%: 3000
6. Total General Lighting Load – 3000 = 17916 @ 35%= 6271
7. Net General Lighting Load (Per NEC 220.42) (Add lines 5 & 6): 9271

*Fixed Appliances(if insufficient space, use back): YES NO


 Garbage Disposal ✔ 1400
 Bathroom Fan ✔ 300
 Microwave ✔ 1800
 Dishwasher ✔ 1500
 Other: Refrigerator ✔ 800
 Other: Smoke and Carbon Monooxide Detector ✔ 200
Total 6000
8. 3 or less Appliances, Total Appliance VA;
4500
4 or more Appliances, 75% of Total Appliance VA (NEC 220.53):

Nameplate Rating
*Other Loads (including motors, EV charger(s), etc.) YES NO
(VA)
9. Electric Range (8000VA or Nameplate)** ✔

10. HVAC ✔ 14019


11. Electric Oven
12. Electric Dryer (5000 VA minimum)**
13. Electric Vehicle Charger ✔ 0
14. Other: Water Heater (Gas) ✔ 100
15. Other: ✔

16. 25% of largest motor (NEC 430.24) 3504


Total Service Load Volt-Amperes (VA) (Add lines 7, 8 & 9 thru 16) = 32194
Total Service Load Volt-Amperes / 240-volts = 134 Amperes

***Service Rating (Amperes)= 200


* For every “YES” answer, indicate VA rating of equipment
** Nameplate rating must be used if larger
*** Service Rating shall be greater than or equal to the Service load