AP Application Information Mersen en
AP Application Information Mersen en
Information
NEED TO KNOW HOW?
YOU’VE TURNED TO THE
RIGHT PLACE...LITERALLY
• Definitions . . . . . . . . . . . . . . . . AP 2
Your problem: Whether your objective • Fuse Descriptions . . . . . . . . . . AP 4
is optimum protection of motor • Fuse Construction &
control equipment, power or control Operation . . . . . . . . . . . . . . . . . AP 4
transformers, cable wiring, or lighting and • How to Read a
heating circuits — you need fast, accurate Time Current Curve . . . . . . . . AP 5
information to do the job right. Problem • Low Voltage
is, not all electrical pros have the same Motor Protection . . . . . . . . . . AP 6
familiarity with circuit protection theories • Transformer Protection . . . . . AP 11
and practices.
—General . . . . . . . . . . . . . . . . . AP 11
Our solution: Every application has its —Low Voltage Primary
Protection . . . . . . . . . . . . . . . AP 11
unique challenges. But you’ll find the path
to a basic understanding of applied circuit —Primary and Secondary Fuses
protection principles in our Applications
for LV Transformers . . . . . AP 12
section. Be it a glossary of relevant —Control Transformers . . . . AP 13
electrical terms, an introduction to fuse —MV Transformers . . . . . . . . AP 14
construction, guidance on reading and • Let-Thru Current & I2T . . . . AP 20
applying Peak Let-thru curves, or a look
• Fuse Let-Thru Current
at the most common applications. Tables . . . . . . . . . . . . . . . . . . . AP 21
Want more information fast? For • Capacitor Protection . . . . . . AP 27
more technical or application-specific • Cable Protection . . . . . . . . . . AP 29
information, please call our Applications • Motor Starter General Info AP 30
Engineering experts at 978-248-8914 or • Auxiliary Contacts . . . . . . . . AP 31
visit our website at mersen.com.
• Selectivity Between Fuses . AP 32
• Short Circuit Calculations . . AP 33
• Short Circuit Rating . . . . . . . AP 34
• 11 Reasons for Using
Current-Limiting Fuses . . . . AP 34
• Fuse Obsolescence . . . . . . . AP 35
• Suggested Fuse
Specifications . . . . . . . . . . . . AP 36
A P P L I C AT I O N
Definitions I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
The external live parts of the fuse which provide
continuity between the fuse and the balance of Clearing I2t is the total I2t passed by a fuse as the
the circuit. Also referred to as ferrules, blades or fuse clears a fault, with t being equal to the time
terminals. elapsed from the initiation of the fault to the
instant the fault has been cleared.
Coordination
The use of overcurrent protective devices which Melting I2t is the minimum I2t required to melt
will isolate only that portion of an electrical the fuse element.
system which has been overloaded or faulted. See
Selectivity. Interrupting Rating (Abbreviated I.R.)
The maximum current a fuse can safely interrupt.
Current-Limiting Fuse Some special purpose fuses may also have a
A fuse which will limit both the magnitude and “Minimum Interrupting Rating”. This defines the
duration of current flow under short circuit minimum current that a fuse can safely interrupt.
conditions.
Kiloamperes (abbreviated kA)
Current-Limiting Range 1,000 amperes.
The available fault current a fuse will clear in less
than 1/2 cycle, thus limiting the actual magnitude of Limiter or Back-up Fuse
current flow. A special purpose fuse which is intended to provide
short circuit protection only.
Dual Element Fuse
Often confused with time delay, dual element is a Overcurrent
term describing fuse element construction. A fuse Any current in excess of conductor ampacity or
having two current responsive elements in series. equipment continuous current rating.
Element
A calibrated conductor inside a fuse which melts
M E R S E N .CO M AP 2
A P P L I C AT I O N
Definitions I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
amperes. ANSI and UL Standards are followed.
Renewable Element or Link Current-Limiting Motor Starter Fuses are
The field-replaceable element of a renewable fuse. available for nominal voltages of 2.4, 4.8 and
Also referred to as a renewable link. 7.2kV in current ratings up to 36R (650A). These
are special purpose R-Rated fuses for motor
Selectivity short circuit protection only (back-up fuses)
A main fuse and a branch fuse are said to be and are not full-range power fuses. ANSI and UL
selective if the branch fuse will clear all overcurrent Standards are followed.
conditions before the main fuse opens. Selectivity
is desirable because it limits outage to that portion PT Fuses (Potential Transformers) require
of the circuit which has been overloaded or faulted. current limiting fuses or equivalent on the
Also called selective coordination. primary connection side. Standard PT primary
voltages range from 2.4kV to 36kV. Since the
Semiconductor Fuse power requirement is low (for relays, metering,
An extremely fast acting fuse intended for the etc.) fuses of the proper voltage are applied
protection of power semiconductors. Sometimes in the 1/2 to 5 ampere range. Several voltage
referred to as a rectifier or ultra fast fuse. ratings are available, physical sizes vary among
manufacturers.
Short Circuit
Excessive current flow caused by insulation Low Voltage (600V or less)
breakdown or wiring error. Many types of low voltage fuses are classified and
identified for use in 125, 250, 300, 480, or 600V
Threshold Current circuits. UL/CSA/NOM standards are followed.
The minimum available fault current at which a fuse Common types are briefly summarized in the chart
is current limiting. on the next page.
Time-Delay Fuse
M E R S E N .CO M AP 3
A P P L I C AT I O N
Fuse Descriptions I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Capacitor 600-5500VAC 25-300 Up to 200 A100C-A550C Other
Welder 600VAC 100-600 200 A4BX Other
Photovoltaic See Section MF
Element
M E R S E N .CO M AP 4
How to Read a
A P P L I C AT I O N
Time-Current Curve I N F O R M AT I O N
This characteristic is desirable because it parallels this need? Find the 3000 ampere line on the
the characteristics of conductors, motors, horizontal axis (Pt. G) and follow it up to the 1
transformers and other electrical apparatus. These second line (Pt. H). The nearest curve to the right
components can carry low level overloads for is the AJT400. If the point is not near a curve
relatively long times without damage. However, shown, other intermediate curves are available
under high current conditions damage can occur from the factory.
quickly. Because of its inverse time current Sometimes the fuse family or type has not been
characteristic, a properly applied fuse can provide chosen, so a design requirement can be presented
effective protection over a broad current range, to several family characteristic curves. One fuse
from low level overloads to high level short circuits. type will emerge as a good choice. Voltage rating,
interrupting rating, physical size, time delay, etc. are
HOW TO READ A all considerations in the final choice.
TIME-CURRENT CURVE
A time-current characteristic curve, for any
specified fuse, is displayed as a continuous line
representing the average melting time in seconds AJT TIME DELAY / CLASS J
for a range of overcurrent conditions. The melting
time is considered nominal unless noted otherwise.
Melting Time -Current Data
Several curves are traditionally shown on one sheet
1-600 Amperes, 600 Volts AC
to represent a family of fuses. The family shown
here is the Time Delay Class J AJT Amp-Trap 2000®
fuse.
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Information can be accessed from these curves in
several ways:
M E R S E N .CO M AP 5
Low Voltage Fuses
A P P L I C AT I O N
For Motor Protection I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
thermal protector is included in the branch circuit. Overload Relay
Time delay fuse ratings may be increased to 225% and
non-time delay fuse ratings to 400% (300% if over
600 amperes) if the ratings shown in Table 2 will not
carry motor starting current. Motor
M E R S E N .CO M AP 6
Low Voltage Fuses
A P P L I C AT I O N
For Motor Protection I N F O R M AT I O N
The Class J fuse is also about half the physical size Sizing time delay fuses between 125% and 150% of
of the RK5 and RK1 reducing panel space and saving motor full load current provides advantages. The fuse
money. will coordinate with NEMA Class 20 overload relays.
Nuisance fuse opening will virtually be eliminated and
TIME DELAY VS. NON-TIME DELAY effective short circuit protection will be maintained.
Time delay fuses are the most useful fuses for motor For newer, premium efficiency motors, sizing fuses
branch circuit application. A time delay fuse can be between 125% and 150% may not be sufficient enough
sized closer to motor full load current, providing a to handle the expected higher motor locked-rotor
degree of overload protection, better short circuit currents. For suggestions on sizing fuses for these
protection, and possible use of a smaller disconnect situations, refer to the high-efficiency sizing summary
switch. at the end of this section.
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
capability.
M E R S E N .CO M AP 7
Low Voltage Fuses
A P P L I C AT I O N
For Motor Protection I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Three Phase, 230 V
0.5 2.2 7 10 10 3-1/2 6 6
0.75 3.2 10 10 12 5 6 7
1 4.2 12 15 15 6-1/4 10 10
1.5 6 17-1/2 20 20 9 15 15
2 6.8 20 25 25 10 15 15
3 9.6 30 30 30 15 20 20
5 15.2 25 30 30
7.5 22 35 40 45
10 28 40 50 60
15 42 70 80 90
20 54 80 100 110
25 68 110 125 150
30 80 125 150 175
40 104 150 200 225
50 130 200 250 250
60 154 225 300 300
75 192 300 350 400
100 248 350 450 500
125 312 450 600 600
150 360 500 600 -
* Values obtained from NEC 2017 Table 430.250. Fuse ampere ratings based on percentages of full-load current values from this table.
† Sizing based on 175% of motor FLA for Time-Delay Class J/R fuses and 300% of motor FLA for Time-Delay Class CC fuses.
Values rounded up to the next standard rating.
†† Sizing based on 225% of motor FLA for Time-Delay Class J/R fuses and 400% of motor FLA for Time-Delay Class CC fuses.
Fuse ratings cannot exceed these values.
M E R S E N .CO M AP 8
Low Voltage Fuses
A P P L I C AT I O N
For Motor Protection I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
150 180 250 350 400
200 240 350 450 500
250 302 450 600 600
300 361 600 - -
Three Phase, 575V
0.5 0.9 2-8/10 3 3-1/2 1-1/2 3 3
0.75 1.3 4 6 6 2 3 3
1 1.7 5-6/10 6 6-1/4 2-8/10 3 3-1/2
1.5 2.4 8 10 10 3-1/2 6 6
2 2.7 8 10 10 4 6 6
3 3.9 12 15 15 6 10 10
5 6.1 17-1/2 20 20 10 15 15
7.5 9 30 30 30 15 20 20
10 11 17-1/2 20 20
15 17 25 30 35
20 22 35 40 45
25 27 40 50 60
30 32 50 60 70
40 41 60 80 90
50 52 80 100 110
60 62 90 110 125
75 77 125 150 150
100 99 150 175 200
125 125 200 225 250
150 144 225 300 300
200 192 300 350 400
250 242 350 450 500
300 289 450 600 600
* Values obtained from NEC 2017 Table 430.250. Fuse ampere ratings based on percentages of full-load current values from this table.
† Sizing based on 175% of motor FLA for Time-Delay Class J/R fuses and 300% of motor FLA for Time-Delay Class CC fuses.
Values rounded up to the next standard rating.
†† Sizing based on 225% of motor FLA for Time-Delay Class J/R fuses and 400% of motor FLA for Time-Delay Class CC fuses.
Fuse ratings cannot exceed these values.
M E R S E N .CO M AP 9
Low Voltage Fuses
A P P L I C AT I O N
For Motor Protection I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
to increase. In addition to this, with across-the-line
starting applications, it is critical to understand not
only the locked rotor current, but also the starting
time that can be expected.
M E R S E N .CO M AP 10
Transformer A P P L I C AT I O N
Protection I N F O R M AT I O N
This section summarizes transformer overcurrent To accommodate this inrush current, fuses are often
protection as required by the National Electrical selected which have time-current withstand values of
Code (NEC) and Canadian Electric Code.
at least 12 times transformer primary rated current for
.1 second and 25 times for .01 second. Recommended
TRANSFORMERS - PRIMARY 1000 VOLTS primary fuses for popular, low voltage 3-phase
OR LESS transformers are shown on the next page. Some small
If secondary fuse protection is not provided, dry-type transformers may have substantially greater
primary fuses are to be selected according to Table inrush currents. For these applications, the fuse may
1. If both primary and secondary fuses are used, have to be selected to withstand 45 times transformer
they are to be selected according to Table 2.
primary rated current for .01 second.
Table 1 - Primary Fuse Only
SECONDARY FUSES
Transformer Primary Amperes Maximum Primary Fuse % Rating
9 or more 125* Selecting fuses for the secondary is simple once rated
2 to less than 9 167 secondary current is known. Fuses are sized at 125%
less than 2 300 of secondary FLA or the next higher rating; or at
maximum 167% of secondary FLA, see Table 2 for rules.
Table 2 - Primary & Secondary Fuses The preferred sizing is 125% of rated secondary current
Maximum Primary Fuse % Rating
Transformer Secondary Amperes
Primary Fuse Secondary Fuse
Isec or next higher fuse rating. To determine Isec, first
9 or more 250 125* determine transformer rating (VA or kVA), secondary
less than 9 250 167 voltage (Vsec) and use formulas below.
* If 125% does not correspond to a standard ampere rating, the next higher
standard rating shall be permitted. 1. Single Phase : Isec = Transformer VA
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Vsec
M E R S E N .CO M AP 11
Primary and Secondary Fuses for
LV Transformers A P P L I C AT I O N
I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
7.5 9 15 - - - 36 45 21 30 18 25
9 11 25 - - - 43 60 25 35 22 30
15 18 35 - - - 72 100 42 60 36 45
30 36 60 - - - 145 200 83 110 72 100
45 54 100 - - - 217 300 125 175 108 150
75 90 175 - - - 361 450 208 300 181 250
100 120 225 - - - 482 600 278 350 241 350
112.5 135 300 - - - 542 700 313 400 271 350
150 180 400 - - - 723 900 417 600 361 500
225 371 500 - - - 1084 1350 625 800 542 700
300 361 600 - - - 1445 1800 834 1200 723 1000
500 601 - 1000 1000 1200 2408 2500 1390 1600 1204 1600
750 902 - 1400 1600 2000 3613 4000 2084 2500 1806 2000
1000 1203 - 1800 2000 2500 4817 5000 2779 3000 2408 2500
M E R S E N .CO M AP 12
Primary Fuses for
A P P L I C AT I O N
LV Control Transformers I N F O R M AT I O N
Control circuit transformers used as part of a motor the NEC guidelines specified above.
control circuit are to be protected as outlined in
Tables 1 & 2 with one important exception. Primary For example: 300VA Transformer, 600V primary.
fuses may be sized up to 500% of transformer rated
Ipri = Transformer VA = 300 = 1/2A = FLA
primary current if the rated primary current is less
Primary V 600
than 2 amperes.
The fuse time-current curve must lie to the right of
When a control circuit transformer is energized,
the point 40 x (1/2A) = 20A @ .01 sec.
the typical magnetizing inrush will be 25-40 times
rated primary full load current (FLA) for the first 1/2 Secondary fuses are still sized at 125% of the
cycle and dissipates to rated current in a few cycles. secondary FLA.
Fuses must be sized so they do not open during
this inrush. We recommend that fuses be selected
to withstand 40 x FLA for .01 sec. and to stay within
Recommended Primary Fuses for Single Phase Control Transformers
Trans 600 Volt Primary 480 Volt Primary
VA FLA ATQR ATMR A6D-R+ AJT+ TRS-R FLA ATQR ATMR A6D-R+ AJT+ TRS-R
25 .042 1/10 2/10 2/10 - 1/10 .052 1/10 1/4 1/4 - 1/10
50 .083 1/4 3/10* 4/10 - 2/10 .104 1/4 1/2* 1/2 - 2/10
75 .125 1/4 1/2* 6/10 - 2/10 .156 3/10 3/4* 6/10 - 2/10
100 .167 3/10 3/4* 8/10 - 3/10 .208 4/10 1 1 1 3/10
130 .22 4/10 1 1 1 4/10 .27 1/2 1 1 1-1/2 4/10
150 .25 1/2 1* 1-1/4 1 4/10 .313 1/2 1-1/2 1-4/10 1-1/2 4/10
200 .33 1/2 1-1/2 1-6/10 1-1/2 6/10 .417 6/10 2 2 2 6/10
250 .42 6/10 2 2 2 6/10 .52 8/10 2 2-1/2 2-1/2 6/10
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
300 .50 1 2 2-1/2 2 8/10 .62 1-1/2 3 3 3 8/10
350 .583 1-1/4 2 2-8/10 2 1 .73 1-1/2 3-1/2 3-1/2 3-1/2 1
500 .833 1-1/2 4 4 4 1-1/4 1.04 2 5 4 4 1-4/10
750 1.25 2-1/2 6 4 4 1-6/10 l.56 3* 7 5 5 2
1000 1.67 3 8 5 5 2-1/4 2.08 4+ - 5+ 5+ 3
1500 2.5 5+ - 6+ 6+ 4 3.125 7+ - 6-1/4+ 6-1/4+ 4
2000 3.33 8+ - 8+ 8+ 5 4.17 10+ - 7+ 7+ 5
3000 5.00 12+ - 12+ 12+* 8 6.25 15+* - 15+* 15+ 8
5000 8.33 20+* - 20+* 20+** 12+ 10.4 - - 25+* 25+* 15+
7500 12.5 30+* - 30+* 30+** 17-1/2+ 15.6 - - 35+** 35+** 20+
10000 16.7 - - 40+* 40+** 25+ 20.8 - - 50+** 50+** 30+
240 Volt Primary 120 Volt Primary
25 .104 2/10 1/2 1/2 - 2/10 .21 4/10 1 1 1 3/10
50 .21 4/10 1 1 1 3/10 .42 6/10 2 2 2 6/10
75 .31 1/2 1-1/2 1-4/10 1-1/2 4/10 .6 1 3 3 3 8/10
100 .42 6/10 2 2 2 6/10 .83 1-1/2 4 4 4 1
130 .54 1 2-1/2 2-1/2 2-1/2 8/10 1.08 2-1/2 5 4 4 1-6/10
150 .625 1 3 3 3 8/10 1.25 2-1/2 6 4 4 1-6/10
200 .83 1-1/2 4 3-1/2 3-1/2 1 1.67 3* 8 5 5 2-1/4
250 1.04 2 5 4 4 1-4/10 2.08 4+ - 5+ 5+ 2-8/10
300 1.25 2-1/2 6 4 4 1-6/10 2.5 5+ - 6+ 6+ 3-2/10
350 1.46 3* 7 5 5 2 2.92 7+ - 6+ 6+ 4
500 2.08 4+ - 5+ 5+ 2-8/10 4.17 10+ - 10+ 6 5-6/10
750 3.13 7+ - 6-1/4+ 6-1/4+ 4 6.25 15+* - 15+** 15+ 8
1000 4.2 10+ - 7 7 5-6/10 8.33 20+* - 20+** 20+* 12+
1500 6.25 15+ - 15+ 15+ 8 12.5 30+* - 30+ 30+ 15
2000 8.3 20+* - 20+** 20+** 12 16.7 - - 40+** 40+ 25+
3000 12.5 30+* - 30+** 30+** 15 25 - - 60+** 60+* 35+
5000 20.8 - - 50+** 50+* 25 41.7 - - 100+** 100+** 60+
7500 31.3 - - 70+** 70+** 40+ 62.5 - - 150+** 150+** 90+
10000 41.7 - - 100+** 100+** 60+ 83.3 - - 200+** 200+** 125+
The above fuses will withstand 40 x FLA for .01 second except where noted. * Fuse will withstand 30 x FLA for .01 second.
+ Secondary fusing required. ** Fuse will withstand 35 x FLA for .01 second.
M E R S E N .CO M AP 13
Primary Fuses for
A P P L I C AT I O N
MV 3-Phase Power Transformers I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
15 2.1 9F60CED007 9F60DJD007 - A055F1C0R0-5E - - - - - -
30 4.2 9F60CED015 9F60DJD015 - A055F1C0R0-7E - - A055F1D0R0-10E - A055B1DAR0-10E A055C1D0R0-10E
45 6.3 9F60CED015 9F60DJD015 - A055F1C0R0-10E - - A055F1D0R0-10E - A055B1DAR0-10E A055C1D0R0-10E
75 10 9F60CED025 9F60DJD025 9F62HCB025 A055F1C0R0-15E - - A055F1D0R0-15E - A055B1DAR0-15E A055C1D0R0-15E
112.5 16 - - 9F62HCB030 A055F1C0R0-20E 9F60FJD040 - A055F1D0R0-20E - A055B1DAR0-20E A055C1D0R0-20E
150 21 - - 9F62HCB040 A055F1C0R0-30E 9F60FJD040 - A055F1D0R0-30E - A055B1DAR0-30E A055C1D0R0-30E
225 31 - - 9F62HCB050 A055F1C0R0-40E 9F60FJD065 - A055F1D0R0-40E - A055B1DAR0-40E A055C1D0R0-40E
300 42 - - - A055F1C0R0-65E 9F60FJD080 9F62DCB080 A055F1D0R0-65E - A055B1DAR0-65E A055C1D0R0-65E
500 69 - - - - 9F60FJD100 9F62DCB100 A055F1D0R0-100E - A055B1DAR0-100E A055C1D0R0-100E
750 104 - - - - 9F60HJD150 9F62DCB150 A055F1D0R0-150E - A055B1DAR0-150E A055C1D0R0-150E
1000 139 - - - - 9F60HJD200 9F62DCB200 A055F1D0R0-200E - A055B1DAR0-200E A055C1D0R0-200E
1500 208 - - - - - 9F62FCB300 A055F2D0R0-300E - A055B2DAR0-300E A055C1D0R0-300E
2000 278 - - - - - 9F62FCB350 A055F2D0R0-400E - A055B2DAR0-400E A055C1D0R0-400E
2500 347 - - - - - - - 9F62KCB500 A055B2D0R0-500E A055C2D0R0-500E
3000 417 - - - - - - - 9F62KCB600 A055B2D0R0-600E A055C2D0R0-600E
3750 520 - - - - - - - 9F62KCB700 A055B3D0R0-750E -
4000 556 - - - - - - - 9F62KCB700 A055B3D0R0-750E -
4500 625 - - - - - - - 9F62KCB800 A055B3D0R0-900E -
5000 695 - - - - - - - 9F62KCB900 A055B3D0R0-900E -
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
EXAMPLES
1. A new installation has a 300kVA transformer with 4160V 2. What is the normal fuse size recommended for a
primary. It is not fully loaded. What is the typical primary 1500kVA transformer with 12,470V primary?
fuse recommended?
8320V
4160V Source Load
Source Load
A 65 rating (Mersen A055F1DORO-65E or equivalent) For this application use a 100E rating A155F2DORO-100E
is correct. Lower ratings may open when transformer is or equivalent which will allow normal overload operations
energized. of transformer up to 133% of rating.
M E R S E N .CO M AP 14
Primary Fuses for
A P P L I C AT I O N
MV 3-Phase Power Transformers I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
M E R S E N .CO M AP 15
Primary Fuses for
A P P L I C AT I O N
MV 3-Phase Power Transformers I N F O R M AT I O N
Transformer 2" Ferrule mounting 3" Ferrule mounting (single and double) Bolt on
Full Load Amperes
Rating kVA1 9F60 EJO “C” 9F62 EJO “C” 9F60 EJO “D” 9F62 EJO “D” A825X A072B
9 0.72 9F60DJE003 - - - - -
15 1.2 9F60DJE005 - - - - -
30 2.4 9F60DJE010 - - - - -
45 3.6 9F60DJE010 - - - - -
75 6.0 - - 9F60FJE020 - - -
112.5 9.0 - 9F62HCC020 9F60FJE025 - - -
150 12 - 9F62HCC020 9F60FJE040 - A825X20E-1 -
225 18 - 9F62HCC040 9F60FJE050 - A825X25E-1 -
300 24 - 9F62HCC040 9F60FJE065 - A825X40E-1 -
500 40 - 9F62HCC050 9F60FJE100 - A825X65E-1 -
750 60 - - 9F60HJE125 9F62DCC080 A825X80E-1 -
1000 80 - - 9F60HJE150 9F62DCC125 A825X125E-1 -
1500 120 - - 9F60HJE200 9F62FCC200 A825X200E-1 -
2000 161 - - - 9F62FCC200 A825X200E-1 -
2500 201 - - - 9F62FCC250 - A072B2D0R0-250E
3000 241 - - - - - A072B2D0R0-300E
3500 281 - - - - - A072B2D0R0-350E
4000 321 - - - - - A072B2D0R0-400E
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second
EJO fuses can be used outdoors without an enclosure
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
* Use F2 in place of F1 for double barrel fuses.
M E R S E N .CO M AP 16
Primary Fuses for
A P P L I C AT I O N
MV 3-Phase Power Transformers I N F O R M AT I O N
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
* Use F2 in place of F1 for double barrel fuses.
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
* Use F2 in place of F1 for double barrel fuses.
M E R S E N .CO M AP 17
Primary Fuses for
A P P L I C AT I O N
MV 3-Phase Power Transformers I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
* Use F2 in place of F1 for double barrel fuses.
3 Phase 14,400 Volt Typical Primary Fuse Sizing Chart
Trans- Full 2" Ferrule mounting 3" Ferrule mounting (single and double) Bolt on Clip Lock
former Load
9F60 EJO “D” 9F62
Rating Amp- 9F60 EJ “C” EJO 9F62 EJO
9F60 EJO “C” 9F62 EJO “C” A155F A155F A155B A155C
kVA1 eres “D” “DDDD”
9 0.4 9F60DMH002 9F60CJH002 - - - - - - - -
15 0.6 9F60DMH003 9F60CJH003 - - - - - - - -
30 1.2 9F60DMH005 9F60CJH005 - - - - - - - -
45 1.8 9F60DMH007 9F60CJH007 - A155F1C0R0-5E - - - - - -
75 3.0 9F60DMH010 9F60CJH010 - A155F1C0R0-7E - - - - - -
112.5 5 - - - A155F1C0R0-10E 9F60FMH015 - A155F1D0R0-10E - A155B1D0R0-10E A155C1D0R0-10E
150 6 - - - A155F1C0R0-10E 9F60FMH020 - A155F1D0R0-10E - A155B1D0R0-10E A155C1D0R0-10E
225 9 - - 9F62HDD020 A155F1C0R0-15E 9F60FMH030 - A155F1D0R0-15E - A155B1D0R0-15E A155C1D0R0-15E
300 12 - - 9F62HDD020 A155F1C0R0-20E 9F60FMH040 - A155F1D0R0-20E - A155B1D0R0-20E A155C1D0R0-20E
500 20 - - 9F62HDD030 A155F1C0R0-30E 9F60FMH050 - A155F1D0R0-30E - A155B1D0R0-30E A155C1D0R0-30E
750 30 - - - - 9F60FMH080 9F62DDD050 A155F1D0R0-40E - A155B1D0R0-50E A155C1D0R0-50E
1000 40 - - - - 9F60FMH100 9F62DDD065 A155F1D0R0-65E* - A155B1D0R0-65E A155C1D0R0-65E
1500 60 - - - - - 9F62DDD080 A155F1D0R0-80E* - A155B1D0R0-100E A155C1D0R0-100E
2000 80 - - - - - 9F62FDD125 A155F2D0R0-125E - A155B2D0R0-125E A155C2D0R0-125E
2500 100 - - - - - 9F62FDD150 A155F2D0R0-150E - A155B2D0R0-150E A155C2DORO-150E
3000 120 - - - - - 9F62FDD175 A155F2D0R0-175E - A155B2D0R0-150E A155C2DORO-150E
3500 140 - - - - - 9F62FDD200 A155F2D0R0-200E - A155B2D0R0-200E A155C2DORO-200E
4000 161 - - - - - - - - A155B3D0R0-250E A155C3D0R0-250E
4500 181 - - - - - - - - A155B3D0R0-250E A155C3D0R0-250E
5000 201 - - - - - - - - A155B3D0R0-300E A155C3D0R0-300E
5500 221 - - - - - - - 9F62KED300 A155B3D0R0-300E A155C3D0R0-300E
6000 241 - - - - - - - 9F62KED300 A155B3D0R0-300E A155C3D0R0-300E
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
* use F2 in place of F1 for double barrel fuses.
M E R S E N .CO M AP 18
Primary Fuses for
A P P L I C AT I O N
MV 3-Phase Power Transformers I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
45 0.79 9F60FPK002 9F60FPT002
75 1.31 9F60FPK005 9F60FPT005
112.5 1.98 9F60FPK005 9F60FPT005
150 2.62 9F60FPK007 9F60FPT007
225 3.96 9F60FPK010 9F60FPT010
300 5.26 9F60FPK015 9F60FPT015
500 8.71 9F60FPK025 9F60FPT025
750 13.1 9F60FPK030 9F60FPT030
1000 17.5 9F60FPK040 9F60FPT040
1500 26.2 9F60HPK065 9F60HPT065
2000 35 9F60HPK065 9F60HPT065
2500 43.7 9F60HPK080 9F60HPT080
Fuses will carry transformer magnetizing inrush current of 25 times full load amperes for .01 second and 12 times full load current for .1 second.
EJO fuses can be used outdoors without an enclosure.
1
The self cooled rating of the transformer. If using a force cooled transformer rating, the fuse E rating must be sized > 1.25 times the force cooled transformer FLA.
M E R S E N .CO M AP 19
A P P L I C AT I O N
Let-Thru Current and I2t I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
current-limiting range. Figure 1 illustrates this. Let-
thru current is expressed as a peak instantaneous
value (lp).
Current
M E R S E N .CO M AP 20
A P P L I C AT I O N
Let-Thru Current and I2t I N F O R M AT I O N
IP VERSUS I2T current and time constant of the DC circuit are the
determining factors.
Ip has a rather limited application usefulness. Two
fuses can have the same Ip but different total Fuse I2t value can be used to determine the level of
clearing times. See Figure 4. protection provided to circuit components under
fault current conditions. Manufacturers of diodes,
thyristors, triacs, and cable publish I2t withstand
ratings for their products. The fuse chosen to
protect these products should have a clearing I2t
that is lower than the withstand I2t of the device
being protected.
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
current-limiting range and are calculated as follows: with prospective fault currents as high as 200,000
amperes. At each prospective fault current, let-
The “t” in the equation is the total clearing time thru data is given in two forms for an individual
for the fuse. To be proper, I2t should be written as fuse - lrms and lp. Where lrms is the “Apparent RMS
(IRMS)2t. It is generally understood that the “I” in I2t Symmetrical Current” and lp is the maximum peak
is really IRMS, and the RMS is dropped for the sake of instantaneous current passed by the fuse, the lp let-
brevity. thru current is 2.3 times lrms. This relationship exists
between peak current and RMS available current
under worst-case test conditions (i.e. closing angle
of 0o at 15% power factor).
M E R S E N .CO M AP 21
Fuse Let-Thru A P P L I C AT I O N
Current Tables I N F O R M AT I O N
Table 2 - Class L, A4BY Fuses at 600 Volts AC, 15% Power Factor
Fuse Let-Thru Current In Kilo-Amperes
Prospective
Short Circuit By Fuse Rating In Amperes
Rms. Sym
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
601 800 1000 1200 1600 2000 2500 3000 4000
Amperes Irms lp Irms lp Irms lp Irms lp Irms lp Irms lp Irms lp Irms lp Irms lp
15,000 11 24 13 29 15 35 15 35 15 35 15 35 15 35 15 35 15 35
20,000 12 26 14 32 16 37 19 43 20 46 20 46 20 46 20 46 20 46
25,000 13 29 15 34 18 40 20 46 24 55 25 58 25 58 25 58 25 58
30,000 13 30 16 36 19 43 21 49 25 58 29 67 30 69 30 69 30 69
35,000 14 32 17 38 20 45 23 52 27 61 30 70 33 76 35 81 35 81
40,000 15 34 17 40 21 47 24 54 28 64 32 73 35 79 37 86 40 92
50,000 16 36 19 43 22 51 25 58 30 68 34 78 37 86 41 95 50 115
60,000 17 38 20 45 24 54 27 62 31 72 37 84 40 91 44 100 53 121
80,000 18 42 22 50 26 59 29 67 35 80 40 92 44 100 48 110 58 133
100,000 20 45 24 54 28 64 32 73 38 87 43 99 47 108 52 119 62 143
150,000 23 52 27 62 32 73 37 84 43 99 49 113 54 123 59 137 73 167
200,000 25 56 29 67 35 80 40 91 48 110 54 123 59 136 65 150 79 181
Table 3 - Class L, A4BT Fuses at 600 Volts AC, 15% Power Factor
Fuse Let-Thru Current In Kilo-Amperes
Prospective
Short Circuit By Fuse Rating In Amperes
Rms. Sym 800 1000 1200 1600 2000
Amperes Irms lp Irms lp Irms lp Irms lp Irms lp
15,000 14 33 15 35 15 35 15 35 15 35
20,000 16 36 18 41 20 46 20 46 20 46
25,000 17 39 19 45 22 50 25 58 25 58
30,000 18 41 21 48 23 54 28 63 30 69
35,000 19 43 22 50 25 56 29 67 34 79
40,000 20 45 23 52 26 59 30 70 35 81
50,000 21 49 25 56 28 63 33 75 38 87
60,000 23 52 26 60 29 67 35 80 40 93
80,000 25 57 29 66 32 74 38 88 44 102
100,000 27 62 31 71 35 80 41 95 48 110
150,000 31 70 35 81 40 92 47 109 55 126
200,000 34 78 39 89 44 101 52 120 60 139
M E R S E N .CO M AP 22
Fuse Let-Thru A P P L I C AT I O N
Current Tables I N F O R M AT I O N
Table 5 - Class RK1, A6D Fuses at 600 Volts AC, 15% Power Factor
Prospective Fuse Let-Thru Current In Kilo-Amperes
Short Circuit By Fuse Rating In Amperes
Rms. Sym 30 60 100 200 400 600
Amperes Irms lp Irms lp Irms lp Irms lp Irms lp Irms lp
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
5,000 .80 1.8 1.5 3.5 2.0 4.6 3.5 8.0 5.0 12 - -
10,000 1.0 2.3 1.9 4.4 2.5 5.8 4.4 10.1 7.1 16.4 10 23
15,000 1.2 2.7 2.2 4.9 2.9 6.6 5.0 11.6 8.2 18.8 12 27
20,000 1.3 2.9 2.4 5.4 3.1 7.1 5.5 12 9.0 20.7 13 29
25,000 1.4 3.2 2.6 5.9 3.4 7.8 6.0 13.8 9.7 22.3 14 32
30,000 1.5 3.4 2.7 6.2 3.6 8.3 6.3 14.6 10.3 23.6 15 33
35,000 1.5 3.5 2.9 6.6 3.8 8.7 6.7 15.4 10.8 24.9 15 35
40,000 1.6 3.7 3.0 6.9 4.0 9.1 7.0 16.5 11.3 26 16 37
50,000 1.7 4.0 3.2 7.4 4.3 9.8 7.5 16.5 12.2 28 17 40
60,000 1.8 4.2 3.4 7.8 4.5 11 8.0 17 13 30 18 42
80,000 2.0 4.7 3.8 8.6 5.0 12 8.8 20.3 13 33 20 46
100,000 2.2 5.0 4.1 9.3 5.4 12 9.5 20 14 35 22 50
150,000 2.5 5.8 4.6 11 6.1 14 10.9 25 16 40 25 57
200,000 2.8 6.3 5.1 12 6.8 16 11 25 19 45 27 63
Table 6 - Class J, A4J Fuses at 600 Volts AC, 15% Power Factor
M E R S E N .CO M AP 23
Fuse Let-Thru A P P L I C AT I O N
Current Tables I N F O R M AT I O N
Table 8 - Class T, A6T Fuses at 600 Volts AC, 15% Power Factor
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
5,000 .62 1.4 1.2 2.8 1.6 3.8 2.6 6.0 4.2 9.7 5.0 12 5.0 12
10,000 .78 1.8 1.5 3.5 2.1 4.8 3.3 7.5 5.3 12 8.2 19 10 22
15,000 .89 2.1 1.7 4.0 2.4 5.4 3.7 8.6 6.1 14 9.4 22 11 26
20,000 .98 2.3 1.9 4.4 2.6 6.0 4.1 9.5 6.7 15 10 24 12 28
25,000 1.1 2.4 2.0 4.8 2.8 6.5 4.4 10 7.2 17 11 26 13 31
30,000 1.1 2.6 2.2 5.0 3.0 6.9 4.7 11 7.7 18 12 27 14 32
35,000 1.2 2.7 2.3 5.3 3.1 7.2 5.0 11 8.1 19 12 29 15 34
40,000 1.2 2.9 2.4 5.6 3.3 7.5 5.2 12 8.5 19 13 30 16 36
50,000 1.3 3.1 2.6 6.0 3.5 8.1 5.6 13 9.1 21 14 32 17 38
60,000 1.4 3.3 2.8 6.4 3.8 8.6 5.9 14 9.7 22 15 34 18 41
80,000 1.6 3.6 3.0 7.0 4.1 9.5 6.5 15 11 25 16 38 20 45
100,000 1.7 3.9 3.2 7.5 4.5 10 7.0 16 11 26 18 40 21 48
150,000 1.9 4.4 3.8 8.6 5.1 12 8.1 19 13 30 20 46 24 55
200,000 2.1 4.9 4.1 9.5 5.6 13 8.9 20 14 33 22 51 27 61
Table 9 - Class T, A3T Fuses at 300 Volts AC, 15% Power Factor
M E R S E N .CO M AP 24
Fuse Let-Thru A P P L I C AT I O N
Current Tables I N F O R M AT I O N
Table 11 - Class RK1, A2D Fuses at 250 Volts AC, 15% Power Factor
Prospective Fuse Let-Thru Current In Kilo-Amperes
Short Circuit By Fuse Rating In Amperes
Rms. Sym 30 60 100 200 400 600
Amperes Irms lp Irms lp Irms lp Irms lp Irms lp Irms lp
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
5,000 .77 1.8 1.4 3.2 2.0 4.6 3.2 7.3 5.0 12 5.0 12
10,000 .97 2.2 1.8 4.0 2.5 5.8 4.0 9.2 6.4 15 8.0 18
15,000 1.1 2.6 2.0 4.6 2.9 6.6 4.6 11 7.3 17 9.2 21
20,000 1.2 2.8 2.2 5.1 3.2 7.3 5.0 12 8.1 19 10 23
25,000 1.3 3.0 2.4 5.5 3.4 7.9 5.4 12 8.7 20 11 25
30,000 1.4 3.2 2.5 5.8 3.6 8.3 5.8 13 9.2 21 12 27
35,000 1.5 3.4 2.7 6.1 3.8 8.8 6.1 14 9.7 22 12 28
40,000 1.5 3.5 2.8 5.7 4.0 9.2 6.4 15 10 23 13 29
50,000 1.7 3.8 3.0 6.9 4.3 9.9 6.8 16 11 25 14 32
60,000 1.8 4.0 3.2 7.3 4.6 11 7.3 17 12 27 15 34
80,000 1.9 4.5 3.5 8.1 5.0 12 8.0 18 13 29 16 37
100,000 2.1 4.8 3.8 8.7 5.4 12 8.6 20 14 32 17 40
150,000 2.4 5.5 4.3 9.9 6.2 14 9.9 23 16 36 20 46
200,000 2.6 6.0 4.8 11 6.8 16 11 25 17 40 22 50
Table 12 - Class RK5, TRS Fuses at 600 Volts AC, 15% Power Factor
Prospective Fuse Let-Thru Current In Kilo-Amperes
Short Circuit By Fuse Rating In Amperes
Rms. Sym 30 60 100 200 400 600
Amperes Irms lp Irms lp Irms lp Irms lp Irms lp Irms lp
5,000 1.7 3.9 3.2 7.4 3.4 7.8 5.0 12 - - - -
10,000 2.1 4.8 4.0 9.2 4.2 9.7 6.2 14 10 23 10 23
15,000 2.4 5.5 4.6 11 4.8 11 7.1 16 12 27 15 35
20,000 2.7 6.2 5.1 12 5.3 12 7.8 18 13 30 18 42
25,000 2.9 6.7 5.5 13 5.7 13 8.4 19 14 32 20 45
30,000 3.1 7.1 5.8 13 6.1 14 8.9 20 15 35 21 48
35,000 3.3 7.6 6.1 14 6.4 15 9.4 22 16 36 22 50
40,000 3.4 7.8 6.4 15 6.7 15 9.8 23 17 38 23 53
50,000 3.7 8.5 6.9 16 7.2 17 11 24 18 41 25 57
60,000 3.9 9.0 7.3 17 7.7 18 11 26 19 43 26 60
80,000 4.3 9.9 8.1 19 8.5 20 12 29 21 48 29 66
100,000 4.6 11 8.7 20 9.1 21 13 31 22 52 31 72
150,000 5.3 12 9.9 23 10 24 15 35 26 59 36 82
200,000 5.8 13 11 25 12 26 17 39 28 65 39 90
M E R S E N .CO M AP 25
Fuse Let-Thru A P P L I C AT I O N
Current Tables I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
M E R S E N .CO M AP 26
Capacitor A P P L I C AT I O N
Protection I N F O R M AT I O N
The primary responsibility of a capacitor fuse is to For applications 600V or less in lieu of specific
isolate a shorted capacitor before the capacitor fusing recommendations from the capacitor
can damage surrounding equipment or personnel. manufacturer, we suggest a Mersen A60C Type 121
Typical capacitor failure occurs when the dielectric or an A6Y Type 2SG fuse sized at 165% to 200% of
in the capacitor is no longer able to withstand the capacitor’s current rating (contact factory for
the applied voltage. A low impedance current technical data). If these fuses are not dimensionally
path results. The excessive heat generated builds acceptable, then a non-time delay Class J or Class
pressure and can cause violent case rupture. A RK1 fuse could be used and sized at 185% to 220%
fuse will isolate the shorted capacitor before case of the capacitor’s current rating.
rupture occurs.
For applications over 600V to 5.5kV, we suggest
Amp-Trap A100C to A550C capacitor fuses. These
FUSE PLACEMENT medium voltage fuses are available in a variety of
voltage ratings and mounting configurations. Refer
The Code requires that an overcurrent device be
to Section MV for specific data. Medium voltage
placed in each ungrounded conductor of each
capacitor fuses are sized at 165% to 200% of the
capacitor bank (see Figure 1). The Code further
capacitor current rating.
requires that the rating or setting of the over-
current device be as low as practicable. A separate Capacitor fuses are selected for their ability to
overcurrent device is not required if the capacitor is provide short circuit protection and to ride through
connected on the load side of a motor-running capacitor inrush current. Inrush current is affected
overcurrent device. by the closing angle, capacitance, resistance and
inductance of the circuit, and varies from one
Fusing per the Code provides reasonable protection
application to another. Inrush lasts for less than
if the capacitors are the metallized film self-healing
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
1/4 cycle and is typically less than 25 times the
type. If not, each capacitor should be individually
capacitor’s current rating.
fused as shown in Figure 2.
Steady state capacitor current is proportional to
Fusing each individual capacitor is especially
the applied voltage and frequency. Since voltage
important in large banks of parallel capacitors.
and frequency are fixed in power factor correction
Should one capacitor fail, the parallel capacitors will
applications, the capacitor is not expected to be
discharge into the faulted capacitor and violent case
subjected to an overload. Therefore, capacitor fuses
rupture of the faulted capacitor can result. Individual
are not selected to provide overload protectors for
capacitor fusing eliminates this problem.
the capacitor.
If the capacitors are to be placed in banks
comprised of both series and parallel combinations,
the capacitor manufacturer must be consulted for
fuse placement recommendations. The opening of
improperly placed fuses can cause overvoltage and
result in damage to other capacitors in the network.
AMPERE RATING
How much overcurrent can a capacitor withstand?
What effects do neighboring capacitors have
on the inrush of a given capacitor? These and
other questions influence fuse selection. Circuit
analysis can be very complex. It is best to
consult the capacitor manufacturer for specific
recommendations.
M E R S E N .CO M AP 27
Capacitor A P P L I C AT I O N
Protection I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
120 amps x 1.65 = 198 amps
M E R S E N .CO M AP 28
Cable A P P L I C AT I O N
Protection I N F O R M AT I O N
USING CABLE PROTECTORS the cable. In all other applications, Cable Protectors
Cable Protectors are special purpose limiters should be placed at both ends of each cable. This
which are used to protect service entrance and allows a faulted cable to be isolated from the source
distribution cable runs. The National Electrical Code end and from a back feed at its load end. Isolation
(NEC) does not require using cable protectors. of a faulted cable is only possible if there are 3 or
more parallel cables per phase.
When unprotected cables are paralleled, a single
conductor faulting to ground can result in damage CABLE PROTECTOR AMPACITY
to and eventual loss of all parallel conductors. The Cable Protectors are not ampere rated. They are
resultant cost of cable replacement, loss of service, not intended to provide overload protection for
and down time can be significant. This cost can be the cable. Cable Protectors are designed to open in
minimized by the use of Cable Protectors. case of a short circuit or after a cable has faulted.
Thus total system reliability is maximized. For these
When each phase consists of three or more parallel
reasons Cable Protectors are rated in terms of the
conductors, Cable Protectors are installed at each
cable material (aluminum or copper) and the cable
end of each conductor. Should one cable fault,
size (250kcmil, 500kcmil, etc.)
the Cable Protectors at each end of the faulted
cable will open and isolate the faulted cable. The
SELECTING A CABLE PROTECTOR
unfaulted cables will maintain service.
The following questions must be answered to
choose the correct Cable Protector:
TERMINATIONS
In addition to improving system reliability, Cable • Is the cable copper or aluminum?
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Protectors provide a means of terminating
cable, thus eliminating the need for cable lugs. • What is the cable size?
Cable Protectors are available with the following
• What termination type is desired?
configurations:
• Is the Cable Protector to be insulated or
Aluminum and copper cable require different
protected with a heat-shrink sleeve or a rubber
terminations. Cable Protectors intended for copper
boot?
cable must not be used with aluminum cable. Cable
Protectors intended for aluminum cable include an Once these questions have been answered, the
oxide inhibitor. Cable Protector catalog number can be chosen
from the listings.
Cable to cable Type 1
PLACEMENT OF CABLE PROTECTORS Cable - Size Awg CU or AL Class J Fuse Catalog No.
#4 A4J125
In single phase applications where a single
#3 A4J150
transformer supplies the service and there are #2 A4J175
only one or two conductors per phase, a single #1 A4J200
Cable Protector per cable may be used. The Cable 1/0 A4J250
2/0 A4J300
Protector should be located at the supply end of
3/0 A4J400
M E R S E N .CO M AP 29
Motor Starter A P P L I C AT I O N
General Information I N F O R M AT I O N
Disconnect Switch
UL 98 - UL489 SIRCO
CSA – C22.2 # 4 Non-Fusible FUSERBLOC
CSA – C22.2 # 5 Disconnect Switch Fusible Disconnect Switch
range range
Fuses
Contactor
Overload relay
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
• Disconnect means Fuse or an Inverse-time Circuit-breaker.
• Branch-circuit short-circuit protective device
• Motor-controller MOTOR-CONTROLLER
• Motor overload protective devices Any switch or device that is normally used to
start and stop a motor according to the National
DISCONNECT MEANS Electrical Code article 430.82.
The Disconnect means can be a Manual Disconnect
Switch according to UL 98. MOTOR OVERLOAD PROTECTIVE
A manual Motor Controller (according to UL 508) DEVICES
additionally marked “Suitable as Motor Disconnect” The National Electrical Code permits fuses to be
is only permitted as a disconnecting means where used as the sole means of overload protection
installed between the final branch-circuit short- for motor branch circuits. This approach is often
circuit and ground-fault protective device and the practical only with small single phase motors. Most
motor (NEC 2008 Article 430.109). integral horsepower 3 phase motors are controlled
by a motor starter which includes an overload
relay. Since the overload relay provides overload
protection for the motor branch circuit, the fuses
may be sized for short-circuit protection.
M E R S E N .CO M AP 30
Auxiliary A P P L I C AT I O N
Contacts I N F O R M AT I O N
Designation Example
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
numerical suffix designates the maximum voltage
design values, which are to be 600, 300, and 150
volts for suffixes 600, 300, and 150 respectively. The Thus a C600 rated auxiliary device is the minimum
table below gives some typical rating codes: rating required.
Contact Rating Code Max Operating Voltage (V) Network Type Making Max Load (VA) Breaking Max Load (VA)
Designation
A600 600 AC 7200 720
B600 600 AC 3600 360
C600 600 AC 1800 180
D300 300 AC 432 72
E150 150 AC 216 36
N600 600 DC 275 275
P600 600 DC 138 138
Q600 600 DC 69 69
R300 300 DC 28 28
Note: A
600 and N600 are the highest categories and may be used to cover all cases.
M E R S E N .CO M AP 31
Selectivity A P P L I C AT I O N
Between 240, 480, or 600V Main and Branch Fuses I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
two fuses are said to be selective if the downstream
fuse opens while the upstream fuse remains operable
M E R S E N .CO M AP 32
Quick Three-Phase
A P P L I C AT I O N
Short Circuit Calculations I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
Is it ok to replace only the open fuses?
M E R S E N .CO M AP 33
SCCR and A P P L I C AT I O N
11 Reasons for Using Current Limiting Fuses I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
components with the lowest individual SCCR in the adversely affected by the passage of time.
circuit. If there is no feeder over-current protective
device (OCPD) this component is the weakest link Minimal Maintenance: Fuses do not require periodic
and would determine the overall SCCR of the panel. recalibration as do electromechanical overcurrent
Typically the feeder circuit will have an OCPD and protective devices.
we must consider its current-limiting effects on the
Component Protection: The current limiting action
circuit.
of a fuse minimizes or eliminates component
The feeder OCPD may limit fault currents enough damage.
so that the weakest link components are protected
North American Standards: Tri-national Standards
and the panel can have a higher overall SCCR. For
specify fuse performance and maximum allowable
more information please contact Mersen Technical
fuse Ip and I2t let-thru values.
Services at 978-248-8914 or technicalservices.nby@
mersen.com. Selectivity: Fuses may be easily coordinated to
provide selectivity under both overload and short
circuit conditions.
M E R S E N .CO M AP 34
Fuse A P P L I C AT I O N
Obsolescence I N F O R M AT I O N
THREE CLUES FOR DETECTING WHEN Once fuses absorb too much moisture, they lose
their interrupting (safety) capacity. Even if they are
IS A FUSE TOO OLD FOR STOREROOM
dried out after the exposure, they are permanently
INVENTORY damaged. In normal use they generate enough heat
Storeroom managers often have the responsibility to keep themselves safe from absorbing moisture,
for identifying obsolete inventory. There are but not in storage. The absorption of moisture
advantages to having the right inventory for permanently changes the structure of the filler
needs, without the clutter of fuses that should packing around the fuse link and consequently
never be used. Obsolete fuses can mask stock- decreases the safety capacity.
out of important spare fuses resulting in needless
A common check for water damage is to check
emergencies. Sometimes, an electrician will
for wrinkling on the fuse’s paper label. If the paper
mistakenly use an obsolete fuse and create a
label is wrinkled, it indicates excessive moisture
dangerous safety condition.
during storage. Also, any water stains on the fuse
What conditions would make a fuse obsolete? There body or corrosion on the ends can indicate moisture
is functional obsolescence, concealed damage damage.
obsolescence, and age obsolescence. Any of these
Other concealed damage can occur when a fuse
conditions justify discarding a fuse. The electrical
is used and returned to the storeroom. Any fuse
safety experts at Mersen offer the following three
that show scratches on the blades or ferrules was
clues for determining when a fuse should be
probably inserted into fuse clips and returned to
removed from storeroom inventory:
inventory.
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
1. Functional Obsolescence
3. Fuses Over 10 Years Old
Functional obsolescence occurs when the fuse
When fuses are more than 10 years old, the history
can’t protect the equipment due to changes in the
of these fuses is uncertain. More than likely, they
electrical system, or when the end-use equipment
were exposed to moisture or damaging conditions
needing this particular fuse has been abandoned.
sometime during the 10 years of storage. This would
Either way, the fuse will not help in restoring the
make them unsafe and unreliable for maintenance.
equipment to service. If it’s accidently used by an
Most manufacturers mark a date code on their
electrician, it could create a hazardous situation.
fuses.
An example of a functionally obsolete fuse is a One-
Time with a safety rating of only 10kA IR. When the Summary
fuse was originally purchased, it could have had an If storeroom fuses exhibit functional obsolescence,
adequate safety rating. Now the electrical system signs of moisture damage, or are more than 10 years
has changed and requires a safety rating of more old, they should be replaced. For a free fuse audit
than 10kA. If the fuse is installed without adequate and inventory analysis, visit call 978-462-6662.
IR as required by OSHA, it could explode or cause
personal injury.
2. Concealed Damage
Obsolescence can be caused by concealed
damaged. An electrician normally only checks
for fuse continuity to determine its suitability for
continued service. But other concealed damage
can occur in storage. The biggest threat to fuses in
storage is moisture.
M E R S E N .CO M AP 35
Suggested Fuse A P P L I C AT I O N
Specifications I N F O R M AT I O N
© 2024 Mersen. All rights reserved. Mersen reserves the right to change, update, or correct, without notice, any information contained in this datasheet.
shall be a minimum of 8 seconds) and shall be
UL Listed and CSA Certified with an interrupting 4.0 Execution
rating of 200,000 amperes rms symmetrical. A. Fuses shall not be installed until equipment is
C. Motor Protection to be energized. All fuses shall be of the same
All individual motor circuits shall be protected manufacturer to assure selective coordination.
by Mersen Amp-Trap 2000® Class RK1, Class J B. As-installed drawings shall be submitted to the
or Class L time-delay fuses as follows: engineer after completion of the job.
C. All fusible equipment rated 600 amperes or less
Circuits up to 480A: Class RK1 - A2D (250V) or shall be equipped with fuse clips to accept Class
A6D(600V) RK1 or Class J fuses as noted in the specifications.
Class J - AJT
5.0 Substitution
Circuits over 480A: Class L - A4BQ
Fuse sizes and types indicated on drawings are based
Fuse sizes for motor protection shall be on Mersen Amp-Trap 2000® fuse current-limiting
chosen from tables published by Mersen for performance and selectivity ratios. Alternative
the appropriate motor rating. Heavy load submittals to furnish materials other than those
and maximum fuse ratings are also shown specified, shall be submitted to the engineer in writing
for applications where typical ratings are not two weeks prior to bid date, along with a short circuit
sufficient for the starting current of the motor. and selective coordination study.
D. Motor Controllers
Motor controllers shall be protected from short
circuits by Mersen Amp-Trap 2000® time-
delay fuses. For Type 2 protection of motor
controllers, fuses shall be chosen in accordance
with motor control manufacturers’ published
recommendations, based on Type 2 test results.
The fuses shall be Class RK1 A2D (250V) or
A6D (600V) or Class J AJT or Class CC ATDR
(600V).
M E R S E N .CO M AP 36