Midea Datos de Ingenieria VRF IDU
Midea Datos de Ingenieria VRF IDU
Engineering Data
Medium Static Pressure Duct
VRF IDU
MIH15T2HN18 MIH71T2HN18
MIH22T2HN18 MIH80T2HN18
MIH28T2HN18 MIH90T2HN18
MIH36T2HN18 MIH112T2HN18
MIH45T2HN18 MIH140T2HN18
MIH56T2HN18 MIH160T2HN18
V8 VRF Indoor Units
2 Dimensions.................................................................................................... 7
3 Unit Placement.............................................................................................. 9
6 Capacity Tables............................................................................................ 13
3
V8 VRF Indoor Units
1 Specifications
Table 1.1: MIH15(22,28,36)T2HN18 specifications
Model MIH15T2HN18 MIH22T2HN18 MIH28T2HN18 MIH36T2HN18
Power supply 1-phase, 220-240V, 50/60Hz
kW 1.5 2.2 2.8 3.6
Capacity
Cooling1 kBtu/h 5.1 7.5 9.6 12.3
Power input W 33 36 40 50
kW 1.8 2.5 3.2 4
Capacity
Heating2 kBtu/h 6.1 8.5 10.9 13.7
Power input W 33 36 40 50
Fan motor type DC
Midea V8 Series VRF Indoor Units Engineering Data Book
Number of rows 2 2 2 2
Tube pitch mm 18×10.72
Fin spacing and type mm 1.35 Hydrophilic aluminum
Indoor coil
Tube OD and type mm Ф5 Inner-groove
Dimensions (L×H×W) mm 400×21.44×360
Number of circuits 5 5 5 5
470/438/407/375/3 500/467/433/400/3 540/503/467/430/ 575/535/495/455/
Air flow rate3 m3/h
43/312/280 67/333/300 393/357/320 415/375/335
External static pressure4 Pa 30 (10-160)
26.5/26/25/24/23/2 26.5/26/25/24/23/2 26.5/26/25/24/23/ 29/28/27/26/25/2
Sound pressure level5 dB(A)
2.5/22 2.5/22 22.5/22 3/22
46/44.5/43/41.5/40 47/45.5/44/42.5/41 47/45.5/44/42.5/4 50/48.5/47/45/43/
Sound power level dB(A)
/38.5/37 /39.5/38 1/39.5/38 41/39
Net dimensions6 (W×H×D) mm 600×245×750
Packed dimensions
Unit mm 765×305×885
(W×H×D)
Net/Gross weight kg 18.5/21
Refrigerant type R410A/R32
Throttle type Electronic expansion valve
Design pressure (H/L) MPa 4.4/2.6
Pipe Liquid/Gas pipe mm Ф6.35/Ф12.7
connections Drain pipe mm OD Ф25
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level
difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range
may lead to higher noise levels and lower airflow rate. For the optimal external static pressure range refer to the un it’s installation
manual.)
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below
the unit in an anechoic chamber.
6. The dimension is only the body size, excluding the size of the installation lug, connecting copper pipe, etc. For detailed dimensions,
please refer to the installation manual
7. All specifications are measured at standard external static pressure
8. G1 air filter is standard for Medium Static Pressure Duct.
4
V8 VRF Indoor Units
Table 1.2: MIH45(56,71,80)T2HN18 specifications
Model MIH45T2HN18 MIH56T2HN18 MIH71T2HN18 MIH80T2HN18
Power supply 1-phase, 220-240V, 50/60Hz
kW 4.5 5.6 7.1 8
Capacity
Cooling1 kBtu/h 15.4 19.1 24.2 27.3
Power input W 70 70 96 102
kW 5 6.3 8 9
Capacity
Heating2 kBtu/h 17.1 21.5 27.3 30.7
Power input W 70 70 96 102
Fan motor type DC
Number of rows 3 2 3 2
Tube pitch mm 18×10.72
Fin spacing and type mm 1.35 Hydrophilic aluminum
Indoor coil
Tube OD and type mm Ф5 Inner-groove
Dimensions (L×H×W) mm 400×32.16×360 600×21.44×360 600×32.16×360 850×21.44×360
Number of circuits 5 5 10 10
665/623/580/538/4 970/904/838/773 1150/1068/986/9 1355/1263/1172/1
Air flow rate3 m3/h
95/453/410 /707/641/575 04/822/740/660 080/988/897/805
External static pressure4 Pa 30 (10-160) 40 (10-160)
33/32/29.5/28/26.5 33/32/31/30/27.5 35/33.5/32/30.5/ 37/35.5/34/32.5/31
Sound pressure level5 dB(A)
/25/24 /26/25 29/27.5/26 /29.5/28
53/51/49/47/45/43 55/53/51/49/47/4 58/56/54/51.5/48 59/57/55/53/51/49
Sound power level dB(A)
/41 5/43 /47/45 /47
Net dimensions6 (W×H×D) mm 600×245×750 800×245×750 1050×245×750
Unit Packed dimensions (W×H×D) mm 765×305×885 965×305×885 1215×305×885
Net/Gross weight kg 19.5/22 24/27.5 25/28.5 30/34.0
Refrigerant type R410A/R32
Throttle type Electronic expansion valve
Design pressure (H/L) MPa 4.4/2.6
Pipe Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.52/Ф15.9
connections Drain pipe mm OD Ф25
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level d ifference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher
noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit’s installation manual.)
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in an
anechoic chamber.
6. The dimension is only the body size, excluding the size of the installation lug, connecting copper pipe, etc. For detailed dimensions, please refer to the
installation manual.
7. All specifications are measured at standard external static pressure
8. G1 air filter is standard for Medium Static Pressure Duct.
5
V8 VRF Indoor Units
Table 1.3: MIH90(112,140,160)T2HN18 specifications
Model MIH90T2HN18 MIH112T2HN18 MIH140T2HN18 MIH160T2HN18
Power supply 1-phase, 220-240V, 50/60Hz
kW 9 11.2 14 16
Capacity
Cooling1 kBtu/h 30.7 38.2 47.8 54.6
Power input W 110 138 172 210
kW 10 12.5 16 18
Capacity
Heating2 kBtu/h 34.1 42.7 54.6 61.4
Power input W 110 138 172 210
Fan motor type DC
Number of rows 3 2 3 3
Midea V8 Series VRF Indoor Units Engineering Data Book
6
V8 VRF Indoor Units
2 Dimensions
2.1 Unit Dimensions
Figure 2.1: External dimension, air outlet size, and size of fresh air outlet (unit: mm)
Φ100 10
34
225
3-Φ5
142
6-M4
227
245
179
54
Φ110
24.5
45 B 750
A 770
Figure 2.2: Size of return air inlet (rear return air mode): (unit: mm) Figure 2.3: Piping and water pipe size:(unit: mm)
I (liquid side)
H (gas side)
External thread of connector
External thread
Φ23
of connector (inner diameter)
D D E
78
103
8 M4
143
221
104.5 78.5
209
245
186 Φ25
380 (outer diameter)
C
9
412
Figure 2.4: Size of return air inlet (bottom return air mode) and distance between lifting lugs:(unit: mm)
14 13
G
35
12
65
M4
630
104.5 78.5
227
209
9
E D D
8 Electric control component
F
7
V8 VRF Indoor Units
Table 2.1: Letter-Size Correspondence Table: (unit: mm)
Capacity (kW) A B C D E F G H I
7.1<kW<11.2 1050 850 940 220 146 956 1095 7/8-14 UNF 5/8-18 UNF
8
V8 VRF Indoor Units
3 Unit Placement
3.1 Placement Considerations
Unit placement should take account of the following considerations:
Units should not be installed in the following locations:
A place filled with mineral oil, fumes or mist, like a kitchen.
A place where there are corrosive gases, such as acid or alkaline gases..
A place exposed to combustible gases and using volatile combustible gases such as diluent or gasoline.
A place where there is equipment emitting electromagnetic radiation.
A place where there is a high salt content in the air like a coast.
Do not use the air conditioner in an environment where an explosion may occur.
Places like in vehicles or cabin rooms.
Factories with major voltage fluctuations in the power supplies.
Other special environmental conditions.
Units should be installed in positions where:
Ensure that the airflow in and out of the IDU is reasonably organized to form an air circulation in the room.
Ensure IDU maintenance space.
The nearer the drainage pipe and copper pipe are to the ODU, the lower the pipe cost is.
Prevent the air conditioner from blowing directly to the human body.
The closer the wiring to the power cabinet, the lower the wiring cost is.
Keep the air-conditioning return air away from the setting sun of the room.
Be careful not to interfere with the light tank, fire pipe, gas pipe and other facilities.
The IDU should not be lifted in the places like load-bearing beam and columns that affect the structural safety of
the house.
The wired controller and the IDU should be in the same installation space; otherwise, the sampling point setting
of the wired controller need to be changed.
Figure 3.1: Medium Static Pressure Duct space requirements (unit: mm)
≥200mm
600mmx600mm
Maintenance space
(access hole)
≥20
≥30 ≥200
≥200mm Maintenance space
≥300mm
Maintenance
Maintenance
space
space
Access hole
Notes:
1. The centerline of the maintenance hole should be in the same position as the centerline of the indoor unit.
9
V8 VRF Indoor Units
4 Piping Diagram
Figure 4.1: Medium Static Pressure Duct piping diagram
4
3
2
Gas pipe
6
Midea V8 Series VRF Indoor Units Engineering Data Book
5 Liquid pipe
1
10
V8 VRF Indoor Units
5 Wiring Diagram
Figure 5.1: Medium Static Pressure Duct wiring diagram
11
V8 VRF Indoor Units
Caution
All installation, servicing and maintenance must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation.
Units should be grounded in accordance with all applicable legislation. Metal and other conductive components
should be insulated in accordance with all applicable legislation.
Power supply wiring should be securely fastened at the power supply terminals – loose power supply wiring
would represent a fire risk.
After installation, servicing or maintenance, the electric control box cover should be closed. Failing to close the
electric control box cover risks fire or electric shock.
The dotted lines indicate the field wiring or optional function.
Midea V8 Series VRF Indoor Units Engineering Data Book
PQ and M1M2 communication ports both are used for indoor and outdoor communication, and only one of them
can be used at a time. Meanwhile, be sure to connect the same communication ports (PQ to PQ; M1M2 to
M1M2) in case of damage of the main control board.
D1D2 communication ports are used for group control communication. When connecting the group controller,
the D1D2 port of the indoor units that are to be group controlled must be connected in daisy chain, and the
group controller must be connected to the X1X2 port of one of the indoor units in the group control, and set to
group control mode. In addition, D1D2 communication ports can also be connected to the central controller.
12
V8 VRF Indoor Units
6 Capacity Tables
6.1 Cooling Capacity Table
Table 6.1: Medium Static Pressure Duct cooling capacity
Indoor air temperature (°C WB/DB)
Model 14/20 16/23 18/26 19/27 20/28 22/30 24/32
TC SC TC SC TC SC TC SC TC SC TC SC TC SC
MIH15T2HN18 1.4 1.3 1.5 1.4 1.5 1.3 1.5 1.3 1.6 1.3 1.6 1.2 1.6 1.1
MIH22T2HN18 2.0 1.9 2.1 1.9 2.2 1.9 2.2 1.8 2.3 1.8 2.3 1.7 2.4 1.7
MIH28T2HN18 2.5 2.3 2.7 2.4 2.8 2.4 2.8 2.3 2.9 2.3 2.9 2.2 3.0 2.1
MIH36T2HN18 3.2 3.0 3.4 3.1 3.6 3.1 3.6 3.0 3.7 3.0 3.8 2.8 3.9 2.7
MIH45T2HN18 4.0 3.7 4.3 3.8 4.5 3.9 4.5 3.7 4.6 3.6 4.7 3.5 4.8 3.3
MIH56T2HN18 5.0 4.6 5.3 4.7 5.6 4.8 5.6 4.6 5.7 4.5 5.8 4.3 6.0 4.1
MIH71T2HN18 6.3 5.8 6.7 5.9 7.0 6.0 7.1 5.8 7.2 5.7 7.4 5.4 7.6 5.2
MIH80T2HN18 7.1 6.3 7.6 6.5 7.9 6.6 8.0 6.5 8.1 6.3 8.3 6.0 8.5 5.8
MIH90T2HN18 8.0 7.1 8.5 7.3 8.9 7.4 9.0 7.3 9.1 7.1 9.4 6.8 9.6 6.5
MIH112T2HN18 9.9 8.8 10.6 9.1 11.1 9.3 11.2 9.1 11.3 8.8 11.6 8.4 11.9 8.1
MIH140T2HN18 12.4 11.1 13.2 11.4 13.8 11.5 14.0 11.3 14.2 11.0 14.5 10.5 14.9 10.1
MIH160T2HN18 14.2 12.7 15.1 13.0 15.8 13.2 16.0 12.9 16.2 12.6 16.6 12.0 17.0 11.5
Abbreviations:
TC: Total capacity (kW)
SC: Sensible capacity(kW)
Notes:
1.Shaded cells indicate rating condition.
Notes:
1.Shaded cells indicate rating condition.
13
V8 VRF Indoor Units
7 Electrical Characteristics
Table 7.1: Medium Static Pressure Duct electrical characteristics
Power supply Indoor Fan Motor
Model name Rated power
Hz Volts Min. volts Max. volts MCA MFA FLA
output (W)
MIH15T2HN18 50/60 220-240 198 264 0.63 15 50 0.50
MIH22T2HN18 50/60 220-240 198 264 0.63 15 50 0.50
MIH28T2HN18 50/60 220-240 198 264 0.63 15 50 0.50
MIH36T2HN18 50/60 220-240 198 264 0.80 15 50 0.64
MIH45T2HN18 50/60 220-240 198 264 1.19 15 50 0.95
MIH56T2HN18 50/60 220-240 198 264 1.19 15 60 0.95
MIH71T2HN18 50/60 220-240 198 264 1.50 15 60 1.2
Midea V8 Series VRF Indoor Units Engineering Data Book
14
V8 VRF Indoor Units
8 Sound Levels
8.1 Overall
Table 8.1: Medium Static Pressure Duct sound pressure levels1 Figure 8.2: Medium Static Pressure Duc sound
pressure level measurement
Sound pressure levels dB
Model name
SSH SH H M L SL SSL
ΔP=External static pressure
MIH15T2HN18 26.5 26 25 24 23 22.5 22
MIH22T2HN18 26.5 26 25 24 23 22.5 22 Outlet duct Inlet duct
MIH28T2HN18 26.5 26 25 24 23 22.5 22
MIH36T2HN18 29 28 27 26 25 23 22
2m 1m
1.5m
MIH45T2HN18 33 32 29.5 28 26.5 25 24
Adjustable grille Attached air filter
.
MIH56T2HN18 33 32 31 30 27.5 26 25
MIH71T2HN18 35 33.5 32 30.5 29 27.5 26 Measurement location
MIH80T2HN18 37 35.5 34 32.5 31 29.5 28
MIH90T2HN18 37 35.5 34 32.5 31 29.5 28 Connected to a top-discharge outdoor unit and
Figure 8.3: MIH15T2HN18 octave band levels Figure 8.4: MIH22T2HN18 octave band levels
90 90
Octave band sound pressure level dB
80 80
70 NC-70 70 NC-70
60 NC-60
60 NC-60
50 NC-50
50 NC-50
40 NC-40
40 NC-40
30 NC-30
30 NC-30
20 NC-20
20
NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
15
V8 VRF Indoor Units
Figure 8.5: MIH28T2HN18 octave band levels Figure 8.6: MIH36T2HN18 octave band levels
90 90
Octave band sound pressure level dB
60 NC-60
60 NC-60
50 50
NC-50 NC-50
40 NC-40
40 NC-40
30 NC-30
30 NC-30
20 20
NC-20 NC-20
10 10
Midea V8 Series VRF Indoor Units Engineering Data Book
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
Figure 8.7: MIH45T2HN18 octave band levels Figure 8.8: MIH56T2HN18 octave band levels
90 90
Octave band sound pressure level dB
80 80
70 NC-70 70 NC-70
60 NC-60
60 NC-60
50 50 NC-50
NC-50
40 40 NC-40
NC-40
30 30 NC-30
NC-30
20 20
NC-20 NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
Figure 8.9: MIH71T2HN18 octave band levels Figure 8.10: MIH80T2HN18 octave band levels
90 90
Octave band sound pressure level dB
80 80
70 NC-70 70 NC-70
60 NC-60
60 NC-60
50 NC-50
50
NC-50
40 NC-40
40 NC-40
30 NC-30
30 NC-30
20 20
NC-20 NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
16
V8 VRF Indoor Units
Figure 8.11: MIH90T2HN18 octave band levels Figure 8.12: MIH112T2HN18 octave band levels
90 90
Octave band sound pressure level dB
60 NC-60
60 NC-60
50 NC-50
50 NC-50
40 NC-40
40 NC-40
30 NC-30
30 NC-30
20 NC-20
20
NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
Figure 8.13: MIH140T2HN18 octave band levels Figure 8.14: MIH160T2HN18 octave band levels
90 90
Octave band sound pressure level dB
80 80
70 NC-70 70 NC-70
60 NC-60
60 NC-60
50 50
NC-50 NC-50
40 NC-40
40 NC-40
30 NC-30
30 NC-30
20 20
NC-20 NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
17
V8 VRF Indoor Units
9 Fan Performance
9.1 How to switch between Constant Airflow mode and Constant Speed mode
①In the main interface, press " " +" " for 3 seconds at the same
time, and the main interface will display "CC". Press the "▲" and "▼"
to select the indoor unit ("n00-n63" is displayed, and the last two
digits are the indoor unit addresses). Press the " " to enter the
parameter setting interface, and "n00" will be displayed.
②Press the "▲" and "▼" until "N30" is displayed on the page, and
then press the " " to enter the mode setting. Use the "▲" and "▼"
keys to adjust to the demand mode parameter values, and press the "
Midea V8 Series VRF Indoor Units Engineering Data Book
" to confirm.
③Press the " " button to return to the previous menu and exit the
parameter setting. Parameter setting will also exit after 60 s of no
operation
Notes:
1. The above is only an example. If you choose other controllers, please refer to their instructions for setting.
180 180
SSH SSH
External static pressure [pa]
170
External static pressure [pa]
170
160 160
150 SH 150 SH
140 140
130 H 130 H
120 120
110 M 110 M
100 100 L
90 L 90
80 SL 80 SL
70 70
60 SSL SSL
60
50 50
40 40
30 30
20 20
10 10
0 0
220 250 280 310 340 370 400 430 460 490 240 270 300 330 360 390 420 450 480 510
18
V8 VRF Indoor Units
Figure 9.3: MIH28T2HN18 Figure 9.4: MIH36T2HN18
170
160 160
150 SH 150 SH
140 140
130 H 130 H
120 120
110 M 110 M
100 100
90 L 90 L
80 SL 80 SL
70 70
60 SSL 60
50 50 SSL
40 40
30 30
20 20
10 10
0 0
260 290 320 350 380 410 440 470 500 530 560 290 320 350 380 410 440 470 500 530 560 590
Air flow rate [m³/h] Air flow rate [m³/h]
160 160
150 SH 150 SH
140 140
130 H 130 H
120 M 120
110 110 M
100 L 100 L
90 90
80 SL 80 SL
70 70
60 60
50 SSL 50 SSL
40 40
30 30
20 20
10 10
0 0
370 400 430 460 490 520 550 580 610 640 670 480 530 580 630 680 730 780 830 880 930 980
180 180
SSH
External static pressure [pa]
SSH
External static pressure [pa]
170 170
160 160
150 SH 150 SH
140 140
130 H 130 H
120 120
110 M 110 M
100 100 L
90 L 90
80 SL 80 SL
70 70
60 60
50 SSL 50 SSL
40 40
30 30
20 20
10 10
0 0
540 610 680 750 820 890 960 1030 1100 1170 680 750 820 890 960 1030 1100 1170 1240 1310 1380
Air flow rate [m³/h] Air flow rate [m³/h]
19
V8 VRF Indoor Units
Figure 9.9: MIH90T2HN18 Figure 9.10: MIH112T2HN18
170 170
160 SH 160
150 150 SH
140 H 140
130 130 H
120 M 120 M
110 110
100 L 100
90 90 L
80 SL 80 SL
70 70
60 SSL 60
50 50 SSL
40 40
30 30
20 20
10 10
0 0
1100 1210 1320 1430 1540 1650 1760 1870 1980 2090 1200 1330 1460 1590 1720 1850 1980 2110 2240 2370
20
V8 VRF Indoor Units
9.3 Constant Speed mode
9.3.1 Set external static pressure parameters
①In the main interface, press " " +" " for 3 seconds at the same time,
and the main interface will display "CC". Press the "▲" and "▼" to select
the indoor unit ("n00-n63" is displayed, and the last two digits are the
indoor unit addresses). Press the " " to enter the parameter setting
interface, and "n00" will be displayed.
②When "n00" is displayed, press the " " to enter the static pressure
setting. Use the "▲" and "▼" keys to adjust to the demand parameter
Level 00 01 02 03 04 05 06 07 08 09 10
Static
0 5 10 15 20 25 30 40 50 60 70
pressure(Pa)
Level 11 12 13 14 15 16 17 18 19
Static
80 90 100 110 120 130 140 150 160
pressure(Pa)
Notes:
1. The above is only an example of 86S wired controller. If you choose other controllers, please refer to their manuals for setting.
21
V8 VRF Indoor Units
Figure 9.15: MIH28T2HN18 Figure 9.16: MIH36T2HN18
Midea V8 Series VRF Indoor Units Engineering Data Book
22
V8 VRF Indoor Units
Figure 9.21: MIH90T2HN18 Figure 9.22: MIH112T2HN18
23
T-V8T2H
Ver. 2023-10