Woodward Easygen 2300 - 2500 Vs DEIF AGC 150 Comparison File

The document compares four models of Woodward controllers: Easygen 2300, Easygen 2500, AGC150 Core, and AGC150 extended. It outlines their features, including display types, communication options, inputs/outputs, protection mechanisms, and power management capabilities. Each model has unique specifications and functionalities tailored for different applications in power management and control systems.

Uploaded by

rikirik2008
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views3 pages

Woodward Easygen 2300 - 2500 Vs DEIF AGC 150 Comparison File

The document compares four models of Woodward controllers: Easygen 2300, Easygen 2500, AGC150 Core, and AGC150 extended. It outlines their features, including display types, communication options, inputs/outputs, protection mechanisms, and power management capabilities. Each model has unique specifications and functionalities tailored for different applications in power management and control systems.

Uploaded by

rikirik2008
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

MAKE WOODWARD WOODWARD DEIF DEIF

Type Easygen 2300 Easygen 2500 AGC150 Core AGC150 extended

Display-LCD    

Keypad   

Configurable alarm name NA NA Alarm configurable Alarm configurable

Communication

Service port USB / RS232 requires WW special cable USB / RS232 requires WW special cable USB printer cable / ethernet USB printer cable / ethernet

CANBUS1    
depende upon package P1/P2. If MPU selected in
CANBUS2 ( Engine communication ) Package then ENGINE ECU CAN CANBUS2 will not   
available.

Digital AVR support NA NA  

J1939 (Volvo,MTU,Perkins,Cummins,Scania, John-


Deere, depende upon package P1/P2. If MPU selected in
Package then ENGINE ECU CAN CANBUS2 will not  - -
available.
Caterpillar,Iveco,Detroit Diesel,Deutz )

Modbus TP/IP / ethenet port NA NA   `


depende upon package P1/P2. If ENGINECAN ECU
MODBUS, RS485 CANBUS2 selected in Package thenRS485 will not be 1 nos. of RS 485 port 2 nos. of RS 485 port 2 nos. of RS 485 port
available.

Changeable controller type/ model ( DG to Grid to BTB


NA NA NA 
)

INPUTS / OUTPUTS

Digital inputs 8 10 12 12

Relay outputs basic unit 6 11 12 12

ANALOG I/O 4-20 mA

Analog in(VDO,RMI, 4-20mA,0-10vdc) 3 4 4 ( Configurable ) 4 ( Configurable )

change analog input to binary input N.A. N.A. If analog input not used can be convert into Binay input If analog input not used can be convert into Binay input

Analog out(4-20mA,0-20mA, O-10 volt , +/- 10 Volt) 2 4 2(AVR & GOV control) 2(AVR & GOV control)

ANALOG INPUT FOR MEASURING

3 CT’s for FEEDER CURRENT    

CT for GROUND CURRENT 1 ( Earth fault /mains


N.A.   
current measuremnt )
3 PT’s for FEEDER VOLTAGE    

3 PT’s for BUS VOLTAGE 1    

Protection ANSI

Reverse Power     32R

Reverse Current     46

Short Circuit N.A. N.A.   50P

Over Current     51

IEEE/ IEC inverse time over current   N.A.  51 IEEE

Voltage Dependent Over Current N.A. N.A.   51V

Over Voltage     59P

Under Voltage     27P

Over Frequency     81O

Under Frequency     81U

Unbalance Voltage     47

Unbalance Current     46

Under Excitation     32RV

Over Excitation     32FV

Over Load     32

Earth Fault N.A.    51G

Neutral current Fault ( Either neutral current ot earth


N.A. N.A.   51N
fault )

Over Speed     12

Phase Sequence Error     47

Crank Faliure     48

Hz/ V faliure     53

Battery Over Voltage     59DC

Battery Under Voltage     27DC

Vector Surge/ Out Of Step Triping   (grid controller ) - 78/78S

df/dt(ROCOF)   (grid controller )  81R

Directional Over Current N.A. N.A. N.A.  67

Bus Voltage Supervision     27B/59B

Circuit Breaker Faliure     50BF

Auto Synchronization     25A

Synch Check Relay     25

Zero seq.voltage high N.A. N.A. N.A.  50G

Zero seq.current high N.A. N.A. N.A.  59G

Negative seq. voltage High N.A. N.A. N.A.  47

Negative seq. current High N.A. N.A. N.A.  46

Step-up transformer (with phase angle compensation) N.A. N.A. N.A. 


RECORDING UNIT

500 nos record (Event log with 500 entries (can 500 nos record (Event log with 500 entries (can be
Event log /History 300 300
be exported to a CSV file). exported to a CSV file).

500 nos record (Alarm log with 500 entries (can be 500 nos record (Alarm log with 500 entries (can be
Alarm log / History 300 300
exported to a CSV file). exported to a CSV file).

Power Management

DG synchronised Upto 16 Upto 16 Upto 32 Upto 32

Ground Relay Control / neutral contactor logic N.A. N.A. N.A. 

Symmetrical load sharing    

Common PF control    

Close Before Excitation N.A. N.A. N.A. 

Micro Logic (Mini PLC) N.A.   

Load sharing    

Power Management    

fixed power    

load shedding N.A. N.A. N.A. 

Load take over mode N.A. N.A.  

peak shaving N.A. N.A.  

Expansion IO module Upto 2 ( 16 DI & 16 DO ) Upto 2 ( 16 DI & 16 DO ) Upto 9 ( 48 DI, 24 DO, 24 AI ) Upto 9 ( 48 DI, 24 DO, 24 AI )

Support Solar hybrid application N.A. N.A. N.A. 

ENGINE PARAMETER Supervision    

Real Time View of Controller operation    

Emulation ( For FAT assitance ) N.A. N.A.  

Selectable CT ratio 1 A / 5 A ( through Controller Selectable CT ratio 1 A / 5 A ( through Controller keypad


Specific Model need to be order ( 1 or 5 A ) Specific Model need to be order ( 1 or 5 A )
keypad ) )
CT & PT Input
Upto 480 Vac Upto 480 Vac Upto 690 V (above 2000 m derate to max. 480 V) Upto 690 V (above 2000 m derate to max. 480 V)

 Available

NA Not available