MAKE WOODWARD WOODWARD DEIF DEIF
Type Easygen 2300 Easygen 2500 AGC150 Core AGC150 extended
Display-LCD
Keypad
Configurable alarm name NA NA Alarm configurable Alarm configurable
Communication
Service port USB / RS232 requires WW special cable USB / RS232 requires WW special cable USB printer cable / ethernet USB printer cable / ethernet
CANBUS1
depende upon package P1/P2. If MPU selected in
CANBUS2 ( Engine communication ) Package then ENGINE ECU CAN CANBUS2 will not
available.
Digital AVR support NA NA
J1939 (Volvo,MTU,Perkins,Cummins,Scania, John-
Deere, depende upon package P1/P2. If MPU selected in
Package then ENGINE ECU CAN CANBUS2 will not - -
available.
Caterpillar,Iveco,Detroit Diesel,Deutz )
Modbus TP/IP / ethenet port NA NA `
depende upon package P1/P2. If ENGINECAN ECU
MODBUS, RS485 CANBUS2 selected in Package thenRS485 will not be 1 nos. of RS 485 port 2 nos. of RS 485 port 2 nos. of RS 485 port
available.
Changeable controller type/ model ( DG to Grid to BTB
NA NA NA
)
INPUTS / OUTPUTS
Digital inputs 8 10 12 12
Relay outputs basic unit 6 11 12 12
ANALOG I/O 4-20 mA
Analog in(VDO,RMI, 4-20mA,0-10vdc) 3 4 4 ( Configurable ) 4 ( Configurable )
change analog input to binary input N.A. N.A. If analog input not used can be convert into Binay input If analog input not used can be convert into Binay input
Analog out(4-20mA,0-20mA, O-10 volt , +/- 10 Volt) 2 4 2(AVR & GOV control) 2(AVR & GOV control)
ANALOG INPUT FOR MEASURING
3 CT’s for FEEDER CURRENT
CT for GROUND CURRENT 1 ( Earth fault /mains
N.A.
current measuremnt )
3 PT’s for FEEDER VOLTAGE
3 PT’s for BUS VOLTAGE 1
Protection ANSI
Reverse Power 32R
Reverse Current 46
Short Circuit N.A. N.A. 50P
Over Current 51
IEEE/ IEC inverse time over current N.A. 51 IEEE
Voltage Dependent Over Current N.A. N.A. 51V
Over Voltage 59P
Under Voltage 27P
Over Frequency 81O
Under Frequency 81U
Unbalance Voltage 47
Unbalance Current 46
Under Excitation 32RV
Over Excitation 32FV
Over Load 32
Earth Fault N.A. 51G
Neutral current Fault ( Either neutral current ot earth
N.A. N.A. 51N
fault )
Over Speed 12
Phase Sequence Error 47
Crank Faliure 48
Hz/ V faliure 53
Battery Over Voltage 59DC
Battery Under Voltage 27DC
Vector Surge/ Out Of Step Triping (grid controller ) - 78/78S
df/dt(ROCOF) (grid controller ) 81R
Directional Over Current N.A. N.A. N.A. 67
Bus Voltage Supervision 27B/59B
Circuit Breaker Faliure 50BF
Auto Synchronization 25A
Synch Check Relay 25
Zero seq.voltage high N.A. N.A. N.A. 50G
Zero seq.current high N.A. N.A. N.A. 59G
Negative seq. voltage High N.A. N.A. N.A. 47
Negative seq. current High N.A. N.A. N.A. 46
Step-up transformer (with phase angle compensation) N.A. N.A. N.A.
RECORDING UNIT
500 nos record (Event log with 500 entries (can 500 nos record (Event log with 500 entries (can be
Event log /History 300 300
be exported to a CSV file). exported to a CSV file).
500 nos record (Alarm log with 500 entries (can be 500 nos record (Alarm log with 500 entries (can be
Alarm log / History 300 300
exported to a CSV file). exported to a CSV file).
Power Management
DG synchronised Upto 16 Upto 16 Upto 32 Upto 32
Ground Relay Control / neutral contactor logic N.A. N.A. N.A.
Symmetrical load sharing
Common PF control
Close Before Excitation N.A. N.A. N.A.
Micro Logic (Mini PLC) N.A.
Load sharing
Power Management
fixed power
load shedding N.A. N.A. N.A.
Load take over mode N.A. N.A.
peak shaving N.A. N.A.
Expansion IO module Upto 2 ( 16 DI & 16 DO ) Upto 2 ( 16 DI & 16 DO ) Upto 9 ( 48 DI, 24 DO, 24 AI ) Upto 9 ( 48 DI, 24 DO, 24 AI )
Support Solar hybrid application N.A. N.A. N.A.
ENGINE PARAMETER Supervision
Real Time View of Controller operation
Emulation ( For FAT assitance ) N.A. N.A.
Selectable CT ratio 1 A / 5 A ( through Controller Selectable CT ratio 1 A / 5 A ( through Controller keypad
Specific Model need to be order ( 1 or 5 A ) Specific Model need to be order ( 1 or 5 A )
keypad ) )
CT & PT Input
Upto 480 Vac Upto 480 Vac Upto 690 V (above 2000 m derate to max. 480 V) Upto 690 V (above 2000 m derate to max. 480 V)
Available
NA Not available