Maya 62P, Maya 85P Technical Manual
Maya 62P, Maya 85P Technical Manual
Revision
Page 1 of 116 0362M264.A
Log of Changes Made to This Manual
Page 2 of 116
Item Contents Page
1.0 Heights worldwide litho products contact information 5
1.1 Introduction to the Maya processor 7
1.2 Health and safety recommendations 9
2.0 Installation 11
2.1 Height extension bars (option) 11
2.2 Levelling the machine 12
2.3 Water and waste connection 13
2.4 Mains electrical connection 14
2.5 Connection of the power cable 15
2.6 Installing the chiller 16
3.0 The HMI screen 17
3.1 Engineering password code 17
3.2 Engineering password calculation table 19
4.0 Engineering screens 21
4.1 Process settings 23
4.2 Service utilities 27
4.3 Test menu 29
4.4 M/C Config menu 33
4.5 Settings menu 37
4.6 Exiting the engineering section 43
4.7 Re-enable the password 44
4.8 Guard switch override mode 45
5.0 Maya P HMI processor screen tree 47
6.0 PCB Jumper positions 61
6.1 Test points 61
6.2 DIP Switch setting position 62
6.3 Fuse ratings 63
6.4 Safety circuit by-pass switch 64
7.0 Calibrating the PT100 temperature probe input (PL5) 65
7.1 Calibrating the pre-heat thermocouple inputs 67
Page 3 of 116
7.2 Calibrating the developer replenishment pump 69
7.3 Calibrating the second developer replenishment pump (option) 69
7.4 Calibrating the interleaf paper detectors (option) 71
8.0 Setting the developer section level switch 77
8.1 In-feed and exit sensor sensitivity adjustment 78
9.0 Replacing the PCB 79
9.1 Selecting the machine identity 80
9.2 Clearing the Memory/Self check procedure 82
9.3 Advanced self test procedure 82
10.0 Upgrading the software 83
10.1 Upgrading the software by exchanging the EPROM 83
10.2 Upgrading the software by using the flash loader programme 83
10.3 Flash loader trouble shooting 87
11.0 Plate setter interface 93
11.1 Mini chiller 97
11.2 Chiller planned maintenance schedule 99
11.3 Functional explanation of the preheat 101
11.4 Carrying out a preheat temperature test 103
12.0 General fault finding 105
Page 4 of 116
1.0 - Heights World Wide Litho Products Contact Information
Heights UK
Postal Address;
Heights (UK) Ltd
Wainstalls
Halifax
West Yorkshire
HX2 7TJ
UK
Postal Address;
Heights-USA Inc
1445 Lower Ferry Road
Trenton
NJ 08628
USA
Postal Address;
Page 5 of 116
This page
intentionally left
blank
Page 6 of 116
1.1 – Introduction to the Maya Processor
The Maya 62P & 85P lithographic Ctp plate processors are manufactured by Heights UK
Ltd for distribution worldwide. Its design conforms to the latest safety standards
incorporating all the knowledge and experience gained from over 20 years of successful
manufacturing of previous conventional, thermal and red/green/violet processors. The
Maya provides a high value, quality solution for processing violet Ctp plates. The machines
can be installed as part of an automated plate line allowing communication with the plate
exposing devise or as a stand alone installation. The processor has been designed to be
user friendly with a minimum level of operator maintenance coupled with easy access to all
the internal components.
Please use this manual in conjunction with the full product training provided by Heights UK
Ltd, Heights USA or Heights Asia and the full range of technical documentation which
includes the Operator, Pre-installation, Installation, Electrical drawings and Spare parts
manuals.
Due to Heights Ltd commitment to continual improvement, we reserve the right to change
the specification and technical procedures covering the Maya processor at any time and
without prior notice. If there is any doubt about a specific setting or specification, please
seek advice from Heights.
IMPORTANT NOTICE
The use of this manual must be accompanied by adherence to local and national legal
regulations of the country in which the machine is installed. Failure to comply with health &
safety, electrical, water, waste or chemical handling regulations could result in legal
proceedings being pursued by the country of installations responsible authorities. Heights
UK Ltd and/or associated companies cannot accept liability for any subsequent legal
actions due to contravention of these regulations or for any damage to persons or property
or consequential loss arising from the misuse or modification of this product by
unauthorised personnel.
Page 7 of 116
This page
intentionally left
blank
Page 8 of 116
1.2 - Health & Safety Recommendations
i. For Health & Safety reasons only authorised and suitably qualified personnel are
to work on the Maya range of processors.
ii. All installation work should be carried out in accordance with the requirements
laid down in the statutory regulations or the national approved codes of practice
(ACOP) applicable to the country of installation.
iii. The machine is designed for processing lithographic printing plates and
must not be modified or used for any other purpose.
v. During normal operation, all covers, guards and doors must be closed and
where appropriate kept locked.
vi. Always isolate from the electrical supply before carrying out maintenance work
on the machine. NOTE: The lid safety switches and emergency stop switches
do NOT isolate the electrical supply inside the machine.
vii. The area around the machine should be kept clean, dry and clear of any waste
material.
viii. Access to the main electrical power isolator and the emergency stop buttons
must not be obstructed.
x. Health and safety precautions should always be adhered to when working with
plate processors. The wearing of gloves, goggles and protective clothing (PPE)
is recommended when working in the developer / wash section of the Processor.
These sections contain solutions, which can cause burns, and where bacteria
can be present, which can under certain circumstances cause infection.
Page 9 of 116
This page
intentionally left
blank
Page 10 of 116
2.0 - Installation
The installation, connection of services and commissioning of the machine must be carried
out by fully qualified technician and where required an electrician to ensure the electrical
connection conforms to local electrical installation laws. The installation site must be clean,
dry, free from vibration and strong enough to support the unit (Maya 62-425Kg / Maya 85-
475kg dry weight). There must also be sufficient room to operate the machinery efficiently.
It is recommended that the machine is at least 600mm from any wall or adjacent
equipment to allow easy access for operation and servicing. The machine can be moved
by using a forklift or pallet truck under the frame or by using the built in wheels (if fitted).
Ensure that the lifting equipment used is rated at a greater Safe Working Load
(SWL) than the maximum weight of the processor.
If the height of the standard Maya P is too low for the on-line equipment it is to be installed
with. Height extension bars can be ordered factory fitted with the Maya P or they can be
fitted on site. If they are to be fitted on-site, a fork lift truck will need to be available to lift
the Maya P sufficiently to allow the levelling feet and wheels to be removed. Fit the bars
using the existing bolts into the base of the machine. The levelling feet and wheels are
then fitted. Do not stand under the machine when it is on the fork lift truck. Take all
necessary safety precautions to ensure your safety! After levelling the machine is
completed (described in the following section), fit the plastic covers to the ends of the bars.
Page 11 of 116
2.2 - Levelling the Machine
To successfully install the Maya P, it is important to level the machine correctly. To do this,
use a level with a tolerance of 0.5mm/1M. Place the level in the 3 positions shown in the
pictures and level by means of the 4 levelling feet. The adjustment and locking nuts are 24
mm.
Page 12 of 116
2.3 – Water & Waste Connections
The water inlet (3/4” BSP) is centrally located on the brush drive side of the machine. It is
strongly recommended that a stopcock or gate valve be connected in the supply line at a
convenient point to allow local disconnection of the machine. The minimum water pressure
is 1.4 Bar and the water maximum pressure is 3 Bar. If the water supply is greater than
this, fit a pressure regulator valve. The drainage is provided by a ¾”hose tail fitting located
on the brush drive side. Although a flexible hose can temporarily be connected to this
fitting, it is strongly recommended that a permanent, solid PVC drain be installed to ensure
consistent waste water flow to drain.
The user must provide a water supply and waste connection that complies with
local water authority regulations.
Mains Water
Connection
Waste Connection
Page 13 of 116
2.4 – Mains Electrical Connection
The electrical cabinet is located on the conveyor drive side of the machine. The door is
locked by means of a special key (supplied) and an interlocked isolator switch.
The cable sizes shown are a minimum size only. The actual installation wiring size
required should be calculated in accordance with local electrical codes. All
electrical installation work must be carried out by a suitably qualified electrician.
Page 14 of 116
2.5 – Connection of the Power Cable
1W+N+PE or 2W+PE Installation - Provide a power supply cable into the electrical box. It
is recommended that the power supply is routed through a 2 pole wall mounted isolator
near to the machine so that the machine can be easily, quickly and safely disconnected
from the mains power supply. Connect the wires as shown below. To comply fully with the
EMC certification for the machine, route the mains power cable away from all other cables
in the electrical enclosure.
3W+N+PE Installation - Provide a power supply cable into the electrical box. It is
recommended that the power supply is routed through a 4 pole wall mounted isolator near
to the machine so that the machine can be easily, quickly and safely disconnected from
the mains power supply. Connect the wires as shown below. To comply fully with the EMC
certification for the machine, route the mains power cable away from all other cables in the
electrical enclosure.
After connection but before the machine is powered up. Test that the earth loop
impedance of the earth continuity conductor meets the recognised standard for the country
of installation.
Page 15 of 116
2.6 - Installing the Chiller
Carefully remove the chiller assembly from the packing box. Locate the 2 black hoses
stored inside the Maya P and connect them to the chiller as shown below. Secure with the
supplied hose clips. Locate the 2 chiller cables stored inside the Maya P and connect the
chiller using the plug and socket. These can only connect in 1 way so cannot be mixed up.
One is for the power supply to the compressor and electrics, the other connection is for the
pump.
Water
Tank System
Fault
Indicator
Level
Indicator &
Drain
Temperature
Controller
Pressure
Switch
Ensure that the level indicator hose is properly positioned (up to the top of the black plastic
holder as shown) and is properly secured. Enter the Engineering SectionÎ Service
UtilitiesÎ Test MenuÎ I/0 TestÎ Set/Clear OP. Scroll down the list to the “Chiller”. Fill
the tank with water slowly continuously checking the level. Stop once the level reaches the
low level mark. Use the “Toggle” button to start the “Chiller” pump. The level of the water
should drop as the hoses and cooling coil are filled. Fill the water up to between the “Min
Level” and “Max Level” marks. Exit all Engineering screens.
Page 16 of 116
3.0 - The HMI Screen
All adjustable settings on the Maya P processor are inputted via the Liquid Crystal Display
(LCD) Human Machine Interface (HMI) screen. The screens are divided into 2 sections.
Firstly there is the Operator section which displays the current condition of the machine,
the settings which have been inputted into the computer memory and the ability to carry
out every day tasks such as cleaning, sleep mode and plate thickness selection. For more
information on the Operator settings, please refer to the Operator Manual 0362M263.
Secondly there is the password protected section. This is also split into 2 sections; firstly
the Process settings section which allows changes to be made to settings such as
developer temperature and conveyor speed and secondly there is the Engineering section.
This contains screens such as the test menu, language selection, calibration menu and
plate path menu options. All these settings are protected by a 4 digit numeric password
code. How to access the Engineering screens is explained in the next section. The buttons
on either side of the LCD screen execute the commands displayed on the screen.
When entering the Engineering section from the Main Menu, you are asked for the 4 digit
password code. This is changed 6 times per day, 365 days a year. The password is
calculated using the table on the following 2 pages. The correct password code is
dependant on the time and date shown on the front screen display. Once the password
code has been entered successfully, this provides access to all parts of the operator and
utility settings within the Engineering Menu.
When the password protected area is exited and the machine reverts to normal operation
mode, you can re-enter the password protected area at any time within the next 60
minutes without re entering the code. Select the re enter option on exiting the Engineering
Menu. Each time you re enter within the 60 minutes, the 60 minutes is re set. After the 60
minutes has elapsed, the code must then be re entered. If, on exiting the Engineering
menu you wish to disable the re entry option, select the no re entry option.
Set Password
1 Exit 0 2
3 1 2 4
5 3 4 6
7 5 6 8
Page 17 of 116
This page
intentionally left
blank
Page 18 of 116
3.2 – Engineering Password Code Calculation Table
First check that the time and date are correct on the screen.
Hour
Day
Page 19 of 116
Day
Month
Page 20 of 116
4.0 – Engineering Screens
The Engineering Section contains the screens which allow the inputting of data & the
testing of components. To enter this section, use the Engineering password described in
the previous section. The different sections are organised as follows:
Engineering Menu
1 Exit 0277 2
3 4
Process Service
5 Settings Utilities 6
7 8
Please Note;
For information on the Operator Screens, please refer to the Maya P Operator Manual
0362M263.
Page 21 of 116
This page
intentionally left
blank
Page 22 of 116
4.1 - Process Settings
Within this section all the data such as conveyor speed, Pre-heat temperature, dryer
output & replenishment rates are inputted and settings are saved.
Process Settings
1 Exit 0276 2
Prewash/
3 Developer Menu Rinse/Gum 4
5 Preheat Menu 6
Selecting this button (as with all other screens) goes back to the previous screen.
3 – Developer Menu
Processor Speed – Allows the setting of the conveyor motor speed. This may be
done in m/m per minute (or inches per minute if imperial units are selected) or in
seconds, dip to nip (option selectable in M/c Config).
Developer Temperature – Allows the setting of the developer temperature in C° (or
F° if imperial units are selected).
Brush Speed – Allows the setting of the developer brush rotation speed in RPM.
Dev Replen Type – Provides the ability to enter a volume of developer
replenishment per M2 in ml which is automatically added to the developer bath
based on the plate sizes entered in the “Set Plate Sizes” screen or to turn the M2
developer replenishment off.
4 – Prewash/Rinse/Gum Menu
5 – Preheat Menu
This menu allows the inputting of individual temperature values for the 4 different plate
gauges available. Each plate gauge setting allows for the 3 zones to be individually set.
0.15 – Selecting this option will allow for the setting of the pre-heat zone settings for
0.15mm gauge plates.
PH Left 1 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.15 gauge plates for the outside left zone.
Page 23 of 116
PH Outer (Right) 1 – Enter a value in °C to provide the optimum
temperature measured on the plate for 0.15 gauge plates for the outside right
zone.
PH Inner 1 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.15 gauge plates for the inner zone.
Set Back – This is the temperature drop in °C that the pre-heat zone can
reduce to before the pre-heat starts to heat again. This function stops the
back edge of the plate overheating.
0.20 – Selecting this option will allow for the setting of the pre-heat zone settings for
0.20mm gauge plates.
PH Left 2 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.20 gauge plates for the outside left zone.
PH Outer (Right) 2 – Enter a value in °C to provide the optimum
temperature measured on the plate for 0.20 gauge plates for the outside right
zone.
PH Inner 2 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.20 gauge plates for the inner zone.
Set Back – This is the temperature drop in °C that the pre-heat zone can
reduce to before the pre-heat starts to heat again. This function stops the
back edge of the plate overheating.
0.24 – Selecting this option will allow for the setting of the pre-heat zone settings for
0.24mm gauge plates.
PH Left 3 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.24 gauge plates for the outside left zone.
PH Outer (Right) 3 – Enter a value in °C to provide the optimum
temperature measured on the plate for 0.24 gauge plates for the outside right
zone.
PH Inner 3 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.24 gauge plates for the inner zone.
Set Back – This is the temperature drop in °C that the pre-heat zone can
reduce to before the pre-heat starts to heat again. This function stops the
back edge of the plate overheating.
0.30 – Selecting this option will allow for the setting of the pre-heat zone settings for
0.30mm gauge plates.
PH Left 4 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.30 gauge plates for the outside left zone.
PH Outer (Right) 4 – Enter a value in °C to provide the optimum
temperature measured on the plate for 0.30 gauge plates for the outside right
zone.
PH Inner 4 – Enter a value in °C to provide the optimum temperature
measured on the plate for 0.30 gauge plates for the inner zone.
Set Back – This is the temperature drop in °C that the pre-heat zone can
reduce to before the pre-heat starts to heat again. This function stops the
back edge of the plate overheating.
7 – Dryer menu
Dryer Warm Up – Allows the option to start the Dryer Heater earlier if required.
Input this value in seconds.
Dryer Output – The heater output settable in %.
Page 24 of 116
8 - Data menu
Save Settings – Selecting this will save the current configuration to memory.
Changes cannot be undone.
Restore Settings – Restores basic configuration settings when an E2 ROM is fitted
from an old board after a PCB change.
Restore Cons data – Restores consumable data when an E2 ROM is fitted from an
old board after a PCB change.
Page 25 of 116
This page
intentionally left
blank
Page 26 of 116
4.2 – Service Utilities
The selection of screens available within the Service Utilities section of the Engineering
Menu consist of the following;
Service Utilities
1 Exit 0272 2
3 Test Settings 4
Alarm Cancel
5 M/c Config
Time 6
Watchdog Clear
7 Events Process DB
8
Selecting this button (as with all other screens) goes back to the previous screen.
3 – Test Menu
This menu contains screens, which allow for individual operation of components such as
heaters and pumps so that they can be tested individually or included in a group test.
4 – Settings Menu
This menu contains screens, which allow the input of all the machines operating
parameters such as replenishment calibration and heater controls setup.
This menu contains screens, which allow the input of all the machines operating
parameters such as replenishment calibration and heater controls setup.
Input the time in minutes that the alarm signal will return after cancelling.
7 - Watchdog Events
A log of all on/off events is kept along with electronic fault codes & data.
Selecting this option will re-set ALL data back to default values. All data will be lost.
Page 27 of 116
This page
intentionally left
blank
Page 28 of 116
4.3 - Test Menu
The Maya processor software comes complete with an on-board set of diagnostic tools for
testing electrical components on the machine. The tests can all be carried out from the
HMI.
Test
1 Exit 0271
Debug
2
Displays
Set Gum
5 Section
Motor Ctrl 6
Setter I/F
7 A to D Test
Test
8
Selecting this button (as with all other screens) goes back to the previous screen.
2 – Debug Displays
In this screen you have the option to select a number of different lines of information which
are displayed on the main screen.
All the screens except Watchdog & Error display a “Show” or “Hide” option. Selecting
“Show” displays the extra line of data on the normal operating screen.
Dose Data – Shows in real time a numerical countdown when the pumps are activated.
Plate Size Display – Displays a line of data which shows the measured length of the plate
as seen by the in-feed sensor. The selected plate size number (as inputted into the Plate
Size table) is also displayed.
Watchdog & Error – This allows the non-reversible clearing of sections of memory.
Clear Open Errors – Clears the Open Errors List in the Alarm History/Open
Alarms.
Clear Error List – Clears the entire error log in the Alarm History.
Clear Watch dog List – Clears the entire Watchdog List.
Clear Unused Change – If the processor displays a warning that a solution or filter
needs changing, but the option to change it is not displayed. This will remove the
warning. This only occurs after a major upgrade in software.
Setter Debug – For Heights use only.
Debug Exit Sensor – Shows the time at which the sensor turns on and at which time it
first detects the plate (off). There is also the option for a re-entry sensor which is not
available on the Maya.
Page 29 of 116
3 – I/O Test
Set/Clear OP – Use the “Toggle” button to turn each output component on or off
(I/O).
Display IP - This screen displays all the input components. Activating or de-
activating the component will display the I/O state. Selecting Beep X/I/O will turn off
the bleep, turn it on when the component is activated or turn it on when it is de-
activated.
4 - Heater Ctrl
This allows all the heating components to be tested. There are 5 options:
PH Right Test - Increase or decrease the % output from the right pre-heat zone.
The temperature as monitored by the K-type thermocouples is also displayed.
PH Left Test - Increase or decrease the % output from the left pre-heat zone. The
temperature as monitored by the K-type thermocouples is also displayed.
PH Inner Test – Increase or decrease the % output from the inner pre-heat zone.
The temperature as monitored by the K-type thermocouples is also displayed.
Developer Heater – Increase or decrease the % output from the heater cartridge in
the developer section. The temperature as monitored by the PT100 probe is
displayed.
Important – The developer section must be at least 50% full before this test is
carried out otherwise the heater, tank and PCB will be damaged.
Dryer Heater – Increase or decrease the % output from the dryer heater. The fans
will turn on automatically the heaters are started.
This provides the ability to manual start the conveyor and gum pump so that the gum
supply can be regulated for the optimum gum flow rate.
6 – Motor Ctrl
Drive – The screen allows the selecting of any conveyor speed from 500 mm per
min to 2000 mm per min. The monitored speed from the encoder is displayed. It is
normal for the displayed speed to fluctuate. The screen also displays the volts going
into the motor from the DC drive system and the amps consumed by the motor.
Brush - The screen allows the selecting of any brush rotation speed. The speed
selected is the rotational speed of the first brush, the second brush is slower. The
screen also displays the volts going into the motor from the DC drive system and
the amps consumed by the motor.
7 – A to D Test
Page 30 of 116
8 – I/F Test
To test the interface relays, enter one of the options shown below:
Depending on how the interface has been programmed (see the individual interface
instructions for the particular plate setter) the switching of the relays will be different.
Please note; any combination of tests such as conveyor/brush motors, heaters and output
components can be tested at the same time. Simply change screen to activate or de-
activate the required test components. The IP status can also be monitored at the same
time as output components are be tested.
Page 31 of 116
This page
intentionally left
blank
Page 32 of 116
4.4 – M/c Config Menu
To select different languages, change & fill options or Imperial units use the M/c Config
menu as follows:
M/c Config
1 Exit 0259
Change &
Fill 2
Languages
3 Offsets and Units 4
Selecting this button (as with all other screens) goes back to the previous screen.
Fill Times Menu – These screens allow the input in seconds of the maximum time
the fill functions will operate before being automatically stopped and the time in
seconds that the pumps will continue to operate once the float switch has been
activated.
Change Menu – These screens allow the input in M2 of plate material and days the
maximum period that the developer, developer filter or wash water (when in
recirculation mode) can be used. When the M2 or days (whichever comes first) has
been exceeded, an alarm will be displayed on the HMI and the machine will be put
into a “Warning” state telling the user to change that particular solution or filter.
Set Dual Replenish – Selecting “Dual Pump” activates the electrical function for 2,
independently controlled developer replenishment pumps. This is usually set to
“Normal” for a single replenishment pump unless informed otherwise.
3 – Offsets
Dev Temp Offset – This allows for the displayed temperature to be modified by +/-
2° C. This is used when the processor temperature is required to match a hand held
devise regardless of actual temperature.
Page 33 of 116
0323C676.1/.2 – This function is no longer used. Ensure that the option
“0323C676.3 up” is selected.
Preheat Type – This allows the option to select either 2 zone or 3 zone preheat
types. Always select 3 zone.
Chiller Restart Delay – This is no longer used.
Reset PDI Flag – This resets the PCB into PDI (Pre Delivery Inspection) mode for
setup and component testing. I list of test point shortcuts are displayed. Only select
this under the guidance of Heights. If it is selected by mistake, scroll to the bottom
of the list and select “End PDI”. This will return the machine back to normal
operating mode.
Plate Speed – Select between the option of metric (m/m) and Imperial (inch/min) as
required.
Temperature – Select between the option of Metric (C°) and imperial (F°) as
required.
Replen Rate – Select between the option of Metric (ml) and Imperial (floz) as
required.
Date Style – Select between the option of the international date style dd/mm/yyyy
and the US date style mm/dd/yyyy.
Language – Select the required language from those listed. The translations only
apply to the operator screens.
Speed Display Type – Select between the 2 conveyor speed setting options of
m/m per min and the dip to nip time in seconds.
Plate Count – If a PCB has had to be changed, the new board will show zero on
the total plate counter and M2. To display the old plate count and M2 information in
the new PCB, input the total number of plates processed and the M2 plate area into
these screens and the board will record the new settings.
5 – Entry Sensors
This option allows for the fitting of dual input sensors. This option is not currently available
on the Maya P. Selecting 2 sensors does however disable the exit sensor if required.
Select the required option between the conveyor motor continuously crawling (rolling) or
for the conveyor to stop after each plate is processed. Always set to Rolling.
7 – Re-entry Present
This option allows for a re-entry facility to be added to the machine. This option is not
currently available on the Maya P. Always set to No Reentry.
Page 34 of 116
8 – Wash Section Type
As standard the Maya P is configure for direct to drain rinse water. However there is an
option to fit a water saving system comprising of a water recirculation pump and additional
hoses. To select either system follow the on-screen instructions. Currently internal water
recirculation is not available so this function is not available. External water recirculation is
available and does not require this function to be activated.
Page 35 of 116
This page
intentionally left
blank
Page 36 of 116
4.5 – Settings Menu
Settings
1 Exit 0266 Autorun Menu 2
Set Heater
3 Motor Setup
PI Constants
4
Selecting this button (as with all other screens) goes back to the previous screen.
2 – Autorun Menu
Page 37 of 116
3 – Motor Setup
Drive I Limit – This is the amps threshold at which the electronic control of the
motor shuts the power supply down due to an overload condition. This should be
left at the default value unless instructed by Heights to change it.
Drive Smoothing – Do not adjust.
I Limit Shutdown – This is the number of pulses or tick that the encoder produces
during an overload condition before the power is cut off.
Brush Speed Scaling – To ensure that the brush motor is rotating the developer
brushes at the same speed that is displayed on the screen. The brush speed
scaling is used to calibrate the true RPM. The rotational speed of the first developer
brush is measured either by using a tachometer or by simply counting the rotations
of the brush per minute. If the rotational speed of the brush is too slow, increase the
brush speed scaling value slowly (by 0.1 increment per change). If the rotational
speed of the brush is too fast, de-crease the brush speed scaling value slowly (by
0.1 increment per change). Exit all screens to finish the process.
Brush I Limit - This is the amps threshold at which the electronic control of the
motor shuts the power supply down due to an overload condition. This should be
left at the default value unless instructed by Heights to change it.
Brush Smoothing – This controls the brush motor drive characteristics. Do not
adjust.
Brush Armature Resolution – This controls the brush motor drive characteristics.
Do not adjust
4 – Heater PI Constants
.
There are 5 options available:
Dev – The KP, KD & KI should not be adjusted under normal conditions. However,
when the “Dev” screen is displayed the heater automatically turns on and will run
normally stabilising the developer temperature if there is demand for developer
heating. This screen can be used to monitor the heater for correct operation.
Ensure that the developer heater cartridge is fully covered with liquid before using
this screen.
Chiller - The KP, KD & KI should not be adjusted under normal conditions.
However, when the “Chiller” screen is displayed the chiller automatically turns on
and will run normally stabilising the developer temperature if there is demand for
developer cooling. This screen can be used to monitor the chiller for correct
operation.
Preheat Outer (Right) - The KP, KD & KI should not be adjusted under normal
conditions. However, when the “Preheat Outer (Right)” screen is displayed the
ceramic tiles in that zone automatically turn on and run normally stabilising the
preheat temperature selected on the main operation screen if there is demand for
the tiles to heat. This screen can be used to monitor the ceramic tiles for correct
operation.
Preheat Outer Left - The KP, KD & KI should not be adjusted under normal
conditions. However, when the “Preheat Outer (Left)” screen is displayed the
ceramic tiles in that zone automatically turn on and run normally stabilising the
preheat temperature selected on the main operation screen if there is demand for
Page 38 of 116
the tiles to heat. This screen can be used to monitor the ceramic tiles for correct
operation.
Preheat Inner - The KP, KD & KI should not be adjusted under normal conditions.
However, when the “Preheat Inner” screen is displayed the ceramic tiles in that
zone automatically turn on and run normally stabilising the preheat temperature
selected on the main operation screen if there is demand for the tiles to heat. This
screen can be used to monitor the ceramic tiles for correct operation.
The options available in this menu allow for a range of interface types that are not all
available for the Maya 85T. However a description is provided for all the options displayed.
Select Setter Interface – This allows for the appropriate interface type to be
selected. These include:
No Setter – No communication is available. Also the conveyor start is
delayed by 2 seconds when a plate is placed over the on sensor to allow for
the plate to be positioned correctly.
Fuji – This is for an RS232 bi-directional serial connection dedicated for use
with FFEI/FujiFilm engines.
Python – This is for an RS232 bi-directional serial connection dedicated for
use with the Highwater Python engine.
External Unit – This is for a bi-directional, programmable interface (for
further information, see the section on interfaces, the information below or
contact Heights for dedicated interface instructions). This function requires
optional hardware.
User – This is for a uni-directional, programmable interface (for further
information, see the section on interfaces, the information below or contact
Heights for dedicated interface instructions). This function requires optional
hardware.
Configure User Setter – When “User” is selected from the “Select Setter Interface”
menu, this screen provides options for the 2 bit signal switching to be programmed.
Page 39 of 116
For further information, see the section on interfaces or contact Heights for
dedicated interface instructions.
Configure External Interface – When “External Unit” is selected from the “Select
Setter Interface” menu, this set of 2 screens provides options for the 4 bit input and
output switching/signal generation to be programmed. For further information, see
the section on interfaces or contact Heights for dedicated interface instructions.
External Interface by Code – This is an 8 digit code that when entered into this
screen, will automatically configure the I/0 of the external unit interface.
Configure Error Codes – This should not normally require changing. For further
information, see the section on interfaces or contact Heights for guidance on any
specific interface requirements.
7 - Temperature Limits
Page 40 of 116
return to a “Ready” condition when the temperature has stabilised within the upper
and lower limits. This is settable in C° in increments of 0.1 C°.
8 – Calibration Menu
Cal PT100 Dev – For further information on this option please refer to the section
“Calibrating the PT100 temperature probe input (PL5)” later on in this manual.
Preheat Calibration – Options are provided to calibrate all 3 K-Type thermocouple
inputs on the board. For further information please refer to the section “Calibrating
the K-Type Thermocouple Preheat Temperature Inputs PL6/7/9”.
Replenish Calibration - For further information on this option please refer to the
section “Calibrating the Developer Replenishment Pump” later on in this manual.
Cal Bulk Dev Replen – This option is only displayed when Dual Replenish Pumps
have been fitted and selected in the M/C Config Menu. For further information on
this option please refer to the section “Calibrating the Second Developer
Replenishment Pump” later on in this manual.
Read System Data – Read System Data reads all the data from the removable
EEROM (IC12) if you have to change a board. You need to perform a read in the
first few minutes, or the data will get overwritten.
Page 41 of 116
This page
intentionally left
blank
Page 42 of 116
4.6 - Exiting the Engineering Section
EEPROM Update
1 Exit 2415 2
3 4
Save Any Change Made
To EEPROM Memory
5 6
7 Quit Continue 8
To exit the engineering section, exit all the engineering screens until the following screen
is displayed;
Selecting this button (as with all other screens) goes back to the previous screen.
7 – Quit
Selecting this option will immediately discard any changes made and will exit the
engineering section to the “Reenable Password” screen.
8 – Continue
Selecting this option will save all changes made to the engineering section. Once this
option has been selected, all changes are non reversible. After selecting “Continue” there
will be a flash screen (2402) displayed confirming the changes. This automatically
disappears after 3 seconds. The “Reenable Password” screen is then displayed.
Page 43 of 116
4.7 – Re-enable Password
Reenable Password
1 Exit 2411 2
3 4
Enable After 1 Hour
Enable Password NOW
5 Up 6
7 Down 8
Selecting this button (as with all other screens) goes back to the previous screen.
5 – Up
7 – Down
Enable After 1 Hour – You may re-enter the engineering section without re-
entering the current password for the next 1 hour. After 1 hour the password will be
re-set and the current password will need to be entered to gain access to the
engineering section. If you re-enter the engineering section within the 1 hour, when
you exit you may select “Enable After 1 Hour” again.
Enable Password NOW – Immediately re-sets the password. To re-enter the
engineering section, enter the current password.
Page 44 of 116
4.8 - Guard Switch Override Mode
To enable “Guard Switch Override Mode” place the supplied key into the key switch
mounted on the electrical panel door as shown below.
Normal Guard
Operation Switch
Switch Override
Position Position
Rotate the key to the Guard Switch Override position. The screen shown below will be
displayed. The machine will not now process plates automatically but it will keep the
developer temperature stable.
Cancel
5 Inch Forward
Plate 6
7 Engineering 8
Selecting this button (as with all other screens) goes back to the previous screen.
Page 45 of 116
2 – Fill Tanks
Select from the options available – Dev Fill (option). Selecting this option will start the
developer fill pump. They will run until;
a) The developer float switch is activated indicating that the tank is full.
b) The developer max fill time is reached (See M/c config section, Change & Fill).
c) The button is depressed a second time to stop the pump.
3 – Inch Forward
Using this button will start the conveyor motor to drive the conveyor in the normal direction.
Releasing the button will stop the motor.
4 – Hold to Run
This function allows a plate to be made automatically with the top cover removed, however
the button must be continually depressed for this to work. Releasing this button will stop
the process immediately. Also, the processor must be in an OK condition to make a plate,
for example; the developer must be up to the float switch and the temperature must be
within the normal working tolerance for both the developer and the preheat.
5 – Inch Back
Using this button will start the conveyor motor to drive the conveyor in the opposite to
normal direction. Releasing the button will stop the motor
6 – Cancel Plate
Selecting this option will cancel all plates currently being processed.
8 – Engineering
Selecting this option will prompt you for the current engineering password. See the section
on the engineering password code calculation table.
Page 46 of 116
5.0 - Maya P HMI Processor Screen Tree
Page 47 of 116
Turn M/c ON
A
Startup Display
Go To Go To Go To Go To Go To
B C D E F This screen is
password protected.
Go To
G
Page 48 of 116
Operator
B From
A Settings
Restore Cons
Data
NOT
Manual Gum
Replen
USED
Page 49 of 116
Change
C From
A Menu
Developer
From System
D A Summary
Developer Alarms
Cancel
Alarm
Alarm
History
Open
Alarms
Page 50 of 116
From Sleep/Close
E A Down Menu
Conveyor
F From
A Menu
Cancel Plate
Page 51 of 116
G From
A
Engineering
Menu
Process Service Go To
Settings Utilities H
Processor Go To
Speed G1 Dryer Gum Repl Save Settings
Warmup Type
Developer
Temperature
Dryer
Restore Settings
O/P
Brush Speed
Page 52 of 116
From Pre Heat
G1 G Menu
Page 53 of 116
From
H G
Service Utilities
Go To Go To Go To
I J K
Clear
Process DB
Page 54 of 116
From
I H
Test
Plate Size
Set/Clear Start Display PH Right
Drive
OP Drive Test
Setter
Debug
Display Start Gum PH Left Brush
IP Pump Test
Debug Exit
Sensor
Clear Open
Errors PH Inner
Debug Exit Test
Sensor
Clear W/Dog
List
Watch Dog Dryer
& Error Heater
Clear Error
List
Dose
Data Developer
Clear Unused Heater
Change
Page 55 of 116
From M/C Config
J H
Page 56 of 116
From
K H
Settings
Motor Plate Path Temperature Auto Run Set Heater P/I Plate Setter Calibration
Setup (*) Menu Limits Menu Constants Menu Menu
Page 57 of 116
From Anti Ox
K1 K Type
Averaging Timed
Anti Ox Anti Ox
Samples /
Average
Page 58 of 116
From
L A Guard Switch
Override Menu
Developer Go To
G
From Configure
K3 K Sleep
Page 59 of 116
Set Heater Only adjust under
K2 From
K P/I Constants factory advice.
Page 60 of 116
6.0 - PCB Jumper Positions
Jumper positions J1~J8 as seen with the board in normal orientation, fuses to the top.
* Both TP7 & TP8 are powered off the same line.
Page 61 of 116
6.2 – DIP Switch Setting Positions
On fitting a new board it is recommended that the following DIP switch settings are
checked and if required, set. To access the DIP switches please carefully remove the
protective film over the switch assembly if fitted.
Page 62 of 116
6.3 - Fusing (Issue B)
Fuse
No. Description Rating (A) Rating (B)
F01 Chiller/Compressor 1AT 1AT
F02 Drier Fan 1AT 1AT
F03 Pre-Wash Recirculation Pump or Solenoid 2AT 2AT
F04 Vacant 2AT 2AT
F05 Second Developer Replen Pump (option) 1AT 1AT
F06 Dev Circulation Pump 1AT 1AT
F07 Vacant ---------------- ----------------
F08 Vacant ---------------- ----------------
F09 Vacant ---------------- ----------------
F10 Gum Recirculation Pump 1AT 1AT
F11 Rinse Recirculation Pump or Solenoid 2AT 2AT
F12 Vacant ---------------- ----------------
F13 First Developer Replen Pump 1AT 1AT
F14 Vacant ---------------- ----------------
F15 Vacant ---------------- ----------------
F16 Vacant ---------------- ----------------
F17 Vacant ---------------- ----------------
F18 PCB Main AC Power Supply 1AT 1AT
F19 Not Available ---------------- ----------------
F20 Not Available ---------------- ----------------
F21 65VDC Motor Power Supply 6.3AT ----------------
F22 Not Available ---------------- ----------------
F23 TR1 Power Supply 6.3AT 6.3AT
RCCB1 RCB 100mA Trip (option) 1 Phase Machine 40A
RCCB1 RCB 100mA Trip (option) 3 Phase Machine 25A
CB1 Pre-Heat Oven 16A
CB2 Developer Heater 6A
CB3 Drier Heater 10A
CB4 Cooling Fans & PCB Outputs Supply 10A
Please note: The item RCCB1 is not fitted to all machines. When it is fitted
the rating of the device depends on whether the machine is for 1 phase or 3
phase installation.
Page 63 of 116
6.4 - Safety Circuit By-Pass Switch
To assist in the maintenance of the Maya P processor and make access easier, a by-pass
switch has been fitted to the electrical cabinet. When the cabinet door is opened, the 1 or 2
(depending on the type of machine) switches are released and the safety circuit/s are de-
activated. The main isolator can then be rotated manually to turn the machine on. This
permits the technician to work on and test the machine with the top cover off the machine.
It is absolutely forbidden under Health & Safety law to by-pass safety circuits during
the normal operation of the machine by the customer. This function is only for use
by fully trained technicians and under no circumstances is information on this
function to be passed to the customer. This function must be de-activated as soon
as possible and all safety features fully operational before the customer starts to
operate the machine. Heights accept no responsibility for mis-use of this function or
the by-passing of safety functions on this machine.
Page 64 of 116
7.0 – Calibrating the PT100 Temperature Probe Input (PL5)
Under normal conditions, the board will not require calibrating for the PT100 input (PL5).
This is because the calibration is done during the manufacturing process of the board
when the calibration values are entered into the board’s E2 ROM memory. However the
following information is provided as a safeguard against unforeseen corruption of the
board’s memory. To help with the re-calibration process, please order a calibration tool
P/N 0323K958 (Fig.1). This will assist in the quick re-calibration of the board.
110 ohm
Toggle
switch
B
105 ohm
Plug A
Fig.1
Go to the calibration menu. This menu can be found in the Engineering section > Settings
> Calibration Menu. Select Cal PT100 Dev. Please note that continuing the calibration
process from this point will destroy all previous settings. These old settings cannot be
restored once overwritten. You must have the correct calibration tool to continue (Fig.1).
Remove the Dev Temp Sensor plug connected onto PL5 (Fig.2).
Fig.2 Fig.3
Page 65 of 116
Connect the plug “A” (Fig.1) to PL5 (Fig.3). Select 105 with the toggle switch “B” (Fig.1). It
is VERY important that you wait 30 seconds from this point before doing anything else.
Now you can follow the on screen instructions by pressing any key. Once the 10 seconds
sample time has finished, the on-screen instructions will request the 110 position is
selected using the toggle switch “B” (Fig.1). Select 110 and again wait 30 seconds. Now
follow the on screen instructions and press any key. Once the 10 seconds sample time
has finished the following screen will be displayed:
Please note that the values shown here are for illustrative purposes only and may not be the same on your machine.
If the Gradient and Offset values are displayed as “+INF and -INF” then some part of the
calibration procedure has failed and the process needs to be repeated. Take care that the
calibration tool is correctly connected to PL5.
Once the calibration procedure has been completed, exit this screen. To confirm that the
calibration process has been successful, exit the Engineering menu to the front operational
screen. Check that the “Act” temperature value is 12.8°C (*) when the 105Ω position is
selected on the calibration tool and that 25.7°C (*) when the 110Ω position is selected.
Remove the calibration tool and replace the PT100 plug onto PL5.
(*)+/-0.2°C is an acceptable tolerance.
Alternatively, if the tool 0323K958 is not available, connect the resistor 105 ohm and 110
ohm as shown below onto PL5 when requested during the calibration process instead of
using the toggle switch “B”. Otherwise the calibration process is the same as previously
described.
Page 66 of 116
7.1 - Calibrating the Pre-heat Thermocouple Inputs
Under normal conditions, the board will not require calibrating for the K-type thermocouple
inputs (PL6~PL10). This is because the calibration is done during the manufacturing
process of the board when the calibration values are entered into the board’s E2 ROM
memory. However the following information is provided as a safeguard against unforeseen
corruption of the board’s memory.
Fig.4
Go to the calibration menu. This can be found in the Engineering section > Settings >
Calibration Menu > Cal Pre-Heat. From here select one of the 3 options, Outer Left, Outer
Right or Inner. This refers to the 3 temperature control zones within the pre-heat box (left
to right orientation as seen from the plate input slot). Please note that continuing the
calibration process from this point will destroy all previous settings. These old settings
cannot be restored once overwritten. You must have the correct calibration tool to continue
(Fig.4). Remove the appropriate plug from the side of the electrical box TC sockets (Fig.5).
These are numbered TC1 - Outer Right (PL6), TC2 - Inner (PL7), TC3 - Outer Left (PL9).
Fig.5
Page 67 of 116
For example, if the outer left requires calibrating, select Outer Left from the screen options.
Plug in the calibration device lead (2 blade thermocouple plug) into the TC-3 Outer Left
socket. When prompted, select 200°C output from the calibration device. It is VERY
important that you wait 10 seconds from this point before doing anything else. Now you
can follow the on screen instructions by pressing any key.
Once the 10 seconds sample time has finished, the on-screen instructions will request the
700°C output from the calibration device. Select 700°C and once again, wait 10 seconds.
Now you can follow the on screen instructions by pressing any key. Once the 10 seconds
sample time has finished the following screen will be displayed (Cal Preheat Left is used
as an example).
Please note that the values shown here are for illustrative purposes only and may not be the same on your machine.
If the Gradient and Offset values are displayed as “+INF and -INF” then some part of the
calibration procedure has failed and the process needs to be repeated. Take care that the
calibration device lead is correctly connected to the TC input socket. Once the calibration
procedure has been completed, exit this screen. To confirm that the calibration process
has been successful, exit the Engineering menu to the front operational screen. Check that
the “Act” temperature value of the calibrated pre-heat zone is 700°C (*) when the
calibration device is set to output 700°C. Remove the calibration device from the TC input
socket and replace the thermocouple plug onto the TC input socket.
(*) +/- 3°C is an acceptable tolerance.
Page 68 of 116
7.2 - Calibrating the Developer Replenishment Pump.
For the Developer replenishment setting, using an accurate measuring jug (10ml
graduations) and place the replenishment/fill spear into the jug filled with developer. Note
the amount of developer in the jug. Go to the Engineering section Ä Settings Ä
Calibration Menu. Select Cal Dev Replen. Follow the on screen instructions. Enter the
quantity of developer that was pumped out of the jug in the 30 second test period. Save
the setting.
Clear
Replenish
Tubing
Developer
Replenish
Probe
Measuring Cylinder
with replenish probe
inserted
If the optional second developer replenishment pump is fitted. The calibration process is
the same as the normal developer replenishment calibration as described in section 8.1.
However the calibration screen that needs selecting is as follows: Go to the Engineering
section Ä Settings Ä Calibration Menu. Select Cal Bulk Fill Replen. Then follow the
instructions as above.
Page 69 of 116
This page
intentionally left
blank
Page 70 of 116
7.4 – Calibrating the Interleaf Paper Detectors (Option)
Overview
The interleaf detection system fitted to the Maya processor is normally a factory fit option.
However the parts can be fitted in the field if required, P/N 0323B961. The kit consists of 2
fibre optic sensors as shown below and 2 amplifier units fitted inside the electrical box.
Function
As the plate passes over the In-feed (On) sensor the encoder counts 10mm from the
On/start position. At 10mm the Interleaf paper detectors (top & bottom) are activated (the
PCB starts to monitor the signal). This means that the detectors are constantly detecting a
change in reflectivity. The sensors stay activated until the back edge of the plate passes
over the In-feed (On) sensor at which point they then are de-activated (the PCB stops
monitoring the signal). When an Interleaf paper is detected, the sensor must record a
constant signal for more than 20mm of plate travel from either of the detectors. Any period
less than this and the signal will be ignored. If a Interleaf paper is detected, the machine
will stop and a warning will be displayed on the HMI “Interleaf Detected”. The “Jam
Screen” will then displayed so that the plate and paper can be removed. These functions
are available in software 05.01.05 onwards. The Interleaf paper detectors are normally
only used with On-line applications and are therefore not normally required for hand fed
Off-line machines.
Description
There are 2 Keyence FS-V21RP amplifier units fitted to the DIN mounting rail in the
electrical box. Connected to them are the 2 fibre optic cables upper & lower. SW19 is for
the upper sensor and SW20 is for the lower sensor. Please note that the fibre optic cables
should be treated with care as they are easily damaged. Fitting of the fibre optic cable to
the amplifier units is by a cable clamp so do not remove unnecessarily. There should not
Page 71 of 116
normally be any reason to disassemble the units except for parts replacement. The cable
connection from the amplifier units to the PCB is as follows:
Items a to c are normally only required when the fibre optic cable or amplifier unit is
replaced. Items d to g are required when the interleaf paper density changes or the plate
aluminium surface reflectivity changes. Before re-calibrating the sensors, please ensure
that the fibre optic sensor is clean and free from dust particles. Cleaning may also avoid
the need for re-calibration.
a) To set the Light/Dark option, press the L/D button once. Then use the ÏÐ button to
select the correct option for both units.
Page 72 of 116
b) To enter the programming menus, press the Mode button for 3 seconds. This allows
entry to the Access Mode Selection Menu. The currently selected option will be
displayed. As a default the units are supplied pre-programmed as “Easy”. If this is
displayed, use the ÍÎ button to select “Full”. This setting allows for the full range
of adjustments and setting to be accessed. This setting is for both amplifier units.
c) To select the correct sensitivity for the amplifier unit, press the Mode button for 3
seconds. The currently selected option will be displayed; this should be “Full”. Press
the Mode button again. This is the Power Mode Selection Menu. The options
available are: FinE/turb/SuPr/ULtr/hSP/rESa. To change this setting, use the ÍÎ
button to select “ULtr” (top sensor) and “SuPr” (lower sensor).
Page 73 of 116
d) To set the sensitivity of the amplifier units the amplifier unit must know the different
reflective values of the plate coating, substrate and the interleaf paper. For the
upper sensor, place a fully coated plate of the type which is going to be used under
the sensor and press the SET button once. The plate must be flat on the conveyor
as it would be in normal operation. Now place an interleaf paper on top of the plate,
press the SET button one more time.
e) For the lower sensor, place a plate of the type which is going to be used over the
sensor so that the sensor is facing the bare aluminium substrate and press the SET
button once. The plate must be flat on the conveyor as it would be in normal
operation. Now place an interleaf paper under the plate, press the SET button one
more time.
Plate
Interleaf
Page 74 of 116
f) The amplifier units are now ready to work. The green display is the Pre-set Value
(PV) which was programmed during the calibration process and the red display is
the Current Value (CV) being read by the amplifier unit.
g) Both the interleaf paper detectors now should now be ready to work. If for whatever
reason the detectors need to be de-activated, remove PL25 from the PCB inputs
and the interleaf paper detection will no longer work.
Page 75 of 116
This page
intentionally left
blank
Page 76 of 116
8.0 - Setting the Developer Section Level Switch
On installation or when the machine is moved and re levelled, the developer section float
switch assembly will need setting. To set, fill the tank up to its highest level with developer
(not water) and let a small amount of liquid overflow. Go to the Engineering section Ä
Test Ä Display IP. Release the locking bolts and push the float switch mounting bracket
to its highest position. The I/O signal reading should be O. Push the float switch mounting
block downwards until the I/O reads I. From this point push the float switch mounting block
1mm further down. Tighten the locking bolts. Place the anti-ox cover into the developer
section and check the I/O still reads I.
Locking Bolts
Float Switch
Mounting
Bracket
Float Switch
Float
Page 77 of 116
8.1 - In-Feed and Exit Sensor (*) Sensitivity Adjustment
For the Maya to work automatically, the plate must be seen consistently by the in-feed
sensor fitted to the upper in-feed guard. This also applies to the exit sensor jam function so
that it works accurately and consistently
(Plate Material)
To set the in-feed and exit sensor correctly, ensure that it is securely mounted to the In-
feed guard using the lock nuts 2. Make sure that the sensor is not mounted so close to the
plate that it touches the plate surface. Place an un-processed plate under the sensor and
check that it activates. This can be confirmed by the yellow LED built into the sensor or by
using the Inputs list of the Test Menu found in the Engineering section. If the sensor does
not activate, rotate the adjustment screw 1 in the direction of the arrow (clockwise). This
will increase the sensitivity of the sensor. As soon as the sensor is activated rotate the
adjustment screw a further 5° in the direction of the arrow.
Page 78 of 116
9.0 - Replacing the PCB
If the PCB needs to be changed the following needs to be done. Before you unplug
anything the settings should be saved in the operator menu. This ensures that the latest
settings have been saved.
It is most important that ESD precautions such as a wrist strap are used before the
PCB is touched.
Remove the board and swap over the fuse holders (if required). If in doubt, please refer to
section 6.3 on fuse positions and ratings. Make sure that the jumpers are in the same
position as the old board (if in doubt please refer to section 6.0, jumper positions and
section 6.2 DIP switch settings). Most boards supplied are Flash Loaded with the correct
software, however if an EPROM is fitted, remove it, also remove IC12 (this is near the
main EPROM) from the old board and fit them to the new board. The EPROM carries the
operating system and IC12 carries the usage data, error log and other history/information
to the new board. Please make a note of process data such as pre-heat temperatures,
developer temperature and replenishment rates just in case this is lost during the data
transfer procedure.
Flash
Chip
IC12
EPROM
If you are not using an EPROM then please refer to the Flash Loader instructions for PC
upgrading of the PCB if it is not already programmed or it requires an upgrade. Once the
board is fitted and all the plugs checked for their correct position, start up the machine.
Please note that for illustrative purposes only the off board transformer version of
the PCB has been shown. For machines fitted with the on board transformer PCB
the process is exactly the same.
Page 79 of 116
9.1 – Selecting the Machine Identity
If the new board has not been pre-programmed then item 1 to 3 may be displayed.
Regardless of whether the board was pre-programmed or not, item 4 to 9 will always be
displayed. Items 10 & 11 are extra steps that are required.
1) The Select Board Type screen will be displayed. The options are 0247K301 or 0323
C676. To check which board type is fitted please refer to the label affixed between
the PCB transformer connectors (see picture below). The Maya P will always be
fitted with a 0323C676 board. Select 0323C676 and press exit/return to confirm
your selection. The serial number will be affixed to the on board transformer if the
PCB has one fitted.
2) The Confirm Board Identity screen is displayed. Confirm “Yes” if you are sure that
the correct board type has been fitted. Press exit/return to confirm your selection.
3) The Enter Serial Number screen is displayed. Check the serial number of the PCB.
To check the board serial number, please refer to the label affixed to the PCB
between the 2 sockets for the PCB transformer (see picture above) or the label
affixed to the on board transformer if used. Enter the serial number by using the
increase/decrease keys, once the desired number is displayed, press next to allow
entry of the next number. Once this has been completed, select exit/return to
confirm the number. Please note that once this number has been entered it cannot
be amended.
4) The Select Manufacturer screen will be displayed. Select Heights and exit/return to
confirm your selection.
5) The Select Machine Family screen will be displayed. Select Maya and exit/return to
confirm your selection.
6) The option to confirm the machine width is displayed. Choose either the 62 or 85
cm width option.
7) The Time and Date screen will be displayed. Enter the current local time and date.
Select exit/return to confirm and move to the next screen.
Page 80 of 116
8) The PDI Menu screen will be displayed. PDI stands for Pre Delivery Inspection and
is a factory list for machine checking, setting and calibration. Please scroll to the
bottom of the list (the list is longer than the screen can display). The last entry is
End PDI. Select and confirm by pressing exit/return.
9) Once the End PDI option in the PDI menu has been selected and confirmed by
pressing exit/return, the normal boot up screen will be displayed. Press any key to
start the processor.
10)Go to the Main Menu Ä Engineering (enter the current password using the table in
section 1.0) Ä Service Utilities Ä Settings Ä Calibration MenuÄ Select Read
System Data. This will extract the setting and consumable data information from
IC12 and update the PCB memory. Please note that the operation explained in this
section (section 10) must be carried out within 5 minutes of the board being
powered up for the first time. If it is not the data may be lost as it will be overwritten
after the 5 minutes has expired.
11)After a board change it is always a good idea to check that the correct settings have
been transferred such as the developer temperature, preheat and replenishment
rates.
Page 81 of 116
9.2 - Clearing the Memory / Self Test Procedure.
When selecting J4 and powering the machine up, the basic memory of the machine is
always reset thus loosing all consumable usage data and processor working parameters.
Therefore if you elect to use the self test utilities explained below, always make a note of
the processing parameters and consumable usage data before fitting the link J4.
From 05.01.00 when selecting J4 and powering up the machine you will be presented with
the following options:
Basic tests – This is as the previous tests, interrogating the RTC, EPROM, PTCal,
EEROM & RAM. The number of passes failed or accumulated at the top of the screen. To
exit, power down the machine to exit the J4 screen, and return J4 to open.
Full board test – This is not to be used as it only works correctly when connected to a test
jig (which is held at S2S). If it is used by accident it will not cause any damage. To exit,
power down the machine to exit the J4 screen, and return J4 to open.
Change board type – This allows for the board type to be changed if the wrong type was
entered into memory by mistake when the board was first programmed. The choices are
0247K301 & 0323C676. Select, then confirm yes or no. Once this is done you are returned
to the J4 options screen. To exit, power down the machine to exit the J4 screen, and
return J4 to open.
It is possible to completely re-set the board. If this is required please contact Heights for
further information.
Page 82 of 116
10.0 – Upgrading the Software
There are 2 ways to upgrade the software on the PCB. The first is to change the EPROM
and the second is to upgrade using a PC. Both methods are explained below.
It is most important that ESD precautions such as a wrist strap are used before the
PCB is touched.
Remove the EPROM by means of an appropriate EPROM removal tool being careful to
ensure that the legs of the EPROM are not bent. The EPROMS can be re-used if required.
Slot the replacement EPROM into the vacant socket. Ensure that the notch on the EPROM
matches the notch on the EPROM socket. Check that all the EPROM feet are located into
the socket and push gently but firmly until the feet are fully secured into the socket. Please
refer to section 10.2 for information on software selection options.
The Flash Loaded is a dedicated programme used to load the operating system onto the
PCB from a PC. It is downloadable from the Heights Support Zone with the appropriate
password and user name. Initially a kit will need to be ordered and this can be obtained
from Heights UK Spare Parts Dept using the part number 0323K678. The kit includes a
dedicated download cable needed for connecting the PC to the PCB (0323E677). A serial
to USB adaptor (7279-209) for connecting the serial download cable to a USB port, printed
instructions (0323M695) and a CD containing the latest software (0323B696). The Flash
Loader software is written to only work on PC’s using Windows 95/98/ME/XP.
To load the software onto a PC for the first time, ensure that the file extension of the FI file
is .exe. The FI file is the Flash Installer programme. There is also an FU file which is the
Flash Upgrade programme. The files that are downloaded from the Heights website use
the file extension .exx. This is so the programme can be sent by e-mail and not filtered out
as a potential virus. An example of a full file name is FI_03_00_09.exe. Double click on the
FI file icon and agree to the licence agreement.
Page 83 of 116
By default the software is automatically loaded into the file C:\HFL\ (HFL stands for heights
Flash Loader). The programme files go into C:\HFL\programms and the documentation
goes into C:\HFL\docs\.
When the programme is loaded a shortcut is added to the start menu and to the desktop.
Included in the start menu shortcut is the option to uninstall the programme.
To upgrade the version of software that is resident in the Flash Loader programme
installed on your computer. The FU file needs to be used. Again, ensure that the file
extension is .exe. Double click on the FU file icon and the programme will install the
necessary update files.
Once the Flash Loader programme is installed to your PC, the PCB needs to be prepared
to receive the new software. Turn the processor off at the main isolator. Open the panel
door and connect the serial download cable to PL4 on the board.
PL4
Connect the other end of the serial download cable to a spare 9 pin serial cable port on the
PC with the Flash Loader programme installed. If there is no serial port available (as is the
Page 84 of 116
case with many modern laptop computers) use the supplied RS232~USB adaptor. Ensure
that J2 is linked to pin 2&3 (flash). J5 is linked across pins 1&2 (bootstrap loader
condition). J6 is linked to pins 2&3 (RS232 selected). Now the processor can be powered
up.
J5
J2
J6
When the processor is powered up, you will notice that the HMI is blank. This is correct
while the processor PCB is in Bootstrap mode. Double click the Flash Loader icon on the
PC to start the programme. If it is the first time the programme has been used it will need
to be configured. On starting the Flash Loader programme needs to scan for available
COM ports. You will be asked to confirm this by selecting Return to continue.
The next stage is to confirm the COM port selected. If you are using a serial port than this
will always be the port you use, so save the selected port by typing Y & Return. If you are
using a USB port it may be better not to save the port as there are normally more than 1
USB ports available on a PC. Type N & Return. If you save the USB port, ensure you use
the same port each time you plug the download cable in to the PC.
Page 85 of 116
The programme will now erase the existing Flash programme data on the PCB. The
progress will be displayed in seconds in the dialogue box. The Flash Loader programme
will then automatically download the new version of software to the PCB flash memory.
Again the progress of the download will be displayed in seconds in the dialogue box.
Depending on the speed of the computer this could take anything up to 5 minutes to
complete. Once this has finished, hit Return to exit the Flash Loader programme.
To complete the process, isolate the processor from the mains. Remove J5 from the
Bootstrap Loader position and power the machine back up again. Depending on the type
of upgrade loaded into the processor PCB it may be necessary to refer back to section
10.2 and follow the board configuration process.
Page 86 of 116
10.3 – Flash Loader Trouble Shooting
There are a number of potential causes. This normally only happens when using a
USB/Serial adapter. The following lists options for adjustments using Windows.
A - Close down Heights Flash Loader program. Power down the machine PCB and check
that J5 is in the “Bootstrap” position, J6 is in the “RS232” position and that J2 is in the
“Flash” position. Power the machine back up again and re-start the programming
procedure.
B - Close down all applications on the PC and “Restart”. Power down the machine and
then power the machine back up again and re-start the programming procedure.
C - Check the COM port allocated to the down load cable. This normally only applies to a
download cable using a USB port. Select “System” from the “Control Panel”.
Page 87 of 116
Select “Device Manager”.
Open up the “Ports” option to see what COM port allocation has been made. The Heights
Flash Loader only scans ports 1 to 8, so if the allocated COM port is greater than 8 it won’t
be recognised. Try moving the download cable USB plug to a COM port from between 1
and 8. Close all dialogue boxes and re-start the programming procedure.
Page 88 of 116
D - Go to the “COM Ports” displayed in the “Device Manager. Right click on the COM port
in use. Select “Properties”. Then select “Port Settings”
Change the “Bits Per Second” value to that which is seen on the Heights Flash Loader
dialogue box. Changing from 9600 to 38400 may have an effect
Page 89 of 116
Close all dialogue boxes and re-start the programming procedure.
E - Ensure that the driver for the Serial/USB converter has been installed correctly. Re-
install if required
F - Try a different make of Serial/ USB converter. One with a Prolific chip in it is preferable.
G - Re-assign the COM port number if you are unable to find a suitable COM port
displayed. Go to the “Port Settings”. Select the “Advanced” option.
Page 90 of 116
Select the drop down menu “COM Port Number” from the “Advanced Settings for COM X
(where X is your currently assigned COM port number) and select a COM port that is
between 1 and 8. Select “OK and exit all screens.
H – Always remember to reset (power down and re-start) the PCB when re-trying to
programme the PCB. Without re-setting the PCB the PC will not recognise the PCB target
and will display “Unable to Find Connected Hardware” as shown below..
Page 91 of 116
This page
intentionally left
blank
Page 92 of 116
11.0 – Plate Setter Interface
There are 2 types of setter interface available for the Maya 85T processor. The first is a
unidirectional interface that can be programmed (via the HMI on the processor) to output a
2 bit signal. This signal can send 4 different states to a plate setter by switching 2 voltage
free relays. This is used by Plate Setters that send their own signal for the processor to
switch. The second is a bidirectional interface which is also programmable via the HMI on
the processor however factory instructions are required for this. An instruction sheet for
each Plate Setter is available from Heights UK. The interface can output a 4 bit signal to
the plate setter indicating machine status but it can also receive a 4 bit data signal from the
plate setter. This is used by plate setters that require an opto-isolated 5~12 VDC signal
generated by the processor.
Unidirectional interface
The unidirectional interface assembly (below right) has a PCB 0285P131A (below left)
fitted inside it. The whole assembly is mounted on the DIN rail inside the main electrical
enclosure.
0285P131A
PL2 PL1
Page 93 of 116
Part Numbers
Connections
The input connections PL1 & PL2 are connected to the main PCB at PL1 (just above the
D-Sub 9 pin serial connection for the LCD screen) and PL37 (just below the D-Sub 9 pin
serial connection for the LCD screen). The output connections PL3, 4 & 5 are for the 3
sets of voltage free contacts (relays). These relays switch the output signals from the plate
setter. Each relay has 1 set of NO contacts and 1 set of NC contacts (please refer to
drawing 0231E082). The relevant connections are shown below
The choice of using either the NO or NC set of contacts is dependant on the application
and type of machine that the interface is to be used with.
The interface can be programmed using a programming screen in the software. To get to
this screen go to Engineering Menu Î Settings Î Plate Setter Menu Î Configure User
Setter. The screen is shown below;
3 Next 4
Level Level RL1 RL2
Fault 0 1
5 Relay 1 N Rdy 0 1 6
Busy 0 1
Ready 1 0
7 Relay 2 8
Page 94 of 116
Using the button “Next Level” moves the cursor down through the list - FAULT, N RDY,
BUSY & READY. When one of the levels is selected, press the Relay 1 or Relay 2 button
to change the relay state to 1 (on) or 0 (off). In the example shown above, the ready signal
is being switched by RL1, so when the processor is ready RL1 will be switched on and
RL2 will be switched off. RL2 switches the not ready signal, so all signals from the
processor which indicates that it is not ready to process a plate turns RL2 on and RL1 off.
RL3 is not programmable and is always energised when the power is turned on. When
using the Configure User Setter, the Select Setter I/F menu must have Configure User
Setter selected (see below).
The user interface type can be selected by using the Select Setter I/F. To get to this
screen go to Engineering Menu Î Settings Î Plate Setter Menu Î Select Setter I/F. On
this screen there are a number of plate setter options. Go into the Select Setter I/F menu
and select Configure User Setter otherwise the interface will not operate. Then enter the
required data into the programme interface screen as described in section 12.4.
This should not normally require changing as the default setting works for most plate
setters. Level 1 = Fault. Level 2 = Not Ready. Level 3 = Warning. No level (blank) = No
action. If you think they need changing, please seek assistance from Heights UK.
To test the interface relays, enter the Engineering Menu Î Test Î Setter I/F Test. This
screen allows the selection of the following;
Depending on how the interface has been programmed (see programming the interface
from the LCD screen & selecting a pre-programmed interface) the switching of the relays
will be different. For example, select test number 3. Using the programming shown in the
illustration previously in item 5, the relay RL1 will be energised and the relay RL2 will not
be energised.
Page 95 of 116
This page
intentionally left
blank
Page 96 of 116
11.1 - Mini Chiller
Engineering Menu Î Settings Menu Î Temperature Limits Menu Î Dev Temp Limits.
In this menu you can set the upper limit and the lower limit. Normally this is set to +/- 2 deg
C violet Ctp plates. When the temperature exceeds the upper or lower limits set the
processor will not accept plates. A Not Ready signal will be generated and if the processor
is connected to an interface, the interface will send the Not Ready signal to the Plate
setter. This can be adjusted in increments of 0.1 deg C to a maximum of +/- 10 deg C.
When the developer is 0.2 deg C greater than the set point the microprocessor on the PCB
sends a signal to turn on the chiller circulation pump. The water in the chiller is
automatically kept at a constant temperature (pre-set by the temperature controller built
into the chiller). The PT 100 probe in the developer tank sends the temperature data to the
PCB. The connection to the PCB for the PT100 probe is PL5. When the temperature has
dropped by 0.2 deg C the microprocessor on the PCB sends a signal to turn off the chiller
circulation pump. The water is constantly chiller regardless of demand.
The LED temperature controller on the side of the chiller assembly does NOT control the
temperature of the developer. It controls the temperature of the WATER in the chiller. The
temperature displayed on this controller is the temperature of the water in the holding tank
built into the chiller assembly. Pressing the “prg” (3) button for a couple of seconds will
display the set value for the water. This should normally be 10 deg C. This is the
temperature that the temperature controller keeps the water at all times. It is normal for the
temperature of the water to increase as the chiller pumps cool water through the cooling
trombone in the developer section.
Page 97 of 116
The power supply to the chiller comes from CB4. The compressor runs automatically to
ensure that the water inside the chiller is kept at the programmed temperature all the time.
When there is demand for cooling, RL3 on the PCB will activate. This turns on the chiller
circulation pump and pumps the water through the single cooling trombone in the
developer section. There is a yellow LED just below the relay that shows when it has been
energised.
The chiller assembly has a number of safety functions built into it. If the chiller assembly is
completely inoperable with no LED readout then check the supply from CB4. To ensure
that the chiller has sufficient water in the holding tank, there is a level switch. When the
water level is low the large red light is illuminated next to the temperature controller. The
pump turns off and the chiller will not function. Fill the tank up and the chiller will
automatically re start. There is also a high pressure switch for the coolant. If the pressure
rises due to a blockage, the chiller will turn off. If any of these faults occur, the Maya
processor will still function. Only the developer temperature will rise. In this case,
temporarily change the temperature Limits to allow for a greater rise in temperature until
the chiller can be repaired or replaced.
Page 98 of 116
11.2 – Mini Chiller Planned Maintenance Schedule
• Control Panels
• Fixing Fasteners
• Isolators
• Guards
• Labelling etc
NOTE
All safety devices and controls should be checked during routine maintenance and
adjustments made if necessary.
The following table illustrates a recommended planned maintenance schedule along with
desired frequency. There are items which may not always be fitted.
These are for guideline purposes and will need to be re-evaluated if the chiller is running in
a contaminated atmosphere or has extreme or long operating conditions etc.
Page 99 of 116
* Check noise and vibration Quarterly
Check compressor starting running currents, supply
* Yearly
voltages and record
Check operation and condition of thermostatic expansion
REFRIGERANT CIRCUIT Yearly
valves, record superheat conditions
* Check system for refrigerant leaks Half Yearly
The Maya 62P & 85P use ceramic heater tiles that work in the long wave Infra-red wave
length. This is the same technology that is used in the pre-heat box of the Heights
manufactured photopolymer processors. The output temperatures from the ceramic
heater blocks are controlled by the PCB software using temperature data sent from 3 of
the ceramic heater blocks which have K-type thermocouples embedded inside them. Too
ensure the highest quality of pre-bake the PCB software has to have temperature setting
data entered for different thickness plates (0.15/0.20/0.24/0.30).
The pre-heat box for the Maya 62P has 5 ceramic tiles connected as shown below.
The Maya pre-heat is specifically designed to work with offset lithographic plates which
require fast heating over a very short duration. The accepted speed for these plates and
the Maya pre-heat is at present between 1000 and 1300 mm per min depending on the
chemistry used. Please refer to the plate manufacturers data for accurate setting of the
conveyor speed. The temperature window which the different plate manufacturers systems
work to is generally between 94~116 deg C. The temperature tolerance band anywhere on
the plate that the Maya can control is +/- 1 step on a temperature strip. Although the
machines leave Heights calibrated, this is only a basic setting and an installation
check/adjustment must be made so that the correct temperatures are entered into the
software for the customer’s requirements on each plate thickness. Once this is done it
should not normally need to be adjusted except when there is a component change to the
system.
Productivity
The Maya pre-heat system requires a short period of time to stabilise after each plate. This
ensures the best possible pre-heat temperature consistency. The programming for the
machine as it leaves Heights allows for a 30~35 second gap between plates.
Soak times
These are the times which can be entered into the PCB software to ensure that the pre-
heat temperatures have stabilised when the machine is first turned on or when the
machine is stopped and re-started. The Maya is delivered with no soak values entered into
the software. It is up to the plate technician to decide if it is appropriate for the customer to
have these values entered. If you wish the Maya processor to have these values entered
into the software, go to Engineering MenuÎ Service UtilitiesÎ SettingsÎ Temperature
LimitsÎ Pre-Heat Soak De-BugÎ Enter the times that the machine will be stabilising
next to the off time segments. The soak time means the period of time it takes for the
whole machine to warm up, not just the pre-heat. Once all the metalwork around the pre-
heat has warmed up then the temperature in the pre-heat will be stabilised to the correct
level. It is generally accepted that the Maya pre-heat requires about 20~30 mins to
stabilise from a cold start. After this the machine is ready to go into full production
(providing the developer is at the correct temperature). If a plate is made immediately the
ceramic tiles come up to temperature (<5 mins) without allowing for the correct soak time,
the first plates may have a temperature inconsistency.
To help further control the temperature on the plate there is a setting to help keep the back
edge of the plate cool. Normally, when running at about 1 meter per min the heat from the
pre-heat box travels along the plate quicker than the plate travels into the machine. This
means that there is a very high likelihood of the back edge of the plate being hotter that
the rest of the plate. To help control this, there is the ability in the PCB software to
automatically turn off the pre-heat as the back edge of the plate enters the pre-heat. This
is known as the “Set Back” and is activated in the software when the machine leaves
Heights. This is found in the pre-heat temperature settings.
To ensure the correct processing and run length from the plate, the pre-heat temperature
has to be accurately set for each plate thickness used. To do this, test plates need to be
produced which measure the temperature of the plate as it passes through the pre-heat
box. From this the correct pre-heat box temperatures can be programmed. For the correct
temperature range needed, please use the data supplied from the plate manufacturer or
suppler.
You will need samples of each plate thickness/gauge that the processor will use. These
sample plates must be unused as the pre-heat test must be carried out with the PVA
coating. You will also need some temperature strips. There are many different suppliers of
temperature strips. These should be scale B and preferably 10 steps. Please choose one
that measures the temperature to at least 116 deg C (241 deg F). A supplier of reliable
temperature strips is:
UK & Europe
Thermographic Measurements Co. Ltd
Riverside Buildings, Unit 1 Dock Road, Connah's Quay, Flintshire, CH5 4DS UK
Telephone: +44 (0) 1244 818348 Fax:+44 (0) 1244 818502
E-Mail: [email protected] http://www.t-m-c.com
US & C
Thermographic Measurements
1820 Pickwick Lane, Glenview, IL 60025 USA
Toll Free: +1 877-887-8367 Fax: +1 847-998-6866
E-Mail: [email protected] http://www.t-m-c.com
Heights can supply the Thermax 10 level strip; p/n-7668-877 (per pack).
Ensure that all the covers are fitted to the machine. This is important as it provides the
normal operating environment for the test. Check that the conveyor speed is correctly set
to the plate manufacturer’s recommendation. Select the plate thickness (gauge) from the
top right hand corner of the normal operating screen on the HMI. If the machine is “On-
Line”, select “Off Line” and manually select the test plate gauge. Allow the machine to
soak (temperature stabilisation time) for about 10 mins.
Select the biggest plate of the thickness (gauge) to be tested. Turn the plate over on a flat
surface and affix the temperature stickers to the back side of the plate. The drawing on the
next page will help you to select which positions and how many strips to use. When
applying the stickers to the plate make sure that they are fully stuck to the aluminium.
Firmly push down with your thumb over the full area of the sticker.
Ensure that the test plates and stickers are stored away from temperatures above or
below the room’s ambient temperature before the test is carried out.
Enter the plate into the processor in the direction that it would normally enter the machine.
Allow the plate to complete the full processing cycle. Inspect the temperature stickers and
record the maximum values on the back of the plate. From these values the pre-heat
25mm
(1”)
25mm
(1”)
This example of a
used temperature strip
shows an indicated
temperature of 110
deg C/230 deg F. If the
next segment turns
>30% darker, this
indicates that the next
temperature has been
reached.
To modify the pre-heat zone temperature values, go to the Engineering MenuÎ Process
Settings Î Pre-Heat Menu ÎSelect Plate Thickness/Gauge being tested. Enter the new
values as required to the Pre-Heat Left/Inner/Right. Do not change the Set Back Value.
Exit until you are offered the option to save settings. If you are happy with the values
entered, confirm by pressing Continue and exit the Engineering Menu.
Allow the pre-heat to stabilise for a further 10 minutes and repeat the test. Adjust if
required. Once you are happy with the results go on to test any other plate
thicknesses/gauges that are used in exactly the same way as previously described.
Incorrect developer
Check the replenisher
replenisher rate (too
setting and operation
high)
Check temperature
setting & displayed
temperature (refer to
plate manufacturer for
recommended
temperature)
Check actual
developer temperature
Developer
Check developer flow
temperature too high
Check developer filter
and housing
Check heater
operation and SSR
Calibrate PT100 input
on PCB
Check operation of
chiller
Dot shrinkage
Check the plate dip to
nip time (refer to plate
Highlights disappear
manufacturer for
Platemaking
recommended time)
Check motor
Development time to
Check roller drive
long
system
Check roller nip
pressure
Check encoder step
and feed back
Check the
replenishment setting
Incorrect developer
Check operation of
replenishment
pump
Calibrate pump
Check PH
Exhausted developer
Replace developer
Dot gain
Check temperature
Shadows fill in setting & displayed
temperature (refer to
Residual emulsion in plate manufacturer for
recommended
Platemaking non image area
temperature)
Check actual
Developer
developer temperature
temperature too low
Check developer flow
Check developer filter
and housing
Check heater
operation and SSR
Calibrate PT100 input
on PCB
Check PH
Developer is too weak
Replace developer
Check temperature
setting & displayed
temperature (refer to
plate manufacturer for
recommended
temperature)
Check actual
developer temperature
Developer
Check developer flow
temperature too high
Check developer filter
and housing
Check heater
operation and SSR
Calibrate PT100 input
on PCB
Check operation of
chiller
Scratches or pin
holes in image area
Platemaking
Check the plate dip to
nip time (refer to plate
manufacturer for
recommended time)
Check motor
Development time too
Check roller drive
long
system
Check roller nip
pressure
Check encoder step
and feed back
Scratches or pin
holes in image area Ensure the pre-wash
splash cover is fitted
correctly
Check the first spray
Pre-wash is splashing
bar is directed into the
back towards pre-heat
scrub roller
Set the spray bar
pressure to eliminate
splashing or dripping
Check PH
Check the
Incorrect developer replenishment setting
replenishment Check operation of
pump
Calibrate pump
Check temperature
setting & displayed
temperature (refer to
plate manufacturer for
Scrumming of non- recommended
image area temperature)
Printing Check actual
Developer
Shadow area filling developer temperature
temperature too low
in Check developer flow
Check developer filter
and housing
Check heater
operation and SSR
Calibrate PT100 input
on PCB
Check temperature
setting & displayed
temperature (refer to
plate manufacturer for
recommended
temperature)
Check actual
Developer developer temperature
temperature too high Check developer flow
Check developer filter
and housing
Check heater
operation and SSR
Calibrate PT100 input
on PCB
Check chiller operation
Dot sharpening
Dirty or damaged
Clean rollers
rubber surface of
Replace rollers
conveyor drive rollers
Check condition of
Plate not feeding conveyor rubber
through machine rollers
Insufficient conveyor
correctly Set conveyor rubber
roller pressure
roller pressures
Check roller mounting
blocks/bearings
Inconsistent
Hardened finisher/gum
General finishing/gumming Clean all rollers with
deposits on rollers
(cont) hot water
Empty finisher/gum
Replace with full bottle
bottle
Drain finisher/gum
Clean section with hot
water
Clean all rollers with
Contaminated finisher
hot water
Refill with fresh
finisher/gum