You are on page 1/ 53

EHS

Technical
Data Book
EHS Mono R290 Pump for Europe
(R290, 50Hz, HP)

99%
Lower GWP
R290

Model : AE***CXYB*K/EU
H
 istory

Version Modification Date Remark


Ver.1.0 Released EHS Mono R290 Pump for Europe TDB 23. 09. 05
Ver.1.1 Updated the final specification 23. 10. 10
Nomenclature

Model Name

AE 160 C X Y B G K EU
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (5) Feature 1

AE EHS Y MONO

(2) Capacity (6) Feature 2

X 1/10 kW (3 digits) B EHS Mono R290 Pump

(3) Version (7) Rating Voltage

C 2023 E 220~240V, 50Hz, 1Ф


G 380~415V, 50Hz, 3Ф

(4) Product Type (8) Mode

N Indoor Unit K Heat Pump (R290)


X Outdoor Unit
Features & Benefits
EHS Mono R290 Pump

R290 Refrigerant

The natural R290 refrigerant has an Ozone Depletion Potential (ODP) of zero
and a Global Warming Potential (GWP) of 3, which is lower than conventional
R32 or R410A refrigerants*. It also has a reinforced design with 5 layers
of safety features to reduce the risks of using the R290 refrigerant.
* GWP by refrigerant: R290 = 3, R32 = 675, R410A = 2088.

Creates extremely hot water – up to 75°C

Enjoy a supply of extremely hot leaving water of up to 75°C*, which enables effective convection heating and provides sanitary water. It
improves energy efficiency**, as it can supply sanitary water of up to 70°C*** using only a Heatpump. And it is hot enough to kill Legionella
bacteria****.

* Leaving water temperature from an outdoor unit is 75°C when the outdoor temperature is -10~35°C. Sanitary water leaving a DHW tank is 70°C when the outdoor temperature is -10~43°C. Results may
vary depending on the actual usage conditions.
** Based on internal testing compared to a conventional model AE***RXYD*G/EU.
*** Leaving water temperature of sanitary hot water, when the outdoortemperature is between -10~43°C. If the outdoor temperature is lower than -10°C, a BoosterHeater is required. Results may vary
depending on the actual usage conditions.
**** Sanitary hot water should be stored at 60°C or higher in order to kill Legionella bacteria.
Features & Benefits
EHS Mono R290 Pump

Save time installing


Convenience in Installation

Install the system and check the water pressure easily. All of the parts for the water piping, like the pump and expansion tank, are fitted inside,
which reduces the installation time and space. And a water pressure sensor lets you conveniently monitor the water pressure on a remote
controller.
Features & Benefits
EHS Mono R290 Pump

Adjustable, 4-step, low-noise operation


Low Sound Level of 35dB(A)

Make less noise whenever you need. The 4-Step Quiet mode* enables adjustable low-noise operation to meet the noise level regulations
in European countries. Simply select from four different steps and reduce the sound level by 3dB, 5dB, 7dB or keep it as low as 35dBA*** to
reduce disturbance.
* The heating performance may be reduced when operating in Quiet mode.
** The Technical Instructions on Noise Abatement (German: TA-Lärm) contain regulations for protecting the general public or neighborhood from noise emissions.
*** Based on internal testing. The noise level is measured 3m away from the front of the outdoor unit. Results may vary depending on environmental factors and individual use.

Enhanced efficiency
High Efficiency (SCOP A+++)

Enjoy consistently high energy savings. It has an enhanced Seasonal


Coefficient of Performance (SCOP) A+++ energy efficiency rating across
the whole range of capacities*. It has been increased by up to 14%**
compared to conventional models and is up to 15% more than the A+++
rating criteria***.
* Based on internal testing when generating 35°C water, in accordance with EN14825. Results may vary depending
on the system configuration and actual usage conditions.
** Based on internal testing when generating 35°C water using an EHS R290 Mono 5kW model, AE050CXYDEK/EU
(SCOP: 5.10), compared to an EHS R32 Mono model of the same capacity, AE050RXYDEG/EU (SCOP: 4.46).
*** Based on internal testing when generating 35°C water using an EHS R290 Mono 5kW model,
AE050CXYDEK/EU (SCOP: 5.10), compared to the criteria of A+++, SCOP≧ 4.45.
C
 ontents

1. Line-up 8

2. Outdoor Units 9
2-1. Specifications 9
2-2. Electrical characteristics 15
2-3. Dimensional drawing 16
2-4. Center of Gravity 18
2-5. Electrical wiring diagram 20
2-6. Sound data 22
2-7. Operation range 27
2-8. Piping diagram 28
2-9. Capacity table 30
2-10. Silent mode corrections 31

3. Installation 32
1.Line-up
1-1. Outdoor unit

Capacity 5.0 kW 8.0 kW 12.0 kW 16.0 kW

Image

1 phase AE050CXYBEK/EU AE080CXYBEK/EU AE120CXYBEK/EU AE160CXYBEK/EU


Model
3 phase - AE080CXYBGK/EU AE120CXYBGK/EU AE160CXYBGK/EU
2. Outdoor Units
2-1. Specifications
Model Name - AE050CXYBEK/EU AE080CXYBEK/EU AE080CXYBGK/EU
Power Supply Φ, #, V, Hz 1, 2, 220~240, 50 1, 2, 220~240, 50 3, 4, 380~415, 50
System Mode - Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W)
Performance Capacity Heating A2W Condition #1. W 5,000 8,000 8,000
(A7/W35) ¹⁾* Btu/h 17,100 27,300 27,300
A2W condition #2 5,000 8,000 8,000
A2W condition #3 5,000 8,000 8,000
W
A2/W35 4)* 5,000 8,000 8,000
A-7/W35
4)* 5,000 8,000 8,000
Cooling A2W Condition #1. W 5,000 8,000 8,000
(A35/W18) ¹⁾* Btu/h 17,100 27,300 27,300
A2W condition #2 W 3,900 5,700 5,700
Power Power Input Heating A2W Condition #1. 980 1,630 1,630
(A7/W35) ¹⁾*
A2W condition #2 1,320 2,160 2,160
W
A2W condition #3 1,610 2,670 2,670
A2/W35 4)* 1,160 1,900 1,900
A-7/W35 4)* 1,670 2,670 2,670
Cooling A2W Condition #1. 1,280 2,050 2,050
(A35/W18) ¹⁾* W
A2W condition #2 1,279 1,900 1,900
Current Input Heating A2W Condition #1. 4.63 7.70 2.56
A
Cooling 6.05 9.69 3.22
Heating A2W condition #2 6.24 10.21 3.39
A
Cooling 7.61 12.62 4.19
Current MCA A 16.1 26.0 16.1
MFA A 17.6 28.6 17.7
Efficiency COP (Nominal Heating) A2W condition #1 5.10 4.91 4.91
EER (Nominal Cooling) A2W condition #1 3.91 3.90 3.90
EER (Nominal Cooling) A2W condition #2 3.05 3.00 3.00
COP A2W condition #2 3.8 3.7 3.7
A2W condition #3 3.1 3.0 3.0
W/W
A2/W35 4)* 4.3 4.2 4.2
A-7/W35
4)* 3.0 3.0 3.0
PdesignH (LWT 35℃) 5,500 8,000 8,000
PdesignH (LWT 55℃) 5,500 8,000 8,000
SCOP (35℃) 5.10 4.85 4.85
SCOP (55℃) 3.60 3.55 3.55
SCOP Class (35℃) A+++ A+++ A+++
SCOP Class (55℃) A++ A++ A++
SEER 4.2 4.3 4.3
Water Water Flow Rate Heating LPM 14.4 23.1 23.1
Connections (Nominal) Cooling LPM 14.4 21.6 21.6
Water Flow Rate Min LPM 7 7 7
Max LPM 48 48 48
Water Pressure (Max) bar 3 3 3
Water Pipe threaded Inlet Φ, mm 28 28 28
Type male Outlet Φ, mm 28 28 28
Leaving Min.~Max Heating °C 15 ~ 75 15 ~ 75 15 ~ 75
Water Min.~Max Cooling °C 5 ~ 25 5 ~ 25 5 ~ 25
Temperature Max. DHW °C 70 70 70
Refrigerant Type - R290 R290 R290
Factory Charging kg 630 870 870
tCO₂e 0.00189 0.00255 0.00255
Control Method - EEV EEV EEV
Outdoor Compressor Type - Rotary Rotary Rotary
Unit Model Name - UF8HC5180FEU UF5HC5260FEX UF5HC5260FEX
Oil Type - Mineral Mineral Mineral
Initial Charge cc 590 850 850
Quantity EA 1 1 1
Output W 1551 2236 2236
Starting method - Inverter driven Inverter driven Inverter driven
Heat exchanger Length mm 986/957/928 986/957/928 986/957/928
Rows Quantity EA 2 3 3
Fin pitch mm 1.5 1.5 1.5
Passes Quantity EA 6-6 9-9 9-9
Face area m² 0.79 0.79 0.79
Stages Quantity EA 38 38 38
Tube type Φ 7 7 7
Fin Type - Corrugate Corrugate Corrugate
Treatment - Anti Salt Anti Salt Anti Salt
Water Heat Type - Braszed Plate Exchager Braszed Plate Exchager Braszed Plate Exchager
Exchanger Quantity EA 1 1 1
Internal water volume L 0.588 0.588 1.008
2. Outdoor Units
2-1. Specifications
Model Name - AE050CXYBEK/EU AE080CXYBEK/EU AE080CXYBGK/EU
Outdoor Fan Type - Propeller Fan Propeller Fan Propeller Fan
Unit Discharge direction Horizontal Horizontal Horizontal
Air Flow Rate Heating m³/min 52 65 65
Cooling m³/min 55 69 69
Quantity EA 1 1 1
Fan motor Quantity EA 1 1 1
Model - FMDC531SSJ FMDC531SSJ FMDC531SSJ
Output W 125 125 125
Drive - Direct drive Direct drive Direct drive
Speed Heating rpm 550 720 720
Cooling rpm 580 760 760
Base Heater W 150 150 150
Water Model Name - UPM4K25-75/130 UPM4K25-75/130 UPM4K25-75/130
Pump Motor Input Max W 60 60 60
Quantity EA 1 1 1
Backup Heater Power kW 2/4/6 (Option) 2/4/6 (Option) 2/4/6 (Option)
Safety device Pressure relief valve bar 2.9 2.9 2.9
Flow Sensor LPM ○(5~60) ○(5~60) ○(5~60)
Expansion vessel Internal water volume liter 10 10 10
Working pressure MPa 0.3 0.3 0.3
Air vent - Gas seperator Gas seperator Gas seperator
Water Pressure Sensor - ○ ○ ○
Strainer - ○ ○ ○
Sound Level Sound Pressure Level Heating dB(A) 41 45 45
Cooling dB(A) 41 45 45
Night Mode(3m) dB(A) 35 35 35
Sound Power Level Heating dB(A) 55 59 59
Cooling dB(A) 55 59 59
Connections Water pipe inlet - BSPP male 1" BSPP male 1" BSPP male 1"
outlet - BSPP male 1" BSPP male 1" BSPP male 1"
Casing Color - Shadow Gray Shadow Gray Shadow Gray
Material - GI-SGCC GI-SGCC GI-SGCC
Packing Material - EPS/BOX EPS/BOX EPS/BOX
Weight kg 13 13 13
External Net Weight kg 113 125 125
Dimension Shipping Weight kg 131 143 143
Net Dimensions (WxHxD) mm 1,270 × 850 × 500 1,270 × 850 × 500 1,270 × 850 × 500
Shipping Dimensions (WxHxD) mm 1,330 × 1,018 × 630 1,330 × 1,018 × 630 1,330 × 1,018 × 630
Operating Temp. Heating ℃ -25 ~ 35 -25 ~ 35 -25 ~ 43
Range Cooling ℃ 10 ~ 46 10 ~ 46 10 ~ 46
D.Hot Water ℃ -25 ~ 43 -25 ~ 43 -25 ~ 43
Additional Wi-Fi Kit - ○ ○ ○
Accessorie Shutoff Valve 25A - 1EA (IN) inc. Filter 1EA (IN) inc. Filter 1EA (IN) inc. Filter
s Temperature Sensor for DHW Tank - ○ ○ ○
Connector Wire -PV Control/Peak power control - ○ ○ ○
Water Pressure Sensor - - - -
Gas seperator - - - -
Function SD Card Converter - ○ ○ ○
PV / SG Ready - ○ ○ ○
muti zone (2 zone) - ○ ○ ○
Comm Kit (OEM Modbus) - - - -
Control Kt (Controller of water part) - ○ ○ ○
Remote Controller - Optional Part Optional Part Optional Part
Wi-Fi Enable ○ ○ ○
-
(Wi-Fi Module - Accessory) (Wi-Fi Module - Accessory) (Wi-Fi Module - Accessory)

NOTE
• Specifications may be subject to change without prior notice.
1) A2W Condition #1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃[DB]/6℃[WB]; (Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃[DB].
2) A2W Condition #2 : (Heating) Water In/Out 40℃/45℃, Outdoor Air 7℃[DB]/6℃[WB]; (Cooling) Water In/Out 12℃/7℃, Outdoor Air 35℃[DB].
3) A2W Condition #3 : (Heating) Water In/Out 47℃/55℃, Outdoor Air 7℃[DB]/6℃[WB].
4) A2W Condition : (A2W35) Water In/Out -/35℃, Outdoor Air 2℃[DB]/1℃[WB]; (A-7/W35) Water In/Out -/35℃, Outdoor Air -7℃[DB]/-(※ Peak Capacity)
5) Select wire size based on the value of MCA
6) Soundpressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
7) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted Sound power level
- Reference power : 1pW
- Measured according to ISO 3741
8) These products contain R290 (GWP=3) which isfluorinated greenhouse gas.
9) The system is operated in (-25°C ≤ Outdoor temp. < -20°C) condition, but no guarantee of capacity.
10) The system is operated by only Booster Heater in special condition (35 °C < Outdoor temp. ≤ 43°C).
2. Outdoor Units
2-1. Specifications
Model Name - AE120CXYBEK/EU AE120CXYBGK/EU
Power Supply Φ, #, V, Hz 1, 2, 220~240, 50 3, 4, 380~415, 50
System Mode - Heat Pump (A2W) Heat Pump (A2W)
Performance Capacity Heating A2W Condition #1. W 12,000 12,000
(A7/W35) ¹⁾* Btu/h 40,900 40,900
A2W condition #2 12,000 12,000
A2W condition #3 12,000 12,000
W
A2/W35
4)* 12,000 12,000
A-7/W35
4)* 12,000 12,000
Cooling A2W Condition #1. W 12,000 12,000
(A35/W18) ¹⁾* Btu/h 40,900 40,900
A2W condition #2 W 9,000 9,000
Power Power Input Heating A2W Condition #1. 2,500 2,500
(A7/W35) ¹⁾*
A2W condition #2 3,240 3,240
W
A2W condition #3 4,000 4,000
A2/W35 4)* 2,790 2,790
A-7/W35 4)* 4,000 4,000
Cooling A2W Condition #1. 3,000 3,000
(A35/W18) ¹⁾* W
A2W condition #2 3,103 3,103
Current Input Heating A2W Condition #1. 11.81 3.92
A
Cooling 14.18 4.71
Heating A2W condition #2 15.31 5.08
A
Cooling 18.9 6.28
Current MCA A 32.0 16.1
MFA A 35.2 17.7
Efficiency COP (Nominal Heating) A2W condition #1 4.80 4.80
EER (Nominal Cooling) A2W condition #1 4.00 4.00
EER (Nominal Cooling) A2W condition #2 2.90 2.90
COP A2W condition #2 3.7 3.7
A2W condition #3 3.0 3.0
W/W
A2/W35 4)* 4.3 4.3
A-7/W35 4)* 3.0 3.0
PdesignH (LWT 35℃) 12,000 12,000
PdesignH (LWT 55℃) 12,000 12,000
SCOP (35℃) 4.90 4.90
SCOP (55℃) 3.65 3.65
SCOP Class (35℃) A+++ A+++
SCOP Class (55℃) A++ A++
SEER 4.8 4.8
Water Water Flow Rate Heating LPM 34.6 34.6
Connections (Nominal) Cooling LPM 34.6 34.6
Water Flow Rate Min LPM 7 7
Max LPM 58 58
Water Pressure (Max) bar 3 3
Water Pipe threaded Inlet Φ, mm 28 28
Type male Outlet Φ, mm 28 28
Leaving Min.~Max Heating °C 15 ~ 75 15 ~ 75
Water Min.~Max Cooling °C 5 ~ 25 5 ~ 25
Temperature Max. DHW °C 70 70
Refrigerant Type - R290 R290
Factory Charging kg 1250 1250
tCO₂e 0.00375 0.00375
Control Method - EEV EEV
Outdoor Compressor Type - Scroll Scroll
Unit Model Name - DS4HC5066FNA DS4HC5066FNA
Oil Type - Kixx RF P85 (GSC) Kixx RF P85 (GSC)
Initial Charge cc 1100 1100
Quantity EA 1 1
Output W 3803 3803
Starting method - Inverter driven Inverter driven
Heat exchanger Length mm 1239/1210/1182 1239/1210/1182
Rows Quantity EA 3 3
Fin pitch mm 1.5 1.5
Passes Quantity EA 22-12 22-12
Face area m² 1.17 1.17
Stages Quantity EA 46 46
Tube type Φ 7 7
Fin Type - Corrugate Corrugate
Treatment - Anti Salt Anti Salt
Water Heat Type - Braszed Plate Exchager Braszed Plate Exchager
Exchanger Quantity EA 1 1
Internal water volume L 1.008 1.008
2. Outdoor Units
2-1. Specifications
Model Name - AE120CXYBEK/EU AE120CXYBGK/EU
Outdoor Fan Type - Propeller Fan Propeller Fan
Unit Discharge direction Horizontal Horizontal
Air Flow Rate Heating m³/min 95 95
Cooling m³/min 90 90
Quantity EA 1 1
Fan motor Quantity EA 1 1
Model - SIC-88FWJ-F1122-1 SIC-88FWJ-F1122-1
Output W 122 122
Drive - Direct drive Direct drive
Speed Heating rpm 590 590
Cooling rpm 560 560
Base Heater W 150 150
Water Model Name - UPM4XLK 25-90/130 UPM4XLK 25-90/130
Pump Motor Input Max W 60 60
Quantity EA 1 1
Backup Heater Power kW 2/4/6 (Option) 2/4/6 (Option)
Safety device Pressure relief valve bar 2.9 2.9
Flow Sensor LPM ○(5~60) ○(5~60)
Expansion vessel Internal water volume liter 10 10
Working pressure MPa 0.3 0.3
Air vent - Gas seperator Gas seperator
Water Pressure Sensor - ○ ○
Strainer - ○ ○
Sound Level Sound Pressure Level Heating dB(A) 47 47
Cooling dB(A) 47 47
Night Mode(3m) dB(A) 35 35
Sound Power Level Heating dB(A) 60 60
Cooling dB(A) 60 60
Connections Water pipe inlet - BSPP male 1" BSPP male 1"
outlet - BSPP male 1" BSPP male 1"
Casing Color - Shadow Gray Shadow Gray
Material - GI-SGCC GI-SGCC
Packing Material - EPS/BOX EPS/BOX
Weight kg 20 20
External Net Weight kg 154 154
Dimension Shipping Weight kg 174 174
Net Dimensions (WxHxD) mm 1,270 × 1,018 × 530 1,270 × 1,018 × 530
Shipping Dimensions (WxHxD) mm 1,330 × 1,226 × 630 1,330 × 1,226 × 630
Operating Temp. Heating ℃ -25 ~ 43 -25 ~ 43
Range Cooling ℃ 10 ~ 46 10 ~ 46
D.Hot Water ℃ -25 ~ 43 -25 ~ 43
Additional Wi-Fi Kit - ○ ○
Accessorie Shutoff Valve 25A - 1EA (IN) inc. Filter 1EA (IN) inc. Filter
s Temperature Sensor for DHW Tank - ○ ○
Connector Wire -PV Control/Peak power control - ○ ○
Water Pressure Sensor - ○ ○
Gas seperator - ○ ○
Function SD Card Converter - ○ ○
PV / SG Ready - ○ ○
muti zone (2 zone) - ○ ○
Comm Kit (OEM Modbus) - - -
Control Kt (Controller of water part) - ○ ○
Remote Controller - Optional Part Optional Part
Wi-Fi Enable ○ ○
-
(Wi-Fi Module - Accessory) (Wi-Fi Module - Accessory)

NOTE
• Specifications may be subject to change without prior notice.
1) A2W Condition #1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃[DB]/6℃[WB]; (Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃[DB].
2) A2W Condition #2 : (Heating) Water In/Out 40℃/45℃, Outdoor Air 7℃[DB]/6℃[WB]; (Cooling) Water In/Out 12℃/7℃, Outdoor Air 35℃[DB].
3) A2W Condition #3 : (Heating) Water In/Out 47℃/55℃, Outdoor Air 7℃[DB]/6℃[WB].
4) A2W Condition : (A2W35) Water In/Out -/35℃, Outdoor Air 2℃[DB]/1℃[WB]; (A-7/W35) Water In/Out -/35℃, Outdoor Air -7℃[DB]/-(※ Peak Capacity)
5) Select wire size based on the value of MCA
6) Soundpressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
7) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted Sound power level
- Reference power : 1pW
- Measured according to ISO 3741
8) These products contain R290 (GWP=3) which isfluorinated greenhouse gas.
9) The system is operated in (-25°C ≤ Outdoor temp. < -20°C) condition, but no guarantee of capacity.
10) The system is operated by only Booster Heater in special condition (35 °C < Outdoor temp. ≤ 43°C).
2. Outdoor Units
2-1. Specifications
Model Name - AE160CXYBEK/EU AE160CXYBGK/EU
Power Supply Φ, #, V, Hz 1, 2, 220~240, 50 3, 4, 380~415, 50
System Mode - Heat Pump (A2W) Heat Pump (A2W)
Performance Capacity Heating A2W Condition #1. W 16,000 16,000
(A7/W35) ¹⁾* Btu/h 54,600 54,600
A2W condition #2 16,000 16,000
A2W condition #3 16,000 16,000
W
A2/W35
4)* 16,000 16,000
A-7/W35
4)* 16,000 16,000
Cooling A2W Condition #1. W 14,000 14,000
(A35/W18) ¹⁾* Btu/h 47,800 47,800
A2W condition #2 W 10,400 10,400
Power Power Input Heating A2W Condition #1. 3,550 3,550
(A7/W35) ¹⁾*
A2W condition #2 4,570 4,570
W
A2W condition #3 5,520 5,520
A2/W35 4)* 4,100 4,100
A-7/W35 4)* 5,710 5,710
Cooling A2W Condition #1. 3,680 3,680
(A35/W18) ¹⁾* W
A2W condition #2 3,586 3,714
Current Input Heating A2W Condition #1. 16.78 5.57
A
Cooling 17.39 5.77
Heating A2W condition #2 21.6 7.17
A
Cooling 26.09 8.66
Current MCA A 32.0 16.1
MFA A 35.2 17.7
Efficiency COP (Nominal Heating) A2W condition #1 4.51 4.51
EER (Nominal Cooling) A2W condition #1 3.80 3.80
EER (Nominal Cooling) A2W condition #2 2.90 2.90
COP A2W condition #2 3.5 3.5
A2W condition #3 2.9 2.9
W/W
A2/W35 4)* 3.9 3.9
A-7/W35 4)* 2.8 2.8
PdesignH (LWT 35℃) 15,500 15,500
PdesignH (LWT 55℃) 14,500 15,500
SCOP (35℃) 4.70 4.70
SCOP (55℃) 3.55 3.55
SCOP Class (35℃) A+++ A+++
SCOP Class (55℃) A++ A++
SEER 5.0 5.0
Water Water Flow Rate Heating LPM 46.2 46.2
Connections (Nominal) Cooling LPM 40.4 40.4
Water Flow Rate Min LPM 7 7
Max LPM 58 58
Water Pressure (Max) bar 3 3
Water Pipe threaded Inlet Φ, mm 28 28
Type male Outlet Φ, mm 28 28
Leaving Min.~Max Heating °C 15 ~ 75 15 ~ 75
Water Min.~Max Cooling °C 5 ~ 25 5 ~ 25
Temperature Max. DHW °C 70 70
Refrigerant Type - R290 R290
Factory Charging kg 1250 1250
tCO₂e 0.00375 0.00375
Control Method - EEV EEV
Outdoor Compressor Type - Scroll Scroll
Unit Model Name - DS4HC5066FNA DS4HC5066FNA
Oil Type - Kixx RF P85 (GSC) Kixx RF P85 (GSC)
Initial Charge cc 1100 1100
Quantity EA 1 1
Output W 3803 3803
Starting method - Inverter driven Inverter driven
Heat exchanger Length mm 1239/1210/1182 1239/1210/1182
Rows Quantity EA 3 3
Fin pitch mm 1.5 1.5
Passes Quantity EA 22-12 22-12
Face area m² 1.17 1.17
Stages Quantity EA 46 46
Tube type Φ 7 7
Fin Type - Corrugate Corrugate
Treatment - Anti Salt Anti Salt
Water Heat Type - Braszed Plate Exchager Braszed Plate Exchager
Exchanger Quantity EA 1 1
Internal water volume L 1.008 1.008
2. Outdoor Units
2-1. Specifications
Model Name - AE160CXYBEK/EU AE160CXYBGK/EU
Outdoor Fan Type - Propeller Fan Propeller Fan
Unit Discharge direction Horizontal Horizontal
Air Flow Rate Heating m³/min 95 95
Cooling m³/min 94 94
Quantity EA 1 1
Fan motor Quantity EA 1 1
Model - SIC-88FWJ-F1122-1 SIC-88FWJ-F1122-1
Output W 122 122
Drive - Direct drive Direct drive
Speed Heating rpm 590 590
Cooling rpm 580 580
Base Heater W 150 150
Water Model Name - UPM4XLK 25-90/130 UPM4XLK 25-90/130
Pump Motor Input Max W 60 60
Quantity EA 1 1
Backup Heater Power kW 2/4/6 (Option) 2/4/6 (Option)
Safety device Pressure relief valve bar 2.9 2.9
Flow Sensor LPM ○(5~60) ○(5~60)
Expansion vessel Internal water volume liter 10 10
Working pressure MPa 0.3 0.3
Air vent - Gas seperator Gas seperator
Water Pressure Sensor - ○ ○
Strainer - ○ ○
Sound Level Sound Pressure Level Heating dB(A) 51 51
Cooling dB(A) 51 51
Night Mode(3m) dB(A) 35 35
Sound Power Level Heating dB(A) 65 65
Cooling dB(A) 65 65
Connections Water pipe inlet - BSPP male 1" BSPP male 1"
outlet - BSPP male 1" BSPP male 1"
Casing Color - Shadow Gray Shadow Gray
Material - GI-SGCC GI-SGCC
Packing Material - EPS/BOX EPS/BOX
Weight kg 20 20
External Net Weight kg 154 154
Dimension Shipping Weight kg 174 174
Net Dimensions (WxHxD) mm 1,270 × 1,018 × 530 1,270 × 1,018 × 530
Shipping Dimensions (WxHxD) mm 1,330 × 1,226 × 630 1,330 × 1,226 × 630
Operating Temp. Heating ℃ -25 ~ 43 -25 ~ 43
Range Cooling ℃ 10 ~ 46 10 ~ 46
D.Hot Water ℃ -25 ~ 43 -25 ~ 43
Additional Wi-Fi Kit - ○ ○
Accessorie Shutoff Valve 25A - 1EA (IN) inc. Filter 1EA (IN) inc. Filter
s Temperature Sensor for DHW Tank - ○ ○
Connector Wire -PV Control/Peak power control - ○ ○
Water Pressure Sensor - ○ ○
Gas seperator - ○ ○
Function SD Card Converter - ○ ○
PV / SG Ready - ○ ○
muti zone (2 zone) - ○ ○
Comm Kit (OEM Modbus) - - -
Control Kt (Controller of water part) - ○ ○
Remote Controller - Optional Part Optional Part
Wi-Fi Enable ○ ○
-
(Wi-Fi Module - Accessory) (Wi-Fi Module - Accessory)

NOTE
• Specifications may be subject to change without prior notice.
1) A2W Condition #1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃[DB]/6℃[WB]; (Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃[DB].
2) A2W Condition #2 : (Heating) Water In/Out 40℃/45℃, Outdoor Air 7℃[DB]/6℃[WB]; (Cooling) Water In/Out 12℃/7℃, Outdoor Air 35℃[DB].
3) A2W Condition #3 : (Heating) Water In/Out 47℃/55℃, Outdoor Air 7℃[DB]/6℃[WB].
4) A2W Condition : (A2W35) Water In/Out -/35℃, Outdoor Air 2℃[DB]/1℃[WB]; (A-7/W35) Water In/Out -/35℃, Outdoor Air -7℃[DB]/-(※ Peak Capacity)
5) Select wire size based on the value of MCA
6) Soundpressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
7) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted Sound power level
- Reference power : 1pW
- Measured according to ISO 3741
8) These products contain R290 (GWP=3) which isfluorinated greenhouse gas.
9) The system is operated in (-25°C ≤ Outdoor temp. < -20°C) condition, but no guarantee of capacity.
10) The system is operated by only Booster Heater in special condition (35 °C < Outdoor temp. ≤ 43°C).
2. Outdoor Units
2-2. Electrical characteristics

Nominal Running
Power Supply Voltage Range [V] Current [A]
Capacity Current [A]
Model
[kW] Min. Max.
Φ # Hz Voltage Cooling Heating MCA MFA
(-10%) (+10%)
5.0 AE050CXYBEK/EU 1 2 50 220-240 198 264 6.05 4.63 16.1 17.6
8.0 AE080CXYBEK/EU 1 2 50 220-240 198 264 9.69 7.70 26.0 28.6
12.0 AE120CXYBEK/EU 1 2 50 220-240 198 264 14.18 11.81 32.0 35.2
16.0 AE160CXYBEK/EU 1 2 50 220-240 198 264 17.39 16.78 32.0 35.2
8.0 AE080CXYBGK/EU 3 4 50 380-415 342 457 3.22 2.56 16.1 17.7
12.0 AE120CXYBGK/EU 3 4 50 380-415 342 457 4.71 3.92 16.1 17.7
16.0 AE160CXYBGK/EU 3 4 50 380-415 342 457 5.77 5.57 16.1 17.7

NOTE
• MCA : Mimium circuit amperes
• MFA : Maximum fuse amperes
• Select wire size based on the value of MCA
2. Outdoor Units
2-3. Dimensional drawing

AE050CXYBEK/EU, 080CXYB*K/EU Units : mm [inches]

NO Name Description
1 Water Pipe (Out) BSPP 1"Male
2 Water Pipe (In) BSPP 1"Male
3 Power wiring conduit Φ25
4 Communication wiring conduit Φ25
5 Conduit Φ25
6 Conduit Φ25
7 Drain holes Connect with the provided drain plug
2. Outdoor Units
2-3. Dimensional drawing

AE120/160CXYB*K/EU Units : mm [inches]

NO Name Description
1 Water Pipe (Out) BSPP 1"Male
2 Water Pipe (In) BSPP 1"Male
3 Power wiring conduit Φ25
4 Communication wiring conduit Φ25
5 Conduit Φ25
6 Conduit Φ25
7 Drain holes Connect with the provided drain plug
2. Outdoor Units
2-4. Center of Gravity

AE050CXYBEK/EU, 080CXYB*K/EU Units : mm [inches]

A C

Model A B C

AE050CXYBEK/EU
AE080CXYBEK/EU 490 [19 5/16] 360 [14 3/16] 280 [11]
AE080CXYBGK/EU
2. Outdoor Units
2-4. Center of Gravity

AE120/160CXYB*K/EU Units : mm [inches]

Model A B C

AE120CXYB*K/EU
470 [18 1/2] 410 [16 1/8] 240 [9 7/16]
AE160CXYB*K/EU
2. Outdoor Units
2-5. Electrical wiring diagram

AE050CXYBEK/EU, AE080CXYBEK/EU, AE120CXYBEK/EU, AE160CXYBEK/EU

ASSY PCB MAIN-OUT Printed circuit board(MAIN) EVA OUT(10k) Thermistor (EVA OUT_10Kohm)
ASSY PCB INVER Printed circuit board(INVERTER) EVA-IN(10k) Thermistor (EVA-IN_10Kohm)
ASSY PCB SUB-EMI Printed circuit board(EMI) WATER OUT(10k) Thermistor (WATER OUT_10Kohm)
ASSY PCB MAIN-
IN (CONTROL KIT) Printed circuit board (CONTROL KIT) WATER-IN(10k) Thermistor (WATER-IN_10Kohm)
OUT-TH(10k) Thermistor (OUT_10Kohm) WATER OUT-TH(200k) Thermistor (WATER OUT_200Kohm)
COND-TH(10k) Thermistor (COND_10Kohm) HOT GAS Solenoid Valve - Hot Gas bypass
DIS-TH(200k) Thermistor (DISCHARGE_200Kohm) 4WAY VALVE Solenoid Valve - 4Way
OLP-TH(200k) Thermistor (OLP_200Kohm) EVI SOL Solenoid Valve - EVI
SUCTION-TH(10k) Thermistor (SUCTION_10kKohm) EVI BYPASS Solenoid Valve - EVI Bypass
EVA IN-TH(200k) Thermistor (EVA IN_200Kohm) M-BLDC Motor for Outdoor Fan
WATER IN-TH(200k) Thermistor (WATER IN_200Kohm) EEV Electronic Expansion Valve
HEATER(10k) Thermistor (HEATER_10Kohm) EXTERNAL CTRL External Control
MIXING(10k) Thermistor (MIXING_10Kohm) UPPER CTRL Upper Control
ROOM(10k) Thermistor (ROOM_10Kohm) PV SIGNAL Photo Voltaic SIGNAL
WATER TANK(200k) Thermistor (WATER TANK_200Kohm) SD CONVERTER Secure Digital Converter
DHW IN(10k) Thermistor (Domestic Hot Water_10Kohm) SD CARD Secure Digital Card

NOTES
1. This wiring diagram applies only to the Outdoor unit.
2. Symbols show as follow :
BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue, GRN: green
3. For connection wiring indoor-outdoor transmission F1-F2.
4. Protective earth(SCREW)
2. Outdoor Units
2-5. Electrical wiring diagram

AE080CXYBGK/EU, AE120CXYBGK/EU, AE160CXYBGK/EU

ASSY PCB MAIN-OUT Printed circuit board(MAIN) EVA OUT(10k) Thermistor (EVA OUT_10Kohm)
ASSY PCB INVER Printed circuit board(INVERTER) EVA-IN(10k) Thermistor (EVA-IN_10Kohm)
ASSY PCB SUB-EMI Printed circuit board(EMI) WATER OUT(10k) Thermistor (WATER OUT_10Kohm)
ASSY PCB MAIN-IN
Printed circuit board (CONTROL KIT) WATER-IN(10k) Thermistor (WATER-IN_10Kohm)
(CONTROL KIT)
OUT-TH(10k) Thermistor (OUT_10Kohm) WATER OUT-TH(200k) Thermistor (WATER OUT_200Kohm)
COND-TH(10k) Thermistor (COND_10Kohm) HOT GAS Solenoid Valve - Hot Gas bypass
DIS-TH(200k) Thermistor (DISCHARGE_200Kohm) 4WAY VALVE Solenoid Valve - 4Way
OLP-TH(200k) Thermistor (OLP_200Kohm) EVI SOL Solenoid Valve - EVI
SUCTION-TH(10k) Thermistor (SUCTION_10kKohm) EVI BYPASS Solenoid Valve - EVI Bypass
EVA IN-TH(200k) Thermistor (EVA IN_200Kohm) M-BLDC Motor for Outdoor Fan
WATER IN-TH(200k) Thermistor (WATER IN_200Kohm) EEV Electronic Expansion Valve
HEATER(10k) Thermistor (HEATER_10Kohm) EXTERNAL CTRL External Control
MIXING(10k) Thermistor (MIXING_10Kohm) UPPER CTRL Upper Control
ROOM(10k) Thermistor (ROOM_10Kohm) PV SIGNAL Photo Voltaic SIGNAL
WATER TANK(200k) Thermistor (WATER TANK_200Kohm) SD CONVERTER Secure Digital Converter
DHW IN(10k) Thermistor (Domestic Hot Water_10Kohm) SD CARD Secure Digital Card

NOTES
1. This wiring diagram applies only to the Outdoor unit.
2. Symbols show as follow :
BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue, GRN: green
3. For connection wiring indoor-outdoor transmission F1-F2.
4. Protective earth(SCREW)
2. Outdoor Units
2-6. Sound data

Summary

Capacity Sound Pressure dB(A) Sound Power dB(A)


Model
(kW)
Heating Cooling Heating Cooling

5.0 AE050CXYBEK/EU 41 41 55 55
8.0 AE080CXYBEK/EU 45 45 59 59
12.0 AE120CXYBEK/EU 47 47 60 60
16.0 AE160CXYBEK/EU 51 51 65 65
8.0 AE080CXYBGK/EU 45 45 59 59
12.0 AE120CXYBGK/EU 47 47 60 60
16.0 AE160CXYBGK/EU 51 51 65 65

NOTE
• Specifications may be subject to change without prior notice.
• Sound Pressure Level
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
• Sound Power Level
- Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level.
- Reference power : 1pW.
- Measured according to ISO 3741.
2. Outdoor Units
2-6. Sound data

Sound Pressure level


Unit: dB(A)

Model Heating Cooling


Microphone 1m
AE050CXYBEK/EU 41 41

AE080CXYBEK/EU 45 45
1.5m

AE120CXYBEK/EU 47 47
Front AE160CXYBEK/EU 51 51

• NR Curve
1) AE050CXYBEK/EU 2) AE080CXYBEK/EU
70 NR 75
70 70 70
NR 75
65 NR 70 65 65 NR70 65
60 NR 65 60 60 NR 65 60
Sound Pressure Level (dB)

Sound Pressure Level (dB)

Cooling
55 NR 60 55 55 NR 60 55
Cooling Heating
50 NR 55 50 50 NR 55 50
Heating
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing threshold NR 25 Hearing threshold NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

3) AE120CXYBEK/EU 4) AE160CXYBEK/EU
70 70 70 70
NR 75 NR 75
65 NR 70 65 65 NR 70 65
Cooling
60 NR 65 60 60 NR 65 60
Heating
Sound Pressure Level (dB)

Sound Pressure Level (dB)

Cooling
55 NR 60 55 55 NR 60 55
Heating
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing threshold NR 25 Hearing threshold NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
2. Outdoor Units
2-6. Sound data

Sound Pressure level


Unit: dB(A)

Model Heating Cooling


Microphone 1m
AE080CXYBGK/EU 45 45

AE120CXYBGK/EU 47 47
1.5m

AE160CXYBGK/EU 51 51
Front

• NR Curve
5) AE080CXYBGK/EU 6) AE120CXYBGK/EU
70 NR 75
70 70 NR 75
70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
Sound Pressure Level (dB)

Sound Pressure Level (dB)

Cooling Cooling
55 NR 60 55 55 NR 60 55
Heating Heating
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing threshold NR 25 Hearing threshold NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

7) AE160CXYBGK/EU
70 NR 75 70
65 NR 70 65
Cooling
60 NR 65 60
Heating
Sound Pressure Level (dB)

55 NR 60 55
50 NR 55 50
45 NR 50 45
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 20
Hearing threshold NR 25
15 15
NR 20
10 10
NR 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)
2. Outdoor Units
2-6. Sound data

Sound Power level


Unit: dB(A)
NOTE
Model Heating Cooling
• Specifications may be subject to change without prior notice
AE050CXYBEK/EU 55 55
- Sound power level is an absolute value that a sound source
AE080CXYBEK/EU 59 59
generates.
- dBA = A-weighted sound power level. AE120CXYBEK/EU 60 60

- Reference power : 1pW. AE160CXYBEK/EU 65 65

- Measured according to ISO 3741.

• NR Curve
1) AE050CXYBEK/EU 2) AE080CXYBEK/EU
80 80 80 80
NR85 NR85
75 75 75 75
NR80 NR80
70 70 70 70
NR75 NR75
65 65 65 65
Sound Power Level (dB)
Sound Power Level (dB)

NR70 NR70
60 60 60 60
NR65 NR65
55 55 55 55
NR60 NR60
50 50 50 50
NR55 NR55
45 45 45 45
NR50 NR50
40 40 40 40
NR45 NR45
35 35 35 35
NR40 NR40
30 30 30 30
NR35 NR35
25 25 25 25
NR30 NR30
20 20 20 20
NR25 NR25
15 15 15 15
NR20 NR20
10 10 10 10
5 NR15 5 5 NR15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

3) AE120CXYBEK/EU 4) AE160CXYBEK/EU
80 80 80 80
NR85 NR85
75 75 75 75
NR80 NR80
70 70 70 70
NR75 NR75
65 65 65
Sound Power Level (dB)
Sound Power Level (dB)

65
NR70 NR70
60 60 60 60
NR65 NR65
55 55 55 55
NR60 NR60
50 50 50 50
NR55 NR55
45 45 45 45
NR50 NR50
40 40 40 40
NR45 NR45
35 35 35 35
NR40 NR40
30 30 30 30
NR35 NR35
25 25 25 25
NR30 NR30
20 20 20 20
NR25 NR25
15 15 15 15
NR20 NR20
10 10 10 10
5 NR15 5 5 NR15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
2. Outdoor Units
2-6. Sound data

Sound Power level


Unit: dB(A)
NOTE
Model Heating Cooling
• Specifications may be subject to change without prior notice
AE080CXYBGK/EU 59 59
- Sound power level is an absolute value that a sound source
AE120CXYBGK/EU 60 60
generates.
- dBA = A-weighted sound power level. AE160CXYBGK/EU 65 65

- Reference power : 1pW.


- Measured according to ISO 3741.

• NR Curve
5) AE080CXYBGK/EU 6) AE120CXYBGK/EU
80 80 80 80
NR85 NR85
75 75 75 75
NR80 NR80
70 70 70 70
NR75 NR75
65 65 65 65
Sound Power Level (dB)

Sound Power Level (dB)

NR70 NR70
60 60 60 60
NR65 NR65
55 55 55 55
NR60 NR60
50 50 50 50
NR55 NR55
45 45 45 45
NR50 NR50
40 40 40 40
NR45 NR45
35 35 35 35
NR40 NR40
30 30 30 30
NR35 NR35
25 25 25 25
NR30 NR30
20 20 20 20
NR25 NR25
15 15 15 15
NR20 NR20
10 10 10 10
5 NR15 5 5 NR15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

7) AE160CXYBGK/EU
80 80
NR85
75 75
NR80
70 70
NR75
Sound Power Level (dB)

65 65
NR70
60 60
NR65
55 55
NR60
50 50
NR55
45 45
NR50
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
15 15
NR20
10 10
5 NR15 5
0 0
125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz)
2. Outdoor Units
2-7. Operation range

1) Cooling 2) Heating

46
35
, DB)

Backup heater operation


& No guarantee of capacity
24
Outdoor temp.

-10
10
-25

5 25 15 25 65 75

Leaving water temp. ( )

Water Temp. (℃) Water Flow Rates (LPM) Air Temp. (℃, DB/WB)
Outdoor Unit
Min Std Max Min Std Max Min Std Max

Cooling 5 - 25
Controller
Heating 15 - 75
Inlet - 23 (12*2) 30
Cooling 10/- 35/24 46/28
Outlet 5 18 (7*2) 25
7 Δ 5℃ 58 (48*1)
Inlet 5 30 (40*2) -
Heating -25/- 7/6 35/24
Outlet 25 (15*3) 35 (45*2) 75

*1) Model : AE050CXYBEK/EU


AE080CXYB*K/EU

*2) Eurovent Test Condition #2


*3) Back up heater operation.

3) DHW (Domestic Hot Water Tank)

43
Outdoor Temp. (˚C DB)

-10

-25 Booster
heater
Operation
25 60 70 only
DHW Tank Temp. (˚C)
2. Outdoor Units
2-8. Piping diagram

AE050CXYBEK/EU, 080CXYB*K/EU

Gas Pressure Pressure


Separator Relief v/v Sensor - Water
(G_S)
Outdoor FanMotor (PS_W)
Thermistor - Ambient (T_A)
(OFM)

Thermistor - Cond Out (T_CO)


Thermistor -
Heat Exchanger - Main Water Out
(Outdoor unit)(HX_M) (T_WO)

Heat Exchanger -
Electronic Expansion PHE (HX_PHE)
Pressure Sensor - Valve - Main (E_M)
Solenoid Low (PS_L) Thermistor -
Suction pipe

E
valve - 4 Way
Service Port - (V_4W) (T_S)
Charging
(PT_C)
Solenoid valve -
S Hot Gas Bypass
(V_HG)
Pressure
Sensor - High
(PS_H)

Thermistor -
Pressure Switch Water In
(PW_H) (T_WI)
ф4.76x240mm Thermistor -
Service Port - Heat Exchanger In
Charging (T_II)
Thermistor -
(PT_C) Reservoir
Thermistor - Discharge pipe PWN
Compressor Top (T_D) Pump
(T_CT)

Compressor
(COMP) Expansion
Vessel(10L) Flow
sensor
2. Outdoor Units
2-8. Piping diagram

AE120/160CXYB*K/EU

Gas Pressure Pressure


Separator Relief v/v Sensor - Water
(G_S)
Outdoor FanMotor (PS_W)
Thermistor - Ambient (T_A)
(OFM)

Thermistor - Cond Out (T_CO)


Thermistor -
Heat Exchanger - Main Water Out
(Outdoor unit)(HX_M) (T_WO)

Heat Exchanger -
Electronic Expansion PHE (HX_PHE)
Pressure Sensor - Valve - Main (E_M)
Solenoid Low (PS_L) Thermistor -
Suction pipe

E
valve - 4 Way
Service Port - (V_4W) (T_S)
Charging
(PT_C)
Solenoid valve -
S Hot Gas Bypass
(V_HG)
Pressure
Sensor - High
(PS_H)

Pressure Switch
(PW_H)
ф4.76x240mm Thermistor -
Heat Exchanger In Thermistor -
Service Port - (T_II) Water In
Thermistor - Charging (T_WI)
Thermistor - Discharge pipe (PT_C) Reservoir
Compressor Top (T_D)
(T_CT)

Compressor Accumulator
(COMP) (AC) Expansion
Flow PWN Vessel(10L)
sensor Pump
2. Outdoor Units
2-9. Capacity table
1) Maximum Heating Capacity (Peak Value)
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input), WF (Water Flow)
LWT (℃)
25 30 35 40 45 50 55 60 65 70 75
Model
Tamb (℃)
HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM)

-25 3,850 1,980 11.1 3,695 1,970 10.6 3,540 1,950 10.2 3,470 1,990 10.0 3,390 2,020 9.8 3,350 2,110 9.7 3,310 2,220 7.0 3,250 2,290 7.0 3,190 2,380 7.0
-20 4,410 1,930 12.7 4,295 2,010 12.4 4,180 2,100 12.1 4,100 2,130 11.8 4,020 2,160 11.6 3,900 2,220 11.3 3,780 2,290 7.0 3,710 2,380 7.0 3,640 2,480 7.0
-15 4,900 1,850 14.1 4,815 2,000 13.9 4,730 2,180 13.6 4,620 2,190 13.3 4,520 2,210 13.1 4,410 2,290 12.8 4,300 2,390 7.8 4,220 2,480 7.7 4,140 2,590 7.0 4,040 2,610 7.0
-10 5,470 1,680 15.7 5,235 1,760 15.1 5,000 1,850 14.4 5,000 2,020 14.4 5,000 2,210 14.5 5,000 2,350 14.5 5,000 2,500 9.1 4,940 2,650 9.0 4,850 2,800 7.1 4,710 2,920 7.0 4,560 3,040 7.0
-7 5,710 1,580 16.4 5,355 1,600 15.4 5,000 1,670 14.4 5,000 1,800 14.4 5,000 2,020 14.5 5,000 2,190 14.5 5,000 2,380 9.1 5,000 2,520 9.1 5,000 2,680 7.3 5,000 2,940 7.3 5,000 3,260 7.3
-2 5,840 1,340 16.8 5,420 1,310 15.6 5,000 1,280 14.4 5,000 1,460 14.4 5,000 1,700 14.5 5,000 1,870 14.5 5,000 2,070 9.1 5,000 2,200 9.1 5,000 2,360 7.3 5,000 2,600 7.3 5,000 2,890 7.3
2 5,900 1,170 17.0 5,450 1,160 15.7 5,000 1,160 14.4 5,000 1,310 14.4 5,000 1,520 14.5 5,000 1,650 14.5 5,000 1,810 9.1 5,000 1,990 9.1 5,000 2,200 7.3 5,000 2,390 7.3 5,000 2,610 7.3
AE050CXYBEK/EU
7 6,090 980 17.5 5,545 980 16.0 5,000 980 14.4 5,000 1,130 14.4 5,000 1,320 14.5 5,000 1,450 14.5 5,000 1,610 9.1 5,000 1,740 9.1 5,000 1,890 7.3 5,000 2,100 7.3 5,000 2,360 7.3
12 6,400 920 18.4 6,270 1,010 18.1 6,140 1,110 17.7 6,080 1,220 17.6 6,010 1,340 17.4 5,980 1,510 17.3 5,950 1,730 10.8 5,920 1,820 10.8 5,880 2,070 8.6 5,850 2,290 8.5 5,820 2,480 8.5
15 6,890 900 19.8 6,675 980 19.2 6,460 1,080 18.6 6,390 1,200 18.5 6,330 1,360 18.3 6,250 1,510 18.1 6,180 1,710 11.2 6,100 1,790 11.1 6,080 2,010 8.9 6,060 2,220 8.8 6,040 2,500 8.8
20 7,490 850 21.5 7,225 950 20.8 6,960 1,080 20.1 6,880 1,220 19.9 6,790 1,400 19.6 6,700 1,520 19.4 6,610 1,670 12.0 6,530 1,770 11.9 6,480 2,020 9.4 6,470 2,270 9.4 6,390 2,560 9.4
25 8,020 810 23.1 7,800 920 22.5 7,580 1,070 21.9 7,490 1,210 21.6 7,390 1,410 21.4 7,270 1,530 21.1 7,160 1,690 13.0 7,020 1,840 12.8 6,920 2,070 10.1 6,840 2,250 10.0 6,770 2,470 9.9
30 8,510 770 24.5 8,305 880 23.9 8,100 1,030 23.4 7,990 1,190 23.1 7,880 1,400 22.8 7,820 1,530 22.7 7,750 1,700 14.1 7,690 1,880 14.0 7,620 2,120 11.1 7,550 2,280 11.0 7,410 2,460 10.8
35 9,080 730 26.1 8,840 840 25.5 8,600 1,010 24.8 8,410 1,150 24.3 8,220 1,360 23.8 8,150 1,490 23.6 8,080 1,660 14.7 8,020 1,840 14.6 7,950 2,050 11.6 7,850 2,200 11.5 7,690 2,350 11.3
-25 5,700 3,020 16.4 5,475 3,000 15.8 5,250 2,980 15.1 5,135 3,030 14.8 5,020 3,080 14.5 4,960 3,220 14.4 4,900 3,380 8.9 4,810 3,500 8.7 4,720 3,630 7.0
-20 6,600 2,970 19.0 6,425 3,090 18.5 6,250 3,230 18.0 6,130 3,270 17.7 6,010 3,320 17.4 5,830 3,420 16.9 5,650 3,530 10.2 5,550 3,670 10.1 5,450 3,820 7.9
-15 7,400 2,880 21.3 7,270 3,110 20.9 7,140 3,380 20.6 6,980 3,400 20.2 6,820 3,430 19.7 6,655 3,560 19.3 6,490 3,710 11.8 6,370 3,860 11.6 6,250 4,030 9.1 6,100 4,070 8.9
-10 8,250 2,610 23.7 8,125 2,820 23.4 8,000 3,080 23.1 7,940 3,310 22.9 7,880 3,580 22.8 7,730 3,730 22.4 7,580 3,910 13.7 7,450 4,120 13.5 7,320 4,360 10.7 7,105 4,530 10.4 6,890 4,740 10.1
-7 8,620 2,460 24.8 8,310 2,560 23.9 8,000 2,670 23.1 8,000 2,960 23.1 8,000 3,330 23.1 8,000 3,600 23.2 8,000 3,920 14.5 8,000 4,160 14.5 8,000 4,420 11.6 7,775 4,710 11.3 7,550 5,070 11.0
-2 8,810 2,080 25.3 8,405 2,090 24.2 8,000 2,110 23.1 8,000 2,410 23.1 8,000 2,810 23.1 8,000 3,080 23.2 8,000 3,400 14.5 8,000 3,630 14.5 8,000 3,880 11.6 8,000 4,280 11.7 8,000 4,760 11.7
2 8,910 1,820 25.6 8,455 1,860 24.3 8,000 1,900 23.1 8,000 2,160 23.1 8,000 2,500 23.1 8,000 2,720 23.2 8,000 2,990 14.5 8,000 3,270 14.5 8,000 3,620 11.6 8,000 3,930 11.7 8,000 4,300 11.7
AE080CXYBEK/EU
7 9,190 1,520 26.4 8,595 1,570 24.7 8,000 1,630 23.1 8,000 1,860 23.1 8,000 2,160 23.1 8,000 2,390 23.2 8,000 2,670 14.5 8,000 2,870 14.5 8,000 3,110 11.6 8,000 3,460 11.7 8,000 3,880 11.7
12 9,850 1,470 28.3 9,650 1,600 27.8 9,450 1,770 27.2 9,350 1,930 27.0 9,250 2,130 26.8 9,200 2,390 26.7 9,150 2,730 16.6 9,100 2,890 16.5 9,050 3,280 13.2 9,000 3,630 13.1 8,950 3,930 13.1
15 10,400 1,390 29.9 10,075 1,520 29.0 9,750 1,680 28.1 9,650 1,870 27.9 9,550 2,110 27.6 9,440 2,350 27.4 9,330 2,670 16.9 9,210 2,780 16.7 9,180 3,120 13.4 9,150 3,450 13.4 9,110 3,880 13.3
20 11,300 1,320 32.5 10,905 1,480 31.4 10,510 1,680 30.3 10,380 1,900 30.0 10,250 2,180 29.7 10,115 2,370 29.3 9,980 2,600 18.1 9,860 2,760 17.9 9,780 3,140 14.2 9,760 3,530 14.2 9,650 3,990 14.1
25 12,110 1,270 34.8 11,775 1,430 33.9 11,440 1,660 33.0 11,300 1,880 32.6 11,160 2,190 32.3 10,980 2,390 31.8 10,800 2,620 19.6 10,600 2,860 19.3 10,450 3,210 15.2 10,320 3,490 15.1 10,220 3,840 15.0
30 12,850 1,200 37.0 12,535 1,370 36.1 12,220 1,610 35.2 12,060 1,840 34.8 11,900 2,180 34.4 11,800 2,380 34.2 11,700 2,640 21.2 11,600 2,930 21.1 11,500 3,290 16.7 11,400 3,540 16.6 10,800 3,690 15.8
35 13,700 1,140 39.4 13,340 1,310 38.4 12,980 1,570 37.4 12,690 1,790 36.6 12,400 2,110 35.9 12,300 2,320 35.7 12,200 2,580 22.1 12,100 2,850 22.0 12,000 3,190 17.5 11,100 3,200 16.2 10,100 3,180 14.8
-25 5,700 3,020 16.4 5,475 3,000 15.8 5,250 2,980 15.1 5,135 3,030 14.8 5,020 3,080 14.5 4,960 3,220 14.4 4,900 3,380 8.9 4,810 3,500 8.7 4,720 3,630 7.0
-20 6,600 2,970 19.0 6,425 3,090 18.5 6,250 3,230 18.0 6,130 3,270 17.7 6,010 3,320 17.4 5,830 3,420 16.9 5,650 3,530 10.2 5,550 3,670 10.1 5,450 3,820 7.9
-15 7,400 2,880 21.3 7,270 3,110 20.9 7,140 3,380 20.6 6,980 3,400 20.2 6,820 3,430 19.7 6,655 3,560 19.3 6,490 3,710 11.8 6,370 3,860 11.6 6,250 4,030 9.1 6,100 4,070 8.9
-10 8,250 2,610 23.7 8,125 2,820 23.4 8,000 3,080 23.1 7,940 3,310 22.9 7,880 3,580 22.8 7,730 3,730 22.4 7,580 3,910 13.7 7,450 4,120 13.5 7,320 4,360 10.7 7,105 4,600 10.4 6,890 4,890 10.1
-7 8,620 2,460 24.8 8,310 2,560 23.9 8,000 2,670 23.1 8,000 2,960 23.1 8,000 3,330 23.1 8,000 3,600 23.2 8,000 3,920 14.5 8,000 4,160 14.5 8,000 4,420 11.6 7,775 4,710 11.3 7,550 5,070 11.0
-2 8,810 2,080 25.3 8,405 2,090 24.2 8,000 2,110 23.1 8,000 2,410 23.1 8,000 2,810 23.1 8,000 3,080 23.2 8,000 3,400 14.5 8,000 3,630 14.5 8,000 3,880 11.6 8,000 4,280 11.7 8,000 4,760 11.7
2 8,910 1,820 25.6 8,455 1,860 24.3 8,000 1,900 23.1 8,000 2,160 23.1 8,000 2,500 23.1 8,000 2,720 23.2 8,000 2,990 14.5 8,000 3,270 14.5 8,000 3,620 11.6 8,000 3,930 11.7 8,000 4,300 11.7
AE080CXYBGK/EU
7 9,190 1,520 26.4 8,595 1,570 24.7 8,000 1,630 23.1 8,000 1,860 23.1 8,000 2,160 23.1 8,000 2,390 23.2 8,000 2,670 14.5 8,000 2,870 14.5 8,000 3,110 11.6 8,000 3,460 11.7 8,000 3,880 11.7
12 9,850 1,470 28.3 9,650 1,600 27.8 9,450 1,770 27.2 9,350 1,930 27.0 9,250 2,130 26.8 9,200 2,390 26.7 9,150 2,730 16.6 9,100 2,890 16.5 9,050 3,280 13.2 9,000 3,630 13.1 8,950 3,930 13.1
15 10,400 1,390 29.9 10,075 1,520 29.0 9,750 1,680 28.1 9,650 1,870 27.9 9,550 2,110 27.6 9,440 2,350 27.4 9,330 2,670 16.9 9,210 2,780 16.7 9,180 3,120 13.4 9,150 3,450 13.4 9,110 3,880 13.3
20 11,300 1,320 32.5 10,905 1,480 31.4 10,510 1,680 30.3 10,380 1,900 30.0 10,250 2,180 29.7 10,115 2,370 29.3 9,980 2,600 18.1 9,860 2,760 17.9 9,780 3,140 14.2 9,760 3,530 14.2 9,650 3,990 14.1
25 12,110 1,270 34.8 11,775 1,430 33.9 11,440 1,660 33.0 11,300 1,880 32.6 11,160 2,190 32.3 10,980 2,390 31.8 10,800 2,620 19.6 10,600 2,860 19.3 10,450 3,210 15.2 10,320 3,490 15.1 10,220 3,840 15.0
30 12,850 1,200 37.0 12,535 1,370 36.1 12,220 1,610 35.2 12,060 1,840 34.8 11,900 2,180 34.4 11,800 2,380 34.2 11,700 2,640 21.2 11,600 2,930 21.1 11,500 3,290 16.7 11,400 3,540 16.6 11,300 3,880 16.5
35 13,700 1,140 39.4 13,340 1,310 38.4 12,980 1,570 37.4 12,690 1,790 36.6 12,400 2,110 35.9 12,300 2,320 35.7 12,200 2,580 22.1 12,100 2,850 22.0 12,000 3,190 17.5 11,100 3,260 16.2 11,820 3,880 17.3
-25 9,800 4,830 28.2 9,650 4,990 27.8 9,500 5,160 27.4 9,400 5,450 27.1 9,300 5,780 26.9 9,150 5,950 26.5 9,000 6,200 16.3 8,850 6,420 16.1 8,800 6,720 12.8
-20 10,500 4,550 30.2 10,400 4,790 29.9 10,300 5,070 29.7 10,250 5,360 29.6 10,150 5,660 29.4 10,100 5,940 29.3 10,000 6,250 18.1 9,850 6,510 17.9 9,760 6,920 14.2
-15 11,700 4,460 33.6 11,420 4,780 32.9 11,150 5,180 34.6 11,125 5,400 32.1 11,075 5,620 32.0 11,050 5,900 32.0 11,000 6,220 19.9 10,930 6,580 19.9 10,680 6,960 15.6 9,800 6,710 14.3
-10 12,890 3,710 37.1 12,445 4,100 35.8 12,000 4,620 34.6 12,000 5,050 34.7 12,000 5,500 34.7 12,000 5,760 34.8 12,000 6,140 21.8 12,000 6,700 21.8 11,500 6,970 16.7 10,660 6,940 15.6 9,940 6,900 14.5
-7 12,930 3,360 37.2 12,470 3,640 35.9 12,000 4,000 34.6 12,000 4,430 34.7 12,000 5,010 34.7 12,000 5,460 34.8 12,000 5,860 21.8 12,000 6,230 21.8 12,000 6,770 17.5 11,270 6,970 16.5 10,200 6,900 14.9
-2 13,220 3,100 38.0 12,610 3,160 36.3 12,000 3,140 34.6 12,000 3,630 34.7 12,000 4,190 34.7 12,000 4,600 34.8 12,000 5,070 21.8 12,000 5,390 21.8 12,000 5,940 17.5 12,000 6,550 17.5 11,680 6,880 17.1
2 13,370 2,660 38.5 12,680 2,800 36.5 12,000 2,790 34.6 12,000 3,210 34.7 12,000 3,640 34.7 12,000 4,110 34.8 12,000 4,490 21.8 12,000 4,940 21.8 12,000 5,540 17.5 12,000 6,020 17.5 12,000 6,450 17.6
AE120CXYBEK/EU
7 13,790 2,180 39.7 12,890 2,360 37.1 12,000 2,500 34.6 12,000 2,790 34.7 12,000 3,240 34.7 12,000 3,550 34.8 12,000 4,000 21.8 12,000 4,270 21.8 12,000 4,710 17.5 12,000 5,290 17.5 12,000 5,880 17.6
12 14,780 2,190 42.5 14,480 2,420 41.7 14,180 2,660 40.9 14,030 2,900 40.5 13,880 3,260 40.2 13,800 3,570 40.0 13,730 4,090 24.9 13,650 4,330 24.8 13,580 4,880 19.8 13,500 5,480 19.7 13,430 5,860 19.7
15 15,600 2,100 44.9 15,110 2,260 43.5 14,630 2,510 42.2 14,480 2,780 41.8 14,330 3,250 41.5 14,160 3,540 41.1 14,000 3,990 25.4 13,820 4,140 25.1 13,770 4,650 20.1 13,730 5,130 20.0 13,670 5,820 20.0
20 16,950 1,990 48.7 16,360 2,230 47.1 15,770 2,510 45.5 15,570 2,840 45.0 15,380 3,300 44.5 15,170 3,590 44.0 14,970 3,870 27.1 14,790 4,140 26.9 14,670 4,720 21.4 14,640 5,290 21.4 14,620 5,850 21.4
25 18,170 1,900 52.3 17,660 2,150 50.8 17,160 2,480 49.5 16,950 2,840 49.0 16,740 3,210 48.4 16,470 3,540 47.7 16,200 3,920 29.4 15,900 4,250 28.9 15,680 4,870 22.8 15,480 5,210 22.6 15,000 5,470 21.9
30 19,280 1,790 55.4 18,800 2,040 54.1 18,330 2,400 52.9 18,090 2,770 52.2 17,850 3,230 51.6 17,700 3,560 51.3 17,550 4,000 31.8 17,400 4,350 31.6 17,250 4,920 25.1 15,900 5,050 23.2 14,900 5,050 21.8
35 20,550 1,720 58.0 20,010 1,950 57.6 19,470 2,350 56.1 19,040 2,710 55.0 18,600 3,130 53.8 18,450 3,480 53.5 18,300 3,890 33.2 18,150 4,260 33.0 17,250 4,620 25.1 15,900 4,600 23.2 14,750 4,600 21.6
-25 9,800 4,830 28.2 9,650 4,990 27.8 9,500 5,160 27.4 9,450 5,480 27.3 9,400 5,840 27.2 9,380 6,100 27.2 9,350 6,440 17.0 9,300 6,890 16.9 9,250 7,400 13.5
-20 11,000 4,760 31.6 10,900 5,020 31.4 10,800 5,320 31.1 10,750 5,630 31.0 10,650 5,940 30.8 10,550 6,210 30.6 10,350 6,470 18.8 10,250 6,770 18.6 10,150 7,360 14.8
-15 11,700 4,460 33.6 11,420 4,780 32.9 11,150 5,180 32.1 11,125 5,400 32.1 11,075 5,620 32.0 11,050 5,900 32.0 11,000 6,220 19.9 10,930 6,580 19.9 10,870 7,200 15.8 10,400 7,270 15.2
-10 12,890 3,710 37.1 12,445 4,100 35.8 12,000 4,620 34.6 12,000 5,050 34.7 12,000 5,500 34.7 12,000 5,760 34.8 12,000 6,140 21.8 12,000 6,700 21.8 12,000 7,500 17.5 11,100 7,450 16.2 10,450 7,410 15.3
-7 12,930 3,360 37.2 12,470 3,640 35.9 12,000 4,000 34.6 12,000 4,430 34.7 12,000 5,010 34.7 12,000 5,460 34.8 12,000 5,860 21.8 12,000 6,230 21.8 12,000 6,770 17.5 11,800 7,520 17.2 11,500 7,930 16.8
-2 13,220 3,100 38.0 12,610 3,160 36.3 12,000 3,140 34.6 12,000 3,630 34.7 12,000 4,190 34.7 12,000 4,600 34.8 12,000 5,070 21.8 12,000 5,390 21.8 12,000 5,940 17.5 12,000 6,550 17.5 12,000 7,410 17.6
2 13,370 2,660 38.5 12,680 2,800 36.5 12,000 2,790 34.6 12,000 3,210 34.7 12,000 3,640 34.7 12,000 4,110 34.8 12,000 4,490 21.8 12,000 4,940 21.8 12,000 5,540 17.5 12,000 6,020 17.5 12,000 6,450 17.6
AE120CXYBGK/EU
7 13,790 2,180 39.7 12,890 2,360 37.1 12,000 2,500 34.6 12,000 2,790 34.7 12,000 3,240 34.7 12,000 3,550 34.8 12,000 4,000 21.8 12,000 4,270 21.8 12,000 4,710 17.5 12,000 5,290 17.5 12,000 5,880 17.6
12 14,780 2,190 42.5 14,480 2,420 41.7 14,180 2,660 40.9 14,030 2,900 40.5 13,880 3,260 40.2 13,800 3,570 40.0 13,730 4,090 24.9 13,650 4,330 24.8 13,580 4,880 19.8 13,500 5,480 19.7 13,430 5,860 19.7
15 15,600 2,100 44.9 15,110 2,260 43.5 14,630 2,510 42.2 14,480 2,780 41.8 14,330 3,250 41.5 14,160 3,540 41.1 14,000 3,990 25.4 13,820 4,140 25.1 13,770 4,650 20.1 13,730 5,130 20.0 13,670 5,820 20.0
20 16,950 1,990 48.7 16,360 2,230 47.1 15,770 2,510 45.5 15,570 2,840 45.0 15,380 3,300 44.5 15,170 3,590 44.0 14,970 3,870 27.1 14,790 4,140 26.9 14,670 4,720 21.4 14,640 5,290 21.4 14,620 5,850 21.4
25 18,170 1,900 52.3 17,660 2,150 50.8 17,160 2,480 49.5 16,950 2,840 49.0 16,740 3,210 48.4 16,470 3,540 47.7 16,200 3,920 29.4 15,900 4,250 28.9 15,680 4,870 22.8 15,480 5,210 22.6 15,330 5,590 22.4
30 19,280 1,790 55.4 18,800 2,040 54.1 18,330 2,400 52.9 18,090 2,770 52.2 17,850 3,230 51.6 17,700 3,560 51.3 17,550 4,000 31.8 17,400 4,350 31.6 17,250 4,920 25.1 16,850 5,190 24.6 16,390 5,560 24.0
35 20,550 1,720 58.0 20,010 1,950 57.6 19,470 2,350 56.1 19,040 2,710 55.0 18,600 3,130 53.8 18,450 3,480 53.5 18,300 3,890 33.2 18,150 4,260 33.0 17,950 4,810 26.1 17,750 5,100 25.9 17,560 5,480 25.7
2. Outdoor Units
2-9. Capacity table
1) Maximum Heating Capacity (Peak Value)
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input), WF (Water Flow)
LWT (℃)
25 30 35 40 45 50 55 60 65 70 75
Model
Tamb (℃)
HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM)

-25 9800 4830 28.2 10650 5630 30.7 11500 6570 33.2 11050 6680 31.9 10600 6790 30.7 10370 6950 30.1 9800 6950 17.8 9390 6950 17.1 8800 6720 12.8
-20 13300 6240 38.3 13135 6570 37.8 12970 6940 37.4 12400 6940 35.8 11830 6950 34.2 11460 6950 33.2 11100 6940 20.1 10190 6940 18.5 9760 6920 14.2
-15 14980 6350 43.1 14370 6620 41.4 13760 6950 39.7 13390 6950 38.7 13010 6950 37.6 12630 6950 36.6 11880 6950 21.5 11070 6950 20.1 10680 6960 15.6 9800 6710 14.3
-10 16200 5180 46.6 16100 5930 46.4 16000 6960 46.2 15195 6950 43.9 14390 6950 41.6 13890 6950 40.3 13320 6950 24.2 12230 6950 22.2 11500 6970 16.7 10660 6940 15.6 9940 6900 14.5
-7 16250 4690 46.7 16125 5150 46.4 16000 5710 46.2 15600 6170 45.1 15200 6740 44.0 14430 6770 41.8 13810 6950 25.0 12720 6950 23.1 11820 6940 17.2 11270 6970 16.5 10200 6900 14.9
-2 16300 4250 46.9 16150 4410 46.5 16000 4590 46.2 15800 5140 45.6 15600 5860 45.1 15500 6190 44.9 15400 6850 27.9 14700 6950 26.7 13450 6940 19.6 12050 6920 17.6 11680 6880 17.1
2 16400 3480 47.2 16200 3760 46.6 16000 4100 46.2 16000 4640 46.2 16000 5330 46.3 16000 5710 46.4 16000 6300 29.0 15500 6720 28.2 14420 6940 21.0 13110 6920 19.1 12600 6920 18.4
AE160CXYBEK/EU
7 17500 3110 50.3 16750 3310 48.2 16000 3550 46.2 16000 4000 46.2 16000 4570 46.3 16000 4940 46.4 16000 5520 29.0 16000 5930 29.1 16000 6540 23.3 14890 6910 21.7 13400 6910 19.6
12 18520 3050 53.3 18150 3290 52.3 17770 3580 51.2 17585 3940 50.8 17400 4390 50.3 17300 4660 50.2 17210 5340 31.2 17110 5600 31.1 17020 6370 24.8 15900 6680 23.2 15400 6700 22.5
15 19970 2990 57.4 19285 3190 55.5 18600 3430 53.6 18500 3860 53.4 18400 4420 53.2 18120 4720 52.5 17920 5320 32.5 17760 5480 32.3 17500 6360 25.5 15900 6360 23.2 15400 6360 22.5
20 20400 2660 58.0 19770 2930 56.9 19140 3280 55.2 18975 3730 54.8 18810 4340 54.4 18610 4580 54.0 18400 4960 33.4 18210 5260 33.1 17600 6050 25.6 15900 6050 23.2 15100 6040 22.1
25 20830 2420 58.0 20255 2690 58.0 19680 3060 56.7 19450 3420 56.2 19220 3880 55.6 19100 4280 55.4 19050 4800 34.5 18800 5110 34.2 17600 5480 25.6 15900 5480 23.2 15000 5470 21.9
30 22110 2280 58.0 21565 2560 58.0 21020 2960 58.0 20745 3390 58.0 20470 3990 58.0 20300 4250 58.0 20010 4750 36.3 19600 5050 35.6 17600 5050 25.6 15900 5050 23.2 14900 5050 21.8
35 23560 2190 58.0 22945 2490 58.0 22330 2900 58.0 21830 3300 58.0 21330 3860 58.0 21160 4150 58.0 20500 4540 37.2 19600 4600 35.6 17600 4600 25.6 15900 4600 23.2 14750 4600 21.6
-25 9800 4830 28.2 10650 5630 30.7 11500 6570 33.2 11400 7000 32.9 11300 7480 32.7 11200 7800 32.5 11000 8270 19.9 10800 8570 19.6 10600 8880 15.4
-20 13300 6240 38.3 13135 6570 37.8 12970 6940 37.4 12500 7030 36.1 12400 7460 35.9 12300 7730 35.7 12100 7900 21.9 11700 8540 21.3 11500 8850 16.7
-15 14980 6350 43.1 14370 6620 41.4 13760 6950 39.7 13450 7000 38.8 13100 7020 37.9 12850 7130 37.3 12560 7550 22.8 12260 8100 22.3 11860 8140 17.3 10800 7990
-10 16200 5180 46.6 16100 5930 46.4 16000 6960 46.2 15195 6950 43.9 14390 6950 41.6 13890 6950 40.3 13320 6950 24.2 12860 7490 23.4 12250 7660 17.8 11000 7490 16.1 10500 7760 15.4
-7 16250 4690 46.7 16125 5150 46.4 16000 5710 46.2 15600 6170 45.1 15200 6740 44.0 14430 6770 41.8 13810 6950 25.0 13520 7550 24.6 13210 8010 19.2 11850 7500 17.3 11450 8010 16.8
-2 16300 4250 46.9 16150 4410 46.5 16000 4590 46.2 15800 5140 45.6 15600 5860 45.1 15500 6190 44.9 15400 6850 27.9 14700 6950 26.7 13450 6940 19.6 12050 6920 17.6 11680 6880 17.1
2 16400 3480 47.2 16200 3760 46.6 16000 4100 46.2 16000 4640 46.2 16000 5330 46.3 16000 5710 46.4 16000 6300 29.0 15500 6720 28.2 14420 6940 21.0 13110 6920 19.1 12600 6920 18.4
AE160CXYBGK/EU
7 17500 3110 50.3 16750 3310 48.2 16000 3550 46.2 16000 4000 46.2 16000 4570 46.3 16000 4940 46.4 16000 5520 29.0 16000 5930 29.1 16000 6540 23.3 16000 7550 23.4 16000 8510 23.4
12 18520 3050 53.3 18150 3290 52.3 17770 3580 51.2 17585 3940 50.8 17400 4390 50.3 17300 4660 50.2 17210 5340 31.2 17110 5600 31.1 17020 6370 24.8 16920 7170 24.7 16780 7360 24.6
15 19970 2990 57.4 19285 3190 55.5 18600 3430 53.6 18500 3860 53.4 18400 4420 53.2 18120 4720 52.5 17920 5320 32.5 17760 5480 32.3 17600 6420 25.6 17400 7020 25.4 17000 7110 24.9
20 20400 2660 58.0 19770 2930 56.9 19140 3280 55.2 18975 3730 54.8 18810 4340 54.4 18610 4580 54.0 18400 4960 33.4 18210 5260 33.1 18050 6220 26.3 17750 6830 25.9 17420 7050 25.5
25 20830 2420 58.0 20255 2690 58.0 19680 3060 56.7 19450 3420 56.2 19220 3880 55.6 19100 4280 55.4 19050 4800 34.5 18800 5110 34.2 18600 5810 27.1 18300 6350 26.7 17900 6680 26.2
30 22110 2280 58.0 21565 2560 58.0 21020 2960 58.0 20745 3390 58.0 20470 3990 58.0 20300 4250 58.0 20010 4750 36.3 19750 5100 35.9 19520 5660 28.4 19090 6120 27.9 18650 6390 27.3
35 23560 2190 58.0 22945 2490 58.0 22330 2900 58.0 21830 3300 58.0 21330 3860 58.0 21160 4150 58.0 20750 4620 37.6 20430 4840 37.1 20260 5350 29.5 19960 5870 29.1 19590 6220 28.7

1. Heating Capacity
- Capacity is according to EN14511.
- Valid for heated water range (ΔT = Leaving water temperature - Entering water temperature)
: If LWT≤50℃, ΔT=5℃ or 50℃<LWT≤60℃ , ΔT=8℃ or LWT>60℃, ΔT=10℃, within the minimum ~ maximum water flow rate.
2. Cooling Capacity
- Capacity is according to EN14511.
- Valid for Cooling water range (ΔT =Entering water temperature - Leaving water temperature)
: ΔT=5℃, within the minimum ~ maximum water flow rate.
3. Power input : Power input is according to EN14511.
4. Peak value : Tested without defrost operation in accordance with EN14511.
※ The real capacity would be changed according to the install environment.
2. Outdoor Units
2-9. Capacity table
2) Maximum Heating Capacity (Integrated Value)
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input), WF (Water Flow)
LWT (℃) 25 30 35 40 45 50 55 60 65 70 75
Model
Tamb (℃)
HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM)

-25 3,850 1,980 11.1 3,695 1,970 10.6 3,540 1,950 10.2 3,470 1,990 10.0 3,390 2,020 9.8 3,350 2,110 9.7 3,310 2,220 7.0 3,250 2,290 7.0 3,190 2,380 7.0
-20 4,410 1,930 12.7 4,295 2,010 12.4 4,180 2,100 12.1 4,100 2,130 11.8 4,020 2,160 11.6 3,900 2,220 11.3 3,780 2,290 7.0 3,710 2,380 7.0 3,640 2,480 7.0
-15 4,900 1,850 14.1 4,815 2,000 13.9 4,730 2,180 13.6 4,620 2,190 13.3 4,520 2,210 13.1 4,410 2,290 12.8 4,300 2,390 7.8 4,220 2,480 7.7 4,140 2,590 7.0 4,040 2,610 7.0
-10 5,310 1,730 15.3 5,110 1,840 14.7 4,910 1,980 14.2 4,880 2,090 14.1 4,850 2,220 14.0 4,840 2,320 14.0 4,830 2,420 8.8 4,820 2,590 8.8 4,800 2,770 7.0 4,680 2,900 7.0 4,560 3,040 7.0
-7 5,380 1,550 15.5 5,165 1,650 14.9 4,950 1,770 14.3 4,950 1,900 14.3 4,950 2,040 14.3 4,950 2,210 14.4 4,940 2,410 9.0 4,920 2,590 8.9 4,900 2,800 7.1 4,900 2,980 7.2 4,890 3,190 7.2
-2 5,460 1,390 15.7 5,205 1,440 15.0 4,950 1,500 14.3 4,950 1,700 14.3 4,950 1,960 14.3 4,950 2,100 14.4 4,950 2,270 9.0 4,950 2,410 9.0 4,950 2,570 7.2 4,870 2,760 7.1 4,770 2,970 7.0
2 5,540 1,230 15.9 5,245 1,260 15.1 4,950 1,300 14.3 4,950 1,470 14.3 4,950 1,710 14.3 4,950 1,890 14.4 4,950 2,150 9.0 4,950 2,220 9.0 4,950 2,290 7.2 4,950 2,510 7.2 4,840 2,710 7.1
AE050CXYBEK/EU
7 6,090 980 17.5 5,545 980 16.0 5,000 980 14.4 5,000 1,130 14.4 5,000 1,320 14.5 5,000 1,450 14.5 5,000 1,610 9.1 5,000 1,740 9.1 5,000 1,890 7.3 5,000 2,100 7.3 5,000 2,360 7.3
12 6,400 920 18.4 6,270 1,010 18.1 6,140 1,110 17.7 6,080 1,220 17.6 6,010 1,340 17.4 5,980 1,510 17.3 5,950 1,730 10.8 5,920 1,820 10.8 5,880 2,070 8.6 5,850 2,290 8.5 5,820 2,480 8.5
15 6,890 900 19.8 6,675 980 19.2 6,460 1,080 18.6 6,390 1,200 18.5 6,330 1,360 18.3 6,250 1,510 18.1 6,180 1,710 11.2 6,100 1,790 11.1 6,080 2,010 8.9 6,060 2,220 8.8 6,040 2,500 8.8
20 7,490 850 21.5 7,225 950 20.8 6,960 1,080 20.1 6,880 1,220 19.9 6,790 1,400 19.6 6,700 1,520 19.4 6,610 1,670 12.0 6,530 1,770 11.9 6,480 2,020 9.4 6,470 2,270 9.4 6,390 2,560 9.4
25 8,020 810 23.1 7,800 920 22.5 7,580 1,070 21.9 7,490 1,210 21.6 7,390 1,410 21.4 7,270 1,530 21.1 7,160 1,690 13.0 7,020 1,840 12.8 6,920 2,070 10.1 6,840 2,250 10.0 6,770 2,470 9.9
30 8,510 770 24.5 8,305 880 23.9 8,100 1,030 23.4 7,990 1,190 23.1 7,880 1,400 22.8 7,820 1,530 22.7 7,750 1,700 14.1 7,690 1,880 14.0 7,620 2,120 11.1 7,550 2,280 11.0 7,410 2,460 10.8
35 9,080 730 26.1 8,840 840 25.5 8,600 1,010 24.8 8,410 1,150 24.3 8,220 1,360 23.8 8,150 1,490 23.6 8,080 1,660 14.7 8,020 1,840 14.6 7,950 2,050 11.6 7,850 2,200 11.5 7,690 2,350 11.3
-25 5,700 3,020 16.4 5,475 3,000 15.8 5,250 2,980 15.1 5,135 3,030 14.8 5,020 3,080 14.5 4,960 3,220 14.4 4,900 3,380 8.9 4,810 3,500 8.7 4,720 3,630 7.0
-20 6,600 2,970 19.0 6,425 3,090 18.5 6,250 3,230 18.0 6,130 3,270 17.7 6,010 3,320 17.4 5,830 3,420 16.9 5,650 3,530 10.2 5,550 3,670 10.1 5,450 3,820 7.9
-15 7,400 2,880 21.3 7,270 3,110 20.9 7,140 3,380 20.6 6,980 3,400 20.2 6,820 3,430 19.7 6,655 3,560 19.3 6,490 3,710 11.8 6,370 3,860 11.6 6,250 4,030 9.1 6,100 4,070 8.9
-10 8,020 2,690 23.1 7,715 2,860 22.2 7,410 3,070 21.4 7,365 3,250 21.3 7,320 3,460 21.2 7,310 3,600 21.2 7,300 3,760 13.2 7,275 4,020 13.2 7,250 4,320 10.6 7,070 4,510 10.3 6,890 4,740 10.1
-7 8,120 2,410 23.4 7,810 2,570 22.5 7,500 2,780 21.6 7,490 2,970 21.6 7,480 3,180 21.6 7,465 3,440 21.6 7,450 3,740 13.5 7,425 4,020 13.5 7,400 4,350 10.8 7,390 4,630 10.8 7,380 4,950 10.8
-2 8,240 2,170 23.7 8,020 2,290 23.1 7,800 2,430 22.5 7,825 2,760 22.6 7,850 3,200 22.7 7,775 3,400 22.5 7,700 3,630 14.0 7,600 3,810 13.8 7,500 4,010 10.9 7,350 4,290 10.7 7,200 4,620 10.5
2 8,360 1,910 24.0 8,155 2,020 23.5 7,950 2,150 22.9 7,950 2,430 23.0 7,950 2,790 23.0 7,950 3,120 23.0 7,950 3,550 14.4 7,800 3,600 14.2 7,650 3,650 11.1 7,475 3,900 10.9 7,300 4,210 10.7
AE080CXYBEK/EU
7 9,190 1,520 26.4 8,595 1,570 24.7 8,000 1,630 23.1 8,000 1,860 23.1 8,000 2,160 23.1 8,000 2,390 23.2 8,000 2,670 14.5 8,000 2,870 14.5 8,000 3,110 11.6 8,000 3,460 11.7 8,000 3,880 11.7
12 9,850 1,470 28.3 9,650 1,600 27.8 9,450 1,770 27.2 9,350 1,930 27.0 9,250 2,130 26.8 9,200 2,390 26.7 9,150 2,730 16.6 9,100 2,890 16.5 9,050 3,280 13.2 9,000 3,630 13.1 8,950 3,930 13.1
15 10,400 1,390 29.9 10,075 1,520 29.0 9,750 1,680 28.1 9,650 1,870 27.9 9,550 2,110 27.6 9,440 2,350 27.4 9,330 2,670 16.9 9,210 2,780 16.7 9,180 3,120 13.4 9,150 3,450 13.4 9,110 3,880 13.3
20 11,300 1,320 32.5 10,905 1,480 31.4 10,510 1,680 30.3 10,380 1,900 30.0 10,250 2,180 29.7 10,115 2,370 29.3 9,980 2,600 18.1 9,860 2,760 17.9 9,780 3,140 14.2 9,760 3,530 14.2 9,650 3,990 14.1
25 12,110 1,270 34.8 11,775 1,430 33.9 11,440 1,660 33.0 11,300 1,880 32.6 11,160 2,190 32.3 10,980 2,390 31.8 10,800 2,620 19.6 10,600 2,860 19.3 10,450 3,210 15.2 10,320 3,490 15.1 10,220 3,840 15.0
30 12,850 1,200 37.0 12,535 1,370 36.1 12,220 1,610 35.2 12,060 1,840 34.8 11,900 2,180 34.4 11,800 2,380 34.2 11,700 2,640 21.2 11,600 2,930 21.1 11,500 3,290 16.7 11,400 3,540 16.6 10,800 3,690 15.8
35 13,700 1,140 39.4 13,340 1,310 38.4 12,980 1,570 37.4 12,690 1,790 36.6 12,400 2,110 35.9 12,300 2,320 35.7 12,200 2,580 22.1 12,100 2,850 22.0 12,000 3,190 17.5 11,100 3,200 16.2 10,100 3,180 14.8
-25 5,700 3,020 16.4 5,475 3,000 15.8 5,250 2,980 15.1 5,135 3,030 14.8 5,020 3,080 14.5 4,960 3,220 14.4 4,900 3,380 8.9 4,810 3,500 8.7 4,720 3,630 7.0
-20 6,600 2,970 19.0 6,425 3,090 18.5 6,250 3,230 18.0 6,130 3,270 17.7 6,010 3,320 17.4 5,830 3,420 16.9 5,650 3,530 10.2 5,550 3,670 10.1 5,450 3,820 7.9
-15 7,400 2,880 21.3 7,270 3,110 20.9 7,140 3,380 20.6 6,980 3,400 20.2 6,820 3,430 19.7 6,655 3,560 19.3 6,490 3,710 11.8 6,370 3,860 11.6 6,250 4,030 9.1 6,100 4,070 8.9
-10 8,020 2,690 23.1 7,715 2,860 22.2 7,410 3,070 21.4 7,365 3,250 21.3 7,320 3,460 21.2 7,310 3,600 21.2 7,300 3,760 13.2 7,275 4,020 13.2 7,250 4,320 10.6 7,070 4,580 10.3 6,890 4,890 10.1
-7 8,120 2,410 23.4 7,810 2,570 22.5 7,500 2,780 21.6 7,490 2,970 21.6 7,480 3,180 21.6 7,465 3,440 21.6 7,450 3,740 13.5 7,425 4,020 13.5 7,400 4,350 10.8 7,390 4,630 10.8 7,380 4,950 10.8
-2 8,240 2,170 23.7 8,020 2,290 23.1 7,800 2,430 22.5 7,825 2,760 22.6 7,850 3,200 22.7 7,775 3,400 22.5 7,700 3,630 14.0 7,600 3,810 13.8 7,500 4,010 10.9 7,350 4,290 10.7 7,200 4,620 10.5
2 8,360 1,910 24.0 8,155 2,020 23.5 7,950 2,150 22.9 7,950 2,430 23.0 7,950 2,790 23.0 7,950 3,120 23.0 7,950 3,550 14.4 7,800 3,600 14.2 7,650 3,650 11.1 7,475 3,900 10.9 7,300 4,210 10.7
AE080CXYBGK/EU
7 9,190 1,520 26.4 8,595 1,570 24.7 8,000 1,630 23.1 8,000 1,860 23.1 8,000 2,160 23.1 8,000 2,390 23.2 8,000 2,670 14.5 8,000 2,870 14.5 8,000 3,110 11.6 8,000 3,460 11.7 8,000 3,880 11.7
12 9,850 1,470 28.3 9,650 1,600 27.8 9,450 1,770 27.2 9,350 1,930 27.0 9,250 2,130 26.8 9,200 2,390 26.7 9,150 2,730 16.6 9,100 2,890 16.5 9,050 3,280 13.2 9,000 3,630 13.1 8,950 3,930 13.1
15 10,400 1,390 29.9 10,075 1,520 29.0 9,750 1,680 28.1 9,650 1,870 27.9 9,550 2,110 27.6 9,440 2,350 27.4 9,330 2,670 16.9 9,210 2,780 16.7 9,180 3,120 13.4 9,150 3,450 13.4 9,110 3,880 13.3
20 11,300 1,320 32.5 10,905 1,480 31.4 10,510 1,680 30.3 10,380 1,900 30.0 10,250 2,180 29.7 10,115 2,370 29.3 9,980 2,600 18.1 9,860 2,760 17.9 9,780 3,140 14.2 9,760 3,530 14.2 9,650 3,990 14.1
25 12,110 1,270 34.8 11,775 1,430 33.9 11,440 1,660 33.0 11,300 1,880 32.6 11,160 2,190 32.3 10,980 2,390 31.8 10,800 2,620 19.6 10,600 2,860 19.3 10,450 3,210 15.2 10,320 3,490 15.1 10,220 3,840 15.0
30 12,850 1,200 37.0 12,535 1,370 36.1 12,220 1,610 35.2 12,060 1,840 34.8 11,900 2,180 34.4 11,800 2,380 34.2 11,700 2,640 21.2 11,600 2,930 21.1 11,500 3,290 16.7 11,400 3,540 16.6 11,300 3,880 16.5
35 13,700 1,140 39.4 13,340 1,310 38.4 12,980 1,570 37.4 12,690 1,790 36.6 12,400 2,110 35.9 12,300 2,320 35.7 12,200 2,580 22.1 12,100 2,850 22.0 12,000 3,190 17.5 11,100 3,260 16.2 11,820 3,880 17.3
-25 9,800 4,830 28.2 9,650 4,990 27.8 9,500 5,160 27.4 9,400 5,450 27.1 9,300 5,780 26.9 9,150 5,950 26.5 9,000 6,200 16.3 8,850 6,420 16.1 8,800 6,720 12.8
-20 10,500 4,550 30.2 10,400 4,790 29.9 10,300 5,070 29.7 10,250 5,360 29.6 10,150 5,660 29.4 10,100 5,940 29.3 10,000 6,250 18.1 9,850 6,510 17.9 9,760 6,920 14.2
-15 11,700 4,460 33.6 11,420 4,780 32.9 11,150 5,180 32.1 11,125 5,400 32.1 11,075 5,620 32.0 11,050 5,900 32.0 11,000 6,220 19.9 10,930 6,580 19.9 10,680 6,960 15.6 9,800 6,710 14.3
-10 12,030 4,130 34.6 11,570 4,380 33.3 11,120 4,540 32.1 11,050 5,030 31.9 10,980 5,290 31.8 10,970 5,460 31.8 10,950 5,760 19.9 10,910 6,150 19.8 10,870 6,590 15.8 10,660 6,940 15.6 9,940 6,900 14.5
-7 12,180 3,730 35.0 11,720 3,860 33.7 11,450 4,160 33.0 11,240 4,590 32.5 11,220 4,820 32.5 11,200 4,980 32.5 11,180 5,670 20.3 11,140 6,160 20.2 11,100 6,660 16.2 10,900 6,900 15.9 10,050 6,930 14.7
-2 12,360 3,350 35.5 12,030 3,430 34.6 11,900 3,710 34.3 11,820 4,310 34.1 11,780 4,900 34.1 11,660 5,000 33.8 11,550 5,340 20.9 11,400 5,710 20.7 11,250 6,130 16.4 11,030 6,500 16.1 10,200 6,610 14.9
2 12,540 2,950 36.1 12,230 3,090 35.2 11,900 3,310 34.3 11,900 3,750 34.4 11,900 4,410 34.4 11,900 4,590 34.5 11,900 5,020 21.6 11,700 5,340 21.3 11,480 5,590 16.7 11,350 5,990 16.6 11,200 6,590 16.4
AE120CXYBEK/EU
7 13,790 2,180 39.7 12,890 2,360 37.1 12,000 2,500 34.6 12,000 2,790 34.7 12,000 3,240 34.7 12,000 3,550 34.8 12,000 4,000 21.8 12,000 4,270 21.8 12,000 4,710 17.5 12,000 5,290 17.5 12,000 5,880 17.6
12 14,780 2,190 42.5 14,480 2,420 41.7 14,180 2,660 40.9 14,030 2,900 40.5 13,880 3,260 40.2 13,800 3,570 40.0 13,730 4,090 24.9 13,650 4,330 24.8 13,580 4,880 19.8 13,500 5,480 19.7 13,430 5,860 19.7
15 15,600 2,100 44.9 15,110 2,260 43.5 14,630 2,510 42.2 14,480 2,780 41.8 14,330 3,250 41.5 14,160 3,540 41.1 14,000 3,990 25.4 13,820 4,140 25.1 13,770 4,650 20.1 13,730 5,130 20.0 13,670 5,820 20.0
20 16,950 1,990 48.7 16,360 2,230 47.1 15,770 2,510 45.5 15,570 2,840 45.0 15,380 3,300 44.5 15,170 3,590 44.0 14,970 3,870 27.1 14,790 4,140 26.9 14,670 4,720 21.4 14,640 5,290 21.4 14,620 5,850 21.4
25 18,170 1,900 52.3 17,660 2,150 50.8 17,160 2,480 49.5 16,950 2,840 49.0 16,740 3,210 48.4 16,470 3,540 47.7 16,200 3,920 29.4 15,900 4,250 28.9 15,680 4,870 22.8 15,480 5,210 22.6 15,000 5,470 21.9
30 19,280 1,790 55.4 18,800 2,040 54.1 18,330 2,400 52.9 18,090 2,770 52.2 17,850 3,230 51.6 17,700 3,560 51.3 17,550 4,000 31.8 17,400 4,350 31.6 17,250 4,920 25.1 15,900 5,050 23.2 14,900 5,050 21.8
35 20,550 1,720 58.0 20,010 1,950 57.6 19,470 2,350 56.1 19,040 2,710 55.0 18,600 3,130 53.8 18,450 3,480 53.5 18,300 3,890 33.2 18,150 4,260 33.0 17,250 4,620 25.1 15,900 4,600 23.2 14,750 4,600 21.6
-25 9,800 4,830 28.2 9,650 4,990 27.8 9,500 5,160 27.4 9,450 5,480 27.3 9,400 5,840 27.2 9,380 6,100 27.2 9,350 6,440 17.0 9,300 6,890 16.9 9,250 7,400 13.5
-20 11,000 4,760 31.6 10,900 5,020 31.4 10,800 5,320 31.1 10,750 5,630 31.0 10,650 5,940 30.8 10,550 6,210 30.6 10,350 6,470 18.8 10,250 6,770 18.6 10,150 7,360 14.8
-15 11,700 4,460 33.6 11,420 4,780 32.9 11,150 5,180 32.1 11,125 5,400 32.1 11,075 5,620 32.0 11,050 5,900 32.0 11,000 6,220 19.9 10,930 6,580 19.9 10,870 7,200 15.8 10,400 7,270 15.2
-10 12,030 4,130 34.6 11,570 4,380 33.3 11,120 4,540 32.1 11,050 5,030 31.9 10,980 5,290 31.8 10,970 5,460 31.8 10,950 5,760 19.9 10,910 6,150 19.8 10,870 6,590 15.8 10,800 7,250 15.8 10,450 7,410 15.3
-7 12,180 3,730 35.0 11,720 3,860 33.7 11,450 4,160 33.0 11,240 4,590 32.5 11,220 4,820 32.5 11,200 4,980 32.5 11,180 5,670 20.3 11,140 6,160 20.2 11,100 6,660 16.2 10,950 7,020 16.0 10,700 7,540 15.7
-2 12,360 3,350 35.5 12,030 3,430 34.6 11,900 3,710 34.3 11,820 4,310 34.1 11,780 4,900 34.1 11,660 5,000 33.8 11,550 5,340 20.9 11,400 5,710 20.7 11,250 6,130 16.4 11,030 6,500 16.1 10,900 7,220 16.0
2 12,540 2,950 36.1 12,230 3,090 35.2 11,900 3,310 34.3 11,900 3,750 34.4 11,900 4,410 34.4 11,900 4,590 34.5 11,900 5,020 21.6 11,700 5,340 21.3 11,480 5,590 16.7 11,350 5,990 16.6 11,200 6,590 16.4
AE120CXYBGK/EU
7 13,790 2,180 39.7 12,890 2,360 37.1 12,000 2,500 34.6 12,000 2,790 34.7 12,000 3,240 34.7 12,000 3,550 34.8 12,000 4,000 21.8 12,000 4,270 21.8 12,000 4,710 17.5 12,000 5,290 17.5 12,000 5,880 17.6
12 14,780 2,190 42.5 14,480 2,420 41.7 14,180 2,660 40.9 14,030 2,900 40.5 13,880 3,260 40.2 13,800 3,570 40.0 13,730 4,090 24.9 13,650 4,330 24.8 13,580 4,880 19.8 13,500 5,480 19.7 13,430 5,860 19.7
15 15,600 2,100 44.9 15,110 2,260 43.5 14,630 2,510 42.2 14,480 2,780 41.8 14,330 3,250 41.5 14,160 3,540 41.1 14,000 3,990 25.4 13,820 4,140 25.1 13,770 4,650 20.1 13,730 5,130 20.0 13,670 5,820 20.0
20 16,950 1,990 48.7 16,360 2,230 47.1 15,770 2,510 45.5 15,570 2,840 45.0 15,380 3,300 44.5 15,170 3,590 44.0 14,970 3,870 27.1 14,790 4,140 26.9 14,670 4,720 21.4 14,640 5,290 21.4 14,620 5,850 21.4
25 18,170 1,900 52.3 17,660 2,150 50.8 17,160 2,480 49.5 16,950 2,840 49.0 16,740 3,210 48.4 16,470 3,540 47.7 16,200 3,920 29.4 15,900 4,250 28.9 15,680 4,870 22.8 15,480 5,210 22.6 15,330 5,590 22.4
30 19,280 1,790 55.4 18,800 2,040 54.1 18,330 2,400 52.9 18,090 2,770 52.2 17,850 3,230 51.6 17,700 3,560 51.3 17,550 4,000 31.8 17,400 4,350 31.6 17,250 4,920 25.1 16,850 5,190 24.6 16,390 5,560 24.0
35 20,550 1,720 58.0 20,010 1,950 57.6 19,470 2,350 56.1 19,040 2,710 55.0 18,600 3,130 53.8 18,450 3,480 53.5 18,300 3,890 33.2 18,150 4,260 33.0 17,950 4,810 26.1 17,750 5,100 25.9 17,560 5,480 25.7
2. Outdoor Units
2-9. Capacity table
2) Maximum Heating Capacity (Integrated Value)
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input), WF (Water Flow)
LWT (℃) 25 30 35 40 45 50 55 60 65 70 75
Model
Tamb (℃)
HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM) HC (W) PI (W) WF (LPM)

-25 9,800 4,830 28.2 10,650 5,630 30.7 11,500 6,570 33.2 11,050 6,680 31.9 10,600 6,790 30.7 10,370 6,950 30.1 9,800 6,950 17.8 9,390 6,950 17.1 8,800 6,720 12.8
-20 13,300 6,240 38.3 13,135 6,570 37.8 12,970 6,940 37.4 12,400 6,940 35.8 11,830 6,950 34.2 11,460 6,950 33.2 11,100 6,940 20.1 10,190 6,940 18.5 9,760 6,920 14.2
-15 14,980 6,350 43.1 14,370 6,620 41.4 13,760 6,950 39.7 13,390 6,950 38.7 13,010 6,950 37.6 12,630 6,950 36.6 11,880 6,950 21.5 11,070 6,950 20.1 10,680 6,960 15.6 9,800 6,710 14.3
-10 15,000 5,880 43.1 14,380 6,030 41.4 13,750 6,190 39.6 13,400 6,490 38.7 13,050 6,830 37.8 12,650 6,840 36.7 12,200 6,850 22.1 11,770 6,770 21.4 11,100 6,770 16.2 10,660 6,940 15.6 9,940 6,900 14.5
-7 14,800 5,150 42.6 14,400 5,360 41.5 14,000 5,600 40.4 13,960 6,080 40.3 13,910 6,640 40.2 13,800 6,830 40.0 12,820 6,850 23.2 12,000 6,770 21.8 11,140 6,750 16.2 10,900 6,900 15.9 10,050 6,930 14.7
-2 14,500 4,460 41.7 14,630 4,740 42.1 14,760 5,050 42.6 14,690 5,730 42.4 14,610 6,610 42.3 14,300 6,590 41.5 13,400 6,450 24.3 12,840 6,770 23.3 12,140 6,750 17.7 11,300 6,770 16.5 10,300 6,780 15.1
2 14,200 3,790 40.8 14,850 4,210 42.8 15,500 4,700 44.7 15,250 5,210 44.0 15,000 5,880 43.4 14,600 6,120 42.3 14,000 6,060 25.4 13,930 6,770 25.3 13,450 6,750 19.6 12,300 6,760 18.0 11,500 6,760 16.8
AE160CXYBEK/EU
7 17,500 3,110 50.3 16,750 3,310 48.2 16,000 3,550 46.2 16,000 4,000 46.2 16,000 4,570 46.3 16,000 4,940 46.4 16,000 5,520 29.0 16,000 5,930 29.1 16,000 6,540 23.3 14,890 6,910 21.7 13,400 6,910 19.6
12 18,520 3,050 53.3 18,150 3,290 52.3 17,770 3,580 51.2 17,585 3,940 50.8 17,400 4,390 50.3 17,300 4,660 50.2 17,210 5,340 31.2 17,110 5,600 31.1 17,020 6,370 24.8 15,900 6,680 23.2 15,400 6,700 22.5
15 19,970 2,990 57.4 19,285 3,190 55.5 18,600 3,430 53.6 18,500 3,860 53.4 18,400 4,420 53.2 18,120 4,720 52.5 17,920 5,320 32.5 17,760 5,480 32.3 17,500 6,360 25.5 15,900 6,360 23.2 15,400 6,360 22.5
20 20,400 2,660 58.0 19,770 2,930 56.9 19,140 3,280 55.2 18,975 3,730 54.8 18,810 4,340 54.4 18,610 4,580 54.0 18,400 4,960 33.4 18,210 5,260 33.1 17,600 6,050 25.6 15,900 6,050 23.2 15,100 6,040 22.1
25 20,830 2,420 58.0 20,255 2,690 58.0 19,680 3,060 56.7 19,450 3,420 56.2 19,220 3,880 55.6 19,100 4,280 55.4 19,050 4,800 34.5 18,800 5,110 34.2 17,600 5,480 25.6 15,900 5,480 23.2 15,000 5,470 21.9
30 22,110 2,280 58.0 21,565 2,560 58.0 21,020 2,960 58.0 20,745 3,390 58.0 20,470 3,990 58.0 20,300 4,250 58.0 20,010 4,750 36.3 19,600 5,050 35.6 17,600 5,050 25.6 15,900 5,050 23.2 14,900 5,050 21.8
35 23,560 2,190 58.0 22,945 2,490 58.0 22,330 2,900 58.0 21,830 3,300 58.0 21,330 3,860 58.0 21,160 4,150 58.0 20,500 4,540 37.2 19,600 4,600 35.6 17,600 4,600 25.6 15,900 4,600 23.2 14,750 4,600 21.6
-25 9,800 4,830 28.2 10,650 5,630 30.7 11,500 6,570 33.2 11,400 7,000 32.9 11,300 7,480 32.7 11,200 7,800 32.5 11,000 8,270 19.9 10,800 8,570 19.6 10,600 8,880 15.4
-20 13,300 6,240 38.3 13,135 6,570 37.8 12,970 6,940 37.4 12,500 7,030 36.1 12,400 7,460 35.9 12,300 7,730 35.7 12,100 7,900 21.9 11,700 8,540 21.3 11,500 8,850 16.7
-15 14,980 6,350 43.1 14,370 6,620 41.4 13,760 6,950 39.7 13,450 7,000 38.8 13,100 7,020 37.9 12,850 7,130 37.3 12,560 7,550 22.8 12,260 8,100 22.3 11,860 8,140 17.3 10,800 7,990 15.8
-10 15,000 5,880 43.1 14,380 6,030 41.4 13,750 6,190 39.6 13,400 6,490 38.7 13,050 6,830 37.8 12,650 6,840 36.7 12,200 6,850 22.1 11,820 7,250 21.5 11,720 7,560 17.1 11,000 7,490 16.1 10,500 7,760 15.4
-7 14,800 5,150 42.6 14,400 5,360 41.5 14,000 5,600 40.4 13,960 6,080 40.3 13,910 6,640 40.2 13,800 6,830 40.0 12,820 6,850 23.2 12,030 7,120 21.9 11,800 7,420 17.2 11,030 7,500 16.1 10,340 7,600 15.1
-2 14,500 4,460 41.7 14,630 4,740 42.1 14,760 5,050 42.6 14,690 5,730 42.4 14,610 6,610 42.3 14,300 6,590 41.5 13,400 6,450 24.3 12,650 6,800 23.0 12,060 6,850 17.6 11,330 6,950 16.5 10,500 7,050 15.4
2 14,200 3,790 40.8 14,850 4,210 42.8 15,500 4,700 44.7 15,250 5,210 44.0 15,000 5,880 43.4 14,600 6,120 42.3 14,000 6,060 25.4 13,610 6,770 24.7 13,290 6,780 19.4 12,240 6,800 17.9 11,510 6,850 16.8
AE160CXYBGK/EU
7 17,500 3,110 50.3 16,750 3,310 48.2 16,000 3,550 46.2 16,000 4,000 46.2 16,000 4,570 46.3 16,000 4,940 46.4 16,000 5,520 29.0 16,000 5,930 29.1 16,000 6,540 23.3 16,000 7,550 23.4 16,000 8,510 23.4
12 18,520 3,050 53.3 18,150 3,290 52.3 17,770 3,580 51.2 17,585 3,940 50.8 17,400 4,390 50.3 17,300 4,660 50.2 17,210 5,340 31.2 17,110 5,600 31.1 17,020 6,370 24.8 16,920 7,170 24.7 16,780 7,360 24.6
15 19,970 2,990 57.4 19,285 3,190 55.5 18,600 3,430 53.6 18,500 3,860 53.4 18,400 4,420 53.2 18,120 4,720 52.5 17,920 5,320 32.5 17,760 5,480 32.3 17,600 6,420 25.6 17,400 7,020 25.4 17,000 7,110 24.9
20 20,400 2,660 58.0 19,770 2,930 56.9 19,140 3,280 55.2 18,975 3,730 54.8 18,810 4,340 54.4 18,610 4,580 54.0 18,400 4,960 33.4 18,210 5,260 33.1 18,050 6,220 26.3 17,750 6,830 25.9 17,420 7,050 25.5
25 20,830 2,420 58.0 20,255 2,690 58.0 19,680 3,060 56.7 19,450 3,420 56.2 19,220 3,880 55.6 19,100 4,280 55.4 19,050 4,800 34.5 18,800 5,110 34.2 18,600 5,810 27.1 18,300 6,350 26.7 17,900 6,680 26.2
30 22,110 2,280 58.0 21,565 2,560 58.0 21,020 2,960 58.0 20,745 3,390 58.0 20,470 3,990 58.0 20,300 4,250 58.0 20,010 4,750 36.3 19,750 5,100 35.9 19,520 5,660 28.4 19,090 6,120 27.9 18,650 6,390 27.3
35 23,560 2,190 58.0 22,945 2,490 58.0 22,330 2,900 58.0 21,830 3,300 58.0 21,330 3,860 58.0 21,160 4,150 58.0 20,750 4,620 37.6 20,430 4,840 37.1 20,260 5,350 29.5 19,960 5,870 29.1 19,590 6,220 28.7

1. Heating cap ity


- Capacity is according to EN14511.
- Valid for heated water range (ΔT = Leaving water temperatu e - Entering water temperature)
: If LWT≤50℃, ΔT=5℃ or 50℃<LWT≤60℃ , ΔT=8℃ or LWT>60℃, ΔT=10℃, within the minimum ~ maximum water flow rate.
2. Cooling capacit
- Capacity is according to EN14511
- Valid for ooling water range (ΔT =Entering water temperature - Leaving water temperature)
: ΔT=5℃, within the minimum ~ maximum water flow rate.
3. Power input : Power input is according to EN1451
4. Peak value : Tested wi out defrost operation in accordance with EN14511.
※ T e real capacity would be changed according to the install environment.
2. Outdoor Units
2-9. Capacity table
3) Cooling Capacity
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), CC (Cooling Capacity), PI (Power input), WF (Water Flow)
LWT(℃) 7 10 13 15 18 25
Model
Tamb(℃) CC (W) PI (W) WF(LPM) CC (W) PI (W) WF(LPM) CC (W) PI (W) WF(LPM) CC (W) PI (W) WF(LPM) CC (W) PI (W) WF(LPM) CC (W) PI (W) WF(LPM)
10 4,485 670 12.9 4,577 670 13.2 4,959 720 14.3 5,244 730 15.1 5,750 730 16.5 6,327 690 18.2
20 4,290 790 12.3 4,415 800 12.7 4,785 750 13.8 5,060 780 14.6 5,550 830 16.0 6,105 860 17.6
AE050CXYBEK/EU 30 4,095 1,040 11.8 4,253 1,030 12.2 4,611 1,090 13.3 4,876 1,100 14.0 5,350 1,020 15.4 5,883 1,020 17.0
35 3,900 1,280 11.2 4,050 1,300 11.6 4,350 1,200 12.5 4,600 1,220 13.2 5,000 1,280 14.4 5,550 1,080 16.0
46 3,650 1,870 10.5 3,850 1,860 11.1 4,120 1,830 11.8 4,420 1,870 12.7 4,800 1,930 13.8 5,246 1,900 15.1
10 6,560 990 18.8 7,010 1,030 20.1 7,870 1,140 22.6 8,440 1,170 24.3 9,200 1,160 26.5 10,260 1,120 29.6
20 6,270 1,150 18.0 6,760 1,220 19.4 7,590 1,220 21.8 8,140 1,250 23.4 8,880 1,320 25.6 9,900 1,390 28.5
AE080CXYBEK/EU 30 5,990 1,520 17.2 6,510 1,580 18.7 7,310 1,730 21.0 7,840 1,780 22.5 8,560 1,640 24.6 9,540 1,650 27.5
35 5,700 1,900 16.4 6,200 1,990 17.8 6,900 1,900 19.8 7,400 1,970 21.3 8,000 2,050 23.1 9,000 1,750 26.0
46 5,250 2,690 15.1 5,820 2,810 16.7 6,390 2,840 18.4 6,900 2,920 19.8 7,750 3,110 22.3 8,320 3,020 24.0
10 6,560 990 18.8 7,010 1,030 20.1 7,870 1,140 22.6 8,440 1,170 24.3 9,200 1,160 26.5 10,260 1,120 29.6
20 6,270 1,150 18.0 6,760 1,220 19.4 7,590 1,220 21.8 8,140 1,250 23.4 8,880 1,320 25.6 9,900 1,390 28.5
AE080CXYBGK/EU 30 5,990 1,520 17.2 6,510 1,580 18.7 7,310 1,730 21.0 7,840 1,780 22.5 8,560 1,640 24.6 9,540 1,650 27.5
35 5,700 1,900 16.4 6,200 1,990 17.8 6,900 1,900 19.8 7,400 1,970 21.3 8,000 2,050 23.1 9,000 1,750 26.0
46 5,250 2,690 15.1 5,820 2,810 16.7 6,390 2,840 18.4 6,900 2,920 19.8 7,750 3,110 22.3 8,320 3,020 24.0
10 10,350 1,590 29.7 10,740 1,600 30.9 11,630 1,650 33.4 12,430 1,690 35.7 13,800 1,700 39.7 15,050 1,470 43.4
20 9,900 1,850 28.4 10,360 1,890 29.8 11,220 1,780 32.3 11,990 1,800 34.5 13,320 1,930 38.3 14,520 1,770 41.9
AE120CXYBEK/EU 30 9,450 2,440 27.1 9,980 2,450 28.7 10,810 2,490 31.1 11,550 2,550 33.2 12,840 2,400 37.0 13,990 2,030 40.3
35 9,000 3,100 25.9 9,500 3,070 27.3 10,200 2,700 29.3 10,900 2,830 31.3 12,000 3,000 34.6 13,200 2,230 38.1
46 7,500 3,920 21.5 8,150 3,970 23.4 9,050 3,920 26.0 9,650 3,970 27.8 10,050 3,940 28.9 12,200 3,970 35.2
10 10,350 1,590 29.7 10,740 1,600 30.9 11,630 1,650 33.4 12,430 1,690 35.7 13,800 1,700 39.7 15,050 1,470 43.4
20 9,900 1,850 28.4 10,360 1,890 29.8 11,220 1,780 32.3 11,990 1,800 34.5 13,320 1,930 38.3 14,520 1,770 41.9
AE120CXYBGK/EU 30 9,450 2,440 27.1 9,980 2,450 28.7 10,810 2,490 31.1 11,550 2,550 33.2 12,840 2,400 37.0 13,990 2,030 40.3
35 9,000 3,100 25.9 9,500 3,070 27.3 10,200 2,700 29.3 10,900 2,830 31.3 12,000 3,000 34.6 13,200 2,230 38.1
46 8,550 4,620 24.6 9,030 4,400 25.9 9,690 4,200 27.9 10,360 4,260 29.8 11,400 4,470 32.8 12,540 4,080 36.2
10 11,960 1,910 34.4 12,430 1,930 35.7 13,510 2,060 38.8 14,480 1,990 41.6 16,100 2,090 46.3 17,670 1,820 50.9
20 11,440 2,190 32.9 11,990 2,220 34.5 13,040 2,210 37.5 13,970 2,200 40.2 15,540 2,370 44.7 17,050 2,190 49.2
AE160CXYBEK/EU 30 10,920 2,880 31.4 11,550 3,000 33.2 12,560 3,110 36.1 13,460 2,960 38.7 14,980 2,940 43.1 16,430 2,510 47.4
35 10,400 3,590 29.9 11,000 3,590 31.6 11,850 3,350 34.1 12,700 3,480 36.5 14,000 3,680 40.4 15,500 2,750 44.7
46 7,520 3,940 21.6 8,170 3,990 23.5 9,080 3,940 26.1 9,680 3,970 27.8 10,100 3,960 29.1 12,270 3,980 35.4
10 11,960 1,910 34.4 12,430 1,930 35.7 13,510 2,060 38.8 14,480 1,990 41.6 16,100 2,090 46.3 17,670 1,820 50.9
20 11,440 2,190 32.9 11,990 2,220 34.5 13,040 2,210 37.5 13,970 2,200 40.2 15,540 2,370 44.7 17,050 2,190 49.2
AE160CXYBGK/EU 30 10,920 2,880 31.4 11,550 3,000 33.2 12,560 3,110 36.1 13,460 2,960 38.7 14,980 2,940 43.1 16,430 2,510 47.4
35 10,400 3,590 29.9 11,000 3,590 31.6 11,850 3,350 34.1 12,700 3,480 36.5 14,000 3,680 40.4 15,500 2,750 44.7
46 9,880 5,340 28.4 10,450 5,150 30.0 11,260 5,000 32.4 12,070 5,070 34.7 13,300 5,340 38.3 14,730 4,990 42.5

1. Heating cap ity


- Capacity is according to EN14511.
- Valid for heated water range (ΔT = Leaving water temperatu e - Entering water temperature)
: If LWT≤50℃, ΔT=5℃ or 50℃<LWT≤60℃ , ΔT=8℃ or LWT>60℃, ΔT=10℃, within the minimum ~ maximum water flow rate.
2. Cooling capacit
- Capacity is according to EN14511
- Valid for ooling water range (ΔT =Entering water temperature - Leaving water temperature)
: ΔT=5℃, within the minimum ~ maximum water flow rate.
3. Power input : Power input is according to EN1451
4. Peak value : Tested wi out defrost operation in accordance with EN14511.
※ T e real capacity would be changed according to the install environment.
2. Outdoor Units
2-10. Silent mode corrections

Heating

Outdoor Air Temperature(℃ DB)


Silent Function
-15 2 7 15

Level 1 0.92 0.90 0.95 0.95

Level 2 0.82 0.80 0.86 0.86

Level 3 0.68 0.67 0.72 0.72

Low-noise 0.54 0.60 0.65 0.65

Cooling

Outdoor Air Temperature(℃ DB)


Silent Function
10 20 35 45

Level 1 1.00 1.00 0.95 0.95

Level 2 0.98 0.98 0.86 0.86

Level 3 0.78 0.78 0.65 0.65

Low-noise 0.70 0.70 0.65 0.65

Correction factor by % glycol

Anti-
Propylene glycol
freeze

Correction factor
%wt Power
Capacity
Input

0% 1.000 1.000

10% 0.988 0.994

20% 0.973 0.988

30% 0.955 0.982

40% 0.933 0.976

50% 0.910 0.970


3. Installation
Outdoor unit

Safety Zone

WARNING
• In case of a leakage the refrigerant must not be able to enter the indoor under any circumstances.
The Safety Zone shall not have any building openings such as:
Windows, Doors, Light wells, Flat roof windows, Air Inlet / Outlet of ventilation systems, etc.
• R
 -290 refrigerant is heavier than air and can be collected on the ground. There should be no sinking or deepening
of the ground in the safety zone.
• The safety zone should not extend to intact buildings or public spaces.
• The safety zone cannot be modified later to violate the protection rules.

(Unit : mm)

• When installed on the ground


• When installed in a place with a flat roof • When installed on the ground in front of a building wall

• When installed at the right corner of a building • When installed at the Left corner of a building
3. Installation
Outdoor unit

When installing 1 outdoor unit


(Unit : mm)

• Wall on suction-side • When the air outlet is towards the wall

• Top-side obstacle
• Discharge-side obstacle • Top-side obstacle
• Wall on discharge-side • Wall on suction-side

• Suction-side obstacle
• Wall on discharge-side
3. Installation ᶹ⸖ⸯⸯⸯ or more
ᶺⸯⸯ or more
ᶺ⸖ⸯⸯⸯ or more
ᶹ⸖ⸯⸯⸯ or more
Outdoor unit
ᶹ⸖ⸯⸯⸯ or more ᶺ⸖ⸯⸯⸯ or more
ᶹ⸖ⸯⸯⸯ or
When installing morethan 1 outdoor unit
more ᶹ⸖ⸯⸯⸯ or more
ᶹ⸖ᶻⸯⸯ or more
ᶹ⸖ᶻⸯⸯ or more (Unit : mm)
ᶹ⸖ᶻⸯⸯ or more

300 or more

ᶺⸯⸯ or more ᶺⸯⸯ or more


1,000 or more
ᶺ⸖ⸯⸯⸯ or more
1,000 or more
ᶹ⸖ⸯⸯⸯ or more 1,000 or more
ᶺ⸖ⸯⸯⸯ or more
300 or more
ᶹ⸖ⸯⸯⸯ or more
1,000 or more ᶹ⸖ⸯⸯⸯ or
600 more
or more
ᶺⸯⸯ or more ᶹ⸖ᶻⸯⸯ or more
ᶼⸯⸯ or more 1,500 or more
• S
 uction-side obstacle (3 sides)
• Wall on discharge-side • No top-side obstacle

ᶺⸯⸯ or more

ᶹ⸖ⸯⸯⸯ or more
ᶹ⸖ⸯⸯⸯ or more 300 or more
3,000 or more
ᶹ⸖ⸯⸯⸯ or more ᶹ⸖ⸯⸯⸯ or more ᶹ⸖ⸯⸯⸯ or more
1,000 or more
ᶺⸯⸯ or more 3,000 or more ᶺⸯⸯ or more
ᶼⸯⸯ or more
ᶹ⸖ⸯⸯⸯ or more 1,000 or more 1,000 or more ᶹ⸖ᶻⸯⸯ or more

300 or more ɵ 1,500 or more


ᶹ⸖ᶻⸯⸯ or more
1,500 or more

• Wall on suction-side • Wall on suction-side ʀ


a' Baff
• Wall on discharge-side • Wall on discharge-side ɵ b' Pre
ɇ c' Air o
a' Baffle plate
CAUTION b' Prevailing wind direction
• The units must be installed according to distances declared, in order to permit accessibility from each side, to
c' Air outlet
ᶺⸯⸯ or more guarantee correct operation of maintenance or repairing of the products. The unit’s parts must be accessible and
serviceable under safe working conditions (for people or things).
ᶹ⸖ⸯⸯⸯ or more
ᶹ⸖ⸯⸯⸯ or more

ᶹ⸖ⸯⸯⸯ or more
ᶹ⸖ⸯⸯⸯ or more
ᶺⸯⸯ or more
ᶼⸯⸯ or more ᶺⸯⸯ or more ɵ
ᶹ⸖ᶻⸯⸯ or more

ʀ
ɵ
3. Installation
Outdoor unit

Mounting the outdoor unit

The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration,
particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be fixed to
an appropriate support (wall or ground).

CAUTION
• When tightening the anchor bolt, tighten the rubber washer to prevent the outdoor unit bolt connection part from
corroding.
• Make a drain outlet around the base for outdoor unit drainage.
• If the outdoor unit is installed on the roof, you have to check the ceiling strength and waterproof the unit.
• The anchor bolt must be 20 mm or higher from the base surface.
※ In order to prevent freezing of water drains, additional protection such as application of a heating cable may be required.

4 x M12

620 mm
344 mm

4 x M12

Outdoor unit

Anchor bolt Outdoor unit support

20 mm
Base surface

Designed to cut off residual vibration


from outdoor unit to rack.
(not supplied with product)
3. Installation
Outdoor unit

General area
While the air to water heat pump is operating in heating mode, ice can accumulate on the surface of the condenser.
To prevent ice from growing, the system occasionally enters a defrost mode and the ice on the surface thaws off.
Water dripping from the condenser is guided through the drain holes to prevent ice formation inside the base plate at
subzero temperatures.
• In case there is not enough space for natural drainage from the outdoor unit, additional drain work is required.
Follow the description as per below:
– Provide a minimum of 150 mm of free space to the floor.
– Insert the drain plug into the hole at the bottom of the outdoor unit.
– Connect the drain hose to the drain plug.
– Make sure dirt and debris cannot block the drain (hose). Clean the base plate whenever needed.
– For the remaining holes (that do not have the drain plug), insert the drain cap
– Make sure that the water dripping from the drain hose runs away correctly and safely.

≥ 150 mm

WARNING
• If the drainage is not adequate, it can lead to stagnant water and ice build-up, causing system performance issues and
possible damages.

Drain hole Φ 20

13 mm

Drain plug x 1ea

212.5 mm

1 Prepare a water drainage channel around the foundation, to drain waste water from around the unit.
2 If the water drainage from the unit is inadequate, please raise the unit on construction concrete blocks, etc.
(the height of the construction should be at least 150 mm).
3. Installation
Outdoor unit

3 If you install the unit on a frame, please install a slanted waterproof plate within 150 mm of the underside of the unit to
prevent water from plashing against the bottom plate from below.

4 When installing the unit in a place frequently exposed to snow, pay special attention to elevating the foundation as high
as the average snow height plus the additional required 150 mm.

5 If you install the unit on a wall support bracket, please install drainage pipework. In order to avoid the drain water from
dripping on the floor potentially creating a slippery surface or an ice layer under freezing conditions.

※ Please securely mount the outdoor unit before connecting the water piping.
3. Installation
Outdoor unit

About the piping work


Water connections must be made in accordance with the Water Piping and Wiring diagram delivered with the unit,
respecting the water inlet and outlet. If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting the water circuit:
• Use clean pipes only.
• Hold the pipe end downwards when removing burrs.
• Cover the pipe end when inserting it through a wall so that no dust and dirt enter.
• Use a good thread sealant for the sealing of the connections.
• The sealing must be able to withstand the pressures and temperatures of the system. When using non-brass
metallic piping, make sure to insulate both materials from each other to prevent galvanic corrosion.
• Because brass is a soft material, use appropriate tooling for connecting the water circuit. Inappropriate tooling
will cause damage to the pipes.

CAUTION
• B e careful not to deform the unit piping by using excessive force when connecting the piping. Deformation of the
piping can cause the unit to malfunction.
• Always use two wrenches (spanners) for tightening or loosening the water connections, and tighten connections
with a torque wrench as specified in the below table. If not, connections and parts can be damaged and leak.
• The unit is only to be used in a closed water system. If applications are in open water circuit, it will generate heat
exchangers fouling, corrosion, and leak.

Name Tightening torque


BSPP1 350~380 kgf•cm 34~37 N•m

Connecting the water pipes


Connecting the water piping typically follows the below procedure:
1 Connect the water piping to the outdoor unit.
2 Connect the water piping to the indoor unit.
3 Connect the recirculation piping.
4 Connect the drain hose to the drain.
5 Fill the water circuit.
6 Fill the DHW tank.
7 Insulate the water piping.

NOTE
• D o not use excessive force when connecting the piping.
Deformation of the piping can cause malfunctioning of the unit.
• Connect the shut-off valve (with integrated filter) to the outdoor unit water inlet, using the thread sealant.
At this time, the filter should be directed downward so that impurities can be collected.
• Connect the field piping to the shut-off valve.
• Connect the shut-off valve to the outdoor unit water outlet, using the thread sealant.
3. Installation
Outdoor unit

Water
Outlet

Water
Outlet
Water
Inlet

Water
Inlet

Shut Off Valve –ᶹ‒ IN –inc'ilter‒


F ⸛
Shut Off Valve –ᶹ‒ OUT

Shut Off Valve (1) IN (inc. Filter) /


Shut Off Valve (1) OUT

NOTE
• About the shut-off valve with integrated filter:
− The installation of the shut-off valve at the water inlet is mandatory.
− Mind the flow direction of the valve.

Water Charging
Fill water into the outdoor unit by opening the shut-off and drain valves.

Water outlet
Water inlet

Water outlet
3. Installation
Outdoor unit

CAUTION
• The operating range of leaving water temperature is 15~75˚C at heating conditions and 5~25˚C at cooling conditions.
• The minimum required water flow for operation is 7 liters/min. At all times the required water flow-rates should
remain. Otherwise, the unit can stop due to a lack of water.
• Water quality must be according to EN directive 98/83 EC. (Please refer to the reference guide for details.)
• Charge the water higher than pressure of 1.0 bar by using make-up water assembly(Field supply).
(The water pressure indicated on the manometer will vary depending on the water temperature) The nominal
water pressure in the system should remain about 1.0 bar at all times to avoid air entering the water system.

Setting capacity and pre-pressure of the expansion vessel


When it is required to change the default pre-pressure of the expansion vessel(1 bar), keep in mind the following
guidelines:
▶ Use only dry nitrogen to set the expansion vessel prepressure.
▶ Inappropriate setting of the expansion vessel prepressure will lead to malfunction of the system.
Therefore, the pre-pressure should only be adjusted by a licensed installer.

Ϯ͘ϱ
Pre-pressure(bar)

Ϯ͘Ϭ

ϭ͘ϱ
Operation range
ϭ͘Ϭ

Ϭ͘ϱ

Ϭ͘Ϭ
ϭϬϬ ϭϱϬ ϮϬϬ ϮϱϬ

Total water volume (ℓ)

Installation Water volume


height
difference(a) < 185 Litres > 185 Litres
Actions required:
• Pre-pressure must be decreased, calculate
according to “Calculating the pre-pressure of
<7m No pre-pressure adjustment required.
the expansion vessel”.
• Check if the water volume is lower than
maximum allowed water volume.
Actions required:
• Pre-pressure must be increased, calculate the
appropriate value following by “Calculating Expansion vessel of the unit too small for the
>7m
the pre-pressure of the expansion vessel”. installation.
• Check if the water volume is lower than
maximum allowed water volume.

(a) Installation height difference: height difference(m) between the highest point of the water circuit and the indoor
unit. If the unit is located at the highest point of the installation, the installation height is considered 0m.
• When Expansion vessel has a capacity 8 liters and 1bar pre-charged. Water volume of total system for reliable
performance is minimum 30 Liter (AE050/080CXYB**), 50 Liter (AE120/160CXYB**).
3. Installation
Outdoor unit

Calculating the pre-pressure of the expansion vessel


▶ T he pre-pressure(Pg) to be set depends on the maximum installation height difference(H) and is calculated as below :
Pg=(H/10+0.3) bar

Protection of the water circuit freezing


To prevent the hydraulic components from freezing, it has a freezing protection function that includes activation of
the pump at low temperatures.
However, in case of a power failure, these functions cannot guarantee protection.
To protect the water circuit from freezing, any one of the following acts shall be performed.
• Add glycol to water. Glycol lowers the freezing point of water.
• Install the anti-freeze valve. The anti-freeze valve discharges water from the system before it freezes.

Freeze protection by glycol


Freeze protection solutions must use propylene glycol with a toxicity rating of Class 1 as listed in Clinical Toxicology
of Commercial Products, 5th Edition.

WARNING
• E
 thylene glycol is toxic and must not be used in the primary water circuit in case of any cross-contamination of
the portable circuit.
• If you add glycol to the water, do NOT install anti-freeze valve, to avoid Glycol leaking out of the anti-freeze valves
into the environment.
• If an anti-freeze protection is used, it will result in increased pressure drop and it may also cause a slight capacity
reduction.

CAUTION
• D ue to the presence of glycol, corrosion of the system is possible. Uninhibited glycol will turn acidic under the
influence of oxygen. The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that
cause severe damage to the system.
• A glycol with corrosion inhibitors is selected to counteract acids formed by the oxidation of glycols.
• No automotive glycol is used because their corrosion inhibitors have a limited lifetime and contain silicates which
can foul or plug the system.
• Galvanized pipes are NOT used in glycol systems since the presence may lead to the precipitation of certain
components in the glycol’s corrosion inhibitor.

Unit resistance and PHE resistance by glycol concentrate


The unit is composed of water pipes and PHE basically. To ensure correct operation and predict the expected
performance, Flow and Resistance table can be used and Flow and resistance characteristic is dependent on Glycol
concentration.
3. Installation
Outdoor unit

AE050/080CXYB**
140
ǮɇϩʪθťθʪϑϑЇθʪUθͱΧ̧࣋ťɇ࣌

120
WATER
100
PG 10%
80
PG 20%
60
PG 30%
40
PG 40%
20
PG 45%
0
10 20 35 40 50 60 70
Ǯɇϩʪθ˜̷ͱиθɇϩʪ࣋øťđ࣌

AE120/160CXYB**
60
ǮɇϩʪθťθʪϑϑЇθʪUθͱΧ̧࣋ťɇ࣌

50
WATER
40
PG 10%
30 PG 20%
20 PG 30%
10 PG 40%
PG 45%
0
10 20 35 40 50 60 70
Ǯɇϩʪθ˜̷ͱиθɇϩʪ࣋øťđ࣌

Changing Glycol concentration can cause the pressure drop of the system and it can lead to make flow rate slow.
Just in case of performance degradation, installer shall be careful of flow rate changes.
The required concentration of glycol depends on the lowest expected outdoor temperature, and on whether you
want to protect the system from bursting or from freezing. To prevent the system from freezing, more glycol is
required. Add glycol according to the table below.

Freezing Points of Propylene Glycol - Water Mixtures


Percent Propylene
Freezing Point [℉] Freezing Point [℃]
Glycol [wt.%]
0 32 0
10 26 -3
20 20 -7
30 10 -12
36 0 -18
40 -5 -20
43 -10 -23
48 -20 -29
3. Installation
Outdoor unit

Outdoor water piping insulation


The complete water circuit, inclusive all the piping, must be insulated to prevent condensation during cooling
operation and reduction of the heating and cooling capacity as well as prevention of freezing of the outside water
piping during winter time. The thickness of the sealing materials must be at least 9 mm with ƛ=0.035 W/mK in order
to prevent freezing on the outside water piping. If the temperature is higher than 30°C and the humidity is higher
than RH 80%, then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation
on the surface of the sealing.

For piping in free air, it is recommended to use the insulation thickness as shown in the below table as a minimum
(with ƛ=0.035 W/mK).

Piping length (m) Minimum insulation thickness (mm)


< 20 19
20 ~ 30 32
30 ~ 40 40
40 ~ 50 50

NOTE
• This recommendation ensures good operation of the unit, however, local regulations may differ and shall be followed.

Minimum active water volume


The minimum active water volume of the system is the amount of water which is always pumped around, even
when all valves in the system are closed. The use of a buffer tank can increase the active volume and therefore the
operation time between compressor start and stop.
Ideally, systems should be designed for around 12 to 15 minutes of operation, in order to meet with our declared
efficiencies. This time frame is based on a maximum of 4 On/Off cycles per hour. The required minimum active
water volume can be calculated via the below stated formula:

tmin x Φmin
Vmin =
Cwater X ΔT

Vmin : Minimum active volume [dm3]


tmin : Minimum allowed operation time is 12 min or 720 sec per cycle [s, sec]
Φmin : Minimum compressor output [kW = kJ/s]
Cwater : Specific heat of water (4,2) [kJ/kg*K]
ΔT : Temperature increase (5-10 K) [K]
3. Installation
Outdoor unit

Electrical wiring diagram

Communication Cable

Power Supply

MCCB+ELB
or
ELCB(RCBO)

10P Terminal Wired remote control,


block EHS Wi-Fi Kit
Power supply Control PBA T/B

Specification of power cable


• 1 Phase
− The power cables are not supplied with the air to water heat pump.
− Power supply cords of parts of appliances for outdoor use shall not be thinner than polychloroprene sheathed
flexible cord (Code designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
− This equipment complies with IEC 61000-3-12.

Rated Voltage Range MCA MFA


Outdoor unit
Hz Volts Min Max Min Circuit Amps. Max Fuse Amps.
AE050CXYBEK 50 220-240 198 264 16.1 17.6
AE080CXYBEK 50 220-240 198 264 26 28.6
AE120CXYBEK 50 220-240 198 264 32 35.2
AE160CXYBEK 50 220-240 198 264 32 35.2

• 3 Phase
− The power cables are not supplied with the air to water heat pump.
− Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord (Code designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
− This equipment complies with IEC 61000-3-12 provided that the short-circuit power (SSC) is greater than or
equal to 3.3[MVA] at the interface point between the user’s supply and the public system. It is the responsibility
of the installer to ensure, by consultation with the energy company if necessary, that the equipment is
connected only to a supply with a short-circuit power (SSC) greater than or equal to 3.3[MVA].

Rated Voltage Range MCA MFA


Outdoor unit
Hz Volts Min Max Min Circuit Amps. Max Fuse Amps.
AE080CXYBGK 50 380-415 342 457 16.1 17.7
AE120CXYBGK 50 380-415 342 457 16.1 17.7
AE160CXYBGK 50 380-415 342 457 16.1 17.7
3. Installation
Outdoor unit

Terminal block specification


• 1 Phase
(Unit: mm)
AC power: M5 screw Communication: M4 screw

/ 1 / 1

/ 1 / 1
ᶹᶺ ᶹᶺ
ᶹⸯ 'ᶹ ᶹⸯ 'ᶹ
ᶹ0 ᶹ0
13 ᶹᶺ
ᶹⸯ 'ᶹ 10.1
17 ᶹ0

• 3 Phase
(Unit: mm)
AC power: M5 screw Communication: M4 screw

5 6 7 5 1 6 7 1

5 6 7 51 6 7 1
12 ᶹᵛ 17 ᶹⸯ 'ᶹ ᶹ0 10.1

ᶹᵛ ᶹᵛ ᶹ0 ᶹⸯ 'ᶹ ᶹ0 ᶹⸯ 'ᶹ
Outdoor wiring
1 Open the switch side cover.

2
3. Installation
Outdoor unit

2 Remove 2 screws and pull the plate to the left.

3 If the plate is rotated to where the hook is, it will be fixed to


the hook.

4 Insert the cables at the rear of the unit, and route them
through the factory mounted cable sleeves into the switch box.
3. Installation
Outdoor unit

Route the cable through the frame


• Connect the wires to the terminal block and fix the cable with the cable tie.

• When installing electrical wiring: tension on the cable(s) must be avoided.


• Earth wire for the outdoor unit cables must be clamped to a suitable ring terminal clamp (not supplied)

• For the power cable, use the grade H07RN-F or H05RN-F materials.

• Power supply cords of parts of appliances for outdoor unit use shall not be thinner than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)

• Specification of communication cable

Communication cable Specifications


0.75 mm², 2 wires shielded LiYCY
3. Installation
Outdoor unit

Important information: regulation regarding the refrigerant used


Please fill in the following with indelible ink on the refrigerant charge label supplied with this product and on this
manual.
• ① the factory refrigerant charge of the product.
• ② the additional refrigerant amount charged in the field.

Ã͝ʒͱͱθЇ̈͝ϩ

ŵࣞߜߣߚ
GWP=3

幩 Outdoor
unit

Unit kg tCO₂e
①, a
②, b DO NOT CHARGE

Refrigerant type GWP value


R-290 3

• GWP: Global Warming Potential


• Calculating tCO₂e: kg x GWP/1000

NOTE
a Factory refrigerant charge of the product: see unit name plate.
b Additional refrigerant amount charged in the field.
(Refer to the above information for the quantity of refrigerant replenishment.)

CAUTION
• T
 he filled-out label must be adhered in the proximity of the product charging port.
(ex. onto the inside of the stop valve cover.)
2023. 10
Ver.1.1

Samsung Electronics Co., LTD.


Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, https://partnerhub.samsung.com Email : [email protected]
Images and data in this book may subject to change without prior notice.