Product datasheet
Specifications
variable speed drive, Easy Altivar
310, heavy duty, 22kW, 30hp,
normal duty, 30kW, 40hp, 380 to
460V, without EMC
ATV310HD22N4E
Main
Range of product Easy Altivar 310
Product or component type Variable speed drive
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product specific application Simple machine
Assembly style With heat sink
Device short name ATV310
Network number of phases Three phase
[Us] rated supply voltage 380...460 V - 15...10 %
Motor power kW 22 kW for heavy duty
30 kW for normal duty
Motor power hp 30 hp for heavy duty
40 hp for normal duty
Noise level 50 dB
Complementary
Quantity per set Set of 1
EMC filter Without EMC filter
type of cooling Integrated fan
Communication port protocol Modbus
Connector type RJ45 (on front face) for Modbus
Physical interface 2-wire RS 485 for Modbus
Transmission frame RTU for Modbus
Transmission rate 4800 bit/s
9600 bit/s
19200 bit/s
38400 bit/s
Number of addresses 1…247 for Modbus
Communication service Read holding registers (03) 29 words
Write single register (06) 29 words
Write multiple registers (16) 27 words
Read/write multiple registers (23) 4/4 words
Read device identification (43)
Line current 64.2 A at 380 V (heavy duty)
71.2 A at 380 V (normal duty)
53.2 A at 460 V (heavy duty)
59.2 A at 460 V (normal duty)
Apparent power 46.2 kVA at 460 V (heavy duty)
47 kVA at 460 V (normal duty)
4 Aug 2025 1
Prospective line Isc 22 kA ( heavy duty )
5 kA ( normal duty )
Continuous output current 46 A heavy duty
60 A normal duty
Maximum transient current 69 A during 60 s (heavy duty)
66 A during 60 s (normal duty)
Power dissipation in W 568.8 W, at In (heavy duty)
735.6 W, at In (normal duty)
Speed drive output frequency 0.5…400 Hz
Nominal switching frequency 4 kHz
Switching frequency 2...12 kHz adjustable
Speed range 1…20 for asynchronous motor
Transient overtorque 170…200 % of nominal motor torque depending on drive rating and type of motor
Braking torque Up to 150 % of nominal motor torque with braking resistor
Up to 70 % of nominal motor torque without braking resistor
Asynchronous motor control Voltage/frequency ratio (V/f)
profile Voltage/frequency ratio - Energy Saving, quadratic U/f
Sensorless vector control (SVC)
Motor slip compensation Adjustable
Output voltage 380...460 V three phase
Electrical connection Terminal, clamping capacity: 25...35 mm², AWG 3...AWG 2 (L1, L2, L3, PA/+, PB, U,
V, W)
Tightening torque 2.2…2.4 N.m
Insulation Electrical between power and control
Supply Internal supply for reference potentiometer: 5 V (4.75…5.25 V)DC, <10 mA with
overload and short-circuit protection
Internal supply for logic inputs: 24 V (20.4…28.8 V)DC, <100 mA with overload and
short-circuit protection
Analogue input number 1
Analogue input type Configurable current AI1 0...20 mA 250 Ohm
Configurable voltage AI1 0...10 V 30 kOhm
Configurable voltage AI1 0...5 V 30 kOhm
Discrete input number 4
Discrete input type Programmable LI1...LI4 24 V 18...30 V
Discrete input logic Negative logic (sink), > 16 V (state 0), < 10 V (state 1), input impedance 3.5 kOhm
Positive logic (source), 0...< 5 V (state 0), > 11 V (state 1)
Sampling duration 10 ms for analogue input
20 ms, tolerance +/- 1 ms for logic input
Linearity error +/- 0.3 % of maximum value for analogue input
Analogue output number 1
Analogue output type AO1 software-configurable voltage: 0...10 V AC 0...10 V 0…0.02 A, impedance: 470
Ohm, resolution 8 bits
AO1 software-configurable current: 0...20 mA, impedance: 800 Ohm, resolution 8 bits
Discrete output number 2
Discrete output type Logic output LO+, LO-
Protected relay output R1A, R1B, R1C 1 C/O
Minimum switching current 5 mA at 24 V DC for logic relay
Maximum switching current 2 A at 250 V AC on inductive load cos phi = 0.4 L/R = 7 ms for logic relay
2 A at 30 V DC on inductive load cos phi = 0.4 L/R = 7 ms for logic relay
3 A at 250 V AC on resistive load cos phi = 1 L/R = 0 ms for logic relay
4 A at 30 V DC on resistive load cos phi = 1 L/R = 0 ms for logic relay
2 4 Aug 2025
Acceleration and deceleration Linear from 0...999.9 s
ramps S
U
Braking to standstill By DC injection, <30 s
Protection type Line supply overvoltage
Line supply undervoltage
Overcurrent between output phases and earth
Overheating protection
Short-circuit between motor phases
Against input phase loss in three-phase
Thermal motor protection via the drive by continuous calculation of I²t
Frequency resolution Analog input: converter A/D, 10 bits
Display unit: 0.1 Hz
Time constant 20 ms +/- 1 ms for reference change
Operating position Vertical +/- 10 degree
Height 390 mm
Width 180 mm
Depth 212 mm
Net weight 8.5 kg
Supply frequency 50/60 Hz +/- 5 %
Product destination Asynchronous motors
Environment
Electromagnetic compatibility Electrical fast transient/burst immunity test - test level: level 4 conforming to IEC
61000-4-4
Electrostatic discharge immunity test - test level: level 3 conforming to IEC 61000-4-2
Immunity to conducted disturbances - test level: level 3 conforming to IEC 61000-4-6
Radiated radio-frequency electromagnetic field immunity test - test level: level 3
conforming to IEC 61000-4-3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Surge immunity test - test level: level 3 conforming to IEC 61000-4-5
Standards IEC 61800-5-1
IEC 61800-3
Product certifications CE
EAC
KC
IP degree of protection IP20 without blanking plate on upper part
IP4X top
Pollution degree 2 conforming to IEC 61800-5-1
Environmental characteristic Dust pollution resistance class 3S2 conforming to IEC 60721-3-3
Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3
Shock resistance 15 gn conforming to IEC 60068-2-27 for 11 ms
Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
Ambient air temperature for -25…70 °C
storage
Ambient air temperature for -10…55 °C without derating
operation 55…60 °C protective cover from the top of the drive removed with current derating
2.2 % per °C
Operating altitude <= 1000 m without derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
4 Aug 2025 3
Package 1 Height 30.000 cm
Package 1 Width 40.000 cm
Package 1 Length 60.000 cm
Package 1 Weight 10.701 kg
Unit Type of Package 2 P12
Number of Units in Package 2 12
Package 2 Height 105.000 cm
Package 2 Width 80.000 cm
Package 2 Length 120.000 cm
Package 2 Weight 68.900 kg
4 4 Aug 2025
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Total lifecycle Carbon footprint 22656
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
EU RoHS Directive Compliant with Exemptions
SCIP Number Ebb2456c-fa41-4df8-99a8-0bf7aa14627f
REACh Regulation REACh Declaration
Energy efficiency
Product contributes to saved and avoided emissions Yes
Use Again
Repack and remanufacture
End of life manual availability End of Life Information
Take-back No
The product must be disposed on European Union
WEEE Label markets following specific waste collection and never end
up in rubbish bins
4 Aug 2025 5
Product datasheet ATV310HD22N4E
Dimensions Drawings
Dimensions
Side and Front Sides
6 4 Aug 2025
Product datasheet ATV310HD22N4E
Mounting and Clearance
Mounting Recommendations
Clearance
Mounting Types
Mounting Type A
Mounting Type B
Remove the protective cover from the top of the drive.
4 Aug 2025 7
Product datasheet ATV310HD22N4E
Connections and Schema
Three-Phase Power Supply Wiring Diagram
A1 : Drive
KM1 : Contactor (only if a control circuit is needed)
P1 : 2.2 kΩ reference potentiometer. This can be replaced by a 10 kΩ potentiometer (maximum).
Q1 : Circuit breaker
R : Braking resistor (optional)
(1) Negative logic (Sink)
(2) Positive logic (Source) (factory set configuration)
(3) 0...10 V or 0...20 mA
(4) Line choke three-phase (optional)
8 4 Aug 2025
Product datasheet ATV310HD22N4E
Technical Illustration
Dimensions
4 Aug 2025 9