The document provides a wiring diagram for a hydromodule switchbox, detailing connections for various components such as the power supply unit, user interface, and alarm outputs. It includes specifications for fuses, relays, and thermistors, along with notes on proper operation and wiring practices. Additionally, it outlines the function of each component and provides guidance on remote operation features.

Uploaded by

abdulhaseeb6204
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
97 views1 page

Wiring Diagram Daikin EWAQ ACW1P Bueno Tech Eng

The document provides a wiring diagram for a hydromodule switchbox, detailing connections for various components such as the power supply unit, user interface, and alarm outputs. It includes specifications for fuses, relays, and thermistors, along with notes on proper operation and wiring practices. Additionally, it outlines the function of each component and provides guidance on remote operation features.

Uploaded by

abdulhaseeb6204
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

EWAQ009-013ACW1

EWYQ009-013ACW1

EWAQ009-013ACW1
EWYQ009-013ACW1 Only for OP10
(Option heatertape)

Power supply unit


400V 3N-50Hz

User interface

From compressor
module switchbox

Outdoor unit
To compressor module
switchbox
A11P : Main PCB
A12P : User interf
A4P (EKRP1HB) : Remote ala
E6H : Expansion
E7H : water pipin
E8H : Heatertape
FU1 : Fuse 3,15A
FU2 : Fuse 5A T 2
FuS, FuR : Fuse 5A 25
K4M : pump relay
K7M : Heater rela
M1P : Pump
PHC1 : Optocoupl
Q1DI : Earth leaka
R11T : Outlet wat
R13T : Refrigerant
R14T : Inlet water
S1L : Flowswitch
S12M : Main switc
S2S : benefit kW
S3S : remote he
Alarm output

S4S : remote co
Cooling/heating
on/off output

S5S : remote ON
S2T : thermostat
SS1; SS2 : DIP switch
Only forEKRP1HB
Option TR1 : Transforme
V1S, V2S : Spark supp
heating S3S

cooling S4S

X2M : Terminal st
On/Off S5S

See note 6 X1-2Y : Connector

Notes:
1 This wiring diagram only applies to the hydromodule switchbox
2 :Field wiring No/Nc:Normal open/Normal closed
3 :Terminal strip :Connector :Terminal :Protective earth
4 Do not operate the unit by short-circuiting any protection device.
5 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
6 When the remote ON/OFF, remote heating and remote cooling function is not used, apply wire bridge between terminals 1, 2 and 4.

A11P : Main PCB


A12P : User interface PCB
A4P (EKRP1HB) : Remote alarm PCB
E6H : Expansion vessel heater
E7H : water piping heater
E8H : Heatertape (Field supply Max. 200W)
FU1 : Fuse 3,15A T 250V for PCB
FU2 : Fuse 5A T 250V
FuS, FuR : Fuse 5A 250V Remote alarm PCB
K4M : pump relay
K7M : Heater relay
M1P : Pump
PHC1 : Optocoupler input circuit
Q1DI : Earth leakage protector
R11T : Outlet water heat-exchanger thermistor
R13T : Refrigerant liquid side thermistor
R14T : Inlet water thermistor
S1L : Flowswitch
S12M : Main switch
S2S : benefit kWh rate signal
S3S : remote heating signal
S4S : remote cooling signal
S5S : remote ON/OFF signal
S2T : thermostat expansion vessel heater
SS1; SS2 : DIP switch
TR1 : Transformer 24V for PCB
V1S, V2S : Spark suppression 1, 2
X2M : Terminal strips
X1-2Y : Connector