MiniLine
Data Sheet
MiniLine ML100.100
ML100.109
with DC 24-28V / 100W
• Mounted and connected • Adjustable output voltage
within seconds, no tools required up to DC 28V
• World-wide approvals (UL, EN, CSA, • 115/230V Auto Select Input
CB Scheme) for industry and office/
• PULS Overload Design
home
(high output overload capability)
• Tiny: WxHxD = 73 x 75 x 103mm
• Selectable single/parallel operation
• Hazardous Location Class I Div. 2 (jumper)
PULS GmbH, Elektrastr.6, 81925 Munich
Tel. +49 (0)89 9278-0,
[email protected],
http://www.pulspower.com
ML100e100/240202
Technical Data ML100.100/109
X Input X Output
Input voltage AC 100-120/220-240V (Auto Select), 50...60 Hz Output voltage DC 24-28V (adj. by front panel potentiometer)
(AC 85...132V / AC 184...264V, • preset 24.5V ± 0.5% @ 4.2A
DC 220...375V N= + and L= - ) Voltage regulation stat. <1% Vout (Jumper in pos. 'Single Use')
Input current <2.1A (@ AC 100Vin, 100W Pout) stat. <3% Vout (Jumper in pos. 'Parallel Use'),
<1A (@ AC 220Vin, 100W Pout) dyn. ±1.5% Vout over all
External fusing not required, unit provides internal fuse Ripple/Noise <50mVPP (20 MHz bandw., 50 Ω measurem.)
(T3A15H, not accessible)
Overvoltage prot. (OVP) <36V
Transient immunity Transient resistance acc. to VDE 0160 / W2
Output noise EMI values below EN 61000-6-3, even when using
(750V/ 1.3 ms), over entire load range
suppression long (>2m), unscreened output cables
Hold-up time >40 ms @ AC 230V, 24.5V / 4.2A
Rated continuous up to 4.2A @ 24.5V / 3.6A @ 28V (convection cool-
(see diagram below) >20 ms @ AC 196V, 24.5V / 4.2A
loading ing), depending on built-in orientation,
>20 ms @ AC 100V, 24.5V / 4.2A
Vin and Tamb
For details see derating diagram below
X Efficiency, Reliability
Efficiency typ. 90% (AC 230V, 24.5V / 4.2A) Overload behaviour PULS Overload Design: No switch-off at
(see also diagram below) overload/short-circuit, instead: up to 1.9 ⋅ Irated.
Losses typ. 11.4W (AC 230V, 24.5V / 4.2A) So you need no oversizing to start awkward
loads.
MTBF (Reliability) appr. 500.000 h acc. to Siemensnorm SN 29500
(24.5V / 4.2A, AC 230V, Tamb = +40 °C) Protection Unit is protected against (also permanent) short-
circuit, overload and open-circuit.
Prior to shipment, every unit undergoes the following tests in order to
isolate any defective units which might suffer an early failure: Derating depending on built-in orientation;
• Run-in / burn-in (Full load, Tamb = +60°C, on/off cycle) see diagram below
• Functional test (100 %) Parallel operation yes (selectable by front panel jumper)
Power back immunity 35V
X Construction, Mechanics, Installation
Operating indicator Green LED
Robust plastic housing (US Patent No. D442, 923S), fine ventilation grid
on three housing sides to keep out small parts (e.g. screws), IP20 X Environmental Data, EMC, Safety
Dimensions and weight Ambient temperature range (measured 25 mm below unit)
• WxHxD 73 mm x 75 mm x 103 mm (+ DIN rail)
• storage/transport -25°C ... +85°C
Depth incl. terminals: 98 mm (+ DIN rail)
• operation -10°C ... +70°C (for derating see diagram below)
• Weight 360 g
-10°C ... +60°C (for hazardous location areas)
Mounting orientation , or (cf. ’Output’)
Humidity max. 95% (without condensation)
Ventilation/Cooling Normal convection, no fan required
• Free space f. cooling recom'd.: 25 mm on sides with ventilation grid Safety: SELV (IEC/UL 60950-1 ), PELV (EN 50178)
Easy snap-on mounting onto the DIN-rail (TS35/7,5 or TS35/15). Prot. class/degree: Class I (IEC/UL 60950-1) / IP20 (EN 60529)
Unit sits safely and firmly on the rail; no tools required even to remove
The PSUs comply with all major safety approvals
Connection by Spring Clamp terminals; uniformly firm hold, UL 508 LISTED: E198865,
vibration-resistant and maintenance-free: IEC 61010-2-201 CB Scheme,
2 terminals per output IEC 60950-1 CB Scheme,
Connector size range UL 60950-1: E137006 US and Canada,
• flexible cable 0.3-2.5mm2 (28-12 AWG) CSA Class I Div 2: 5318-01 (Canada), 5318-81 (USA),
Marine DNV: TAA00002JT (ML100.100 only)
• solid cable 0.3-4mm2 (28-12 AWG)
Ferrules admissible
CE: EU Declaration of Conformity (EU DoC): 2014/35/EU (LVD), 2014/30/
• Wire strip length 6mm recommended
EU (EMC), 2011/65/EU (RoHS),
Design details – for your advantage: WEEE Directive (2012/19/EU), WEEE-Reg.-Nr. DE 55837529
• All terminals are easy to reach as mounted on the front panel.
• Input and output are strictly apart from each other (input below, out-
put above) and so cannot be mixed up.
• Mounting and connection do not require any screwdriver
→ Easy, quick, durable and reliable installation.
X Diagrams
Output characteristic Vout/Iout Efficiency Derating Hold-up time with ACin
(min.) (@ Vout = 24.5V, typ.) of output power (at Vout = 24.5V, typ. + min.)
35 91 120 160
Pout=100W, typ.
30 90 A 140 Pout=100W, min.
100
Pout=50W, typ.
89
Output voltage Vout [V]
25 120 Pout=50W, min.
Hold-up time [ms]
80
Output power [W]
a
Efficiency [%]
88 100
20
87 60 b 80
15
86 Mounting 60
115 V ACin 40
10 Vin = AC 115/230V 85
230 V ACin 85-132 V ACin A-a A-b A-b 40
'Single Use'
Vin = AC 115/230V 20 185-264 V ACin A-a A-b A-b 20
5 84
'Parallel Use' 220-375 V DCin A-a A-b A-b
83 0
0 0
0 1 2 3 4 5 6 7 8 1 1,4 1,8 2,2 2,6 3 3,4 3,8 4,2 -10 0 10 20 30 40 50 60 70 80 120 160 200 240 280
Output current Iout [A] Output current Iout [A] Ambient temperature [°C] Input voltage VACin [V]
Product information (ML100e100), Rev.: 02. Feb. 2024 Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time.
They are subject to change without prior notice.
PULS GmbH, Elektrastr. 6, D-81925 München X Tel: +49 (0)89 9278-0, E-Mail: [email protected] X www.pulspower.com