Product datasheet
Specifications
variable speed drive, Altivar
Machine ATV340, 1.5kW, heavy
duty, 400V, 3 phases
ATV340U15N4
Main
Range of product Altivar Machine ATV340
Product or component type Variable speed drive
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product specific application Machine
Mounting mode Cabinet mount
Variant Standard version
Communication port protocol Modbus serial
Option card Communication module, Profibus DP V1
Communication module, PROFINET
Communication module, DeviceNet
Communication module, CANopen
Communication module, EtherCAT
Network number of phases 3 phases
Supply frequency 50...60 Hz +/- 5 %
[Us] rated supply voltage 380...480 V - 15...10 %
nominal output current 4.0 A
Motor power kW 2.2 kW for normal duty
1.5 kW for heavy duty
Motor power hp 3 hp for normal duty
2 hp for heavy duty
EMC filter Class C3 EMC filter integrated
IP degree of protection IP20
Complementary
Discrete input number 5
Discrete input type PTI programmable as pulse input: 0…30 kHz, 24 V DC (30 V)
DI1...DI5 safe torque off, 24 V DC (30 V), impedance: 3.5 kOhm
programmable
number of preset speeds 16 preset speeds
Discrete output number 2.0
Discrete output type Programmable output DQ1, DQ2 30 V DC 100 mA
Analogue input number 2
Analogue input type AI1 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12
bits
AI1 software-configurable temperature probe or water level sensor
AI1 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12
bits
AI2 software-configurable voltage: - 10...10 V DC, impedance: 31.5 kOhm, resolution
12 bits
3 Sept 2025 1
Analogue output number 1
Analogue output type Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10
bits
Software-configurable current AQ1: 0...20 mA impedance 500 Ohm, resolution 10
bits
Relay output number 2
Output voltage <= power supply voltage
Relay output type Relay outputs R1A
Relay outputs R1C electrical durability 100000 cycles
Relay outputs R2A
Relay outputs R2C electrical durability 100000 cycles
Maximum switching current Relay output R1C on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1C on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R2C on resistive load, cos phi = 1: 5 A at 250 V AC
Relay output R2C on resistive load, cos phi = 1: 5 A at 30 V DC
Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Minimum switching current Relay output R1B: 5 mA at 24 V DC
Relay output R2C: 5 mA at 24 V DC
Physical interface 2-wire RS 485
Connector type 1 RJ45
Method of access Slave Modbus RTU
Transmission rate 4.8 kbit/s
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
Transmission frame RTU
Number of addresses 1…247
Data format 8 bits, configurable odd, even or no parity
Type of polarization No impedance
4 quadrant operation possible True
Asynchronous motor control Optimized torque mode
profile Constant torque standard
Variable torque standard
Synchronous motor control profile Reluctance motor
Permanent magnet motor
Pollution degree 2 conforming to IEC 61800-5-1
Maximum output frequency 0.599 kHz
Acceleration and deceleration Linear adjustable separately from 0.01...9999 s
ramps S, U or customized
Motor slip compensation Can be suppressed
Adjustable
Not available in permanent magnet motor law
Automatic whatever the load
Switching frequency 2...16 kHz adjustable
8...16 kHz with derating factor
Nominal switching frequency 4 kHz
Braking to standstill By DC injection
Brake chopper integrated True
2 3 Sept 2025
Line current 5.1 A at 380 V (normal duty)
4.1 A at 480 V (normal duty)
6.0 A at 380 V (heavy duty)
4.9 A at 480 V (heavy duty)
Line current 6 A at 380 V without line choke (heavy duty)
4.9 A at 480 V without line choke (heavy duty)
5.1 A at 380 V with external line choke (normal duty)
4.1 A at 480 V with external line choke (normal duty)
3.5 A at 380 V with external line choke (heavy duty)
2.8 A at 480 V with external line choke (heavy duty)
Maximum input current 6.0 A
Maximum output voltage 480 V
Apparent power 3.8 kVA at 480 V (normal duty)
4.1 kVA at 480 V (heavy duty)
Maximum transient current 6.2 A during 60 s (normal duty)
6 A during 60 s (heavy duty)
7.6 A during 2 s (normal duty)
7.2 A during 2 s (heavy duty)
Electrical connection Screw terminal, clamping capacity: 1.5...4 mm² for line side
Screw terminal, clamping capacity: 4...6 mm² for DC bus
Screw terminal, clamping capacity: 1.5...4 mm² for motor
Screw terminal, clamping capacity: 0.2...2.5 mm² for control
Prospective line Isc 5 kA
Base load current at high 4.0 A
overload
Base load current at low overload 5.6 A
Power dissipation in W Natural convection: 46 W at 380 V, switching frequency 4 kHz (heavy duty)
Forced convection: 46 W at 380 V, switching frequency 4 kHz (heavy duty)
Natural convection: 59 W at 380 V, switching frequency 4 kHz (normal duty)
Forced convection: 59 W at 380 V, switching frequency 4 kHz (normal duty)
Electrical connection Line side: screw terminal 1.5...4 mm²/AWG 14...AWG 12
DC bus: screw terminal 4...6 mm²/AWG 12...AWG 10
Motor: screw terminal 1.5...4 mm²/AWG 14...AWG 12
Control: screw terminal 0.2...2.5 mm²/AWG 24...AWG 12
With safety function Safely True
Limited Speed (SLS)
With safety function Safe brake True
management (SBC/SBT)
With safety function Safe False
Operating Stop (SOS)
With safety function Safe Position False
(SP)
With safety function Safe False
programmable logic
With safety function Safe Speed False
Monitor (SSM)
With safety function Safe Stop 1 True
(SS1)
With sft fct Safe Stop 2 (SS2) False
With safety function Safe torque True
off (STO)
With safety function Safely False
Limited Position (SLP)
With safety function Safe False
Direction (SDI)
3 Sept 2025 3
Protection type Thermal protection: motor
Safe torque off: motor
Motor phase loss: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent: drive
Output overcurrent between motor phase and earth: drive
Output overcurrent between motor phases: drive
Short-circuit between motor phase and earth: drive
Short-circuit between motor phases: drive
Motor phase loss: drive
DC Bus overvoltage: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Input supply loss: drive
Exceeding limit speed: drive
Break on the control circuit: drive
Width 85.0 mm
Height 270.0 mm
Depth 232.5 mm
Net weight 1.7 kg
Continuous output current 5.6 A at 4 kHz for normal duty
4 A at 4 kHz for heavy duty
Environment
Operating altitude <= 3000 m with current derating above 1000m
Operating position Vertical +/- 10 degree
Product certifications UL
CSA
TÜV
EAC
CTick
Marking CE
Standards IEC 61800-3
IEC 61800-5-1
IEC 60721-3
IEC 61508
IEC 13849-1
UL 618000-5-1
UL 508C
Assembly style With heat sink
Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to
IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Environmental class (during Class 3C3 according to IEC 60721-3-3
operation) Class 3S3 according to IEC 60721-3-3
Maximum acceleration under 70 m/s² at 22 ms
shock impact (during operation)
Maximum acceleration under 5 m/s² at 9...200 Hz
vibrational stress (during
operation)
Maximum deflection under 1.5 mm at 2...9 Hz
vibratory load (during operation)
Permitted relative humidity Class 3K5 according to EN 60721-3
(during operation)
Volume of cooling air 18.0 m3/h
Type of cooling Forced convection
Overvoltage category Class III
4 3 Sept 2025
Regulation loop Adjustable PID regulator
Noise level 55.4 dB
Pollution degree 2
Ambient air transport -40…70 °C
temperature
Ambient air temperature for -15…50 °C without derating (vertical position)
operation 50…60 °C with derating factor (vertical position)
Ambient air temperature for -40…70 °C
storage
Isolation Between power and control terminals
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 11.000 cm
Package 1 Width 37.000 cm
Package 1 Length 32.000 cm
Package 1 Weight 2.476 kg
Unit Type of Package 2 P06
Number of Units in Package 2 14
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 47.160 kg
3 Sept 2025 5
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Total lifecycle Carbon footprint 1738
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Pro-active compliance (Product out of EU RoHS legal
EU RoHS Directive
scope)
SCIP Number 81d6792e-d307-4115-9475-2db3f34c93af
REACh Regulation REACh Declaration
Energy efficiency
Product contributes to saved and avoided emissions Yes
Use Again
Repack and remanufacture
End of life manual availability End of Life Information
Take-back No
The product must be disposed on European Union
WEEE Label markets following specific waste collection and never end
up in rubbish bins
6 3 Sept 2025
Product datasheet ATV340U15N4
Dimensions Drawings
Dimensions
Views: Front - Left - Rear
3 Sept 2025 7
Product datasheet ATV340U15N4
Mounting and Clearance
Clearance
X1 X2 X3
mm in. mm in. mm in.
≥ 100 ≥ 3.94 ≥ 100 ≥ 3.94 ≥ 60 ≥ 2.36
8 3 Sept 2025
Product datasheet ATV340U15N4
Mounting Types
Mounting Type A: Side by Side IP20
Possible, at ambient temperature ≤ 50 °C (122 °F)
Mounting Type B: Individual IP20
a ≥ 50 mm (1.97 in.) from 50...60°C, no restriction below 50°C
3 Sept 2025 9
Product datasheet ATV340U15N4
Connections and Schema
Connections and Schema
Three-phase Power Supply - Diagram With Line Contactor
(1) : Use relay output R1 set to operating state Fault to switch Off the product once an error is detected.
NOTE :
• Press S1 until the initialization of the drive is finished.
• An external 24V power supply can be connected so that the control part of the drive is always power supplied.
Three-phase Power Supply - Diagram With Downstream Contactor
10 3 Sept 2025
Product datasheet ATV340U15N4
(1) : Use relay output R1 set to operating state Fault to switch Off the product once an error is detected.
(2) : Command of KM2 can be done by using the [Output contactor cmd] OCC function. For more information, refer
to the programming manual.
NOTE :
• Close upstream contactor, then press S1 after the initialization of the drive is finished.
• An external 24V power supply can be connected so that the control part of the drive is always power supplied.
Sensor Connection
3 Sept 2025 11
Product datasheet ATV340U15N4
Control Block Wiring Diagram
(1) : 24V In, Out, maximum supply current 200 mA is provided,
(2) : STO - Safe Torque Off, see ATV340 Embedded safety function manual NVE64143
(3) : PTI - Pulse Train In, from external source (eg.PLC) Pulse - Direction or A-B signals can be connected
(4) : PTO - Pulse Train Out, can be used to connect to a 2nd ATV340 PTI
(5) : To connect a motor position feedback encoder
(6) : Digital output, e.g. to connect a contactor, also usable as DI
(7) : Digital inputs
(8) : Analog output, e.g. to connect a meter
(9) : Analog input, e.g. from potentiometer
(10) : Differential analog input, e.g. as speed reference from external PLC differential, +/– 10 V
(11) : 2 advanced Ethernet ports ETH1, ETH2 (ATV340•••••E) or 2 Sercos III ports S3P1, S3P2 (ATV340•••••S)
12 3 Sept 2025
Product datasheet ATV340U15N4
Digital Inputs Wiring
Digital Inputs: Internal Supply
Using DISUP Signal
In SRC position DISUP outputs 24 V. In SK position DISUP is connected to 0 V.
Digital Inputs: External Supply
Positive Logic, Source, European Style
Negative Logic, Sink, Asian Style
Digital Inputs: Internal supply
Negative Logic, Sink, Asian Style
3 Sept 2025 13
Product datasheet ATV340U15N4
14 3 Sept 2025
Product datasheet ATV340U15N4
Digital Outputs Wiring
Digital Outputs: Internal Supply
Positive Logic, Source, European Style, DQCOM to +24V
(1) Relay or valve
Negative Logic, Sink, Asian Style, DQCOM to 0V
(1) Relay or valve
Digital Outputs: External Supply
Positive Logic, Source, European Style, DQCOM to +24V
(1) Relay or valve
Negative Logic, Sink, Asian Style, DQCOM to 0V
3 Sept 2025 15
Product datasheet ATV340U15N4
(1) Relay or valve
16 3 Sept 2025
Product datasheet ATV340U15N4
Performance Curves
Derating Curves
40 °C (104 °F) - Mounting type A and B
50 °C (122 °F) - Mounting type A and B
In : Nominal Drive Current
SF : Switching Frequency
3 Sept 2025 17
Product datasheet ATV340U15N4
Technical Illustration
Dimensions