SEVO Systems Technical Data Sheets - Cylinders

The Cylinder Valve Assembly (CV Series) is designed for storing and discharging FK-5-1-12 for fire suppression in Class A, B, and C hazards. It operates at pressures of 360 PSI or 500 PSI and complies with ISO and NFPA 2001 standards, featuring various optional components and safety devices. The assemblies are available in multiple cylinder capacities and require installation according to SEVO Systems manuals and applicable standards.

Uploaded by

scramirez1983
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views1 page

SEVO Systems Technical Data Sheets - Cylinders

The Cylinder Valve Assembly (CV Series) is designed for storing and discharging FK-5-1-12 for fire suppression in Class A, B, and C hazards. It operates at pressures of 360 PSI or 500 PSI and complies with ISO and NFPA 2001 standards, featuring various optional components and safety devices. The assemblies are available in multiple cylinder capacities and require installation according to SEVO Systems manuals and applicable standards.

Uploaded by

scramirez1983
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Technical Data Sheet

Cylinder Valve Assembly


CV Series

General
The Cylinder Valve Assembly (CV SERIES) is used to store FK-5-1-12. The purpose of CV series is used to discharge
pressurized chemical fire suppression material to protect Class A, B & C fire hazards.

Application
The CV Series is a pressure differential valve capable of rapid discharge times in accordance with ISO and NFPA 2001
standards. The Cylinder Valve Assemblies are designed to hold clean agent that is super pressurized with nitrogen at
a normal operating pressure of 360 PSI (24.8 Bar) or 500 PSI (34.5Bar) at 70 ͦF (21.1 ͦC).

Features
Pressure Gauge
Release Valve
Component materials: Steel, Brass, Synthetic Rubber
Operating Temp Range: 0 ͦ -130 Fͦ (-17.8 ͦ – 54.4 C
ͦ )
Available Cylinder Capacities: 40 lb. 76 lb. 164 lb. 322 lb. 601lb. & 910 lb.
Safety Device Burst Pressure: 864 - 950 PSI (59.5 – 65.5 Bar)

Optional Components
Liquid Level Indicator, Pneumatic Actuator, Manual Actuator, Operational Pressure Switch, Low Pressure Switch

Standards/Listings/Approvals
DOT 4BW500, DOT 4BA500 Welded type
UL Listed
ULC Listed
FM Approved
Other approvals may be available upon request

Installation
When properly installed the Cylinder Valve Assemblies are connected to a pipe network to deliver clean agent fire
suppression material to a Class A, B, or C designated hazard area. Installation and maintenance are in accordance
with SEVO Systems manuals, as well as applicable ISO and NFPA standards.

Cylinder Allowable Part Number A B C


Sizes Fill
40 Lb. 16-40 Lb. CV140069 10 1/16” 17 1/4” 21 3/8”
15 L (7-18 Kg.) (255.59mm) (438.15mm) (543mm)
76 Lb. 31-76 Lb. CV140079 10 1/16” 28 1/2” 32 3/4”
29 L (14 -34.5 (255.59mm) (723.90mm) (831.90mm)
Kg.)
164 Lb. 66-164 Lb. CV14817 21 7/8” 37 1/2” 42 1/4”
62 L (30-74.5 (327mm) (842mm) (1073.20mm)
Kg.)
322 Lb. 129-322 Lb. CV140057 20” 33 1/2” 39 3/4”
122 L (5805-146 (508mm) (850mm) (1009mm)
Kg.)
601 Lb. 241-601 Lb. CV14813 20 54 1/4” 61”
277 L (109-272.5 (508mm) (1378mm) (1457.33mm)
Kg.)
910 Lb. 390-910 Lb. CV140107 24 1/2” 60 7/8” 67 3/4”
368 L (177-413 (622.30mm) (1546.20mm) (1720.90mm)
Kg.)