Synchronization equipment Page 1 of 4

SYNCHROMAX 110...600V

SYNCHROMAX 110...600V, Sincro equipment

Code: M14625.
> PID control: No
> Measurement Range (V): 110…600
> Frequency (Hz): 35…80

Description

All parameters can be programmed on the keyboard on the front panel.


Digital unit with 4-digit display and 30 auxiliary LEDs.
Voltage, generator frequency and network measurement and display (TRMS), including the unbalance
between the generator and the network.
Automatic synchronisation by simply programming the contactor closing time.
Wide range of frequencies (35...80 Hz)
Standard power supply: 110, 230 and 400 V ac
2 operating modes: Manual, automatic and assisted
Digital adjustment (without potentiometers)
PI / PID CONTROL (depending on the type) of the speed of the generator with built-in pulse output
Protection with password.

CIRCUTOR has two types of synchronism relays: SYNCHRO MAX and SYNCHRO MAX PID.

Synchro Max

Synchro Max is capable of adapting the generator's frequency with an integrated PI regulation algorithm, in
order to connect it in parallel to the electrical network. In addition, it can be used to measure and display the
voltage, phase and frequency parameters of the generator and network, as well as its differences.

Synchro Max PID

Synchro Max PID offers excellent standard Synchro Max measurement, display and programming features,
with a powerful PID algorithm to control the generator's frequency. This type of control turns Synchro Max
PID into a quick synchronisation device and, therefore, it offers the ideal solution to reduce synchronisation
costs, since it minimises the time invested in such procedures. This type of control is perfect for small-scale
hydraulic power plants, among many other applications. Here is an example of how SYNCHRO MAX moves
forward to a time tbrk (previously programmed by the user) to take into account the connection delay of the
generator's contactor.

Application

The SynchroMax is a synchronization relay which synchronizes the generator with either the network or with
another generator, taken as a reference. This allows both services to be connected, in parallel, in emergency
or support applications when it is necessary to provide more power.

Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 1 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.
Synchronization equipment Page 2 of 4

SYNCHROMAX 110...600V

Synchronization and marine applications equipment

Code: M14625.

Specifications

AC power supply

Consumption 3 ... 10 VA

Frequency 35 … 450 Hz

Nominal voltage 400 Vca (-10 … + 15 %)

DC power supply

Consumption 1 ... 1.5 W

Mechanical characteristics

Size (mm) width x height x depth 96 x 96 x 62.9 (mm)

Envelope Self-extinguishing ABS

Weight (kg) 0,507

Environmental characteristics

Protection class IP 54 (Front), optional IP 65

Storage temperature -40 … +70 °C

Working temperature -10 … +65 ºC

Current measurement circuit

Consumption < 500 µA

Voltage measurement circuit

Sampling frequency 35 … 80 Hz

Frequency measuring range 35 … 80 Hz

Nominal voltage 400 (Ph-N), 565 (Ph-Ph)

Maximum permanent measurement voltage 800 Vac

Standards

Electrical safety, Maximum height (m) 2000

Standards IEC 61010, IEC 348, IEC 664, IEC 801, UNE-EN 50081-2, UNE-EN 50082-2

User interface

Display format Red, high efficiency

LED 30 LED auxiliaries

Resolution of the display 4 digits

Presentation cycle 2/s

Measurement accuracy

Phase angle φ ± 0,5 °

Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 2 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.
Synchronization equipment Page 3 of 4

SYNCHROMAX 110...600V

Synchronization and marine applications equipment

Code: M14625.

Frequency measurement ± 0,01 Hz

Phase voltage measurement Cl 1 ±2 digit

SYNCHROMAX
Synchronization equipment

CODE TYPE Frequency (Hz)

Power Supply 400 V

M14624. SYNCHROMAX 30....150V 35…80

M14625. SYNCHROMAX 110...600V 35…80

M14634. SYNCHROMAX-PID 30...150V 35…80

M14635. SYNCHROMAX-PID 110...600V 35…80

Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 3 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.
Synchronization equipment Page 4 of 4

SYNCHROMAX 110...600V

Synchronization and marine applications equipment

Code: M14625.

Connections

Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 4 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.

You might also like