Synchronization equipment Page 1 of 4
SYNCHROMAX 110...600V
SYNCHROMAX 110...600V, Sincro equipment
Code: M14625.
> PID control: No
> Measurement Range (V): 110…600
> Frequency (Hz): 35…80
Description
All parameters can be programmed on the keyboard on the front panel.
Digital unit with 4-digit display and 30 auxiliary LEDs.
Voltage, generator frequency and network measurement and display (TRMS), including the unbalance
between the generator and the network.
Automatic synchronisation by simply programming the contactor closing time.
Wide range of frequencies (35...80 Hz)
Standard power supply: 110, 230 and 400 V ac
2 operating modes: Manual, automatic and assisted
Digital adjustment (without potentiometers)
PI / PID CONTROL (depending on the type) of the speed of the generator with built-in pulse output
Protection with password.
CIRCUTOR has two types of synchronism relays: SYNCHRO MAX and SYNCHRO MAX PID.
Synchro Max
Synchro Max is capable of adapting the generator's frequency with an integrated PI regulation algorithm, in
order to connect it in parallel to the electrical network. In addition, it can be used to measure and display the
voltage, phase and frequency parameters of the generator and network, as well as its differences.
Synchro Max PID
Synchro Max PID offers excellent standard Synchro Max measurement, display and programming features,
with a powerful PID algorithm to control the generator's frequency. This type of control turns Synchro Max
PID into a quick synchronisation device and, therefore, it offers the ideal solution to reduce synchronisation
costs, since it minimises the time invested in such procedures. This type of control is perfect for small-scale
hydraulic power plants, among many other applications. Here is an example of how SYNCHRO MAX moves
forward to a time tbrk (previously programmed by the user) to take into account the connection delay of the
generator's contactor.
Application
The SynchroMax is a synchronization relay which synchronizes the generator with either the network or with
another generator, taken as a reference. This allows both services to be connected, in parallel, in emergency
or support applications when it is necessary to provide more power.
Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 1 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.
Synchronization equipment Page 2 of 4
SYNCHROMAX 110...600V
Synchronization and marine applications equipment
Code: M14625.
Specifications
AC power supply
Consumption 3 ... 10 VA
Frequency 35 … 450 Hz
Nominal voltage 400 Vca (-10 … + 15 %)
DC power supply
Consumption 1 ... 1.5 W
Mechanical characteristics
Size (mm) width x height x depth 96 x 96 x 62.9 (mm)
Envelope Self-extinguishing ABS
Weight (kg) 0,507
Environmental characteristics
Protection class IP 54 (Front), optional IP 65
Storage temperature -40 … +70 °C
Working temperature -10 … +65 ºC
Current measurement circuit
Consumption < 500 µA
Voltage measurement circuit
Sampling frequency 35 … 80 Hz
Frequency measuring range 35 … 80 Hz
Nominal voltage 400 (Ph-N), 565 (Ph-Ph)
Maximum permanent measurement voltage 800 Vac
Standards
Electrical safety, Maximum height (m) 2000
Standards IEC 61010, IEC 348, IEC 664, IEC 801, UNE-EN 50081-2, UNE-EN 50082-2
User interface
Display format Red, high efficiency
LED 30 LED auxiliaries
Resolution of the display 4 digits
Presentation cycle 2/s
Measurement accuracy
Phase angle φ ± 0,5 °
Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 2 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.
Synchronization equipment Page 3 of 4
SYNCHROMAX 110...600V
Synchronization and marine applications equipment
Code: M14625.
Frequency measurement ± 0,01 Hz
Phase voltage measurement Cl 1 ±2 digit
SYNCHROMAX
Synchronization equipment
CODE TYPE Frequency (Hz)
Power Supply 400 V
M14624. SYNCHROMAX 30....150V 35…80
M14625. SYNCHROMAX 110...600V 35…80
M14634. SYNCHROMAX-PID 30...150V 35…80
M14635. SYNCHROMAX-PID 110...600V 35…80
Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 3 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.
Synchronization equipment Page 4 of 4
SYNCHROMAX 110...600V
Synchronization and marine applications equipment
Code: M14625.
Connections
Creation date: 09/09/2024 - CIRCUTOR, SAU reserves the right to make technical changes or modify the content/images of this document without prior notice, in Page 4 of 4
order to improve its reliability, functionality, design or for other reasons.
It accepts no liability for any errors, inaccuracies or possible lack of information in this document.