PROJECT : BOOMERANG CLUB AT JAYPEE GREENS, NOIDA SUMMARY OF COSTS - HVAC

VRV SYSTEM AND BASEMENT VENTILATION WORKS

AMOUNT
SUB-HEAD DESCRIPTION
(Rs)

I. EQUIPMENTS 19,378,175.00

II. VENTILATION SYSTEM -

III. AIR DISTRIBUTION -

IV. THERMAL INSULATION -

V. ELECTRICAL WORK -

TOTAL 19,378,175.00
BOOMERANG CLUB AT JAYPEE GREENS, NOIDA SUMMARY OF COSTS - HVAC VRV SYSTEM AND BASEMENT VENTILATION WORKS

PREAMBLE TO SCHEDULE OF QUANTITIES

A) GENERAL NOTES:

1 Items of work under this Contract shall be executed strictly to fulfill the requirements laid down in the technical specifications. Equipment type, material specifications, methods of installation
and testing and type of control shall be in accordance with the specifications, approved shop drawings and the relevant Indian Standards.
2 The unit rate for all equipments or materials shall include cost in INR including all applicable taxes and duties forwarding, freight, insurance and transport upto site, storage, installation,
testing, balancing, commissioning and other related works required.

3 The quoted rates shall also include the following:

i. Wastage on materials and labour.


ii. Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and fixing in position, protecting, disposal of debris and all other labour necessary in and for
the full and entire execution and for the job in accordance with the contract documents, good practice and recognize principles.

iii Liabilities, obligations and risks arising out of Conditions of Contract.


iv. All requirements of Specifications, whether such requirements are mentioned in the item or not. The Specifications and Drawings where available, are to be read as complimentary to and
part of the Schedule of Quantities and any work called for in one shall be taken as required for all.
v. In the event of conflict between Schedule of Quantities and other documents including the Specifications, the most stringent shall apply. The interpretation of the Owner/Consultant/Project
Manager shall be final and binding.

4 All equipments, quantities and technical data indicated in this Schedule are for the Contractor’s guidance only, these are based on the documents prepared by the Consultant. This
schedule must be read in conjunction with other documents. The Contractor shall be paid for the actual quantity of work executed by him in accordance with the approved Shop Drawings
at the contract rates.

5 This Schedule shall be fully priced and the extensions and totals duly checked. The rates for all items shall be filled in INK including NIL items.

6 No alteration whatsoever is to be made to the text or quantities of this Schedule unless such alteration is authorised in writing by Consultant. Any such alterations, notes or additions shall,
unless authorized in writing, be disregarded when tender documents are considered

7 In the event of an error occurring in the amount of the Schedule, as a result of wrong extension of the unit rate and quantity, the unit rate quoted by the tenderer shall be regarded as firm
and the extensions shall be amended on the basis of rates.
8 Any error in totaling in the amount column and in carrying forward total shall be corrected. Any error, in description or in quantity, omission of items from this Schedule shall not vitiate this
Contract but shall be corrected and deemed to be variation required by the Consultant/Project Manager.

9 The Contractor shall procure and bring Materials/Equipment to the site only on the basis of drawings approved for construction and shop drawings and not on the basis of Schedule of
Quantities which are provisional only. This also applies to the Contractor’s requisition for Owner supplied materials.
10 HVAC contractor shall clearly mention the scope of electrical work involved in their submittals.
11 Static pressure for indoor units/fan motors shall be checked & confirmed by the vendor at the time of quote & reconfirmed at award & prior to ordering the equipment without any price
implication.

B) ELECTRICAL FOR HVAC

All the starters of HVAC equipment shall have BMS compatibility.

In specific, Each starter shall have-

AUTO / MANUAL switch/status.

Accept start/stop command from BMS

PFC to BMS for Run status & trip status

PFC to BMS for Auto / Manual.

SCHEDULE OF QUANTITIES
S.No. Description Unit Qty. Rate
(INR)

I SUB-HEAD-I: EQUIPMENT
VRV/VRF System (Suitable for Heating & Cooling mode i.e Heat Pump)
1 Supply, Installation, testing and Commissioning of Modular Type Aircooled VRV/VRF system . The unit shall consist of Indoor
and outdoor condensing unit complete in all respect.Outdoor Units shall be equipped with highly efficiency scroll compressors
with 100% Inverter based technology, heat exchanger, HFC Refrigerant cooled inverter PCB module, centrifugal fan for
Condenser. Outdoor units having front suction & top discharge, with Y-branch as required, Outdoor unit shall support auto check
function for connection error, auto address setting and capacity as mentioned below.

VRV/VRF System shall be suitable for working on local ambient temperature, with Refrigerant R-410A suitable for 415V ± 10%;
50cycles,Unit price shall be inclusive of full charge of refrigerant gas& oil, MS/GI powder coated stand with vibration isolation
pads. All interconnecting piping, joints and U bends within the condensing unit shall be painted with two coats of clear transparent
polymer coating for protection against corrosion from ambient air pollution before installation.

Note: All indoor & outdoor units shall be quoted with Hydrophyilic coating for protection from corrosive element in the
surroundings.
1.1 Outdoor unit complete with scroll compressor, condenser & its controller as described below of following capacities.These
outdoor units are dedicated for the recirculated type indoor units.
OUTDOOR UNITS VRF TYPE:

AREA OUTDOOR UNIT RATING HP


1.1.1 Upper Basement Floor
i ODU-1 (Bowling Alley & Snack Bar) 20 HP No. 1 395,000.00
ii ODU-2 (Gaming Zone, Simulator, VR room & Kids 34 HP No. 1 695,000
Zone)
iii ODU-3 (Staff Dining,Conference, Preparation area 34 HP No. 1 695,000
& Food Storage)
1.1.2 Lower Ground Floor
i ODU-4 (Pre-Function, Banquet-01 & 02) 46 HP No. 1 905,000
ii ODU-5 (Reception & Tea Lounge) 30 HP No. 1 600,000
iii ODU-6 (Golf Reception, Office, Simulator, SPA, 30 HP No. 1 600,000
Therapy & Caddies)
1.1.3 Upper Ground Floor
i ODU-7 (Restaurant) 44 HP No. 1 808,000
ii ODU-8 (Library, Lounge & Bar) 30 HP No. 1 600,000
iii ODU-09 (Outlet-01) 14 HP No. 1 295,000
iv ODU-10 (Outlet-02) 8 HP No. 1 245,000
v ODU-11 (Outlet-03) 8 HP No. 1 245,000
1.1.4 First Floor
i ODU-12 (Foodcourt) 44 HP No. 1 808,000.00
ii ODU-13 (Reception, Juice Bar, Gym & Card room) 44 HP No. 1 808,000.00

iii ODU-14 (Piano Bar) 18 HP No. 1 390,000.00


iv ODU-15 (Outlet) 8 HP No. 1 245,000.00
1.1.5 Terrace Floor (Second Floor)
i ODU-17 (Café, Bar & Lounge) 58 HP No. 1 1,095,000
ii ODU-18 ( Meeting Rooms, Conference Rooms,Co- 22 HP No. 1 404,000
iii Working
ODU-19 space)
(Lift Lobby & Passage) 14 HP No. 1 295,000

1.2 Outdoor unit complete with scroll compressor, condenser & its controller as described below of following actual capacities.These
outdoor units are dedicated for the treated fresh air customized airhandling units.

OUTDOOR UNITS VRF TYPE:


AREA OUTDOOR UNIT RATING HP
1.2.1 Upper Basement Floor
TFA ODU 16 (Corridor & Annpurna Kitchen) 18 HP No. 1 390,000.00
1.2.2 Lower Ground Floor
TFA ODU 17 (Banquet Kitchen) 8 HP No. 1 245,000.00
1.2.3 Upper Ground Floor
i TFA ODU 18 (Corridor & Misc areas) 16 HP No. 1 298,000.00
ii TFA ODU 19 (Restaurant Kitchen) 10 HP No. 1 248,000.00
1.2.4 First Floor
i TFA ODU 20 (Corridor & Misc areas) 20 HP No. 1 395,000.00
ii TFA ODU 21 (Foodcourt Kitchen) 10 HP No. 1 248,000.00
1.2.5 Terrace Floor (Second Floor)
TFA ODU 26 (Restaurant Kitchen) 10 HP No. 1 248,000.00

1.3 VRF TYPE INDOOR UNITS : (To be supplied by same manufacturer of outdoor units) Recirculation type
Supply,Installation,testing and commissioning of Ceiling/wall mounted type VRF AC units complete with controls, prefilter, fan
section, DX Coil section & all accessories with fittings, wiring in FRLS conduits from nearest power point till FCU, rubber in shear
supporting arrangement and rubber gromets (for ceiling suspended unit) as per specification as required. Price shall also include
double sleeve fire retardant flexible connection at the outlet,wherever applicable.(Follow the specifications of the flexible
connection as given in the sub head Airdistribution.) Fan coil unit shall be of following refrigeration capacities :

AREA CFM TR
Club
1.3.1 Upper Basement Floor - Ductable Type
i Bowling Alley Seating 1624 4.5 Nos. 2 43,000.00
ii Reception & Snack Bar 1624 4.5 Nos. 2 43,000.00
iii Gaming Zone 2047 5.5 Nos. 4 103,000.00
iv HD Sport Simulator 883 2.5 No. 1 35,500.00
v VR Room 1377 4.0 No. 1 42,500.00
vi Kids Fun Zone 1130 3.2 No. 1 41,800.00
vii Staff Dining 2825 8.0 No. 1 106,000.00
viii Lockers Room 565 1.3 No. 1 32,700.00
ix Conference Room 1130 3.2 No. 1 41,800.00
x Veg Preparation Room 565 1.3 No. 1 32,700.00
xi Non Veg Preparation Room 565 1.3 No. 1 32,700.00
xii Food Storage-01 2047 5.5 No. 1 103,000.00
xiii Food Storage-02 1624 4.5 Nos. 2 43,000.00
1.3.2 Lower Ground Floor - Ductable Type
i Pre-function 2047 5.5 Nos. 2 103,000.00
ii Banquet-01 & 02 2047 5.5 Nos. 2 103,000.00
2825 8.0 Nos. 2 106,000.00
iii Reception & Tea Lounge 1624 4.5 Nos. 6 43,000.00
iv Golf Reception 2047 5.5 Nos. 2 103,000.00
v Pro Shop 1130 3.2 No. 1 41,800.00
vi Golf Office 635 1.6 No. 1 32,900.00
vii Manager Cabin 635 1.6 No. 1 32,900.00
viii Male Spa 1130 3.2 No. 1 41,800.00
ix Therapy 318 0.6 No. 1 31,500.00
x Female Spa 1130 3.2 No. 1 41,800.00
xi Therapy 318 0.6 No. 1 31,500.00
xii Golf Simulator 1377 4.0 No. 1 42,500.00
xiii Caddies 635 1.6 No. 1 32,900.00
1.3.3 Upper Ground Floor - Ductable Type
i Restaurant 2295 6.4 Nos. 6 103,000.00
ii Reception & Lounge & Bar 1624 4.5 Nos. 6 43,000.00
iii Outlet-01 2295 6.4 Nos. 2 103,000.00
iv Outlet-02 2825 8.0 No. 1 106,000.00
v Outlet-03 2295 6.4 No. 1 103,000.00
1.3.4 Upper Ground Floor - 2 way Cassette Type
Library 918 2.5 Nos. 2 35,500.00
1.3.5 First Floor - Ductable Type
i Food Court 2295 6.4 Nos. 6 103,000.00
ii Reception & Juice Bar 2047 5.5 Nos. 6 103,000.00
iii Gym 2825 8.0 No. 1 106,000.00
iv Cards Room 2295 6.4 No. 1 103,000.00
v Piano Bar 2047 5.5 Nos. 4 103,000.00
vi Outlet 2047 5.5 No. 1 103,000.00
1.3.6 Terrace Floor (Second Floor) - Ductable Type
i Meeting room-01 635 1.6 No. 1 32,900.00
ii Meeting room-02 565 1.3 No. 1 32,700.00
iii Co-working Space 2047 5.5 No. 1 103,000.00
iv Conference-01 2047 5.5 No. 1 103,000.00
v Conference-02 1130 3.2 No. 1 41,800.00
vi Conference Lounge 1624 4.5 No. 1 43,000.00
NOTE: All indoor units shall be suitable to operate with Cordless remote as well.

1.4 VRF TYPE INDOOR UNITS: (Tailor made Airhandling units suitable for Recirculation & 100% Fresh air and shall be
procured from other vendors duly approved by the manufacturer of the VRV units)
Double skin Airhandling unit with VRV Compatible DX cooling coil.
Supply, installation, testing and commissioning of double skin construction Celing suspended/Horizontal/Vertical floor mounted(as
per approved shop drawing and specifications) draw/blow through type DX air handling units fabricated out of extruded aluminium
section with 0.6 mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain galvanised steel sheet inside;
each complete with 600 deep mixing box (Wherever specified) low leakage aluminium aerofoil gear driven VCD & fire resistant
neoprene flexible connection at outlet, pre-filter section with filters of non woven synthetic media (efficiency 90% down to 10
microns MERV-8) and coil section having min 6/8 Row Deep DX type coil of copper tube & aluminium fins construction alongwith
distributor of suitable size. Coil shall have copper header and polished SS 304 drain pan made out of 20G sheet duly insulated
complete with squirrel cage induction VFD Compatible motor.

Belt driven DIDW centrifugal Backward curved fan (or Equivalent performance direct driven plug fan) with vibration isolators. Coil
size shall be selected for a maximum face velocity of 500 feet/minute and fan outlet velocity shall be limited to 1800 FPM.
Motor shall be atleast IE 2 rated suitable for 415±10% volts, 50 cycles, 3 phase AC supply, meeting criterion as per ASHRAE
standard 90.1-2010 & high efficiency. The AHU panels shall be insulated with minimum 23 mm thick (for recirculated AHU) &
46mm thick for (TFA AHU) & 40± 2 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be
mounted on Aluminium extruded section only.Total static pressure shall be checked by vendor. Change in static pressure will
not attract any price implication.Fan capacities shall be based on minimum 50mm static pressure for floor mounted AHUs and
minimum 40mm static pressure for ceiling mounted AHUs as mentioned below.The AHUs shall be complete in all respects
along with accessories as per specifications. The capacity of Air-handlers shall be as follows:

Floor Area Type Fan Dia Air qty SP Motor Coil TR Mixing

in mm CFM in mm kW Row Box

1.4.1 UB-01 Corridor+kitchen Horizontal 315 2050 50 1.1 8 13.5 Yes No. 1
FM (TFA)

1.4.2 LGF-02 Banquet Kitchen CSU (TFA) 180 1000 45 0.55 8 6.5 Yes No. 1

1.4.3 UGF-03 Corridor Horizontal 315 1950 50 1.1 8 13.0 Yes No. 1
FM (TFA)

1.4.4 UGF-04 Restaurant CSU (TFA) 200 1250 45 0.75 8 8.0 No No. 1
Kitchen

1.4.5 1F-05 Corridor Horizontal 315 2450 50 1.5 8 16.5 Yes No. 1
FM (TFA)

1.4.6 1F-06 Foodcourt Kitchen CSU (TFA) 200 1250 45 0.75 8 8.0 No No. 1

1.4.7 SF-07 Café Horizontal 400 4600 50 2.2 6 11.5 Yes 600mm deep No. 1
FM
1.4.8 SF-08 Bar Horizontal 500 7750 50 3.7 6 19.5 Yes 600mm deep No. 1
FM
1.4.9 SF-09 Lounge Horizontal 355 3400 50 2.2 6 8.5 Yes 600mm deep No. 1
FM
1.4.10 SF-10 Lift Lobby & Horizontal 355 3600 50 2.2 6 8.5 Yes 600mm deep No. 1
Passage FM
1.4.11 SF-11 Restaurant Horizontal 200 1250 45 0.75 8 6.5 Yes 450mm deep No. 1
Kitchen FM (TFA)

1.5 AHU, Controls, Expansion Kit, Communication PCB & Thermostat


Supply, installation, testing and commissioning of Electronic Type Expansion Kit, Communication PCB with Sensors, Corded Self
Diagnostic Type Digital Thermostat, Y-joints etc. as required.
1.5.1 For VRF DX AHU Of Capacity 2050 CFM, 13.5 TR Set 2 54,000.00
1.5.2 For VRF DX TFA AHU Of Capacity 1000 CFM, 6.5 TR Set 1 51,000.00
1.5.3 For VRF DX TFA AHU Of Capacity 1950 CFM, 13.0 TR Set 1 54,000.00
1.5.4 For VRF DX TFA AHU Of Capacity 1250 CFM, 8.0 TR Set 1 51,000.00
1.5.5 For VRF DX TFA AHU Of Capacity 2450 CFM, 16.5 TR Set 1 54,000.00
1.5.6 For VRF DX TFA AHU Of Capacity 1250 CFM, 8.0 TR Set 1 51,000.00

1.6 FITTINGS & CONTROLLERS


i SITC of Navigation Remote controllers (Corded) for operation of indoor units.(For ductable indoor units).Remote shall have Nos. 5 2,895.00
Backlight display as a integral feature.MODEL Daikin BRC1E62/Equivalent.(For recirculation type only,for TFA/recirculated Air
Handling units it is a part of VRV kit)
ii SITC of Navigation Remote controllers (Cordless) for operation of indoor units.(For ductable as well as High Wall indoor Nos. 22 7,500.00
units).Remote shall have Backlight display as a integral feature.
iii SITC of Centralized remote controller (Intelligent Touch Manager or Equivalent) suitable for operation, scheduling, change of set No. 1 170,000.00
points etc & monitoring of indoor units (Minimum 120nos.units).Controller shall be BMS compatible and come with required
interface.
iv SITC of fittings ;Refnet/Y joints( set of both liquid & gas line duly insulated from factory) to connect the various indoor units to Set 75 3,000.00
outdoor unit.

1.7 REFRIGERANT PIPING WORK (For VRV Units)


Supply, installation, testing and commission of interconnecting refrigerant pipe work with associated accessories/fittings as per
approved shop drawings suitable for R410A refrigerant with (19mm/13 mm thick) closed cell elastomeric nitrile rubber or XLPE
tubular insulation between each set of indoor & outdoor units as per specifications of following sizes as per manufacturer ,
properly supported with GI hangers/tray & clamps.All refrigerant piping insulation shall be covered with factory laminated glass
cloth or aluminium foil for XLPE and coated with epoxy paint(Starbond) to provide adequate mechaical protection. Refrigerant
piping running outdoor/on terrace shall run on galvanized ladder type trays covered from top with galvanized or powder coated
cover of minimum 18 gauge.

Pipe sizes shall be as follows:


i 41.3 mm O.D - 19 mm thick insulation RM 180
ii 34.9 mm O.D - 19 mm thick insulation RM 530
iii 28.6 mm O.D - 19 mm thick insulation RM 460
iv 25.4 mm O.D - 19 mm thick insulation RM 120
v 22.2 mm O.D - 19 mm thick insulation RM 440
vi 19.1 mm O.D - 19 mm thick insulation RM 1370
vii 15.9 mm O.D - 13 mm thick insulation RM 1175
viii 12.7 mm O.D - 13 mm thick insulation RM 375
ix 9.5 mm O.D - 13 mm thick insulation RM 2190
x 6.4 mm O.D - 13 mm thick insulation RM 175

1.8 CONTROL CABLING

i Providing & fixing control cum transmission wiring of 2 core x 1.5 sqmm tinned copper in suitable 20 mm dia heavy duty FRLS RM 3500
PVC conduits or wall chase between indoor units and outdoor units & indoor units and remote controllers.

2.0 AIRCOOLED SPLIT UNITS COMPRISING OF STANDARD INDOOR & OUTDOOR UNITS (DX type Hi- wall/Cassette split unit
with ecofriendly refrigerant)
Supply, installing, testing and commissioning of wall mounted/ceiling mounted air cooled split air condiontioning units as
described in specifications. The unit shall be complete with Indoor type fan coil unit and external condensing unit with,rotary/scroll
compressor, copper refrigerant piping with insulation and refrigerant. Quoted price shall include cost of electrical panel (as
required), cooling thermostat, wiring, cabling, control wiring and earthing. Unit shall be inverter type with cooling mode only
(having 5 star rating crtified by BEE).Condensing unit shall be duly charged with eco-friendly refrigerant (R 410A/R407C/R32)
and lubricant oil. Quoted price should be inclusive of receiving the units at site, unloading and shifting up to the designated place
on terrace,supporting arrangement made of suitable size and strength of MS base frame duly epoxy coated, VI Pad for
condensing unit and requisite cabling for the setup.The unit shall be complete in all respects and capacities shall be as follows :

i 2.0 TR Hi- wall type split air conditioning units


a UPS room (1W+1S) Nos. 2
b Server room (1W+1S) Nos. 2
ii 1.5 TR Hi- wall type split air conditioning units for following areas :
a Fire Control room/CCTV room No. 1

2A ANCILLARY WORKS LIKE FIELD REFRIGERANT PIPING & ELECTRICAL CABLING PERTAINING TO ABOVE SPLIT UNITS
(Item no. 2) ONLY.
Supply, Installing, Testing & Commissioning of copper piping & electrical cabling associated with above mentioned split units.Pair
of copper refrigerant piping (Hard/soft) between indoor & outdoor unit shall be complete with copper fittings & top up of refrigerant
gas for the above split units. Piping associated with split units to be insulated with 13mm thick closed cell elastomeric insulation
with Aluminium foil lamination in tubing form as required.Electrical works shall include adequate size of armoured copper
conductor cables(power & control) between indoor & outdoor units ,controller ,thermostat OR from the unit control panel to Indoor
unit & outdoor unit,double compression glands,end termination,G.I earthing, complete as required per the manufacturer's
recommendation. Copper piping and electrical cables shall be laid over pre galvanized ladder type/perforated cable trays of
adequate width fixed with GI clamps.

i 2.0 TR Hi- wall type split air conditioning units.Cost to include pair(Suction line + liquid line) of soft copper(22 Gauge) refrigerant Rmt 60
piping including insulation ,cabling,Glands, tray, etc as stated above.

ii 1.0 TR/1.5 TR Hi- wall type split air conditioning units.Cost to include pair(Suction line + liquid line) of soft copper(22 Gauge) Rmt 15
refrigerant piping including insulation ,cabling,Glands, tray, etc as stated above.

3.0 Condensate Drain Piping


Supply, installation, testing and commissioning of condensate drain water piping of CPVC complete with fittings like
elbows, tees, reducers, bends, U-traps, braided flexible pipe connections with GI clamps, flanges, supports, solvent etc. as
required conforming to tender specifications and of following sizes.
3.1 25 mm dia pipe Rmt 700
3.2 32 mm dia pipe Rmt 40
3.3 40 mm dia pipe Rmt 40

Sub-Total Carried To Summary GST Extra

II SUB-HEAD- II: VENTILATION SYSTEM

1 Inline Fans
Supply, installation, testing and commissioning of duct mounted Cabinet/Circular Inline fans complete with direct driven centrifugal
blower/impeller, motor, rubber isolation mounts & other accessories including wiring & conduiting complete in all respects. The
casing shall be double skin,internally acoustically lined and constructed of galvanized steel.The inline fans shall be selected for
lower noise level. Single phase Inline fans motor shall have inbuilt speed controller & three phase inline fan motor shall be
compatible with VFD and shall be provided with suitable starter ,power/control cabling and earthing.NC level 3M away from
source should be less than 50db.The fans shall be of following capacity:

1.1 Upper Basement floor


i 300 CFM (25mm static pressure) for Storage area Exhaust No. 1
ii 400 CFM (25mm static pressure) for Dry Garbage Exhaust No. 1
iii 700 CFM (25mm static pressure) for Staff Dining Exhaust No. 1
iv 800 CFM (30mm static pressure) for His & Her Toilet Exhaust No. 1

1.2 First floor


i 400 CFM (25mm static pressure) for Gym Change Room Exhaust No. 1
1.3 Terrace floor (Second Floor)
i 700 CFM (25mm static pressure) for Male Toilet Exhaust No. 1
ii 500 CFM (25mm static pressure) for Female Toilet Exhaust No. 1

2 Propeller Fans
Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust/fresh air as shown in drawings.
Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird
screen and fixed louvers for weather protection as required.Fan shall be provided with speed regulator and NC level 3M away
from source shall be less than 60db. Fan selection arrangement and Electrical characteristics shall be as follows :

i 250 mm dia 1400 RPM fan suitable for 240± 10% volts 50 cycles, 1 phase AC supply. Nos. 1

ii 300 mm dia 1400 RPM fan suitable for 240± 10% volts 50 cycles, 1 phase AC supply. No. 1

iii 450 mm dia 1400 RPM fan suitable for 240± 10% volts 50 cycles, 1 phase AC supply Nos. 1

3 AXIAL FLOW FANS (NORMAL MODE & PRESSURIZATION)


Supply, Installation testing and commissioning of Vane Axial Fans with impeller having adjustable pitch angle blades and complete
with suitable TEFC motor and drive assembly. The fan shall be suitable for ceiling/floor installation along with spring isolators or as
recomended by the manufacturer. Fan motor shall be VFD compatible & shall be of high efficiency Class EFF-1(Only for normal
working fans). Motor shall be suitable for 415 ± 10% V, 3 Phase, 50 ± 3%Hz electrical supply.Fan & motor shall be selected for
minimum 30mm Static pressure.Total static pressure shall be checked by vendor. Change in static pressure will not attract any
price implication. The fan motor shall have class 'F' insulation.The fan shall be selected for low noise level and low RPM as per
technical specifications. Fans shall be AMCA Certified. Price shall also include double sleeve fire retardant flexible connection on
both sides of the fan.The fan duty shall be as follows:

3.1 (Normal mode)


Floor Area Served Application Air qty SP Motor
CFM in mm kW
3.1.1 AF-01 Sewage Sump Room Fresh Air 1000 30 0.55 No. 1
3.1.2 AF-02 Sewage Sump Room Exhaust Air 1100 40 0.75 No. 1
3.1.3 AF-03 Pump room Fresh Air 6100 30 2.2 No. 1
3.1.4 AF-04 Pump room Exhaust Air 6750 30 2.2 No. 1
3.1.5 TERRACE AF- Guest Lift well Fresh Air 11500 30 3.7 Nos. 2
05,06 Pressurization
3.1.6 TERRACE AF- Service Lift well Fresh Air 11500 30 3.7 Nos. 2
07,08 Pressurization
3.1.7 TERRACE AF- Staircase well Fresh Air 12700 30 5.5 Nos. 3
09,10,11 Pressurization

4 AXIAL FLOW FANS (FIRE MODE )


Supply ,Installation testing and commissioning of Vane Axial Fans with impeller having adjustable pitch angle blades and complete
with suitable TEFC motor and drive assembly. The fan shall be suitable for ceiling/floor installation along with spring isolators or as
recomended by the manufacturer. Fan motor shall be VFD compatible & shall be of high efficiency Class EFF-1(Only for normal
working fans). Motor shall be suitable for 415 ± 10% V, 3 Phase, 50 ± 3%Hz electrical supply.Fan & motor shall be selected for
minimum 30mm Static pressure.Total static pressure shall be checked by vendor. Change in static pressure will not attract any
price implication. The complete fan assembly alongwith the motor & drive assembly shall be fire rated i.e. suitable to operate upto
250°C for 2 hours and meet the duty parameters.The fan shall be selected for low noise level and low RPM as per technical
specifications. Fans shall be AMCA Certified. Price shall also include double sleeve fire retardant flexible connection on both sides
of the fan.The fan duty shall be as follows:

4.1 (Smoke Extraction Mode)


Floor Area Served Application Air qty SP Motor
CFM in mm kW
4.1.1 BF AF- LB Car Parking Makeup Air 17300 40 7.5 Nos. 4
12,13,14,15
4.1.2 BF AF- LB Car Parking Smoke Exhaust 19250 40 7.5 Nos. 4
16,17,18,19
4.1.3 BF AF- UB Car Parking Smoke Exhaust 9650 40 5.5 Nos. 4
20,21,22,23
4.1.4 LGF AF-24 Reception/Tea Lounge Smoke Exhaust 7200 30 3.7 No. 1
4.1.5 UGF AF-25 Reception/Lounge Bar Smoke Exhaust 7700 30 3.7 No. 1

4.1.6 1F AF-26 Reception/Lounge Bar Smoke Exhaust 8200 30 3.7 No. 1

5 PACKAGED AIRWASHER
Supply, installation, testing and commissioning of factory fabricated Outdoor type Double Skinned package floor mounted
type evaporating air cooling unit fabricated out of extruded aluminium section with 0.6 mm pre-plasticized /pre-coated
Galvanised steel sheet outside & 0.6 mm plain stainless steel (SS -304) sheet inside with blower section having DIDW forward
curved blower (or equivalent performance direct driven plug fan) and EFF-1 blower motor (VFD Compatible) TEFC type suitable
for operating on 415 ± 10% volts, 50 Hz ± 5% AC supply,1400 RPM, belt driven package, manual type aluminium aerofoil gear
driven VCD & fire retardent double sleeve flexible connections made of silicon/neoprene rubber at outlet, wet section & tank shall
be made of 18 G stainless steel (SS 304) having depth not less than 300mm. The Air-washer shall be complete with
Celdek fill of depth 200 mm ,built-in drift PVC eliminators & with 50mm thick HDPE MERV-8 pre filters.The face velocity across
the fill shall be limited to 500 FPM maximum.The Air-washer shall have minimum saturation efficiency of 90% & shall
be complete with suitable capacity water circulation pump (including standby) GI B Class/CPVC interconnecting piping
including valves ,y strainer & distribution header, , The airwasher panels shall be insulated with minimum 23mm thick &
40 ± 2Kg/m³ density PU foam..Fan & motor shall be selected for minimum 45mm Static pressure as required.Total static pressure
shall be checked by vendor. Change in static pressure will not attract any price implication. The Airwasher shall conform to
specifications given in the tender & shall be of following capacity.

5.1 For Annpurna Kitchen at Upper Basement floor

i AWS/01 - 6000 CFM, 1 x 450 mm DIDW Forward curved Fan,1 x 3.7 KW Fan Motor, 45 mm St. Pressure, 2 x 0.5 HP Water No. 1
Circulation Monoblock Pumps (1W +1S)

5.2 For Banquet Kitchen at Lower Ground floor


i AWS/02 - 10400 CFM, 1 x 560 mm DIDW Forward curved Fan, 1 x 5.5 KW Fan Motor, 45 mm St. Pressure, 2 x 0.75 HP Water No. 1
Circulation Monoblock Pumps (1W +1S)

5.3 For Restaurant Kitchen at Upper Ground floor


i AWS/03 - 10400 CFM, 1 x 560 mm DIDW Forward curved Fan, 1 x 5.5 KW Fan Motor, 45 mm St. Pressure, 2 x 0.75 HP Water No. 1
Circulation Monoblock Pumps (1W +1S)

5.4 For Foodcourt Kitchen at First floor


i AWS/04 - 10400 CFM, 1 x 560 mm DIDW Forward curved Fan, 1 x 5.5 KW Fan Motor, 45 mm St. Pressure, 2 x 0.75 HP Water No. 1
Circulation Monoblock Pumps (1W +1S)

5.5 For Piano Bar Kitchen at First floor


i AWS/05 - 5200 CFM, 1 x 450 mm DIDW Forward curved Fan, 1 x 3.7 KW Fan Motor, 45 mm St. Pressure, 2 x 0.5 HP Water No. 1
Circulation Monoblock Pumps (1W +1S)

5.6 For Kitchen at Terrace floor


i AWS/06 - 14250 CFM, 1 x 710 mm DIDW Forward curved Fan, 1 x 5.5 KW Fan Motor, 45 mm St. Pressure, 2 x 1.0 HP Water No. 1
Circulation Monoblock Pumps (1W +1S)

6 KITCHEN EXTRACT FAN SECTION INTEGRATED WITH DRY SCRUBBER


Supply, Installation, Testing and Commissioning of Airhandling units comprising of fan section, section for accomodating dry
type scrubber unit (specifications as detailed below) and air intake section of minimum 900mm depth for extract air complete
with floor standing backward curved DIDW centrifugal fan (or equivalent plug fan) GI/Extruded aluminium base
frame,TEFCsquirrel cage induction high efficiency EFF-1 motor (VFD Compatible) with class "H" insulation ,drive package and
vibration isolation arrangement including spring isolators or as recommended by manufacturer.Complete unit casing shall be
fabricated out of double skin panels with minimum 23mm thick injected puff of density not less than 40Kg/Cum as specified. Fan
motor shall be suitable for operating on 415± 10% volts, 50 Hz, 3 phase AC power supply. The kitchen fan motor shall be
outside hot air stream. Fan outlet velocity shall not exceed 1800 FPM.Fan & motor shall be selected for minimum 75mm Static
pressure as required.Total static pressure shall be checked by vendor. Change in static pressure will not attract any price
implication.

Scrubber shall comprise of electrostatic precipitator, dry type air cleaner to remove oil, smoke and fumes from exhaust air, as per
the Specifications. Electrostatic section shall be made of 18 gauge galvanised sheet, high bake epoxy powder coated, washable
type aluminium mesh pre filters, Ionizing-Collecting cell(s) shall be of one-piece construction minimum 13.38” inches deep in
direction of airflow, to work as magnet for charged smoke & oil particles.Average efficiency shall be 90-95% in single pass as per
DOP test method. Electrostatic Precipitator shall be able to charge particles from 0.01 micron to 10 microns through solid state
power supply. Collector cell shall be of permanent type and incorporate slide out facility for easy removal for cleaning.Ionizing
electrodes shall be heavy duty tungsten wire rigidly supported both vertically and laterally. High voltage support insulators shall be
made of Teflon, including center hole, glazed to enhance dielectric strength and retard tracking. Insulators shall be mounted out of
the airstream, to reduce contaminant buildup. All high voltage electrical connections within each tier of cells, shall facilitate
automatic connection when cells are installed. Power supplies shall be 100% solid state CE Listed, Module shall be equipped with
Pulse width modulating (PWM).The system shall be fitted with interlock switch for safety . The system shall allow connection to a
fan section to achieve 500 FPM velocity across the air cleaner. All units shall have Arc Supression & Auto Restart and shall have
BMS (Building Management System) compatibility, Performance Indicator Lightsshall be part of the system to indicate the status of
the air cleaning system. Power Consumption shall not be more that 50 watts per ESP cell.

Operating Voltage : 220V, 50 Hz


Ionizing Voltage : 12.5 to 13 KVDC
Collector Cell Voltage : 6 to 6.5 KVDC
Power Consumption : 50 Watts

Note:Srcubber supplied at site shall be factory fitted with in the fan section as an integral part of the airhandling unit
with necessary air intake section.The fan characteristics shall be as follows :

i EFS-1/UB floor/Annpurna kitchen - 7000 CFM, 90 mm St. Pr, DIDW Backward curved Fan 1 x 500 mm dia, 1 x 5.5 Kw Fan Motor No. 1
with class H insulation.(Horizontal floor mounted unit ) Dry scrubber module shall have 3500 cfm x 2 filter modules

ii EFS-02/LG floor/ Banquet kitchen - 12000 CFM,90 mm St. Pr, DIDW Backward curved Fan 1 x 630 mm dia, 1 x 7.5 Kw Fan No. 1
Motor with class H insulation.(Horizontal floor mounted unit ) Dry scrubber module shall have 4000 cfm x 3 filter modules

iii EFS-03/UG floor/ Restaurant kitchen - 12000 CFM,85 mm St. Pr, DIDW Backward curved Fan 1 x 630 mm dia, 1 x 7.5 Kw Fan No. 1
Motor with class H insulation.(Horizontal floor mounted unit ) Dry scrubber module shall have 4000 cfm x 3 filter modules

iv EFS-04/First floor/FoodCourt kitchen - 12000 CFM,85 mm St. Pr, DIDW Backward curved Fan 1 x 630 mm dia, 1 x 7.5 Kw Fan No. 1
Motor with class H insulation.(Horizontal floor mounted unit ) Dry scrubber module shall have 4000 cfm x 3 filter modules

v EFS-05/First floor/Piano Bar kitchen - 5750 CFM,85 mm St. Pr, DIDW Backward curved Fan 1 x 450 mm dia, 1 x 3.7 Kw Fan No. 1
Motor with class H insulation.(Horizontal floor mounted unit ) Dry scrubber module shall have 2875 cfm x 2 filter modules

vi EFS-06/Terrace floor/Kitchen - 15000 CFM,70 mm St. Pr, DIDW Backward curved Fan 1 x 710 mm dia, 1 x 7.5 Kw Fan Motor No. 1
with class H insulation.(Horizontal floor mounted unit ) Dry scrubber module shall have 5000 cfm x 3 filter modules

7.0 Airhandling Fan Sections


Supply, installation, testing & commissioning of Ceiling/Floor mounted Double skin construction,Airhandling fan section having
a air intake section for ventilation / exhaust system. Each fan shall be complete with DIDW Forward curved centrifugal blower (or
Equivalent Performance Plug Fan), VFD compatible squirrel cage induction motor,having efficiency of EFF-1 type, belt drive belt-
guard and vibration isolators. The fan motor shall be suitable for 415±10% volts, 3 phase AC power supply.The fan outlet velocity
shall not exceed 1800 FPM. Price shall also include double sleeve fire retardant flexible connection at the outlet.

Upper Basement floor (Exhaust)


7.1 EFS-1 1000 CFM, 40mm SP forward curved Fan of 180mm Dia (or equivalent plug fan), 0.55 Kw Fan Motor.(Floor mounted) for No. 1
Male & Female Change room in Upper Basement.

7.2 EFS-2 1200 CFM, 40mm SP forward curved Fan of 200mm Dia (or equivalent plug fan), 0.75 Kw Fan Motor.(Floor mounted) for No. 1
Male & Female Change room in Upper Basement.

7.3 EFS-3 1800 CFM, 40mm SP forward curved Fan of 280mm Dia (or equivalent plug fan), 1.1 Kw Fan Motor.(Floor mounted) for No. 1
Male & Female Toilet Exhaust in Lower Ground Floor.

7.4 EFS-4 1500 CFM, 40mm SP forward curved Fan of 280mm Dia (or equivalent plug fan), 0.75 Kw Fan Motor.(Floor mounted) for No. 1
Male & Female SPA Toilet Exhaust in Lower Ground Floor.

7.5 EFS-5 1400 CFM, 40mm SP forward curved Fan of 280mm Dia (or equivalent plug fan), 0.75 Kw Fan Motor.(Floor mounted) for No. 1
Male & Female Toilet Exhaust in Upper Ground Floor.

7.6 EFS-6 1000 CFM, 40mm SP forward curved Fan of 180mm Dia (or equivalent plug fan), 0.55 Kw Fan Motor.(Floor mounted) for No. 1
Male & Female Common areaToilet Exhaust in First Floor.

Sub-Total Carried To Summary


SUB-HEAD-III : AIR DISTRIBUTION

III Rectangular GI Ducting (Factory Made)

1 Supply, fabrication, Installation, testing and commissioning of factory fabricated rectangular ducts using G.I Sheets (120GSM
coating). The price shall include factory fabricated TDF flanges, turning vanes, splitter dampers, supports (factory fabricated, full
threaded GI rod/hangers & G.I slotted channel), sealant, neoprene gasket, access door etc. The joints shall be with least leak and
shall be tested with pressure testing machine of approved vendor.Corrective action shall be taken ,if the leakge is more than the
permissible limit. Report shall be generated after satisfactory testing of ducts for leakage and shall be duly signed by the client's
/PMC representative before giving clearance for the thermal insulation.

i 24 gauge galvanized sheet steel ( TDF 01- 750mm) Sq.m 1625

ii 22 gauge galvanized sheet steel ( TDF 751 - 1500mm) Sq.m 4000

iii 20 gauge galvanized sheet steel ( TDF 1501- 2250mm) Sq.m 10

iv 18 gauge galvanized sheet steel ( TDF 2250mm & above ) Sq.m 5


Note :- The Duct shall be manufactured as per SMACNA Standard but the minimum guage shall be 24 G.

v 16 gauge (MS welded duct with angle frames duly painted with primer & fire rated paint (From outside for Kitchen exhaust) Sq.m 650

2 Site Fabricated GI Duct

Supply, fabrication, Installation, testing and commissioning of site fabricated rectangular ducts using G.I Sheets (120GSM
coating). The price shall include factory fabricated MS flanges (wherever required), turning vanes, splitter dampers, supports
(factory fabricated, full threaded G.I rod/hangers & G.I slotted channel), sealant, neoprene gasket, access door etc.as required and
as per ISI specifications.The joints shall be with least leak and shall be tested with pressure testing machine of approved
vendor.Corrective action shall be taken ,if the leakge is more than the permissible limit. Report shall be generated after satisfactory
testing of ducts for leakage and shall be duly signed by the client's /PMC representative before giving clearance for the thermal
insulation.

i 24 gauge galvanized sheet steel Sq.m 175

ii 22 gauge galvanized sheet steel Sq.m 400

iii 20 gauge galvanized sheet steel Sq.m 5

iv 18 gauge galvanized sheet steel Sq.m 5

v 16 gauge (MS welded duct with angle frames duly painted for Kitchen exhaust) Sq.m 50

3 GSS VOLUME CONTROL DAMPER


Supply, installation, testing and balancing of opposed multiblade box type GI volume control damper within ducts to be provided Sqm 20
with suitable links, levers and quadrants for manual control of volume of air flow and for proper balancing of the air distribution
system as per approved shop drawings & specifications.(All AHUs, fan sections VCD at machine outlets shall be included in the
equipment cost only)

4 NON RETURN DAMPER


Supply, installation, testing and commissioning of back draft dampers, gravity louver type on the supply air/ventilation ducts.The Sqm 22
dampers shall be installed to avoid the short cycling of air w.r.t these fans/blowers installed in the same vicinity. The dampers shall
be with suitable flanges. The frame shall be constructed of minimum 18 Gauge GI and blades shall be minimum of 24Gauge GI.
The blades shall be provided with high class rubber/neoprene gaskets to avoid rattling noise during operation and to permit low
leakage.All blades shall be fitted to a common linkage in such a manner so that all blades shall lift up and shut down
simultaneously. The dampers shall open by the pressure differential generated by fan.

5 FIRE DAMPERS
Supply, installation, testing and commissioning of multi blade sleeve type combined motorised fire & smoke dampers with
spring return actuator. The damper shall be of atleast 1.5 hr. fire rating. The damper shall be as per CBRI approval.The damper
shall be constructed out of 16G galvanised sheet steel. It shall be complete with control panel, spring return actuator, sensor . Cost
to include control cabling between firedamper control panel , actuator and fan starter panel for necessary inter-locking / for tripping
of AHU fan motor.The fire dampers shall be installed at locations shown in approved shop drawings and as per specifications.

i Smoke & Fire Dampers. Sqm 11


ii Control Panels with actuator suitable for 10-12 NM torque Nos. 18

6 LINEAR GRILL (FIXED BAR)


Supply, installation, testing & balancing of removable core type ,continuous, linear, fixed bar extruded aluminium powder coated
Supply Air / Return Air / Exhaust Air grills, normal flow, 15° angle one way / two way deflection with all sides flanges.Blade
thickness shall be minimum 5mm in front and 1.0 mm in rear side.Grills shall be supplied in accordance with specifications and
approved shop drawings.

a. 200 mm/150mm/100mm High Sqm 160

7 VCDs FOR LINEAR GRILL SUPPLY AIR COLLARS


Supply, installation, testing & balancing of key operated extruded Aluminium volume control dampers in black mat finish for Sqm 80
supply/return/exhaust air duct collars as per approved shop drawings and specifications.
8 SUPPLY/RETURN AIR SLOT DIFFUSERS
Supply, installation, testing & commissioning of Extruded Aluminium powder coated Supply/Return Air linear Slot Diffusers with all
side flanges with out damper.Slot diffusers shall be supplied in accordance with specifications and approved shop drawings.

i 1 Slot (20mm gap) Rmt RO


ii 2 Slot (20mm gap) Rmt 30
iii 3 Slot (20mm gap) Rmt 50
iv 4 Slot (20mm gap) Rmt RO

9 FRESH AIR INTAKE LOUVERS


Supply, installation, testing & balancing of Fresh air Extruded Aluminium intake louvers with bird screen and opposed blade box Sqm 8
type GI volume control damper complete as per specification & approved shop drawings.Construction/profile of the louvers shall
give a protection against the rain and suitable for fixing in the external facade of the building.

10 EXHAUST LOUVERS
Supply, installation, testing & balancing of Exhaust air Extruded Aluminium intake louvers with bird screen complete as per Sqm 35
specification & approved shop drawings.Construction/profile of the louvers shall give a protection against the rain and suitable for
fixing in the external facade of the building.

11 SUPPLY/ RETURN AIR DIFFUSERS


Supply, installation, testing and balancing of square, rectangular and round extruded aluminium powder coated Supply/ Return Air Sqm 12
diffusers. Diffuser shall be with spring loaded removable core type distribution grid , key operated aluminium black matt finish
dampers .Diffusers shall be supplied in accordance with specifications and approved shop drawings.
Note: Samples of grilles / diffusers will have to be submitted to the Architect for approval on size / shape / shade / colour
before ordering.
12 RETURN AIR / EXHAUST AIR DIFFUSERS
Supply,installation,testing and balancing of square, rectangular and round extruded aluminium powder coated Return Air Diffusers/ Sqm 3
Exhaust Air Diffusers. Diffuser shall be with spring loaded removable core type distribution grid and shall be without
dampers.Diffusers shall be supplied in accordance with specifications and approved shop drawings.

13 AIR TRANSFER GRILLS


Supply,installation,testing and balancing of extruded aluminium construction duly powder coated non vision air transfer grills with Sqm 4
two side frame to be provided in doors.

14 FLEXIBLE DUCT CONNECTOR


Supply,installation and testing of double layer flexible duct connector consisting of a flame retardant fabric secured to extruded Sqm 1
aluminium frame on both sides to provide a wear resistant airtight flexible connection. Fabric shall be mildew resistant, water proof
and silicon impregnated.Flexible connector shall be supplied in accordance with the specifications and drawings. (This item shall
be an integral part of the AHUs,FCUs, Axial flow fans and already captured in their specifications)

15 BIRD SCREEN
Supply, installation, testing & balancing of factory made Bird screen made out of galvanized steel mesh in 20G having diamond Sqm 21
pattern with GSS flanges and necessary cross bracings suitable for Fresh/ Exhaust air fans on terrace, complete as per
specification & approved shop drawings.

Note: Samples of grilles / diffusers will have to be submitted to the Architect for approval on size / shape / shade / colour
before ordering.

Sub-Total Carried To Summary

SUB-HEAD-IV: THERMAL INSULATION

IV Thermal Insulation(Internal ducting):


1 Supply & installation of external thermal insulation on ducts with approved sample of Aluminium foil faced XLPE duct insulation
with density 25-30 Kg/Cum for XLPE, class 'O' complete as per specifications. All longitudnal and transverse joints shall be sealed
with 50mm wide and 3mm thick XLPE tape .

1.1 9mm thick (Supply air Ducts in return air path) Sqm 2100
1.2 13mm thick (Supply air Ducts in return air path) Sqm 500

1.3 16mm thick (TFA Ducts) Sqm 450

1.4 19mm thick (TFA Ducts) Sqm 100

1.5 13mm thick for supply air duct (Ducts running in non airconditioned area /Ducted SA & RA System). Sqm RO

1.6 9mm thick for return air duct (Ducts running in non airconditioned area /Ducted SA & RA System) Sqm RO

2 Acoustic lining (For Rest of the Ducts)


Supply & Installation of acoustic lining within supply and return air ducting using open cell elastomeric insulation with
antimicrobial protection having 140-160 Kg/cum. density.All ducts shown cross hatched on the approved shop drawings shall be
provided with acoustic lining as per the specifications.

2.1 10 mm thick Sqm 440


2.2 15 mm thick Sqm RO
3 Acoustic lining (For AHU rooms)
Supply and Installation of thermal/acoustic lining of walls & ceiling of AHU rooms using open cell elastomeric with 140-160
Kg/cum. density. The material should be fibre free,as per the specifications.
25mm thick Sqm RO

4 FCU's & AHUs Drain Pipe Insulation:


Supplying & installation of 6 mm thick closed cell nitrile rubber insulation with approved sample of black colour factory laminated
fibre glass cloth with density 40-60 Kg/ Cum, class 'O' complete as per specifications in the form of pre-formed pipe sections and
complete in all respects as per specifications and drawings on condensate drain pipes of the following sizes:

Quoted price shall be inclusive of adhesive and UV/mechanical protection using UV resistant paint/starbond coating spread
over Glass cloth as per specifications.
4.1 25 mm dia Rmt 600

4.2 32 mm dia Rmt 40

4.3 40 mm dia Rmt 40

Sub-Total Carried To Summary

SUB-HEAD-V : ELECTRICAL WORK

V. Preamble to BOQ for MCC , Distribution Boards & wall mounted Starter Panels
General Notes & Specifications as given below shall be applicable to all panels.The vendors shall consider the following
details in their item rates, wherever required:
1 Supporting rigid steel framework.
2 Cubicle type, 14 gauge CRCA sheet steel enclosure.
3 Panel Complete with interconnections and distribution bus bars.
4 Proper bonding to earth.
5 Painting/lettering on Breakers and distribution boards, the location they serve, Providing on each panel its circuit diagram.

6 Providing cable clamps / supports within distribution boards cable alley.


7 TPN MCCBs shall mean 3 pole MCCBs with adequate size of neutral link.
8 All MCBs shall be of minimum 10 KA breaking capacity.
9 All motor feeders MCCBs shall be of motor duty and shall be able to carry the inrush current of motor.
10 Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5.
11 Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.
12 IP 42 for indoor panels.
13 IP 55 for outdoor panels with double door enclosure.
14 All MCCB’s shall be provided with operating mechanism for door interlock.
15 Current density of aluminium shall be 1 sq mm for 1.0 amps for rated current of bus bars and current density of copper shall be 1
sq.mm for 1.25 amps for rated current of bus bars.
16 Tinned copper earth bus shall be provided through out the length of each board.
17 All measuring instruments (Meters) shall be of digital electronic with LED of approved make and compatible with BAS.

18 All indicating lamps shall be LED type.


19 All current/voltage transformers shall be cast resin type.
20 All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.
21 All panels shall have provision of the following:
22 Pad locking of Switch board doors.
23 Pad locking of MCCB’s handles in “OFF” Position.
i Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space
required for various transducers in Main Switch Board sections. Only transducers shall be supplied by BAS contractor.

ii All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall
be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic.

iii All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.

24 All PTs / control transformers shall be provided with centre tap earth secondary.
25 All DOL & Star-Delta Starters shall be provided with voltage based SPPR (single phase preventor relay) and 2 nos. of
Aux.Contacts for Remote operation/monitor.
26 The Panel fabricator shall provide Aluminium Bus-bars link from Breakers wherever more than two nos. of cables are terminated in
the breakers.
27 Readymade 16SWG Sheet steel Enclosure with cutout For MCBs
28 The breaking capacity of MCCB’s shall be mentioned panel wise. All MCCB’s shall be with thermal magnetic releases upto 250
amps and miroprocessor based above 250 amps capacity, unless specified otherwise.

29 All internal control wiring shall be heat resistant type.


30 Bus bar chamber shall be provided at top only. Incoming and outgoing cable entry shall be from top/bottom as required.

31 Live parts shall not be accessible after opening the door, Transparent acrylic sheet to be provided to cover the same.

32 Spare contacts of ACBs / MCCBs / Relay / Contactor shall be wired upto terminal block.
33 All Switchgear used in Starter Circuit shall be type-2 coordinated. Contactor rating shall be selected as per the kVAR rating of the
capacitor bank from capacitor duty contactor range. Vendor to furnish the type-2 coordination chart and capacitor duty contactor
selection chart.
34 Protection Releases Microprocessor based (PRMB) & Thermal magnetic (PRTM) shall be as describe below:

A Protection Release Microprocessor Based (PRMB-1)


Over-current/long time protection range 105% - 120 % with Time setting
short circuit /short time protection range 100% - 1000 % with Time setting
Instantaneous short circuit Protection range 200% - 1500 % with Time setting
Earth Fault Protection range 20% - 100 % with Time setting
Under voltage & over voltage protection
Reverse power
Current unbalance
Phase sequence
Measurements
Voltage
Current
Power (Active,Reactive & Apparent)
Energy ((Active,Reactive & Apparent)
Power factor
Frequency
B Protection Release Microprocessor Based (PRMB-2)
Over-current/long time protection range 105% - 120 % with Time setting
short circuit /short time protection range 100% - 1000 % with Time setting
Instantaneous short circuit Protection range 200% - 1500 % with Time setting
Earth Fault Protection range 20% - 100 % with Time setting
Measurements
Current
C Protection Release Microprocessor Based (PRMB-3)
Over-current/long time protection range 105% - 120 % with Time setting
Instantaneous short circuit Protection range 200% - 1500 % with Time setting
D Protection Release Thermal-Magnetic Based (PRTM)
Over-current
Short circuit

1 AHU STARTER PANEL - VFD STARTER (Type-1)


Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall
mounted AHU starter panels including anchoring into the wall with following details:
All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be
provided with potential free Contacts for Connections to Building Automation System.
The panel shall include the following components and accessories.
a. 16G CRCA Powder Coated panel enclosure with earthing studs & hinged locable doors. IP52 Protection, suitable for 415V, 3
Phase, 4 wire, 50Hz system.
b. Incomer switch shall be TPN MCB (motor duty) of required rating & 10KA fault withstand capacity for motors upto 11.0KW rating.
MCB shall be with short circuit protection.
c. Incomer switch shall be TP MCCB (motor duty) of required rating & 20KA fault withstand capacity for motors beyond 11.0KW
rating. MCCB shall be with overload & short circuit protection.
d. R,Y,B LED Type Phase indication lamps with control MCB's.
e. ON'/OFF/TRIP Indication LED Type lamp with control MCB.
f. ON'/OFF Push Buttons
g. VFD (Variable Frequency Drive) with all inbuilt features like protection against over load, short circuit & single phasing. VFD shall
have inbuilt auto / manual / BMS operation functions selection & shall be BMS compatible. Drive shall have ON/OFF/Trip displays
& metering & display of electrical parameters.Drive shall be Danfoss Vacon-20 series /Equivalent.

h View window to read VFD parameters.


i For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the
automatic operation.
j A fire detection relay module for tripping of AHU motor on receiving fire signal & fire damper interlocking. Necessary nos. of
auxillary contactors & Relays shall be included in cost as required for the interlocking with smoke extraction fans & motorised
firedampers.
k 240/24V AC Step down transformer for powering to fire module relay with control MCB and wiring & conduiting upto relay.24V AC
supply shall also be used for fire module relay.
l 2 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for fire damper actuator & AHU limit
switch/Bulk head lighting.
m Airwasher panel shall have additional set of On/Off push button with indication ,set of contactor and overload relay for the
operation of 1no. Water circulation pump (0.55 Kw) and shall be BMS compatible.

n Scrubber panel shall have additional set of On/Off push button with indication ,set of contactor and overload relay for the operation
of 1no. dry scrubber (0.37 Kw) and shall be BMS compatible.
o Terminal block for power distribution.
p Panel shall have adequate ventilation arrangement for heat dissipated by VFD.
q Note: Vendor to include the cost of all related power & control cabling (for AHU door limit switch,Bulk head light etc) on
GI cable tray along with copper earthing , from airhandling unit motors to VFD control panels, from Exhaust dry scrubber
to control panel and from Airwasher fan motor and its pumps to control panel. (For sizes of cables ,refer to the detailed
specifications of Electrical section).All cables shall be FRLS XLPE insulated armoured.

r The no. of AHU control panels/VFD starters shall be as per KW ratings given below:
i. AHU VFD Panel for 0.55 KW Motor No. 2
ii. AHU VFD Panel for 0.75 KW Motor Nos. 4
iii. AHU VFD Panel for 1.1 KW Motor Nos. 3
iv. AHU VFD Panel for 1.5 KW Motor No. 1
v. AHU VFD Panel for 2.2 KW Motor No. RO
vi. Airwasher VFD Panel for 3.7 KW Motor Nos. 2
vii Airwasher VFD Panel for 5.5 KW Motor Nos. 4
viii Exhaust scrubber VFD Panel for 3.7 KW Motor No. 1
ix Exhaust scrubber VFD Panel for 5.5 KW Motor No. 1
x Exhaust scrubber VFD Panel for 7.5 KW Motor Nos. 4

2 NORMAL EXHAUST/SMOKE EXTRACTION FAN STARTER PANEL - (Type-2)


Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall
mounted Fan starter panels including anchoring into the wall with following details:

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be
provided with potential free Contacts for Connections to Building Automation System.

The panel shall include the following components and accessories.


16G CRCA Powder Coated panel enclosure with earthing studs & hinged locable doors. IP52 Protection, suitable for 415V, 3
Phase, 4 wire, 50Hz system.
Incomer switch shall be TPN MCB (motor duty) of required rating & 10KA fault withstand capacity for motors upto 11.0KW rating.
MCB shall be with short circuit protection.
Incomer switch shall be TP MCCB (motor duty) of required rating & 20KA fault withstand capacity for motors beyond 11.0KW
rating. MCCB shall be with overload & short circuit protection.
a. R,Y,B LED Type Phase indication lamps with control MCB's.
b. ON'/OFF/TRIP Indication LED Type lamp with control MCB.
c. ON'/OFF Push Buttons
d. Digital ammeter with in built selector switch.
e. DOL/Star-delta starter for the ratings given below complete with contactors, over load relay with built in single phase protection.
Starter shall be BMS compatible for Remote ON/Off & status monitoring complete with Auto/manual switch.
f For on/off/remote and local operation, 3 pole single throw switch shall be provided in each Fan panel to facilitate override of the
automatic operation.
g. A fire detection relay module for switching 'ON' of Fan motor on receiving fire signal & fire damper interlocking. Necessary nos. of
auxillary contactors & Relays shall be included in cost as required for the interlocking with AHU fan motor & motorised firedampers.

h 240/24V AC Step down transformer for powering 24V AC auxillary relay.


i 2 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for fire damper actuator & AHU limit
switch/Bulk head lighting.
j Time delay relay for delayed automatic restart of fan motor.
k Terminal block for power distribution.
l Note: Vendor to include the cost of all related power & control cabling on GI cable tray along with copper earthing , from
Axial flow fan/DIDW fan motors to control panels. (For sizes of cables ,refer to the detailed specifications of Electrical
section).All cables shall be FRLS XLPE insulated armoured. For Firemode fans ,Fire survival cable shall be considered.

m DOL starters upto 5.5 KW & beyond star-delta starter shall be considered.
The no. of FAN control panels/starters shall be as per KW ratings given below:
i Fan starter Panel for 0.55 KW Motor Nos. 4
ii Fan starter Panel for 0.75 KW Motor Nos. 6
iii Fan starter Panel for 1.1 KW Motor No. 2
iv Fan starter Panel for 1.5 KW Motor No. RO
v Fan starter Panel for 2.2 KW Motor Nos. 2
vi Fan starter Panel for 3.7 KW Motor Nos. 7
vii Fan starter Panel for 5.5 KW Motor Nos. 7
viii Fan starter Panel for 7.5 KW Motor Nos. 8

Preambles to BOQ for Cables and Cable Trays


The contractor shall consider the following details in their item rates, wherever required:
The rate shall also include the following :
i Providing and fixing junction boxes with covers including painting where ever required.
ii Providing all fixing accessories such as clamping devices nuts, bolts and screws.
iii Wherever the cables are of aluminium and bus bars of copper bimetallic lugs shall be used.
iv All the DB incomer cables shall be unarmoured cable.
v All cable shall be laid with one diameter gap.
vi All cables shall (conform IS norms) be IS approved.
vii Double compression glands
viii Fire retardent paint one meter on both side of wall penetration and at termination as per specifications.

3 Cables from Isolators to each of ODUs


3.1 Supplying & laying of following 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured cables as per
specification in existing trenches, cable trays, ducts, over bed of sand, clamped to wall with suitable clamps including, saddles
fixing bolts, connecting testing and commissioning. The cost of cable shall include the cost of cable tray.

3.1.1 3.5 C x 35 sq.mm RM 10


3.1.2 3.5 C x 25 sq.mm RM 30
3.1.3 4 C x 16 sq.mm RM 50
3.1.4 4 C x 10 sq.mm RM 60
3.1.5 4 C x 6 sq.mm RM 60

3.2 Supply & Installation of Double earthing continuity conductors of G.S.S between isolators and VRV ODU's(21nos.) as required. Lot 1
3.3 Cable end termination of the following XLPE insulated PVC sheathed Copper conductor armoured cables of 1100 volt grade
including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing.

3.1.1 3.5 C x 35 sq.mm Nos. 2


3.1.2 3.5 C x 25 sq.mm Nos. 6
3.1.3 4 C x 16 sq.mm Nos. 10
3.1.4 4 C x 10 sq.mm Nos. 12
3.1.5 4 C x 6 sq.mm Nos. 12

3.4 Isolator Switches With Metal Enclosure


3.4.1 125A ELCB (300mA),4pole switch for VRV Outdoor units with sheet metal enclosure, rain protection etc. as required to suit the site No. 1
condition. (Enclosure shall be suitable for out door installation).
3.4.2 100A ELCB (300mA),4pole switch for VRV Outdoor units with sheet metal enclosure, rain protection etc. as required to suit the site Nos. 6
condition. (Enclosure shall be suitable for out door installation).
3.4.3 63A ELCB (300mA),4pole switch for VRV Outdoor units with sheet metal enclosure, rain protection etc. as required to suit the site Nos. 8
condition. (Enclosure shall be suitable for out door installation).
3.4.4 40A ELCB (300mA),4pole switch for VRV Outdoor units with sheet metal enclosure, rain protection etc. as required to suit the site Nos. 6
condition. (Enclosure shall be suitable for out door installation).
3.4.5 25A ELCB (300mA),4pole switch for VRV Outdoor units with sheet metal enclosure, rain protection etc. as required to suit the site Nos. 6
condition. (Enclosure shall be suitable for out door installation).
3.4.6 20 A 2 pole MCB for equipments with sheet metal enclosure, rain protection etc. as required to suit the site condition. (Enclosure Nos. 1
shall be suitable for out door installation.) For DX Outdoor split units.
3.4.7 25 A 2 pole MCB for equipments with sheet metal enclosure, rain protection etc. as required to suit the site condition. (Enclosure Nos. 4
shall be suitable for out door installation.) For DX Outdoor split units.
Sub-Total Carried To Summary
TION WORKS

tions, methods of installation

pto site, storage, installation,

labour necessary in and for

ad as complimentary to and

he Owner/Consultant/Project

red by the Consultant. This


he approved Shop Drawings

ons, notes or additions shall,

rer shall be regarded as firm

Schedule shall not vitiate this

on the basis of Schedule of

equipment without any price

Amount
(INR)
395,000.00
695,000

695,000

905,000
600,000
600,000

808,000
600,000
295,000
245,000
245,000

808,000.00
808,000.00

390,000.00
245,000.00

1,095,000
404,000
295,000.00

390,000.00

245,000.00

298,000.00
248,000.00

395,000.00
248,000.00

248,000.00

86,000.00
86,000.00
412,000.00
35,500.00
42,500.00
41,800.00
106,000.00
32,700.00
41,800.00
32,700.00
32,700.00
103,000.00
86,000.00
206,000.00
206,000.00
212,000.00
258,000.00
206,000.00
41,800.00
32,900.00
32,900.00
41,800.00
31,500.00
41,800.00
31,500.00
42,500.00
32,900.00

618,000.00
258,000.00
206,000.00
106,000.00
103,000.00

71,000.00

618,000.00
618,000.00
106,000.00
103,000.00
412,000.00
103,000.00

32,900.00
32,700.00
103,000.00
103,000.00
41,800.00
43,000.00

-
108,000.00
51,000.00
54,000.00
51,000.00
54,000.00
51,000.00

14,475.00

165,000.00

170,000.00

225,000.00

-
-
-
-
-
-
-
-
-
-

-
-

-
-

-
-
-

19,378,175.00

-
-
-
-

-
-
-
-
-

-
-

-
-

-
-

-
-

-
-
-

-
-

-
-
-
-
-
-
-
-
-
-

-
-
-

-
-
-
-

-
-
-
-
-

-
-
-
-
-
-