【b】manual - sun-60-80k-sg02hp3-eu-em6-230240301004480 - 20250530 - en
【b】manual - sun-60-80k-sg02hp3-eu-em6-230240301004480 - 20250530 - en
SUN-60K-SG02HP3-EU-EM6
SUN-70K-SG02HP3-EU-EM6
SUN-75K-SG02HP3-EU-EM6
SUN-80K-SG02HP3-EU-EM6
User Manual
Contents
1. Safety Introductions ������������������� 01-02
2. Product instructions ������������������� 02-06
2.1 Product Overview
2.2 Product Size
2.3 Product Features
2.4 Basic System Architecture
2.5 Product handling requirements
3. Installation ����������������������� 06-30
3.1 Parts list
3.2 Mounting instructions
3.3 Function port definition
3.4 Battery connection
3.5Grid connection and backup load connection
3.6 PV Connection
3.7 Meter or CT installation
3.8 Earth Connection(mandatory)
3.9 Data logger connection
3.10 Wiring diagram with neutral line grounded
3.11 Wiring diagram with neutral line ungrounded
3.12 Typical application diagram of on-grid system
3.13 Typical application diagram of diesel generator
3.14 Three phase parallel connection diagram
4. OPERATION ����������������������� 31
4.1 Power ON/OFF
4.2 Operation and Display Panel
5. LCD Display Icons �������������������� 32-46
5.1 Main Screen
5.2 Detail page
5.3 Curve Page-Solar & Load & Grid
5.4 System Setup Menu
5.5 Basic Setting Menu
5.6 Battery Setting Menu
5.7 System Work Mode Setup Menu
5.8 Grid Setting Menu
5.9 Generator Port Use Setup Menu
5.10 Advanced Function Setup Menu
5.11 Device Info Menu
6. Mode �������������������������� 46-47
7. Warranty ������������������ 47-48
8. Troubleshooting ������������������������ 48-53
9. Datasheet ������������������������ 54-55
10. Appendix I ����������������������� 55-57
11. Appendix II ����������������������� 58
12. Appendix III ����������������������� 59
13. EU Declaration of Conformity ��������������� 59-60
About This Manual
This manual provides information and guidelines for the installation, operation, and
maintenance of the SUN-(60-80)K-SG02HP3-EU-EM6 inverter. Please note that it does not
contain comprehensive information about the photovoltaic (PV) system.
1. Safety Introductions
Labels description
Label Description
CE mark of conformity
2. Product Introductions
This is a multifunctional inverter, combining functions of inverter, solar charger and battery
charger to offer uninterruptible power support with portable size. Its comprehensive LCD display
offers user configurable and easy accessible button operation such as battery charging, AC/solar
charging, and acceptable input voltage based on different applications.
2.1 Product Overview
1
2
3 7
4 8
5 9
6
10
13 11
14 12
17 16
15
606.00 mm
927.00 mm
985.26 mm
338.00 mm
314.50 mm
Inverter Size
518.00 mm
314.00 mm
180.00 mm
4- Φ 14
270.00 mm
274.50 mm
2.3 Product Features
- 230V/400V Three phase Pure sine wave inverter.
- Self-consumption and feed-in to the grid.
- Auto restart while AC is recovering.
- Programmable supply priority for battery or grid.
- Programmable multiple operation modes: On grid, off grid and UPS.
- Configurable battery charging current/voltage based on applications by LCD setting.
- Configurable AC/Solar/Generator Charger priority by LCD setting.
- Compatible with mains voltage or generator power.
- Overload/over temperature/short circuit protection.
- Smart battery charger design for optimized battery performance
- With limit function, prevent excess power overflow to the grid.
- Supporting WIFI monitoring and have 3 or 4 built-in MPP Trackers, 1 MPP Tracker can
connect 2 PV strings.
- Smart settable three stages MPPT charging for optimized battery performance.
- Time of use function.
- Smart Load Function.
AC cable DC cable
WiFI computer
GPRS/4G
LAN
phone
Cloud services
CT
OR OR
transport
CAUTION:
Improper handling may cause personal injury!
· Arrange an appropriate number of personnel to carry the inverter according to
its weight, and installation personnel should wear protective equipment such
as anti-impact shoes and gloves.
· Placing the inverter directly on a hard ground may cause damage to its metal
enclosure. Protective materials such as sponge pad or foam cushion should be
placed underneath the inverter.
· Move the inverter by one or two people or by using a proper transport tool.
· Move the inverter by holding the handles on it. Do not move the inverter by
holding the terminals.
3. Installation
3.1 Parts List
Check the equipment before installation. Please make sure nothing is damaged in the package.
You should have received the items in the following package:
User
SET ESC
manual
Solar Photovoltaic
Connector Special Matching Resistor x1
Spanner x1
4 5 6
7
1,2,3 : 23×33×15 mm
4,5,6 : 31×29×19mm
7,8,9 :80×50×25 mm
Protective goggles Anti-dust mask Earplugs Work gloves Work shoes Utlity Knife Slotted screwdriver
Cross screwdriver Percussion drill Pliers Marker Level Rubber hammer socket wrenches set
Anti-static wrist strap Wire cutter Wire stripper Hydraulic pliers Heat gun Crimping tool�-�mm² Solar connector
wrench
5 00mm
For a proper ventilation of the inverter and avoid overheating, allow a clearance of approximately
�� cm around the inverter and at least ��� cm to the front as it can be seen at the picture below.
Remember that this inverter is heavy! Please be careful when lifting out from the package.
Choose the recommend drill head(as shown in below pic) to drill � holes on the wall,
��-��mm deep.
�. Use a proper hammer to fit the expansion bolt into the holes.
�. Screw out the nuts of the expansion bolts, align the holes of the mounting bracket with the �
expansion bolts, and then push in the mounting bracket, tighten the nuts of expansion bolts.
�. Mount the inverter on the mounting bracket and use screws to fix the inverter with mounting
bracket.
Size: M12×60
DIP switch:For
communication setting
of parallel system.
CN1 CN2
SHUT DOWN
CT-L1 CT-L2 CT-L3 B B
For safe operation and compliance, a separate DC over-current protector or disconnect device is
required between the battery and the inverter. In certain applications, a disconnect switch may
not be necessary, but it is always essential to have DC overcurrent protection in place. Refer to
the typical amperage in the page 28 for the required fuse or circuit breaker size.
Orange Black
Pic 3.1 BAT+ plug connector Pic 3.2 BAT- plug connector
Safety Hint:
Please use approved DC cable for battery system.
Cross section(mm )
Model
Range Recommended value
Chart 3-2
The steps to assemble the battery plug connectors are listed as follows:
a) Pass the cable through the terminal, as shown in Pic 3.3.
Pic 3.3
b) Put on the rubber ring, as shown in Pic 3.4.
Pic 3.4
Hydraulic pliers
Pic 3.5
Pic 3.6
Pic 3.7
BMS connection
Note:
In final installation,breaker certified according to IEC 60947-1 and IEC 60947-2
shall be installed with the equipment.
All wiring must be performed by a qualified personnel.It is very important for
system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the proper recommended cable
as below. There are two tables below, the first table recommends cable specififi-
cations based on bypass current(Max.Continuous AC passthrough), and the
second table is based on Max.AC output current.
PE
LOAD E-BAR
9 8
7
LOAD GEN
GRID
7
8
9
Thread the end of wires through the
magne�c ring 7 and connect these wires to Thread the end of wires through the
the terminals of LOAD port corresponding to magne�c ring 8 and connect these wires to
the indica�on of polarity. Thread the end of wires through the the terminals of GEN port corresponding to
magne�c ring 9 and connect these wires to the indica�on of polarity.
the terminals of GRID port corresponding to
the indica�on of polarity.
Be sure that AC power source is disconnected before attempting to wire it to the
unit.
3. Make sure all the wires are securely and completely connected.
4. Some appliances, such as air conditioners and refrigerators, may need a time delay before
recconneting them after a power outage. This delay allows the refrigerant gas to stabilize and
prevents potential damage. Check if your appliance has a built-in time-delay function before
connecting it to our inverter. Examples of appliances that may require a delay include:
Air conditioners: Balancing refrigerant gas.
Refrigerators: Stabilizing the compressor.
Freezers: Allowing the cooling system to balance.
Heat pumps: Protecting against power fluctuations.
This inverter will protect your appliances by triggering an overload fault if no time delay is
present. However, internal damage may still occur. Refer to the manufacturer's documenta-
tion for specific time-delay requirements.
3.6 PV Connection
Before connecting to PV modules, please install a separately DC circuit breaker between
inverter and PV modules. It is very important for system safety and efficient operation to
use appropriate cable for PV module connection.
To avoid any malfunction, do not connect any PV modules with possible leakage
current to the inverter. For example, grounded PV modules will cause leakage
current to the inverter. When using PV modules, please ensure the PV+ & PV-
of solar panel is not connected to the system ground bar.
It is requested to use PV junction box with surge protection. Otherwise, it will
cause damage on inverter when lightning occurs on PV modules.
3.6.1 PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1) Open circuit Voltage (Voc) of PV modules can not exceed max.PV Input Voltage of
inverter.
2) Open circuit Voltage (Voc) of PV modules should be higher than min.PV Input Voltage of inverter.
3) The PV modules used to connected to this inverter shall be Class A rating certified according
to lEC 61730.
Chart 3-5
Safety Hint:
Before connection, please make sure the polarity of PV array matches the
"DC+" and "DC-" symbols.
Safety Hint:
Before connecting to inverter, please make sure that the open circuit voltage of
PV strings haven't exceeded the max.PV input voltage of the inverter.
Pic 5.1 DC+ male connector Pic 5.2 DC- female connector
Safety Hint:
Please use approved DC cable for PV system.
Cross section(mm )
Cable type
Range Recommended value
Industry generic PV cable 2.5-4
2.5(12AWG)
(model: PV1-F) (12-10AWG)
Chart 3-6
The steps to assemble the PV connectors are listed as follows:
a) Strip the insulation of the PV wire by 7 mm, disassemble the cap nut of the connetctor,
thread one PV wire through the cap nut of the connector (see Pic 5.3). Repeat this operation
with all the PV wires, paying special attention to the polarity of the connector.
Hydraulic pliers
c) Insert the contact pin to the top part of the connector and completely tighten the cap nut to
the top part of the connector, as shown in Pic 5.5.
Pic 5.5 connector with cap nut screwed on
d) Finally insert the PV connectors into the positive and negative PV inputs of the inverter, as
shown in Pic 5.6.
Warning:
When operating the PV strings, be aware that sunlight exposure can generate high
voltages in the PV strings. Avoid contact with exposed electrical connecters or
terminals to prevent electrical shock or injury. For safety, it is best to operate the
PV strings at night or when PV modules are not exposed to sunlight. If daytime
operation is necessary, cover the PV modules to minimize sunlight exposure and
prevent high voltage generation. Remember to turn off the DC breaker or switch
before performing any maintenance or adjustments. Do not turn off the DC
breaker or switch when high voltage or high current is present to avoid damage or
hazards. Prioritize personal safety.
Warning:
Please use its own DC power connector from the inverter accessories. Do not
interconnect the connectors of different manufacturers. The Isc current of PV
modules should not exceed the Max.PV Isc current of this inverter. If exceeds,
it may damage the inverter and is not covered by Deye's warranty.
3.7 Meter or CT installation
There are three selectable installation methods to measure the power consumption or to ensure zero power
export to grid. The default installation method is to use the CTs(300A/5A) that come with the packaging
box. When the distance between the AC distribution box and the hybrid inverter exceeds 10 meters, which
means that the wire length of the CT needs to exceed 10 meters, it is recommended to use a smart meter
instead of three CTs. In addition, in a parallel system, if the current to be measured is greater than 300 A, the
default three CTs also need to be replaced with smart meters or larger CTs. Please contact the Deye support
team to confirm which specification of CT or smart meter to use.
3.7.1 CT connection
GRID
L3
L2
N L1
Inverter
CT
Arrow pointing
to inverter
L3
CT3
L2
CT2
L1
CT1
N
Grid PE
*Note:When taking power from the utility grid, if the grid power displayed
on the LCD screen is indeed negative, please adjust the installation direction
of the CTs.Please refer to Chapter 3.10 for the position to be clamped.
3.7.2 Meter connection without CTs
There are two kinds of smart meter, one is passthrough smart meter, and the other is Mutual inductance
smart meter with CTs. The smart meter brands that Deye inverters have been matched with include CHINT
and Eastron,The recommended models here are not all compatible models,It is recommended to
purchase smart meter from authorized distributors of Deye, otherwise it may not be able to be used due to
communication mismatch. The definition of the "Meter" port can be found in the Appendix part which is in
the end of this user manual.
GRID
L3
L2
N L1
Inverter
RS485A
RS485B
L1
L2
(1,4,7,10) L3 (3,6,9,10)
RS 485
CHINT meter
GRID
L3
L2
Inverter
N L1
8 7 6 5
RS485B
RS485A
GND
1 2 3 4 5 6 7 8
L1
L2 L3
L3 L2
L1
(1,2,3,4) (5,6,7,8)
B A G
5 6 7 8
RS 485
RS 485 B RS 485 A GND
Eastron meter
3.7.3 Meter connection with CTs
GRID
Inverter L2
L3
N L1
AC Breaker
RS485A RS485B
AC Breaker
CT1
CT2
CT3
Blue line
White line
Blue line
White line
3 6 9 10 13 14 16 17 19 21
L1
L2
(3,6,9,10) L3
CHINT meter
Phase C current =5.002A
Inverter L3
L2
N L1
RS485A
RS485B AC Breaker
GND
AC Breaker
NA LA L1 L2 L3 N
8 7 6 5 4 3 2 1
meter
CT1
CT2
9 1 0 11 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0
CT3
S1 S2 S1 S2 S1 S2
Black line
Red line
Black line
Red line
Black line
Note: the arrow direction
Red line towards the inverter
9 1 0 11 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0
3 PHASE 4 WIRE
P2 P1
L1
L2
P2 P1 S2 S1
L3
P2 P1 S2 S1
S2 S1
N
1 2 3 4 5 6 15 16 17 18 19 20
Grid voltage Auxiliary Current inputs
sampling power supply
1 2 3 4 5 6 7 8
14 13 12
RS 485
RS 485 A RS 485 B GND
Eastron meter
Meter connection
The conductor should be made of the same metal as the phase conductors.
Warning:
Inverter has built-in leakage current detection circuit,The type A RCD can be connected to
the inverter for protection according to the local laws and regulations.If an external leakage
current protection device is connected to the grid port of inverter, please refer to section
3.11, its operating current must be equal to 10mA/KVA or higher, for this series of inverter it
should be 800mA or higher, otherwise inverter may not work properly.
Load
L2 RCD L2
L3 L3
AC Breaker
Battery
PE or PE
DC Breaker Do not connect this terminal when the neutral
Load wire and PE wire are connected together.
Hybrid Inverter
CT
N N
N
L1 L1
CT1
L1 L2 L2 Grid
GEN L2 CT2
L3 L3
L3 CT3
PORT
PE AC Breaker AC Breaker
AC Breaker PE
3.10 Wiring diagram with neutral line grounded
Grid
PE
E-BAR E-BAR
N L1 L2 L3 PE
Home Loads
PV This diagram is an example for an application in which neutral is separated from the
PE in the distribution box.
For countries such as China, Germany,the Czech Republic, Italy, etc., please follow local
DC Breaker
wiring reguations!
Distribution box
BMS
L1 L1
L2 L2
L3 RCD L3
Backup
N N
Battery Loads
PE or PE
DC Breaker
Backup
CT
800mA RCD (Recommended)
Hybrid Inverter
L1 L1
CT1
L1
L2 L2 L2
L3 RCD CT2
L3 L3
AC Breaker
Grid
CT3
GEN
PORT N N N
PE PE
PE On-Grid
3.11 Wiring diagram with neutral line ungrounded
L1 L2 L3 N PE
Home Loads
3.12 Typical application diagram of on-grid system
Inverter Ground
Backup Load
SHUT DOWN
B B
Ground
Inverter
Note: The idle parallel ports of the first and last inverters
need to be plugged in with matching resistors.
Inverter
OFF ON
Up To go to previous selection
0 0.00 80 0 35.1 80
KW KW
ON
0% 74%
0 -35.0
KW
80 0 0.00
KW
80
1.The icon at the center of the screen indicates whether the system is under normal operation
or not, displaying "ON" for normal status or displaying a code like "Comm./F01-F64" for
communication errors or other errors. Please refer to the Error code list of alarms and errors in
chapter 8 to find out solutions about the error.
2.At the top-center of the screen is the date and local time that must be set during
commissioning.
3.System Setup Icon, Press this set button,you can enter into the system setup screen which
including Basic Setting, Battery Setting , Grid Setting, System Work Mode, Generator
Port Use, Advanced Function and Device info.
4.The main screen includes the icons for PV(left up), grid (right up), load (right bottom)
and battery (left bottom). It also displays the energy flow direction by moving dots. When the
power is approaching to a high level, the color on the panels will change from green to red,
showing vividly the system status on the main screen.
Inverter Page
Main Screen
Battery Page BMS Page
Battery Setting
Grid Setting
System Setup
Gen Port Use
Basic Setting
Advanced Function
Device info
5.2 Detail page
Click the icons on main screen of LCD display, you can enter the detail pages of "Solar",
"Inverter","Load","Grid" and "Batt".
Solar This is Solar Panel detail page.
Today=8.0 KWH ③
Power: 1560W
Total =12.00 KWH Energy Press the "Energy "button will enter into the power
① curve page.
1166w 1244w
50Hz
-81w
50Hz
① This is Inverter detail page.
L1N: 221v
L1N: 222v
0w L2N: 229v
0.8A L1N: 222v
5.0A L2N: 230v
0.1A
0.1A
① DC/AC Inverter module:
L2N: 229v 1166w L3N: 229v 0.9A L3N: 223v 0.1A Voltage, Current, Power of each Phase.
L3N: 225v 0w HM: LD: INV_P: AC-T: Temperature near DC/AC inverter module.
-10W 28W -30W
Load 5W 1192W -26W AC_T:
0W 24W -25W 38.8C
21w
0w 0w Grid Inverter
150V 150V M1:0.00KW/ 0V/ 0.0A M2:0.00KW/ 0V/ 0.0A
-0.41A -0.41A M3:0.00KW/ 0V/ 0.0A M4:0.00KW/ 0V/ 0.0A
27.0C 27.0C M5:0.00KW/ 0V/ 0.0A M6:0.00KW/ 0V/ 0.0A
Battery PV 0.00KW
I:-0.09A I:0.00A
Li-BMS
Power: -50W Power: 0W LiBms2: Not matched
Temp:27.0C
Temp:25.0C Temp:-100.0C
Li-BMS Battery Voltage: 0.0V Battery capacity :0AH
Battery Current: 0.0A Battery Charge Voltage :0.0V
Battery Temp:-100.0C Charge current limit :0A
This is Battery detail page. SOC :0% Discharge current limit :0A
In the main screen of LCD display, click the icons of "Solar", "Grid" and "Load", you can enter
the detail pages of Solar power, Grid power and Load consumption. Click the "Energy" button
on the lower right corner of these detail pages, you can enter the curve page. Using PV as an
example for illustration below.
0 0.00 80 0 35.1 80
KW KW
ON
Today=0.0 KWH
0% 74% Power: 0W
Total =0.00 KWH
Energy
0 -35.0
KW
80 0 0.00
KW
80
CANCEL Day Month Year Total CANCEL Day Month Year Total
System Solar Power:Year System Solar Power:Total
KWh 2022 2000KWh TOTAL
200 2000
160 1600
120 1200
80 800
40 400
0
1 2 3 4 5 6 7 8 9 10 11 12 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
CANCEL Day Month Year Total CANCEL Day Month Year Total
Solar power curve for daily, monthly, yearly and total can be roughly checked on the LCD, for more
accuracy power generation, please check on the monitoring system. Click the up and down buttons
below the LCD screen to view the power curves of different time periods. The operation of checking
the grid power and load power is similar to the above operation.
System Setup
This is System Setup page.
Basic Advanced
Setting Function Device Info.
5.5 Basic Setting Menu
Basic Setting
Time Syncs: Enable the inverter to automatically
Time Syncs Beep Auto Dim synchronize cloud platform time.
Beep: Used to turn on or off the beep sound in inverter's
Year Month Day Basic alarm status.
Auto Dim: Used to automatically adjust the brightness of
2019 03 17
Set1
PassWord
When we select the "factory reset" or"Lock out all changes",
the system will require us to enter a password first to
X--X--X--X DEL confirm the operation.
7 8 9
CANCEL 0 OK
Basic Setting
1. Click the down arrow on the left side of the "Basic Set1"
page to enter the "Basic Set2" page;
2. On the "Basic Set2" page, you can set the display
Basic language of the LCD screen as needed. Click the "UP" and
Language Select Set2
"DOWN" buttons below the LCD screen to switch
Polish language options. The current available options are:
English, German, Polish, Hungarian, Spanish, Czech,
Pack Version: 1004 Ukrainian.
3. After switching to the desired language, click on the
check mark icon in the bottom right corner of the page to
save the settings.
This is Grid Charge, you need select. ② Gen Max Run Time: It indicates the longest time
Start =30%: When battery SOC or voltage Generator can run in one day, when time is up, the
drop to this set value, inverter will start the Generator will be turned off. 24H means that it does
generator connected to the grid port not shut down all the time.
automatically to charge the battery.
Gen Down Time: It indicates the rest time of the
A = 80A: maximum charging current when
only use the power fed from the grid port of Generator before the inverter start it again.
inverter as the power source, which means
using the power of grid or the power of
generator connected to the grid port.
Grid Charge: It's allowed to use power fed
from the grid port, which includes grid or
generator connected to the grid port, to
charge the battery.
Grid Signal: When a generator is connected
to the grid port of hybrid inverter, this 'Grid
signal' can be used to control the dry contact
to start or stop the generator.
01/19/2024 01:23:02 PM Fri When the "GEN signal" is active, the generator icon
will appear on the main screen of inverter LCD
display.
Off grid
0 0.00 80 0 0.00 80
KW KW
ON
0% 74%
Signal 0.00
on KW
0 0.14
KW
80 0 0.00
KW 80
Generator
Click the generator icon on the main screen, you can enter the
Power: 6000W Today=10 KWH 'Generator' detail page. The information contained on this
page is as follows:
(1) How much power is using from generator;
Total =10 KWH
V_L1: 230V P_L1: 2KW (2) How much energy has used from generator in today or in
P_L2: 2KW total;
(3) The output voltage and power on each phase of generator.
V_L2: 230V
V_L3: 230V P_L3: 2KW
Battery Setting When the "Lithium" mode is selected, the content on the "Batt Set 3"
page is shown in the figure on the left.
Lithium Mode: This is the BMS communication protocol code which
can be confirmed on the "Deye Approved Battery list" based on the
Lithium Mode 00 battery model you are using.
Shutdown:Be valid in Off-grid mode, battery can discharge to this
Batt
SOC, then the DC/AC inverter module of this inverter will be shut
down and the solar power can only be used to charge the battery.
Shutdown 10% Set3
Low Batt :Be valid in On-grid mode, when the 'Grid charge' has
been checked and the set target battery SOC on 'Time of Use' page
isn't less than the "Low Batt" value, the battery SOC will remain
Low Batt 20%
above the value of "Low Batt" .
Restart 40% Restart :Be valid in Off-grid mode, after the DC/AC inverter module
of this inverter is shut down, the PV power can only be used to
charge the battery. After the battery SOC has resumed to this
"Restart" value, the DC/AC inverter module will restart to output AC
power.
Battery Setting When the "Use Batt V" mode is selected, the content on the "Batt
Set 3" page is shown in the figure on the left.
Float voltage: Battery full charge voltage.
Shutdown : Be valid in Off-grid mode, battery can discharge to
this voltage, then the DC/AC inverter module of this inverter will be
Float V 536V
shut down and the solar power can only be used to charge the
battery.
Batt
Set3
Low Batt :Be valid in On-grid mode, when the 'Grid charge' has
Shutdown 450V
been checked and the set target battery voltage on 'Time of Use'
Low Batt 470V page isn't less than the "Low Batt" value, the battery voltage will
remain above the value of "Low Batt" .
Restart :Be valid in Off-grid mode, after the DC/AC inverter
Restart 500V module of this inverter is shut down, the PV power can only be
used to charge the battery. After the battery voltage has resumed
to this "Restart" value, the DC/AC inverter module will restart to
output AC power.
1. Solar Panels.
2. Batteries(when the actual battery SOC is higher than
Max Sell Power 32000 Zero-export Power 20
Zero Export To Load: Hybrid inverter will only provide power to the backup load connected. The hybrid inverter
will neither provide power to the home load nor sell power to grid,if the "solar sell" behind is not enabled. The
built-in CT will detect power flowing back to the grid and will reduce the power of the inverter only to supply the
backup load and charge the battery. Load consumption=Backup load.
Battery
Zero Export To CT: Hybrid inverter will not only provide power to the backup load connected but also give power
to the home load connected. If PV power and battery power is insufficient, it will take grid energy as supplement.
The hybrid inverter will not sell power to grid,if the "solar sell" behind is not enabled. In this mode, external CTs or
smart meter must be installed. For the installation method of CTS or smart meter, please refer to the section 3.7 .
The external CTs or smart meter will detect power flowing back to the grid and will reduce the power of the inverter
only to supply the backup load, home load and charge the battery. Load consumption=Backup load+home load.
CT
Battery
Solar Sell: "Solar sell" is selectable for Zero export to load or Zero export to CT. When activating it, the surplus of
the energy generated by the PV can be sold back to grid. When it is active, the energy generated by the PV array
will first power the loads or charge the battery, and then export to grid.
Max. sell power: Maximum power allowed to flow to grid.
Zero-export Power: This parameter will ensure the zero-export by taking from the grid some small amount of
energy that has been set with this value. It is recommended to set it as 20-100W to ensure the hybrid inverter won'
t feed power to grid.
Energy Pattern: Priority of PV power usage. When "Grid charge" is enabled, the default energy pattern is "Load
First", this setting will be invalid.
Batt First: PV power is firstly used to charge the battery, and the excess power will be used to power the load. If
PV power is insufficient, grid will make supplement for battery and load simultaneously.
Load First: PV power is firstly used to power the load, and the excess power will be used to charge the battery. If
PV power is insufficient, Grid will provide power to load.
Grid Peak-shaving: when it is active, grid power will be limited within the set value. If the grid peak-shaving
power plus PV power plus battery power cannot meet the power consumption of the load after peak-shaving, the
grid peak-shaving will be invalid, and the power taken from the grid can exceed this set value.
System Work Mode Time of use: it is used to program when to use grid or
generator to charge the battery, and when to discharge
Grid the battery to power the load. Only tick "Time Of Use"
then the follow items (Grid, charge, time, power etc.)
Time Of Use
Charge Gen Time Power Batt
Work will take effect.
00:00 05:00 32000 160V Mode2 Note: when in selling first mode and click time of use, the battery
power can be sold into grid.
05:00 08:00 32000 160V Grid Charge:uses the grid to charge the battery in the selected
period of time.
Gen charge: utilize diesel generator to charge the battery in the
09:00 10:00 32000 160V
10:00 15:00 32000 160V selected period of time.
Time: real time, from 0:00 to 0:00 the next day.
15:00 18:00 32000 160V Note: For more flexible and controllable use of batteries, it is
recommended to enable the "Time Of Use" function.When the
inverter is operating in on-grid mode and "Time Of Use" is not
18:00 00:00 32000 160V
enabled, the inverter can charge normally, but only discharge to
provide the inverter's self-consumption power, without discharging to
power the loads.
Battery Setting Power: Max. discharge power of battery allowed.
Batt(V or SOC %): The target value of battery voltage or SOC during
the current time period. If the actual SOC or voltage of the battery is
Start 30% 30% lower than the target value, the battery needs to be charged. If there
is a energy source like solar power or grid, the battery will be
Batt charged; If the actual SOC or voltage of the battery is higher than the
target value, the battery can discharge, and when the solar power is
A 80A 80A
Set2
not enough to power the load or the "Selling First "is enabled, the
battery will discharge.
Gen Charge Grid Charge
Assuming that at the end of the previous time period, the actual
Gen Signal Grid Signal battery level reaches or approaches the target value of the previous
time period.
Gen Max Run Time 0.0 hours For example
During 00:00-05:00,
Gen Down Time 0.5 hours if battery SOC is lower than 80%, it will use grid to charge the
battery until battery SOC reaches 80%.
During 05:00-08:00,
System Work Mode if battery SOC is higher than 40%, hybrid inverter will discharge
the battery until the SOC reaches 40%. At the same time,
② Grid if battery SOC is lower than 40%, then grid will charge the
Time Of Use battery SOC to 40%.
Charge Gen Time Power Batt During 08:00-10:00,
Work if battery SOC is higher than 40%, hybrid inverter will discharge
the battery until the SOC reaches 40%.
00:00 05:00 32000 80% Mode2
05:00 08:00 32000 40% During 10:00-15:00,
If battery SOC is lower than 80%, hybrid inverter will charge the
08:00 10:00 32000 40% battery until the SOC reaches 80%. If the PV power is sufficient, the
battery can be charged to 100%.
10:00 15:00 32000 80% During 15:00-18:00,
when battery SOC is higher than 40%, hybrid inverter will discharge
the battery until the SOC reaches 40%.
15:00 18:00 32000 40%
18:00 00:00 32000 35% During 18:00-00:00,
when battery SOC is higher than 35%, hybrid inverter will discharge
the battery until the SOC reaches 35%.
System Work Mode It allows users to choose which day to execute the
setting of "Time of Use".
Mon Tue Wed Thu Fri Sat Sun For example, the inverter will execute the time of use
Work page on Mon/Tue/Wed/Thu/Fri/Sat only.
Mode4
5.8 Grid Setting Menu
Grid Setting/Grid code selection Grid Mode:
General Standard、UL1741 & IEEE1547、CPUC RULE21、
Grid Mode General Standard 0/23 SRD-UL-1741、CEI_0_21_Internal、EN50549_CZ-PPDS(>16A)、
Australia_A、Australia_B、Australia_C、AS4777_NewZealand、
Grid Frequency 50HZ Phase Type Grid VDE4105、OVE-Directive R25、EN50549_CZ_PPDS_L16A、
0/120/240 Set1 NRS097、G98、G99、EN50549_1_Norway_133V、
EN50549_1_Norway_230V、Japan_200VAC_3P3W、
60HZ
CEI_0_21_External、CEI_0_21_Areti、Japan_400VAC_3P3W、
0/240/120
Japan_415VAC_3P4W、EN50549_1_Switzerland.
Grid Level LN:220V/LL:380V(AC) Please follow the local grid code and then choose the
corresponding grid standard.
Grid level: there’re several voltage levels for the inverter
IT system-neutral is not grounded output voltage when it is in off-grid mode.
LN:220V/LL:380V(AC), LN:230V/LL:400V(AC).
IT system: If the grid system is IT system, then please enable this option. All the live lines of IT system are insulated
from ground, and the neutral point of the IT system is grounded through high impedance or not grounded (as shown
in the following figure).
Rz: Large resistance ground resistor. Or the system IT system-neutral is not grounded
doesn’t have Neutral line
HV1 265.0V -- 0.10s HF1 51.50Hz -- 0.10s HF1: Level 1 over frequency protection point;
HF2: Level 2 over frequency protection point;
HF3: Level 3 over frequency protection point.
LV1 185.0V -- 0.10s LF1 48.00Hz -- 0.10s
Start delay F 0.00s Stop delay F 0.00s Droop F of 40%. And then when grid system frequency
is less than 50.1Hz, the inverter will stop decreasing
Under frequency Droop F 40%PE/Hz output power.
For the detailed setup values, please follow the local
grid code.
Start freq F 49.80Hz Stop freq F 49.80Hz
Grid Setting/V(W) V(Q) V(W): It is used to adjust the inverter's active power
according to the set grid voltage.
V(W) V(Q) V(Q): It is used to adjust the inverter's reactive power
according to the set grid voltage.
These two functions are used to adjust inverter's output
Lock-in/Pn Lock-out/Pn
Grid
For example: V2=110%, P2=80%. When the grid voltage reaches 110% of the rated grid voltage,
inverter will reduce its active power output to 80% of the rated power.
For example: V1=94%, Q1=44%. When the grid voltage reaches 94% of the rated grid voltage,
inverter will output reactive power that accounts for 44% of the rated power.
For the detailed setup values, please follow the local grid code.
Grid Setting/P(Q) P(F) P(Q): It is used to adjust the output reactive power of
inverter according to the set active power.
P(PF): It is used to adjust the PF of inverter according
to the set active power.
P(Q) P(PF)
Grid Setting/LVRT LVRT/HVRT: When the voltage of the power grid reaches
the set HV or LV, the relay at the inverter grid port will
L/HVRT
remain closed for the set time to maintain stable grid
connection without tripping.
Grid
HV3 0% HV3_T 30.24s Set7
Micro Inv Input ON 154.0V Smart Load Port will switch off automatically.
Smart Load OFF Batt
• Battery SOC or voltage at which the Smart load will switch off.
Ml export to Grid cutoff
off-grid mode and the SOC or voltage of battery drops to this set
value, the relays on GEN port of hybrid inverter will turn to
SmartLoad Output On Grid always on
55.00Hz solar power and feed into hybrid inverter. When the hybrid inverter
operates in on-grid mode, this parameter will be invalid, the relays
OFF 95%
Micro Inv Input ON on GEN port of hybrid inverter will always be normally colsed(ON),
Grid-Tied inverter can operate normally.
100%
generator to the set rated power on "GEN PORT USE" page, the rest of
DRM 20001 CT Ratio power consumption will be provided by inverter to ensure that the
generator will not overload.
DRM: Demand response mode, receive external commands for active
power scheduling and reactive power scheduling.
Signal Island Mode
Backup Delay: When the grid cuts off, the inverter will output power
Asymmetric phase feeding CEI Report
after the set time.
For example, backup delay: 600s. the inverter will give output power
after 600s when the grid cuts off.
Note: for some old FW version, this function is not available.
*Signal island mode: If "Signal island mode" is checked and When inverter is in off-grid mode, the relay on the Neutral line of
load port will switch on, then the N line of load port will bind to ground.
Asymmetric phase feeding: When the loads connected to the Load port have an unbalanced distribution on the three phases
and the inverter is working in on-grid mode, enabling this function will ensure an equal power absorption from the three phases
of grid.
Parallel: Enable this function when several same model hybrid inverters are
Advanced Function connecting in parallel.
Master: Select any hybrid inverter in the parallel system as the master
Parallel Modbus SN Baud Rate
inverter, and the master inverter needs to manage the working mode of the
parallel system.
Slave: Set the other inverters managed by the master inverter as slave
Master 00 0000
Paral.
inverter.
Modbus SN: The Modbus address of each inverter, should be different.
Slave Set3
Baud Rate: The rate at which inverter transmits data.
Ex_Meter For CT: when using zero-export to CT mode, the hybrid inverter
can select EX_Meter For CT functionand use the different meters.e.g.CHNT
EX_Meter For CT Grid Tie Meter2
6. Mode
Mode I:Basic
AC cable DC cable COM cable
Solar
CT
Battery
Grid
Grid
CT
Battery
Generator
Note: When using the GEN port as the "generator input" port, the
relays on the grid port and GEN port of the inverter will not be
closed simultaneously. The relays on the GEN port will only be
closed when the inverter is running in off-grid mode.
Mode III: With Smart-Load
AC cable DC cable
Grid
CT
Battery
Smart Load
Grid
CT
Battery
On-Grid Inverter
The 1st priority power of the system is always the PV power, then 2nd and
3rd priority power will be the ba�ery bank or grid according to the se�ngs.
The last power backup will be the Generator if it is available.
7. Warranty
As to Warranty terms, please refer to 《General Warranty Agreement - DEYE》.
Under the guidance of our company, customers return our products so that our company can
provide service of maintenance or replacement of products of the same value. Customers need to
pay the necessary freight and other related costs. Any replacement or repair of the product will
cover the remaining warranty period of the product. If any part of the product or product is
replaced by the company itself during the warranty period, all rights and interests of the
replacement product or component belong to the company.
Factory warranty does not include damage due to the following reasons:
· Damage during transportation of equipment;
· Damage caused by incorrect installation or commissioning;
· Damage caused by failure to comply with operation instructions, installation instructions or
maintenance instructions;
· Damage caused by attempts to modify, alter or repair products;
· Damage caused by incorrect use or operation;
· Damage caused by insufficient ventilation of equipment;
· Damage caused by failure to comply with applicable safety standards or regulations;
· Damage caused by natural disasters or force majeure (e.g. floods, lightning, overvoltage,
storms, fires, etc.)
In addition, normal wear or any other failure will not affect the basic operation of the product.
Any external scratches, stains or natural mechanical wear does not represent a defect in the
product.
8. Troubleshooting
Perform troubleshooting according to the solutions in the table below. Contact the
after-sales service if these methods do not work.
Collect the information below before contacting the after-sales service, so that the problems
can be solved quickly.
• Inverter information like serial number, firmware version, installation date, fault time, fault
frequency, etc.
• Installation environment, including weather conditions, whether the PV modules are
sheltered or shadowed, etc. It is recommended to provide some photos and videos to assist
in analyzing the problem.
• Utility grid situation.
Error code Description Solutions
W�� Reserved
F�� EEPROM_Read_Failure Restart the inverter � times and restore the factory settings.
F�� EEPROM_Write_Failure Restart the inverter � times and restore the factory settings
F�� IGBT_Failure Restart the inverter � times and restore the factory settings.
F�� AC_MainContactor_Failure Restart the inverter � times and restore the factory settings.
F�� AC_SlaveContactor_Failure Restart the inverter � times and restore the factory settings.
F�� DC_OverCurr_Failure Restart the inverter � times and restore the factory settings.
F�� Tz_Integ_Fault Restart the inverter � times and restore the factory settings.
Error code Description Solutions
Remotely shutdown
F�� Tz_EmergStop_Fault
It means the inverter is remotely controlled.
F�� DC_Feedback_Fault Restart the inverter � times and restore the factory settings.
F�� DC_Insulation_Fault Restart the inverter � times and restore the factory settings.
F�� DCIOver_M�_Fault Restart the inverter � times and restore the factory settings.
F�� AC_MainContactor_Fault Restart the inverter � times and restore the factory settings.
F�� DCIOver_M�_Fault Restart the inverter � times and restore the factory settings.
F�� AC_Overload_Fault Check the backup load connection, make sure it is within the
allowed power range.
Error code Description Solutions
F�� Reserved
F�� Reserved
F�� Reserved
F�� Reserved
F�� Reserved
F�� AC_U_GridCurr_DcHigh_Fault Restart the inverter � times and restore the factory settings.
F�� AC_V_GridCurr_DcHigh_Fault Restart the inverter � times and restore the factory settings.
Error code Description Solutions
F�� Battery_Temp_High_Fault Check wether the temperature data of BMS is too high.
F�� Reserved
10. Appendix I
Definition of RJ45 Ports
RS���
No. RS���
�
� TX
� RX
�
� D-GND
�
�
DB� (RS���)
�
� ��Vdc
USB
DRMIt is used to accept the external control command.
Definition of RJ45 Port Pin for DRM
PIN 1 DI 1
K1 0%
PIN 2 DI 2
K2 30%
PIN 3 DI 3
K3 60%
PIN 4 DI 4
K4 100%
PIN 5 REF
15K
PIN 6 GND
Inverter RCR
1 2 3 4 5 6 7 8
K4
K3
K2
K1
- �� -
11. Appendix II
1. Split Core Current Transformer (CT) dimension: (mm)
2. Secondary output cable length is 4m.
12. Appendix III
CAN communication to
BMS1 port of the hybrid
inverter
DC combiner box
CAN to BMS1 of
the inverter
CAN(parallel)
Master Slave
CAN communication to
BMS1 port of the hybrid
inverter
CAN to BMS1 of
the inverter
DC combiner box
CAN(parallel)
Master Slave
NINGBO DEYE INVERTER TECHNOLOGY CO., LTD. confirms herewith that the products
described in this document are in compliance with the fundamental requirements and other
relevant provisions of the above mentioned directives. The entire EU Declaration of Conformity
and certificate can be found at https://www.deyeinverter.com/download/#hybrid-inverter-�.
V1.3.1, 2025-04-03