Hitachi ABB Relion Catalogue A4 Web-Spread
Hitachi ABB Relion Catalogue A4 Web-Spread
and monitoring
solutions enable deep insight into 010 – 011 Relion® 670 & 650 series –
Substation evolution.
01
Classical Digital Digital
Network Level
From electro-mechanical relays to
digital substation. Network Management Network Management
Network
Management
Asset Performance
Management
Evolution continues.
Station Level
HMI + Control Board / Event Recording HMI Gateway HMI Gateway
01 Substation evolution The main objective of the utilities is to provide New challenges are arising for the customers,
from classical to Hitachi
ABB Power Grids Ability
affordable electric power of a good quality, and it is the manufacturers task to facilitate usability
Digital Substation continuously and preferably for profit. of the equipment, in order to leverage the maximum Copper Cables IEC 61850 IEC 61850
of all assets in the power system.
Reliability of the power system protection, as well
monitoring, control and asset management have Digital substation is the way forward.
significantly improved from the early days of
Bay Level
electromechanical relays to modern IEDs - leading to
Protection
higher availability. and control
IEDs
Hard-wired Protection & Control Protection & Control IEDs
Process
interface
units in digital
Conventional Conventional marshalling
Marshalling Cubicle Marshalling Cubicle cubicle
Process Level
Conventional AIS bay Conventional AIS bay DCB with FOCS and
Motor Drive
6 RELION® PROTECTION AND CONTROL POWER INFR ASTRUCTURE 7
Grid evolution.
Changes in the grid topology and
business model.
Trends in modern power grids.
02 Traditional and The trends that are having impact on transmission The requirements and expectations on substation
modern day grid
grid technology: protection and control will increase. Evolving grids
• Renewable penetration have direct impact on protection and control systems.
• HVDC
• FACTS
• Phase-shifting transformers
• Micro-grids
• Nano-grids
• Electrical mobility
• Charging infrastructure for electric vehicles
• Digital transformation of transportation
• Digitalization of power grids
Relion® the power of one solution. Relion 670 and 650 series.
For protection, control and monitoring. The power of one.
To cope with any situation, a modern protection IED needs Hitachi ABB Power Grids' high performing series of
to be configurable to fit within its intended application area. intelligent electronic devices (IEDs)
Hitachi ABB Power Grids' solution to this requirement is the Relion® series of IEDs.
The Relion series offers a standardized library of the smart grid, information is of vital importance, so 03 Relion 670 Family Relion 670 series
functionality on a high performance, common advanced and accurate PMU (phasor measurement 04 Relion 650
hardware architecture, and provides the flexibility and unit) functionality will present you with the information • A flexible solution for every application
configurability to suit any application area. you need to make your smart grid truly smart. • Offers solution for the most demanding
requirements of protection and control applications
The Relion series of devices cover the complete With its proven reliability, high accuracy and high • Ordering as pre-configured or customized
protection, control and monitoring needs of your performance operation, the Relion family devices can - Three different hardware casings
power infrastructure. be used for the most demanding applications for your (1/1, 3/4 and 1/2 19”)
power system network. - Advanced protection and control features
Advanced control capabilities and system modeling, - Multiple objects
according to IEC 61850 will give you new ways to - High level of functional integration
design and dynamically operate your network. And in
03
05 Line protection
performance
Differential protection is easier to current that is measured to flow into the line should
also be measured to come out.
characteristics
integrate and delivers more
consistent performance compared Differential protection is easier to integrate into a
protection philosophy than distance protection, as it
to distance protection, at the cost of is a unit protection. It delivers more consistent
an increased hardware and performance, at the cost of an increased hardware
and communication dependency. Some form of high
communication dependency. bandwidth, low latency communication is required in
between the line ends to exchange analog
Distance protection is and remains by far the main information for the line differential algorithm to 05
REL670 REL650 RED670 RED650
protection principle for overhead lines and cables. It process. Typically, this is a direct fiber optic cable, Distance protection
is reliable, fast and largely manages to eliminate the but communication over MPLS-TP, SDH, PDH or Speed < 1 cycle 1 1/2 cycle < 1 cycle 1 1/2 cycle
variable system quantities of load and supply out of SONET network is also possible.
the protection calculation. Power swing blocking
Additional functions Out of step and pole slip detection
Relion RED670 and RED650 offer either a dedicated Phase preference logic
Distance protection is in its core an impedance line differential protection IED, or a so called multi- Series compensated lines X Not available X Not available
measurement, comparing a known line impedance function device, whereby distance protection is Differential protection
against a measured system impedance. integrated in the same IED as well. Speed < 1 cycle 1 1/2 cycle
Maximum line ends 5 3
A modern distance protection IED (Intelligent
In-zone transformer X X
Electronic Device) must deal with many more Not available
Short range communication to multiplexer X X
features though; phase selection, load
Communication speed 64 kbit/s or 2 Mbit/s 64 kbit/s
encroachment, power swing detection, scheme
communication, phasor measurement, monitoring, Direct fiber communication range Up to ~ 110 km Up to ~ 60 km
06 Line distance The REL670 can offer more integrated functionality addition includes synchrophasors (PMU)
protection options
compared to the REL650, such as synchrophasors functionality by default
07 Ordering options (PMU) functionality. In order to facilitate this
for line distance protection
additional functionality, there is a larger and more
flexible choice in available hardware compared to the REL650 comes in two different variants
REL650 as well. • REL650-A11 offers a 7 zone distance protection
function with mho and quad characteristic, load
REL670 and REL650 include features such as: encroachment, power swing detection, out of step
• Distance protection with 7 independent zones, for protection, overcurrent, frequency and thermal
quadrilateral and mho characteristics with 2 fixed overload protection. It also includes breaker failure
and 5 settable directional zones protection, autoreclose and synchrocheck 06 REL670 REL650
• Settable directional sector limits functionality Distance protection X X
• Power swing detection, blocking and unblocking, • REL650-A12 offers everything included in Speed < 1 cycle 1 1/2 cycle
out-of-step and pole slip detection REL650-A11, and additionally phase preference Characteristic Mho, Quad Mho, Quad
• Phase preference logic for the correct tripping of logic, transient earth fault protection, stub Zones 2 instances, 7 zones each 1 instance, 7 zones
multiple phase-to-earth faults in compensated protection among few others. Phase preference Tripping 1ph/3ph 1ph/3ph
networks logic functionality is required for a correct phase Load encroachment X X
• Back-up current, voltage and frequency protection selection in high impedance or resonance earthed
Power swing blocking X X
• Switchgear control functionality networks
Back-up protection Basic and additions as options Basic
• Newly incorporated apparatus control functionality
Control of entire bay Optional Single bay, max 5 ob- jects (1 CB)
for a single bay (in both variants) widens scope of
REL670 comes in four different variants deployment
• REL670-A41 offers a 7 zone distance protection
function with mho and quad characteristic, subcycle 07 REL670-A41 REL670-A42 REL670-B42 REL670-D42 REL650-A11 REL650-A12
tripping times, load encroachment, phase High speed distance protection X X X X
preference logic, power swing detection, blocking Distance protection X X
and unblocking. Overcurrent, overvoltage, Phase preference logic X X
undervoltage, frequency and thermal overload Back-up protection Basic and additions as options Basic
protection are available as backup protection
Single bay, max 5 objects
functions and included as basic or optional Control of entire bay Optional
(1 CB)
functionality. It also includes breaker failure
protection, autoreclose and synchrocheck Double Single breaker Single bay, max 5 objects
Configuration Single breaker
functionality. breaker with PMU (1 CB)
08 Line differential Line differential protection offers an easy, accurate RED670 and RED650 include such features as:
protection options
and secure alternative to line distance protection in • Differential protection from 3 to 5 line ends, with up
09 Ordering options line protection applications, but requires to two in-zone transformers
for line differential
protection
communication between the line ends. • Dedicated IED communication, or multiplexer
support
Relion RED670 and RED650 offer line differential • Back-up current, voltage and frequency protection
protection and the option for line and cable distance
protection in the same device. With its high In addition, RED670 can include all the functionality
RED670 comes in four variants RED650 comes in one variant
performance, high bandwidth and low latency available in REL670, resulting in a single device
• RED670-B33 offers 2 – 5 line ends differential • RED650-A11 offers a 3 ended line differential
communication channel, RED670 delivers subcycle capable of both line differential and line distance
protection with the possibility for increased protection function, with an option for an inzone
trip times in both its differential and distance protection.
performance over a 2 Mbit data link, improving trip transformer. It also offers a 7 zone distance
protection functions.
time performance. protection function with mho and quad
• RED670-A42 offers a high speed differential characteristic, load encroachment, power swing
RED650 provides a predefined, preconfigured variant
protection with sub-cycle trip times, and includes detection, out of step protection, overcurrent,
with a small form factor and a standardized
overcurrent, voltage, frequency and thermal frequency and thermal overload protection. It
application solution.
overload protection. These are included as basic or includes breaker failure protection, autoreclose and
optional functionality. It also includes breaker synchrocheck functionality. It is also equipped with
RED670 and RED650 can either be outfitted with
failure protection, autoreclose and synchrocheck control functionality for a maximum of 5 objects
their own dedicated long/mediumrange
functionality. including 1 CB.
communication module, or use a short-range
• RED670-B42 is equal to the RED670-A42, but is
communication channel to a multiplexer so that an
intended for 1 ½ or double breaker configurations.
independent communication network can be used.
• RED670-C42 is equal to RED670-A42, and
includes the high speed, sub cycle distance
protection as the backup functionality to the
existing high speed line differential protection.
protection, enabling high-speed back-up tripping of REC670 offers a protection solution for the complete Synchrocheck X X X X X X
surrounding breakers, and retripping of the target system irrespective of the complex arrangement of Autoreclose X X X X X X
breaker. REQ650 breaker protection is the ideal the SCB. In this case, an overall SCB protection as IEEE 1344 and IEC/IEEE
Optional
60255.118
choice for refurbishment projects, where old well as individual unit protection is offered making it a
IEC 61850-9-2 8 SV streams (Optional) 4 SV streams (Optional)
protection relays need to be replaced. versatile and complete solution.
10
REC670* REC650**
Circuit breaker, disconnector and earthing
Up to 6 circuit breakers and 24 switches Up to 1 circuit breaker and 9 switches
switch control
Generic switch control Up to 150 double point objects Up to 30 double point objects
IEC 61850 Edition 1 and 2 Edition 1 and 2
Reservation With or without confirmation
Interlocking Pre-defined or user defined
Operation Direct with normal security and select-before-operate with enhanced security
Shunt capacitor bank protection Optional
Busbar protection.
Relion® REB670, REB650 and
REB500
The heart of a substation is its busbar configuration. Although typically
designed in single or double busbar systems, there are many other
designs, each with specific advantages. Hitachi ABB Power Grids' Relion
family of IEDs provides the flexibility to adjust to any busbar configuration,
and delivers unrivaled reliability and performance.
15 Busbar protection Traditional busbar differential protection employs a size and extendibility requirements of the protection
variants
high impedance system. This relatively simple IED – each bay requires a certain number of IOs,
16 Ordering options overvoltage or overcurrent function requires several which must fit in a single device and be wired from
for busbar protection
supporting functions in a modern substation, such as the bay to the centralized IED. This can be difficult
advanced disturbance recording and communication from a station topology point of view, particularly in
capabilities. large, open-air substations.
17 Available phasor Enhanced monitoring enables power network Depending on the product, these devices can
measurements
per product type
operators to take fast remedial action and use transmit up to 32 analog phasors in two different data
existing power systems more efficiently. Better streams. The high accuracy of voltage and current
18 Ordering options
for standalone phasor
information supporting fast, reliable emergency measurements eliminates the need for any external
measurement units actions reduces the need for relatively high measurement transducers, which makes the 670
transmission margins made necessary by potential series ideal for use in all types of Phasor
power system disturbances. Measurement Unit (PMU)-based applications.
Phasor data 16 32 Up to 32
Analog data 8, up to 24 16, up to 24 Up to 24
Binary data 8, up to 24 16, up to 24 Up to 24
System protection Basic and optional Optional
30 RELION® PROTECTION AND CONTROL R A I L W AY S 31
Rapid urbanization plus the urgent need to reduce Relion RER670 applications include protection, Line protection Catenary protection Transformer protection Control and monitoring
carbon dioxide emissions are driving substantial new control and monitoring of AT and BT catenary • Line distance protection • Catenary distance • Transformer • Control for up
interest and investment in the transportation sector. systems, single and double phase power • Scheme communication protection for 2 catenaries differential protection to 15 apparatuses
Because of their specialized nature, traction power transformers, single and double phase transmission • Fault location • Scheme communication • Transformer under • Tap changer control
protection and control systems can be challenging. lines, and incorporate control and communication • Back-up protection • Fault location impedance protection and supervision
functionality based on IEC 61850 edition 2. The • Synchrocheck • Back-up protection • Restricted earth fault • Circuit breaker monitoring
With the Relion RER670, Hitachi ABB Power Grids RER670 is designed to be used on 16.7 Hz, 50 Hz and auto-reclose • Synchrocheck protection
offers a single solution encompassing the entire and 60 Hz networks. and auto-reclose • Transformer tank
scope of railway power delivery; transmission, overcurrent protection
transformation and delivery. In a single device it With over 150000 Relion devices installed globally, • Transformer energization
supports single and two phase systems in isolated, RER670 has a robust family history control (16.7 Hz)
compensated or solidly earthed networks. and is a testament of the trust that has enabled • Back-up protection
numerous users to secure their power infrastructure. • Synchrocheck
• Monitoring of power system
harmonics
32 RELION® PROTECTION AND CONTROL R A I L W AY S 33
Railway solution. 19
Relion® RER670
Transformer protection for Simplified distance
reliable, high-performance protection for your catenary
RER670 is used for the protection, control and monitoring of transmission and flexible applications infrastructure
Transformer
Transformer Line Catenary Back-up Transformer tank Apparatus Auto- Synchro- Tap changer Harmonic I/U vector
energization
protection protection protection protection overcurrent control reclose check control monitoring shift
control
A51 B60 B70 C61 protection - C70 H37/H38 H52 H51 H53/H54 M27 supervision
H55
Transformer
X X X Optional Optional Optional X
protection
Catenary
X X X Optional X
protection
Relion® the power of one solution. Technology may change, but safety, quality and reliability remain the top requirements of
any power generation source. Whether the generation solution is large or small,
For power generation and renewables. centralized or distributed. In the end, every minute not spent producing energy has
tremendous financial and social consequences.
We deliver secure power generation solutions by continuously adapting Hitachi ABB Power Grids is at the forefront of the digitalization that is sweeping over the
to the active system situation, guaranteeing reliability and performance. power generation space. Our digital substation portfolio enables customers to build for
the future - today, while still enjoying the long-term Hitachi ABB Power Grids know-how
and support of the existing market.
Generator protection,
control and monitoring.
Relion® REG670
Relion REG670 Intelligent Electronic Device (IED) is a protection and
monitoring solution for generators, prime movers and step-up
transformers in hydro, pumped storage, gas fired, combined cycle, steam,
and cogeneration power plants.
21 Ordering options Supported by Hitachi ABB Power Grids' extensive No changes are necessary in the primary circuit or
for generator protection
experience in generator protection solutions, grounding resistor, so the design, installation and
REG670 achieves a new level of performance with commissioning of the protection system is simple and
up to 24 analog inputs, and the availability of fast. The third harmonic-based 100 percent stator
IEC61850-9-2 process bus technology. Main and earth fault protection utilizes the differential principle,
back-up protection can be integrated into one IED, providing high sensitivity and security to ensure
and additional components like transformers can be proper operation even in low load conditions.
included in the scope of protection. This reduces the
number of IEDs needed to protect the generating REG670 comes in 3 different
station. It also increases availability, simplifies pre-configured variants, as well as a
installation and reduces lifecycle costs relating to completely customizable solution:
commissioning, maintenance and spare parts. • REG670-A20 offers a solution for a typical
generator protection application with generator 21
REG670-A20 REG670-B30 REG670-C30
differential and back-up protection including 12
Using an advanced and innovative analog inputs transformers in a half 19” case size Generator differential and
Generator differential,
Generator and block
transformer differential and
filtering technique, REG670 can • REG670-B30 offers enhanced generator protection
backup protection
backup protection
transformer protection
Ethernet Switch
Gateway Gateway IED
With firewall With firewall
With the graphical display editor, you can easily The parameter setting tool allows you to change or
PCM600 IED PCM600 engineer the single line diagram according to the view all the parameters that an IED has, for all the
On substation network Connected to the switchgear arrangement for the IED HMI. setting groups. When reading the parameters from
IED front port
the IED, you can easily compare the values in the PC
with the ones in the IED. The graphical
representation of protection characteristics supports
you in visualizing, for example, distance protection
parameter setting.
It features convenient navigation, comprehensive Top 10 features of the integrated testing tool
presentation of application data, and support for ITT600 SA Explorer:
system consistency check both on-line and off-line. • Exploration of the complete IEC 61850
This allows anybody to use the same tool to analyze communication configuration of Hitachi ABB Power
and debug substation automation applications Grids' Relion protection and control IEDs and third-
regardless of their level of knowledge of IEC 61850 party IEDs.
communication. • Process event list with filtering and exporting
capabilities to support testing and commissioning
The ITT600 SA Explorer tool offers facilities for of the IEDs.
exploring and analyzing the communication • Many advanced functionalities, such as creation of
configuration of the protection and control IEDs dynamic datasets and editing of setting group
ITT600 SA Explorer visualizes up to two IEC 61850 When analyzing communication within a substation
(Intelligent Electronic Devices) and IEC 61850 values.
9-2 LE streams in a phasor diagram and as RMS automation system, ITT600 SA Explorer allows you
communication in substation automation systems, • Manual and automatic comparison of the system
values to allow engineers to evaluate primary to focus on the transmitted payload instead of
including GOOSE messages. Its versatile configuration description (.scd) and
currents and voltages sent by merging unit on-line. protocol details. You only need to concentrate on the
functionality eliminates the need for multiple testing • the deployed IED configurations to ensure
Off-line analysis for one stream includes an application values important to you while the tool’s
tools for different purposes, such as MMS browsers, • data consistency.
oscilloscope style view of the sampled values. unique built-in consistency check functionality takes
and protocol and Ethernet analyzers. • Documentation of the system configuration
care of the details.
revisions and IED firmware versions to keep track
The powerful features of ITT600 SA Explorer provide of the changes in the system.
test engineers with access to any IEC • Unique graphical visualization of the data flow
61850-compliant IED. The tool’s various functions within an IEC 61850-based system to verify and, if
allow efficient testing of the IED application and needed, optimize the data flow.
isolate the root cause of system communication • Visualization of GOOSE data in an Oscilloscope
problems. This significantly reduces testing and style view simultaneously for several IEDs showing
commissioning time. correlations and time measuring. This enables
faster debugging and troubleshooting.
ITT600 SA Explorer is easy to use, and does not • Support for decoding and analysis of substation
require the skills of a data communication specialist. automation-related Ethernet-based communication
By translating the complex terminology of protocols, such as IEC 61850-8-1, IEC 61850-9-2,
communication protocols into the standardized IEC IEC 60870-5-104, DNP 3.0/TCP and Modbus/TCP.
61850 language, it makes the essential information • Comparison of any two SCL-based (substation
available to all users. configuration description language) files at the
same time; for instance, comparison of two .icd
files to identify the differences between them.
• Visualization of IEC61850-9-2 LE sampled value
streams in a phasor and Oscilloscope style view.
Hitachi ABB Power Grids
Grid Automation Products
721 59 Västerås, Sweden
hitachiabb-powergrids.com
/protection-control