YDY 450/750
Building wires
Standard: PN-E-90068
Design
1. Copper conductor - round, solid class 1
2. PVC insulation
3. PVC outer sheath
Application
Cables are designed for fixed installation, indoors, in air, in and under plaster.
Installation of the product should only be carried out by personnel trained and qualified for electrical works. The product is
designed according to recognized standards. Applicable rules of installation must be applied at all times.
Properties
Rated voltage Uo/U 0,45/0,75 kV Self-extinguishing of one cable IEC 60332-1-2
Test voltage 2,5 (AC) kV CPR-Classification Eca
Maximal short-circuit conductor 160 °C UV stability no
temperature
Packaging drum, coil
Maximal operating conductor 70 °C
Certificate BBJ
temperature
RoHS yes
Temperature range from -30 up to 70 °C
REACH yes
Minimal temperature for laying 5 °C
and manipulation Declaration of Conformity EU yes
(CE)
Minimal storage temperature -30 °C
Colour of insulation HD 308 S2
Colour of sheath white
CTL00218 rev. 1
Page 1 of 2
YDY 450/750
Technical data
No. of cores and Diameter of Thickness - Thickness - Diameter Weight Minimal radius Max. effective Maximum
cross-section conductor nominal nominal sheath informative informative of bend resistance pulling force *1
insulation conductor at 20°C
mm² mm mm mm mm kg/km mm Ω/km N
2x1 1,1 0,8 1,2 7,6 83 31 18,1 100
2x1,5 1,3 0,8 1,2 8,1 99 32 12,1 150
2x2,5 1,7 0,8 1,2 8,9 127 36 7,41 250
2x10 3,5 1,1 1,3 13,8 363 55 1,83 1000
3x1 1,1 0,8 1,2 8,0 148 32 18,1 150
3x1,5 1,3 0,8 1,2 8,7 127 35 12,1 225
3x2,5 1,7 0,8 1,2 9,6 166 38 7,41 375
3x4 2,2 0,9 1,2 10,8 219 43 4,61 600
3x6 2,7 0,9 1,3 12,0 294 48 3,08 900
3x10 3,5 1,1 1,3 14,6 459 58 1,83 1500
4x1 1,1 0,8 1,2 8,7 119 35 18,1 200
4x1,5 1,3 0,8 1,2 9,3 144 37 12,1 300
4x2,5 1,7 0,8 1,2 10,2 192 41 7,41 500
4x4 2,2 0,9 1,3 12,4 296 50 4,61 800
4x6 2,7 0,9 1,3 13,6 389 54 3,08 1200
4x10 3,5 1,1 1,3 16,7 618 67 1,83 2000
5x1 1,1 0,8 1,2 9,5 144 38 18,1 250
5x1,5 1,3 0,8 1,2 10,5 183 42 12,1 375
5x2,5 1,7 0,8 1,2 11,2 239 45 7,41 625
5x4 2,2 0,9 1,3 13,6 360 54 4,61 1000
5x6 2,7 0,9 1,3 14,9 476 59 3,08 1500
5x10 3,5 1,1 1,3 17,7 725 71 1,83 2500
*1 Force is distributed over all cable conductors; Force for the pulling head or conductor grip
This data was prepared with due diligence and in good faith for informational purposes only and does not contain any representations, legally binding declarations or guarantees unless
otherwise agreed in writing by NKT. NKT® is a registered trademark of NKT. © The copyright of this document is vested in NKT. All rights reserved at the time of issuance.
CTL00218 rev. 1
Page 2 of 2