Reka - Ahxamk W 12 20 KV

The document provides specifications for the AHXAMK-W 12/20 (24) kV 3-core medium voltage cable, suitable for outdoor fixed installations and compliant with ISO standards. It details the cable's construction, temperature limits, technical information, and environmental profile, emphasizing its watertightness and halogen-free nature. The document also includes various technical data such as resistance, current ratings, and installation guidelines.

Uploaded by

sam oy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views6 pages

Reka - Ahxamk W 12 20 KV

The document provides specifications for the AHXAMK-W 12/20 (24) kV 3-core medium voltage cable, suitable for outdoor fixed installations and compliant with ISO standards. It details the cable's construction, temperature limits, technical information, and environmental profile, emphasizing its watertightness and halogen-free nature. The document also includes various technical data such as resistance, current ratings, and installation guidelines.

Uploaded by

sam oy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

ISO 45001, ISO 14001 and ISO 9001 certified

company REACH and RoHS compliant products

2025-09-17 17:01:20

AHXAMK-W 12/20 (24) kV 3-core

Medium voltage cable

12/20 (24) kV

Application
Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet
soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection.
The cable is not CPR-classified.

Design Temperature limits


Standards HD 620 10 F, SFS 5636 Max. conductor temperature °C 90
Product Environmental Profile PEP NXNS-00428-V01.01-EN Max. cond. temp. short circuit max. 5 s °C 250
(PEP/EPD)
Min. cable temperature during operation °C -50
Conductor Watertight, circular, stranded aluminium, EN/IEC
Min. cable temperature during handling °C -20
60228 class 2
Min. cable temperature during transport °C -40
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification White phase numbering: L1, L2, L3
Cable lay up Three sheathed cores are laid up around a bare
copper earth conductor
Inner covering Semiconducting waterswellable tape against
longitudinal water penetration

© Reka rights for changes reserved • www.rekacables.com • 1


ISO 45001, ISO 14001 and ISO 9001 certified
company REACH and RoHS compliant products

2025-09-17 17:01:20

Metal screen Polyethylene laminated aluminium foil, which acts


also as a radial water barrier
Oversheath UV-protected PE-plastic PELLD, Black
Longitudinal watertightness Semiconducting water swellable tape

© Reka rights for changes reserved • www.rekacables.com • 2


ISO 45001, ISO 14001 and ISO 9001 certified
company REACH and RoHS compliant products

2025-09-17 17:01:20

Technical information 3x50+35 Cu 3x70+35 Cu 3x95+35 Cu 3x120+35 Cu 3x150+35 Cu 3x185+35 Cu 3x240+35 Cu 3x240+70 Cu 3x300+35 Cu 3x300+70 Cu
Product code 1187002 1187003 1187004 1187005 1187006 1187007 1187018 1187008 1187019 1187009
Nominal diameter of a sheathed phase conductor mm 27 29 31 32 33 35 38 38 40 40
Nominal cross-sectional area of conductor mm² 50 70 95 120 150 185 240 240 300 300
Nominal diameter of conductor mm 8,0 9,5 11,1 12,6 13,9 15,6 17,8 17,8 19,8 19,8
Nominal thickness of conductor screen mm 0,5 0,5 0,5 0,5 0,5 0,5 0,5 0,5 0,5 0,5
Nominal thickness of insulation mm 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5
Nominal diameter over the insulation without insulation screen mm 19,3 20,7 22,4 23,4 25,1 27,0 29,2 29,2 31,0 31,0
Nominal thickness of insulation screen mm 0,5 0,5 0,5 0,5 0,5 0,5 0,5 0,5 0,5 0,5
Nominal diameter of earth conductor mm 6,9 6,9 6,9 6,9 6,9 6,9 6,9 9,9 6,9 9,9
Nominal thickness of PE-laminated aluminium foil mm 0,2 0,2 0,2 0,2 0,2 0,2 0,3 0,3 0,3 0,3
Nominal thickness of oversheath mm 2,8 2,8 2,9 2,9 2,9 3,0 3,1 3,1 3,2 3,2
(A1-A3) GWP emission kgCO2e/km 11834 13722 16169 18096 20518 23923 30538 31006 33815 35712
Nominal cable diameter mm 58,700 61,710 65,790 67,940 71,490 76,000 81,700 81,700 85,890 85,890
Nominal cable weight kg/km 2242,541 2531,084 2905,244 3199,835 3570,126 4090,594 4867,559 5173,356 5602,800 5892,800
Nominal weight of copper kg/m 0,302 0,302 0,302 0,302 0,302 0,302 0,302 0,592 0,302 0,592
Nominal weight of aluminium kg/m 0,383 0,545 0,735 0,953 1,149 1,461 1,901 1,902 2,428 2,428
Maximum forces during installation when pulling by
Max. pulling force by pulling-eye kN 7,5 10,5 14,3 18,0 20,0 20,0 20,0 20,0 20,0 20,0
Max. pulling force by pulling-stocking kN 2,3 3,2 4,3 5,4 6,8 8,3 8,5 8,5 8,5 8,5
Minimum bending radii
During handling and installation, phase conductor cm 41 44 47 48 50 53 57 57 60 60
During handling and installation, cable cm 70 74 79 82 86 91 98 98 103 103
In final installation, phase conductor cm 28 30 33 34 35 37 40 40 42 42
In final installation, cable cm 49 52 55 57 60 64 69 69 72 72
Minimum bending radii
During handling and installation, phase conductor m 0,41 0,44 0,47 0,48 0,50 0,53 0,57 0,57 0,60 0,60
During handling and installation, cable m 0,70 0,74 0,79 0,81 0,86 0,91 0,98 0,98 1,03 1,03
In final installation, phase conductor m 0,28 0,30 0,33 0,34 0,35 0,37 0,40 0,40 0,42 0,42
In final installation, cable m 0,49 0,52 0,55 0,57 0,60 0,64 0,69 0,69 0,72 0,72
DC resistance
Max. DC resistance of conductor at 20 °C Ω/km 0,641 0,443 0,320 0,253 0,206 0,164 0,125 0,125 0,100 0,100
Nominal DC resistance of PE-laminated aluminium foil 20 °C Ω/km 2,0 1,9 1,8 1,7 1,6 1,5 0,9 0,9 0,9 0,9

© Reka rights for changes reserved • www.rekacables.com • 3


ISO 45001, ISO 14001 and ISO 9001 certified
company REACH and RoHS compliant products

2025-09-17 17:01:20

Technical information 3x50+35 Cu 3x70+35 Cu 3x95+35 Cu 3x120+35 Cu 3x150+35 Cu 3x185+35 Cu 3x240+35 Cu 3x240+70 Cu 3x300+35 Cu 3x300+70 Cu
AC resistance of phase conductor, screen circuit closed
Conductor temperature 40 °C Ω/km 0,6927 0,4788 0,3460 0,2736 0,2229 0,1776 0,1356 0,1356 0,1088 0,1088
Conductor temperature 65 °C Ω/km 0,7573 0,5234 0,3782 0,2991 0,2436 0,1941 0,1482 0,1482 0,1188 0,1188
Conductor temperature 70 °C Ω/km 0,7702 0,5324 0,3846 0,3042 0,2478 0,1974 0,1507 0,1507 0,1208 0,1208
Conductor temperature 90 °C Ω/km 0,8219 0,5681 0,4104 0,3246 0,2644 0,2106 0,1607 0,1607 0,1288 0,1288
Inductance per phase
In flat formation, free space between cables equal to one cable diam 0,61 0,59 0,57 0,55 0,54 0,53 0,52 0,52 0,51 0,51
In trefoil formation, cables touching each other mH/km 0,43 0,41 0,39 0,37 0,36 0,35 0,34 0,34 0,32 0,32
Electrical values
Calculated operation capacitance µF/km 0,17 0,18 0,20 0,23 0,24 0,26 0,29 0,29 0,31 0,31
Calculated charging current with main voltage A/km 0,6 0,7 0,7 0,8 0,9 1,0 1,1 1,1 1,1 1,1
Calculated earth fault current with main voltage A/km 1,8 2,0 2,2 2,5 2,6 2,9 3,2 3,2 3,4 3,4
Current ratings
Cables in air (25 °C)
Flat, conductor 90 °C, open screen A 210 265 320 370 425 485 570 570 650 650
Flat, conductor 90 °C, closed screen A 205 255 310 350 395 440 515 515 580 580
Trefoil, conductor 90 °C, open screen A 195 235 285 330 380 430 505 505 580 580
Trefoil, conductor 90 °C, closed screen A 195 235 280 325 370 425 490 490 565 565
Cables in the ground (15 °C and 1,0 K.m/W), Installation depth 0,7 m
Trefoil, conductor 65 °C, open screen A 155 205 240 270 305 345 395 395 445 445
Trefoil, conductor 65 °C, closed screen A 155 200 235 265 300 330 385 385 435 435
Trefoil, conductor 90 °C, open screen A 185 240 280 320 360 405 465 465 525 525
Trefoil, conductor 90 °C, closed screen A 185 235 275 310 355 390 455 455 510 510
Maximum thermal short circuit current during 1 s
Phase (initial 90 °C, final 250 °C) kA 4,7 6,6 8,9 11,3 14,1 17,4 22,6 22,6 28,3 28,3
Metal screen (initial 35 °C, final 250 °C) kA 2,9 3,0 3,2 3,4 3,6 3,8 5,3 5,3 5,7 5,7
Metal screen (initial 60 °C, final 250 °C) kA 2,7 2,8 2,9 3,1 3,3 3,5 4,9 4,9 5,3 5,3
Metal screen (initial 85 °C, final 250 °C) kA 2,4 2,5 2,7 2,9 3,0 3,2 4,4 4,4 4,8 4,8
Bare earth conductor (initial 55 °C, final 200 °C) kA 5 5 5 5 5 5 5 10 5 10
Environmental information
GWP calculation standard EN15804:2012 EN15804:2012 EN15804:2012 EN15804:2012 EN15804:2012 EN15804:2012 EN15804:2012 EN15804:2012 EN15804:2012 EN15804:2012
+ A2:2019 + A2:2019 + A2:2019 + A2:2019 + A2:2019 + A2:2019 + A2:2019 + A2:2019 + A2:2019 + A2:2019

© Reka rights for changes reserved • www.rekacables.com • 4


ISO 45001, ISO 14001 and ISO 9001 certified
company REACH and RoHS compliant products

2025-09-17 17:01:20

Technical information 3x400+35 Cu


Product code 1187020
Nominal diameter of a sheathed phase conductor mm 42
Nominal cross-sectional area of conductor mm² 400
Nominal diameter of conductor mm 22,4
Nominal thickness of conductor screen mm 0,5
Nominal thickness of insulation mm 5,5
Nominal diameter over the insulation without insulation screen mm 33,6
Nominal thickness of insulation screen mm 0,5
Nominal diameter of earth conductor mm 6,9
Nominal thickness of PE-laminated aluminium foil mm 0,3
Nominal thickness of oversheath mm 2,9
(A1-A3) GWP emission kgCO2e/km 37776
Nominal cable diameter mm 90,300
Nominal cable weight kg/km 6208,369
Nominal weight of copper kg/m 0,302
Nominal weight of aluminium kg/m 2,892
Maximum forces during installation when pulling by
Max. pulling force by pulling-eye kN 20,0
Max. pulling force by pulling-stocking kN 8,5
Minimum bending radii
During handling and installation, phase conductor cm 63
During handling and installation, cable cm 108
In final installation, phase conductor cm 44
In final installation, cable cm 76
Minimum bending radii
During handling and installation, phase conductor m 0,63
During handling and installation, cable m 1,08
In final installation, phase conductor m 0,44
In final installation, cable m 0,76
DC resistance
Max. DC resistance of conductor at 20 °C Ω/km 0,0778
Nominal DC resistance of PE-laminated aluminium foil 20 °C Ω/km 0,81

© Reka rights for changes reserved • www.rekacables.com • 5


ISO 45001, ISO 14001 and ISO 9001 certified
company REACH and RoHS compliant products

2025-09-17 17:01:20

Technical information 3x400+35 Cu


AC resistance of phase conductor, screen circuit closed
Conductor temperature 40 °C Ω/km 0,0850
Conductor temperature 65 °C Ω/km 0,0927
Conductor temperature 70 °C Ω/km 0,0943
Conductor temperature 90 °C Ω/km 0,1005
Inductance per phase
In flat formation, free space between cables equal to one cable diam 0,49
In trefoil formation, cables touching each other mH/km 0,31
Electrical values
Calculated operation capacitance µF/km 0,34
Calculated charging current with main voltage A/km 1,3
Calculated earth fault current with main voltage A/km 3,8
Current ratings
Cables in air (25 °C)
Flat, conductor 90 °C, open screen A 790
Flat, conductor 90 °C, closed screen A 680
Trefoil, conductor 90 °C, open screen A 695
Trefoil, conductor 90 °C, closed screen A 680
Cables in the ground (15 °C and 1,0 K.m/W), Installation depth 0,7 m
Trefoil, conductor 65 °C, open screen A 525
Trefoil, conductor 65 °C, closed screen A 510
Trefoil, conductor 90 °C, open screen A 615
Trefoil, conductor 90 °C, closed screen A 600
Maximum thermal short circuit current during 1 s
Phase (initial 90 °C, final 250 °C) kA 37,8
Metal screen (initial 35 °C, final 250 °C) kA 6,3
Metal screen (initial 60 °C, final 250 °C) kA 5,8
Metal screen (initial 85 °C, final 250 °C) kA 5,3
Bare earth conductor (initial 55 °C, final 200 °C) kA 5
Environmental information
GWP calculation standard EN15804:2012 + A2:2019

© Reka rights for changes reserved • www.rekacables.com • 6