System Adjustments of Single Unit Governor For Cummins Engine
System Adjustments of Single Unit Governor For Cummins Engine
Cummins Engine
Panel Mounted Governor Control Adjustments
The panel mounted governor control has four potentiometers for making system
adjustments. These components are mounted on the control which is located inside the
engine instrument panel or generator control panel.
NOTE: When a two-bearing generator or a single bearing generator with a flexible drive
between the flex discs and shaft (e.g. Kohler 4T10 generators. Models 230ROZ, 250
ROZ and 275ROZ) is installed, use a remote mounted control. If the engine is not
stable after the gain adjustment is made, install a jumper wire between terminals A and
B.
The gain control is a one-turn potentiometer. It is used to adjust the sensitivity of the
governor. A clockwise rotation of the potentiometer dial will shorten the response time
of the governor to load changes. Refer to the glossary for the gain description.
The droop control is a one-turn potentiometer. It is adjustable for zero % (isochronous)
to five % speed droop. Counterclockwise rotation will decrease the speed droop.
The idle speed control is a 20-turn potentiometer for adjusting the idle speed. A
clockwise rotation will increase the idle speed.
The run speed control is a 20-turn potentiometer for setting the desired no-load
governed speed. A clockwise rotation will increase the run speed.
Also located on the engine instrument panel is the Speed Adjust potentiometer which is
used for fine speed adjustment after Run Speed, Droop, and Gain have been set.
3. This will set the idle speed potentiometer to its mid position.
This will set the run speed potentiometer to its mid position. (First and second points
are same to idle speed.)
Place the idle-run switch on the engine instrument panel in the idle position.
NOTE: Open the main line circuit breaker while the engine is at idle.
Start the engine. Adjust the idle speed potentiometer the governor control until the
engine is running at 600 to 650 RPM.
Generators which are to operate at 60 Hz full load, must have the engine no load
governed speed adjusted to:
isochronous operation
5% speed droop
For generators which are to operate at 50 Hz full load, the engine no load governed
speed must be adjusted to:
isochronous operation
5% speed droop
Adjust the run speed potentiometer on the governor control until the no load speed is
correct.
Gain Adjustment
Close the main line circuit breaker and apply approximately 1/4 of the rated load. Make
sure the engine speed is constant.
If the engine speed is constant, turn the GAIN potentiometer clockwise slowly until the
engine speed is not constant.
1. Slowly turn the potentiometer counterclockwise until a constant speed is achieved.
After the gain adjustment is made, the full load governed engine speed may require a
minor adjustment to equal the desired speed (i.e. 60 Hz, 1800 RPM or 50 Hz, 1500
RPM). Use the SPEED ADJUST potentiometer on the engine instrument panel for fine
speed adjustments of less than ±100 RPM.
Follow the panel mounted governor control instructions for setting the governed speed,
idle, droop and gain on the remote mounted control. The wiring for the remote
mounted control is shown.
Caution: Do not attach the battery negative to Terminal Number 11. The
control circuitry will be damaged.
NOTE: When a two-bearing generator or a single bearing generator with a flexible drive
between the flexible drive between the flex discs and shaft (eg. Kohler 4T10
generators, Models 230ROZ, 250 ROZ and 275 ROZ) is used, install a jumper between
terminals A and B. This jumper provides additional stability in the governor control. The
oscillation frequency of the coupling between the engine and the generator can cause
the governor control to react to this oscillation in addition to a change in engine speed.
Caution: Measure the voltage of the panel mounted governor control on the printed
circuit board terminal strip. Do not measure the voltage on the control terminal strip.
1. The "Gain Range" is changed by adding a jumper between Terminals 6 and 14.
2.
a. Closing a contact or jumpering 11 to 12 allows the Auto-Synchronizer to perform as
a sync check relay only, with circuit breaker contact output but no control on the
incoming generator.
4. Systems battery supply. If more than-one engine is started using the same battery
supply, use separate battery supply for the DYNA System. Twist power leads as shown.
Use shielded leads as shown. Use a single pole, single throw 4 ampere switch.
down transformers require a nominal 6 VA/PHASE for the Isochronous Load Sharing
Control.