Technical Specification Sheet
Document No. 149-715
February 19, 2018
Series 2200/3200 Communicating Room Sensors
for Use with Siemens Terminal Equipment
Controllers
QxAx2xx.EWSC QxAx2xx.DWSC QxAx2xx.FWSC
Sensing Only with Display Full HMI
Description Specifications
These Series 2200/3200 Room Sensors are designed for Temperature
use with Siemens Terminal Equipment Controllers Measuring range 32°F to 122°F (0°C to 50°C)
(TECs)*. The sensor and controller communicate using Accuracy
QAA2280.EWxC ± 0.50°F (± 0.28°C)
an RJ-11 cable with plug connections at both ends for QAA2280.DWxC ± 0.9°F (± 0.5°C)
easy and error-free wiring. Installation is quick and QAA2280.FWxC ± 0.9°F (± 0.5°C)
straightforward with all hardware included for mounting QPA2282.EWxC ± 0.9°F (± 0.5°C)
on a standard 2” × 4” electrical box. Screws and anchors All others ± 0.54°F (± 0.3°C) @ 77°F (25°C)
are provided for mounting the sensor directly to a wall. Humidity
Matching gaskets and trim rings are also available. (QFA and QPA2284)
All units include an RJ-11 tool port at the bottoms of the Measuring Range 0 to 100% rh
sensor housings for connection to Siemens Accuracy ± 2% between 10 to 90%
Long-Term Stability <0.5% rh/year
configuration, commissioning and start-up tools.
Resolution 0.03% rh
QAA Series Sensors measure room temperature, while Repeatability ± 0.1% rh
QFA Series sensors measure both temperature and CO2 (QPA Models)
relative humidity. The QPA Series Sensors measure Technology Dual Beam NDIR
temperature and CO 2 or temperature, CO2* and relative Measuring Range 0 to 2000 PPM
humidity. Accuracy* ± (50 ppm + 2% of MV)
Field Calibration Not required
QPA Series sensors are designed to help maintain CO2 Drift ± 5% of range over 5 years
occupant comfort and are not intended for use in life Setpoint/Override
safety applications. (“F” versions only)
The “E” versions have a blank front to prevent Setpoint Range 55°F to 95°F (13°C to 35°C)
unauthorized adjustments and are ideal for high traffic Input Power
QAA and QFA Powered using TEC RJ-11 port
areas or remote spaces that are not supervised.
QPA Requires AQM2200
The “D” versions display room temperature and/or room Agency Listing UL
humidity. cUL
The “F” versions feature a full HMI that can display room CE
FCC
conditions and temperature setpoint. The display is
RCM
easily configured to limit the information that is available White
Color
to the occupant. Temperature setpoint can be adjusted Dimensions 4.5” × 2.75” × 1.18”
using soft touch plus (+) and minus (-) keys, and an (115 mm × 70 mm × 30 mm)
override key enables the user to manually signal to the Shipping Weight 6 oz. (170 g)
controller that the space is occupied. * Allow up to 96 hours for unit to reach published accuracy.
Siemens Industry, Inc. Page 1 of 2
Product Ordering Information
1) 2) 3) Setpoint Communication
Part Number Temp Humidity CO2 Display Tool Port Type
Adjustment
QAA2280.DWSC • — — • — • Digital (P1)
QAA2280.EWSC • — — — — • Analog - Resistive
QAA2280.FWSC • — — • • •
QFA3280.DWSC • • — • — •
QFA3280.EWSC • • — — — •
QFA3280.FWSC • • — • • • Digital (P1)
2)
QPA2282.EWSC • — • — — •
2)
QPA2284.EWSC • • • — — •
2)
QPA2284.FWSC • • • • • •
1)
For no-logo version, change "S" to "N" in part number position 10.
2)
QPA models require an AQM2200 24V Power Module.
3)
P1 TECs cannot read relative humidty and CO 2 data. Use BACnet TECs for applications requiring these measurements.
Accessories Ordering Information
Description Part Number
1)
Power Module (Required only with QPA2282 and QPA2284 sensors) AQM2200
1)
Room Unit Back Plate (10-pack) AQA2200-INTL
1)
Room Unit Back Plate (Single) AQA2200-2X4
Room Sensor Insulating Gasket (10-pack) (Recommended for hollow wall installations.) 563-102 GSKT KIT
25-foot (7.6 m) cable with connections 588-100A
50-foot (15.2 m) cable with connections 588-100B
100-foot (30.5 m) cable with connections 588-100C
Passkey Tool (Used to set room unit parameters) 544-643A
2)
Replacement RH Sensing Element – TEC Room Unit AQF3060
1)
For use when installing Series 2200/3200 Sensors on conduit boxes other than US style 2” × 4”. Back plate measures 3-1/4” ×
5” (82.55 mm × 127 mm).
2)
For use with all QFA models and QPA2284.xxxx only.
Disposal
The devices are considered electrical and electronic equipment for disposal in terms of the applicable
European Directive and may not be disposed of as domestic garbage.
• Dispose of the devices through channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as
design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2018
Siemens Industry, Inc.
Siemens Industry, Inc. Your feedback is important to us. If you have Document No. 149-715
Building Technologies Division comments about this document, please send them to Printed in the USA
1000 Deerfield Parkway SBT_technical.editor.us.sbt@siemens.com Page 2 of 2
Buffalo Grove, IL 60089-4513
USA
+1-847-215-1000