Differential Protection 7UT6: Power Transmission and Distribution
Differential Protection 7UT6: Power Transmission and Distribution
7UT613
7UT633
7UT612 7UT613
7UM62 7UT633
1 ½ C.B. application on
Short lines Short lines HV and LV side with
(2 ends) (3 ends) two winding transformer
7UT635
7UT612 7UT613
7UT633
7UT612
7UM62 7UT6xx
IEE input
Unit Protection of the unit
(Overall Differential)
Y
7UT635
∆
G
3~
M1 IL2M1/I2
M2
400/1A IL3M1/I3
M1 IL1M2/I4
400/1A M3 400/1A
M2 IL2M2/I5
IL3M2/I6
IL1M3/I7
M3 IL2M3/I8
M5 IL3M3/I9
Side 1
3500/1A
200/1A IL1M4/I10
M4 IL2M4/I11
Side 3 IL3M4/I12
Side 2 IL1M5/Ix1
M5 IL2M5/Ix2
M4
IL3M5/Ix3
8000/1A
Ix4
7UT635
IL1M2 IL1M3
IL2M2 IL2M3
IL3M2 IL3M3
IL1M1
IL2M1
IL3M1
7UT613
7UT613
PTD PA 7UT6 Applicat./Eng. 06/04 No. 10
Application: Autotransformer (bank) with (2 of 2)
3 Ct’s at the neutral side
7UT613
7UT613/633:
9 current-
inputs
7UT635:
12 current-
inputs
7UT612
2 more Relays
for Phase 2 and 3
are necessary
7UT613/633:
6 current-
inputs 0.1A
7UT635:
12 current
inputs 0.1A
*) Summation CT
4AM5120-3DA00-0AN2: 1/0.1A
4AM5120-4DA00-0AN2: 5/0.1A
7UT612
Not important
in this case
RS485 interface
7XV5662-(x)AD10 7XV5662-(x)AD10
From Transformer-
Manufacturer
2. Results:
Θ h Θ o H gr k Y 73 23 1.151.6 102C
(L)
73°C
1.6
h hot-spot temp.
1.15
k (I/InO)
t
PTD PA 7UT6 Applicat./Eng. 06/04 No. 21
CT Requirements (1 of 3)
R ct R b I
Request: k ALF k ALF_N 4 P for : TP 100ms
R ct R b
'
I NCtPrim
R ct R b I
k ALF k ALF_N 5 P for : TP 100ms
R ct R b
'
I NCtPrim
where:
kALF_N = rated Accuracy Limiting Factor kALF = actual Accuracy Limiting Factor
Rct = secondary winding resistance
Rb = rated resistive burden R’b = actual resistive burden
IP = max. primary symmetrical short circuit current TP = Primary (Net-) Time constant
Example: (TP ≤ 100ms) Explanation:
110 kV 5P20: kALF_N = 20
7UT6
200/1A Wind.1
5P20,15VA 80m , 2.5 mm2
Rct = 1Ω 0.1 Ω
38.1 MVA
110/11 kV
uk = 10%
2000/1A
50m , 4 mm2 Wind.2
10P10, 10VA
Rct = 2Ω 0.1 Ω
11 kV
PTD PA 7UT6 Applicat./Eng. 06/04 No. 22
CT Requirements (2 of 3)
Side 1 (HV): Side 2 (LV):
Nominal transformer current: Nominal transformer current:
SN 38100kVA SN 38100kVA
InO1 200A InO2 2000A
3 U N1 3 110kV 3 U N2 3 11kV
Sb 15VA Sb 10VA
Rb 2
15Ω Rb 10Ω
I NCtS 1A 2 I 2
NCtS 1A 2
Ωmm 2 Ωmm 2
160m 0.0175 100m 0.0175
2lρ m 0.1Ω 1.22Ω 2l ρ m 0.1Ω 0.54Ω
R 'b R Relay 2
R 'b R Relay 2
q 2.5mm q 4mm
1Ω 15Ω 2Ω 10Ω
k ALF 20 144 k ALF 10 47.2
1Ω 1.22Ω 2Ω 0.54Ω
IP 2200A IP 22000A
k ALF 144 4 4 44 OK! k ALF 47.2 4 4 44 OK!
I NCTprim 200A I NCTprim 2000A
1000A 3 6.3kV
* *) FAdap_Wdg3 5A 0.044
5A 250000kVA
For Winding 3 the Adaption factor is to low ! Here an Interposing CT with a ratio of
6 or greater should be installed.
347 kV
7UT613
Side 1
1000/1A
250/200/10 MVA
Side 2
9000/5A
Side 3
1000/5A
6/1
Interposing CT
15.7 kV 6.3 kV
Settings CT winding 3:
Transformer-
winding
L1
L2
L3
7UT61
7UT61
The magnetising current contains for example at point 3 (50Hz pickup threshold)
approximately 50% of this harmonic.
The setting for 5th harmonic restraint should consider the smallest I250 / I50 for the
applicable voltage range. In this example with Umax = 140% the setting for
I250 / I50 should be at least 30%.
As the 5th harmonic restraint is not effective above (1273A), it will not block during internal short circuits
with harmonics for example due to CT saturation.
Figure 1
50Hz part of the magnetisation current and dominant Harmonics at Over flux
for a 50Hz Transformer with UN = 78kV and SN = 60MVA
Harmonic components
Setting Idiff>