SERGI TRANSFORMER PROTECTOR
TRANSFORMER EXPLOSION AND FIRE PREVENTION
SUMMARY
Design
Types and Principle
System Components
Logic Diagram
Fire Extinction Back Up Principle
Retrofitting On Existing Transformers
Installation Examples
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 2
SERGI TRANSFORMER PROTECTOR
DESIGN
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 3
SERGI TRANSFORMER PROTECTOR
DESIGN, PRINCIPLE
The TRANSFORMER PROTECTOR is a concept that can be applied to
all transformers from 0.1MVA. It enables to:
Depressurise the transformer tank within
milliseconds.
Avoid contact between air (oxygen) and the
evacuated explosive gases.
Separate gases from oil.
Channel the gases far away from the
transformer to a remote area where they can
burn safely.
Eliminate the generation of explosive gases
by making use of nitrogen injection.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 4
SERGI TRANSFORMER PROTECTOR
DESIGN, RELIABILITY
The TRANSFORMER PROTECTOR is a passive mechanical
system, which can only be activated by the level of the
transformer tank internal pressure reached during short-
circuits.
The TRANSFORMER
PROTECTOR has therefore a
very high reliability, as false
activation is impossible.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 5
SERGI TRANSFORMER PROTECTOR
DESIGN, MAINTENANCE
The TRANSFORMER PROTECTOR has been designed to
minimize all maintenance requirements, in order to reduce:
Cost of maintenance.
Probability of Operation Malfunction.
Maintenance outage.
The TRANSFORMER PROTECTOR maintenance can be performed
during transformer regular shutdown for maintenance.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 6
SERGI TRANSFORMER PROTECTOR
TYPES AND PRINCIPLE
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 7
SERGI TRANSFORMER PROTECTOR
TRANSFORMER EXPLOSION AND FIRE PREVENTION
TRANSFORMER PROTECTOR
MTP-A : Vessel protection for transformers above 0.1MVA
STP : Vessel protection for transformers from 0.1 to 5MVA
STP Example 1
STP Example 2
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 8
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR
TYPE MTP FOR TRANSFORMERS FROM 0.1 MVA
MTP-A
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 9
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR
TYPE MTP FOR TRANSFORMERS FROM 0.1 MVA
MTP-A
Buchholz
Conservator Transformer Rupture Disk Explosive Gases
Shutter burn in remote area
Decompression
Isolation Valve Chamber
OLTC
Rupture Oil
Disk Drain Pipe
from other
Transformers
Explosive Oil-Gas Nitrogen
Separation Cylinder
Gas Tank
Elimination
Pipe
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 10
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR
TYPE MTP FOR TRANSFORMERS FROM 0.1 MVA
MTP-A
1/ Pressure rises
2/ Explosion
of the disk,
depressurisation,
evacuation of the
oil-gases mixture
3/ Opening of the air
isolation shutter
N2
4/ Nitrogen injection
5/ Explosive gases
production is
stopped
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 11
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR TYPE MTP FOR TRANSFORMERS FROM 0.1MVA TO
1000MVA
MTP-A
APPLICATIONS
Power Plants, to reduce the loss of production.
Outdoor substations located near buildings or habitations or
outdoor substations when not equipped with Oil Collecting Ducts
and Remote Oil Storage Pit.
Hydro Power Plants, for indoor
transformers.
Indoor or Underground
substations.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 12
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR TYPE MTP FOR TRANSFORMERS FROM 0.1MVA TO
1000MVA
MTP-A
CHARACTERISTICS
Every Depressurisation Set has a Decompression Chamber.
The explosive Oil-Gases mixture is evacuated to an Oil-Gases
Separation Tank.
The explosive gases are
channeled to a remote area where
they can burn safely.
The Oil-Gas Separation Set can
be shared between Several
transformers when not located far
from each other.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 13
SERGI TRANSFORMER PROTECTOR
TRANSFORMER EXPLOSION AND FIRE PREVENTION
TRANSFORMER PROTECTOR
MTP-A : Vessel protection for transformers above 0.1MVA
STP : Vessel protection for transformers from 0.1 to 5MVA
STP Example 1
STP Example 2
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 14
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR EXPLOSION AND FIRE PREVENTION FOR
TRANSFORMERS FROM 0.1 TO 5 MVA
STP Transformer
Bushing
Rupture Disk
Shock Absorber
Isolation Valve
Gas
Evacuation
Conservator Pipe to Safe
Shutter Remote
Area
Buchholz
Nitrogen
Cylinder
Oil-Gas
Explosive Gas Separation
Elimination Pipe Tank
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 15
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR EXPLOSION AND FIRE PREVENTION FOR
TRANSFORMERS FROM 0.1 TO 5 MVA
STP
1/ Pressure rises
INSIDE OUTSIDE
2/ Opening of the
Rupture Disk
and evacuation of the
oil-gas mixture
3/ Opening of the
Non Return Valve N2
4/ Nitrogen injection
5/ Stop the explosive
gas production
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 16
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR EXPLOSION AND FIRE PREVENTION FOR
TRANSFORMERS FROM 0.1 TO 5 MVA
STP
DIFFERENCES WITH THE MTP:
The STP only protects small transformers. This is why the Oil-Gases
Separation Tank is used as a Decompression Chamber.
APPLICATIONS FOR TRANSFORMERS FROM 0.1 TO 5MVA :
Residential and office buildings.
Underground substations.
Indoor and outdoor industrial
plants with high explosion risks.
Railway network power supply station.
Enviromental sensitive areas.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 17
SERGI TRANSFORMER PROTECTOR
TRANSFORMER EXPLOSION AND FIRE PREVENTION
TRANSFORMER PROTECTOR
MTP-A : Vessel protection for transformers above 0.1MVA
STP : Vessel protection for transformers from 0.1 to 5MVA
STP Example 1
STP Example 2
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 18
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR EXPLOSION AND FIRE PREVENTION FOR POWER
TRANSFORMERS FROM 0.1 TO 5 MVA
STP
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 19
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR EXPLOSION AND FIRE PREVENTION FOR
TRANSFORMERS FROM 0.1 TO 5 MVA
STP
Bushing Transformer
Rupture Disk
Oil-Gas
Separation
Tank
Gas
Evacuation
Pipe to Safe
Remote
Area
Nitrogen
Cylinder
Explosive Gas
Elimination Pipe
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 20
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR EXPLOSION AND FIRE PREVENTION FOR
TRANSFORMERS FROM 0.1 TO 5 MVA
STP
1/ Pressure rises
2/ Opening of the
Rupture Disk
and evacuation of the
oil-gas mixture
3/ Opening of the Air
Isolation Valve N2
4/ Nitrogen injection
5/ Stop the explosive
gas production
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 21
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR EXPLOSION AND FIRE PREVENTION FOR
TRANSFORMERS FROM 0.1 TO 5 MVA
STP
DIFFERENCES WITH THE MTP:
No Transformer Isolation Valve.
No Shock Absorber.
APPLICATIONS FOR TRANSFORMERS FROM 0.1 TO 5MVA :
Residential and office buildings.
Underground substations.
Indoor and outdoor industrial
plants with high explosion risks.
Railway network power supply station.
Environmental sensitive areas.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 22
SERGI TRANSFORMER PROTECTOR
TRANSFORMER EXPLOSION AND FIRE PREVENTION
Even though the tank has the priority to be protected, the statistics demonstrates the
importance to protect the other oil capacities. FAILURE ORIGIN
%
Rate (%) 50
45
In many cases, a failure from the On Load Tap Changer 40
35
or Bushing can spread to the transformer tank. 30
25
20
15
10 18 34 48
The same principle, using the Rupture Disk with 5
integrated Burst Indicator and nitrogen injection, is 0
Winding Bushing OLTC
used in this case to stop the explosive gas production.
The extension of the prevention system is simply done by connecting the depressurisation
pipe from On Load Tap Changer, Bushing or Cable Box to the tank explosion and fire
prevention system.
This technique proposes a global solution, for all transformer oil capacities, with only
one system, for the lowest cost.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 23
SERGI TRANSFORMER PROTECTOR
TRANSFORMER EXPLOSION AND FIRE PREVENTION
TRANSFORMER PROTECTOR
MTP-A : Protection for the On Load Tap Changer.
MTP-B : Protection for the Bushings and Cable Boxes.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 24
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR TRANSFORMER AND ON LOAD TAP CHANGER
EXPLOSION AND FIRE PREVENTION
MTP-A
The On Load Tap Changer is the failure origin in 48% of the cases.
Over pressure diaphragms are frequently integrated
to the cover.
diaphragm
Unfortunately, no flange
1 6 allows connecting the
5
diaphragm to an oil passage.
1 - cover diaphragm
2 - tap changer 2 During short circuit, it results
3 - selector in a bazooka effect that
4 - tap changer motor propagates fire to the
4 3
5 - protection relay
transformer and its
6 - conservator oil
environment.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 25
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR TRANSFORMER AND ON LOAD TAP CHANGER
EXPLOSION AND FIRE PREVENTION
MTP-A
The On Load Tap Changer is the failure origin in 48% of the cases.
The diaphragm on the cover is sometimes
replaced by a Pressure Relief Valve.
Pressure Relief Valve
In case of short circuit, where the On
Load Tap Changer is equipped with the
Pressure Relief Valve, the cover is often
ejected by the pressure effect.
It proves the inefficiency of the Pressure
Relief Valve.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 26
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR TRANSFORMER AND ON LOAD TAP CHANGER
EXPLOSION AND FIRE PREVENTION
MTP-A
To channel the oil gush following an internal fault in the On Load Tap Changer, SERGI
proposes a system of depressurisation, evacuation, and cooling, all integrated in the
TRANSFORMER PROTECTOR : type MTP-A.
Flange for the quick depressurisation piping towards the TRANSFORMER PROTECTOR
SERGI Rupture Disk
with integrated
Burst Indicator
Flange for nitrogen
injection
ON LOAD TAP
CHANGER Cover with integrated
flange to install SERGI
Rupture Disk
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 27
SERGI TRANSFORMER PROTECTOR
TRANSFORMER EXPLOSION AND FIRE PREVENTION
TRANSFORMER PROTECTOR
MTP-A : Protection for the On Load Tap Changer.
MTP-B : Protection for Cable Boxes.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 28
SERGI TRANSFORMER PROTECTOR
TRANSFORMER
PROTECTOR TRANSFORMER AND ON LOAD TAP CHANGER
EXPLOSION AND FIRE PREVENTION
MTP-B
The Cable Boxes are the failure origin in 33% of the cases.
Isolation Valve
Oil Collecting
Pipe
To channel the oil gush
following an internal fault in the
Bushing or Cable Box, SERGI
Rupture Disk proposes a system of
with integrated depressurisation, evacuation,
Burst Indicator
and cooling, all integrated in
the TRANSFORMER
PROTECTOR : type MTP-B.
Explosive Gas
Elimination
Injection Pipe
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 29
SERGI TRANSFORMER PROTECTOR
SYSTEM COMPONENTS
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 30
SERGI TRANSFORMER PROTECTOR
Transformer Protector MTPA Components
2
6
1 3
1. Depressurisation Set 4. Explosive Gas Elimination Pipe
2. OLTC Depressurisation Set 5. Cabinet
3. Oil-Gas Separation Tank 6. Explosive Gases Evacuation
Index Quit
7. Conservator Shutter
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 31
SERGI TRANSFORMER PROTECTOR
Transformer Protector MTPA Components
DEPRESSURISATION SET PRINCIPLE:
All Depressurisation Sets include a
Rupture Disk to relieve overpressure
and a Decompression Chamber to
favor high-speed depressurisation.
Their diameter is calculated
individually for each transformer and
On Load Tap Changer types.
In addition, transformer tanks
Depressurisation Sets also include an
Isolation Valve and an Expansion and
Vibration Absorber
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 32
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
Transformer Horizontal Depressurisation Set
3 4 5
1
ELEMENTS:
1. Isolation Valve Flange
2. Isolation Valve
2
3. Absorber
4. Rupture Disk
6
5. Decompression Chamber
7
6. Support Plate
7. Vibration Absorbers
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 33
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
Transformer Vertical Depressurisation Set
ELEMENTS:
1. Transformer interface
2. T-piece for adaptation
3. Pressure Relief Valve
4. Isolation Valve
5. Absorber
6. Rupture Disk
7. Vibration Absorbers
8. Decompression Chamber
9. Exhaust for Gases
10. Exhaust for Oil
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 34
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
On Load Tap Changer Depressurisation Set
ELEMENTS:
2 1. Rupture Disk with
integrated Burst Indicator
2. Depressurisation
Chamber elbow
1 3. Explosive Gas
3
Elimination Pipe
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 35
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
Bushing or Cable Box Depressurisation Set
1
2 ELEMENTS:
3
1. Manual Isolation Valve
2. Rupture Disk with integrated Burst
Indicator
3. Oil Drain Pipe
4. Explosive Gas Elimination
4
Injection Pipe
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 36
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
Oil - Gas Separation Tank (OGST)
PRINCIPLE:
2
The OGST collects the depressurised oil and
3
flammable gas mixture.
1
Then it separates gases from oil, as the mixture is
channeled through the Explosive Gas evacuation pipe
(2) to a remote area.
One OGST can be used for several transformers, if
they are not located far from each other.
ELEMENTS:
4
1. Non Return Valve
2. Explosive gases evacuation to remote safe area
3. Oil Drain Pipe from Depressurisation Set
4. Nitrogen Injection to the OGST
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 37
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
Explosive Gas Elimination Set
PRINCIPLE:
Creates a safe environment inside the
transformer, OLTC and Bushings by
injecting an strong nitrogen flow.
Explosive Gas Elimination Sets can
come with multiple Nitrogen exhausts.
Each exhaust is designed to provide a
different flow of Nitrogen and can be
divided to enable multiple injection points.
ELEMENTS:
1. Exhaust to Transformer main tank
2. Exhaust to OLTC or Bushings
3. Exhaust to OGST
4. In/Out of Service and
Maintenance lamps
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 38
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
Control Box
The Control Box is located in the
control room.
It ensures the logic of the system.
It is connected to the transformer
protections, Fire Detectors,
Isolation Valve, Conservator
Shutter, Rupture Disk and to the
Cabinet.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 39
SERGI TRANSFORMER PROTECTOR
Transformer Protector Components
Conservator Shutter Valve
Should the transformer tank or
any pipe rupture, a consequent
flow of oil will be created.
Without a SERGI Conservator
Shutter, the total conservator oil
volume will be spilled, possibly
fuelling the fire.
The SERGI Conservator Shutter
is designed to close when an
unusual oil flow is detected,
preventing the Conservator from
being drained.
The closing of the Shutter can
be monitored.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 40
SERGI TRANSFORMER PROTECTOR
LOGIC DIAGRAM
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 41
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 42
SERGI TRANSFORMER PROTECTOR
FIRE EXTINCTION BACK UP PRINCIPLE
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 43
SERGI TRANSFORMER PROTECTOR
FIRE EXTINCTION BACK UP PRINCIPLE
1/ Pressure rises
2/ Rupture
Disk and
tank explosion FIRE EXTINCTION
3/ Oil and gases
evacuation
50
140
140
°C
°C
140°C
°C
50 °C°C
140
4/ Shutter closes
5/ Self-flammable
gases start fire
N2
6/ Nitrogen injection 50 °C
mixes oil, provoking fire
extinction within 2 minutes
7/ Nitrogen is injected during 45 minutes
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 44
SERGI TRANSFORMER PROTECTOR
RETROFITTING ON EXISTING
TRANSFORMERS
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 45
SERGI TRANSFORMER PROTECTOR
RETROFITTING ON EXISTING TRANSFORMERS
The SERGI TRANSFORMER PROTECTOR is easily retrofitted without
tank machining by using the existing interfaces.
DEPRESSURISATION PIPING
Cover and Side Manholes, Pressure Relief Valves and Existing Valves can be
used for the adaptation of the Depressurisation Set.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 46
SERGI TRANSFORMER PROTECTOR
RETROFITTING ON EXISTING TRANSFORMERS
NITROGEN INJECTION PIPING
Existing Valves for oil sampling and draining can be used to retrofit
the nitrogen injection.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 47
SERGI TRANSFORMER PROTECTOR
RETROFITTING ON EXISTING TRANSFORMERS
The TRANSFORMER PROTECTOR can be retrofitted on the Transformer
cover by using a vertical Depressurisation Set
The TRANSFORMER
PROTECTOR can be
retrofitted on transformer
covers by replacing the
Pressure Relief Valve by a
T-piece and installing a
Vertical Depressurisation Set
Any manhole available on
the transformer can be used
as a base for retrofitting of a
Vertical or Horizontal
Depressurisation Set
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 48
SERGI TRANSFORMER PROTECTOR
RETROFITTING ON EXISTING TRANSFORMERS
Example of Power Plant GIS transformer leaving the tank top manholes
available for the TRANSFORMER PROTECTOR installation.
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 49
SERGI TRANSFORMER PROTECTOR
TRANSFORMER PROTECTOR
INSTALLATION EXAMPLES
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 50
SERGI TRANSFORMER PROTECTOR
INSTALLATION EXAMPLES
1 : Guatemala, SIDEGUA
2 : Mexico, CFE
3 : France, La Batie Power Plant, EDF
4 : Malaysia, Jalan Pantai, Distribution Substation
5 : Pictures
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 51
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 52
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 53
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 54
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 55
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 56
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 57
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 58
SERGI TRANSFORMER PROTECTOR
INSTALLATION EXAMPLES
1 : Guatemala, SIDEGUA
2 : Mexico, CFE
3 : France, La Batie Power Plant, EDF
4 : Malaysia, Jalan Pantai, Distribution Substation
5 : Pictures
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 59
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 60
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 61
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 62
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 63
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 64
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 65
SERGI TRANSFORMER PROTECTOR
INSTALLATION EXAMPLES
1 : Guatemala, SIDEGUA
2 : Mexico, CFE
3 : France, La Batie Power Plant, EDF
4 : Malaysia, Jalan Pantai, Distribution Substation
5 : Pictures
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 66
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 67
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 68
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 69
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 70
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 71
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 72
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 73
SERGI TRANSFORMER PROTECTOR
INSTALLATION EXAMPLES
1 : Guatemala, SIDEGUA
2 : Mexico, CFE
3 : France, La Batie Power Plant, EDF
4 : Malaysia, Jalan Pantai, Distribution Substation
5 : Pictures
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 74
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 75
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 76
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 77
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 78
SERGI TRANSFORMER PROTECTOR
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 79
SERGI TRANSFORMER PROTECTOR
INSTALLATION EXAMPLES
1 : Guatemala, SIDEGUA
2 : Mexico, CFE
3 : France, La Batie Power Plant, EDF
4 : Malaysia, Jalan Pantai, Distribution Substation
5 : Pictures
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 80
SERGI TRANSFORMER PROTECTOR
Control Box
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 81
SERGI TRANSFORMER PROTECTOR
Cabinet
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 82
SERGI TRANSFORMER PROTECTOR
Depressurisation Set
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 83
SERGI TRANSFORMER PROTECTOR
Depressurisation Set
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 84
SERGI TRANSFORMER PROTECTOR
Conservator Shutter
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 85
SERGI TRANSFORMER PROTECTOR
Nitrogen Injection
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 86
: (33) 1 39 22 48 40 : (33) 1 39 22 11 11 / 48 51
@:
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
P.O. Box 90, 78260 Achères, France
web site : www.sergi-france.com
Index Quit
Copyright © SERGI,referenced: fTPvc06a, dated 29/01/04 87
Slide 01 Slide 02 Slide 03 Slide 04 Slide 05 Slide 06
Slide 07 Slide 08 Slide 09 Slide 10 Slide 11 Slide 12
Slide 13 Slide 14 Slide 15 Slide 16 Slide 17 Slide 18
Slide 19 Slide 20 Slide 21 Slide 22 Slide 23 Slide 24
Copyright © SERGI,referenced: fTPvc05a, dated 29/01/04
Slide 25 Slide 26 Slide 27 Slide 28 Slide 29 Slide 30
Slide 31 Slide 32 Slide 33 Slide 34 Slide 35 Slide 36
Slide 37 Slide 38 Slide 39 Slide 40 Slide 41 Slide 42
Slide 43 Slide 44 Slide 45 Slide 46 Slide 47 Slide 48
Copyright © SERGI,referenced: fTPvc05a, dated 29/01/04
Slide 49 Slide 50 Slide 51 Slide 52 Slide 53 Slide 54
Slide 55 Slide 56 Slide 57 Slide 58 Slide 59 Slide 60
Slide 61 Slide 62 Slide 63 Slide 64 Slide 65 Slide 66
Slide 67 Slide 68 Slide 69 Slide 70 Slide 71 Slide 72
Copyright © SERGI,referenced: fTPvc05a, dated 29/01/04
Slide 73 Slide 74 Slide 75 Slide 76 Slide 77 Slide 78
Slide 79 Slide 80 Slide 81 Slide 82 Slide 83 Slide 84
Slide 85 Slide 86 Slide 87
Copyright © SERGI,referenced: fTPvc05a, dated 29/01/04