MTS-231 Actuating Systems: Kanwal Naveed
MTS-231 Actuating Systems: Kanwal Naveed
Actuating Systems
Kanwal Naveed
Transformers
THE EQUIVALENT CIRCUIT OF A TRANSFORMER
The losses that occur in real transformers have to be accounted for in any
accurate model of transformer behavior.
1. Copper (I2R) losses. Copper losses are the resistive heating losses in the
primary and secondary windings of the transformer. They are proportional
to the square of the current in the windings.
2. Eddy current losses. Eddy current losses are resistive heating losses in the
core of the transformer. They are proportional to the square of the voltage
applied to the transformer.
THE EQUIVALENT CIRCUIT OF A TRANSFORMER
4. Leakage flux. The fluxes ɸLP and ɸLS which escape the core and pass
through only one of the transformer windings are leakage fluxes. These
escaped fluxes produce a self-inductance in the primary and secondary
coils, and the effects of this inductance must be accounted for.
THE EQUIVALENT CIRCUIT OF A TRANSFORMER
• The core- loss current ih+e is a current proportional to the voltage applied to
the core that is in phase with the applied voltage, so it can be modeled by a
resistance RC connected across the primary voltage source.
THE EQUIVALENT CIRCUIT OF A TRANSFORMER
• The currents are really nonlinear, so the inductance XM and the resistance RC are,
at best, approximations of the real excitation effects.
Transformer-Taps
• A tap changes the voltage ratio of a transformer so that its secondary voltage
stays at nominal.
• On large power transformers, taps on the primary are used to offset any higher
or lower input voltages.
• These tap connections are usually set at the factory for nominal line voltage.
Current relations:
• IL=IC+ISE also from Eq.(2) IC=(NSE / NC)ISE
• IL= (NSE / NC)ISE + ISE, since ISE=IH
IL= (NSE / NC)IH +IH = (NSE + NC)/NC . IH
IL / IH = (NSE + NC)/NC (8)
Autotransformer
Apparent Power Rating Advantage of Autotransformer
• Not all power traveling from primary to secondary in autotransformer passes
through windings.
• Therefore if a conventional transformer is reconnected as an autotransformer, it
can handle much more power than its original rating.
Example :
A 5000 kVA autotransformer connecting a 110 kV system to a 138 kV system has
an NC/NSE of 110/28. For this autotransformer actual winding rating is:
SW = SIO NSE/(NSE+NC)
= 5000 (28/ 28+110)
=1015 kVA
Autotransformer
• It is not normally possible to reconnect an ordinary transformer as an
autotransformer due to the fact that insulation of L.V. side may not
withstand full output voltage of autotransformer connection.
• Common practice is to use autotransformer when two voltages are
fairly close because it gives more power rating advantage.
• Also used as variable transformers, where L.V. tap moves up & down
the winding.
Transformer Efficiency (Home Task)
• Efficiency (η) is the ratio of the power out to the power in
• η of an ideal transformer (no power losses)
Pin = Pout = VPIP cos P = VSIS cos S
Sout = SIN = VPIP = VSIS
Pout
real 100%
Pin
• η of a real transformer (power losses)
Pout
real 100%
Pout Ploss
VS I S cos
real 100%
PCu Pcore VS I S cos
The Per-Unit System of Measurement
• An approach to solving circuits containing transformers which
eliminates the need for explicit voltage-level conversions at every
transformer in the system.
• This method don’t require impedance transformations
• This method of calculation is known as the per-unit (pu) system
of measurements.
• per-unit system related to the device's ratings.
The Per-Unit System of Measurement
• In the per-unit system, the voltages, currents, powers, impedances,
and other electrical quantities are not measured in their usual SI
units (volts, amperes, watts, ohms, etc.).
• each electrical quantity is measured as a decimal fraction of some
base level.
b. Suppose a 1:10 step-up transformer is placed at the generator end of the transmission line and a
10:1 step-down transformer is placed at the load end of the line. What will the load voltage be now?
What will the transmission line losses be now?
ip t 1 vp t Np
ZL ’ = a Z L
2 Np ip (t) = Ns is (t) a
is t a vs t Ns
Example 2-3
• A simple power system is shown in Figure 2- 22. This system
contains a 480-V generator connected to an ideal I: 10 step-up
transformer, a transmission line, an ideal 20: I step-down
transformer, and a load. The impedance of the transmission line is
20 + j60 Ω, and the impedance of the load is 10-30°Ω. The base
values for this system are chosen to be 480 V and 10 kVA at the
generator.
Example 2-3
Given
• Region-3: The turns ratio of transformer T2 is a = 20/1 = 20
Given
• (b) Convert this system to its per-unit equivalent circuit.