0% found this document useful (0 votes)
197 views26 pages

Lese0019-00 - C32 Enclosure Product Launch - April 2010

Uploaded by

Liviu Petreus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
197 views26 pages

Lese0019-00 - C32 Enclosure Product Launch - April 2010

Uploaded by

Liviu Petreus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 26

One powerful future.

C32 Enclosure Product Launch


April 2010
One powerful future.

Agenda
• Program Goals
• Features & Benefits
• Competitive Overview
• Sales Support
• Summary

TRANSFORMED BY 6 SIGMA Page 2


One powerful future.

Program Goals
Deliver a factory enclosure for the C32 package generator
set for 50 Hz & 60 Hz markets

In Scope:
– C32 SR5 Generator Sets Griffin Sourced 

Out of Scope:
– SR4B, Tier IV, All Other Genset Platforms, Marine, Gas

TRANSFORMED BY 6 SIGMA Page 3


One powerful future.
C 27
Design Criteria
• Worldwide application
– ISO container shipment
• Isolation of a hard mounted ISO
package Doorway
– Seismic Isolators Height

• Rear power connection (only)


• Cooling system
– Shorter and wider
• Wind load capability
• Sound attenuated
• Decrease water leaks 8.1’

• Stationary use only


7.5’ 27.5’
TRANSFORMED BY 6 SIGMA Page 4
One powerful future.

Results

TRANSFORMED BY 6 SIGMA Page 5


One powerful future.

Features
Inspection Panel:
• For Exhaust System
• Cooling system

Pitched Roof , Flashing


New Louver Design
Shipping Features

Per Door:
2 Door Locks
3 Hinges Access:
• Muffler Drain
• Exhaust
insulation and
New Lifting Lug Design brackets
TRANSFORMED BY 6 SIGMA Page 6
One powerful future.

Features

Min. 42” working space behind the generator –


meets code requirements.

TRANSFORMED BY 6 SIGMA Page 7


One powerful future.

Technical Data – 60 Hz
60 Hz Sound Ambient
Attenuated Enclosure Strategy Capability *
ekW kVA SB/PP/CN °C °F
1000 1250 SB Low BSFC 50 122
910 1138 PP Low BSFC 49 120
830 1038 CN Low BSFC 51 124
1000 1250 SB Tier 2 50 122
910 1138 PP Tier 2 49 120
830 1038 CN Tier 2 25 77

*Calculated ambient capability

1000 KW 60 Hz
Sound Attenuated Enclosure Sound Pressure Levels dBA
Load 1m 7m ** 15m
100% 84.7 80.2 74.1
75% 83.9 79.8 74.1

** Hemisphrical Data

TRANSFORMED BY 6 SIGMA Page 8


One powerful future.

Technical Data – 50 Hz
50 Hz Sound Ambient
Attenuated Enclosure Strategy Capability *
ekW kVA SB/PP/CN °C °F
880 1100 SB Low BSFC 49 120
800 1000 PP Low BSFC 47 117
728 910 CN Low BSFC 34 93
880 1100 SB Low Emissions 32 90
800 1000 PP Low Emissions 35 95
728 910 CN Low Emissions 30 86

*Calculated ambient capability

1100 kVA 50 Hz
Sound Attenuated Enclosure Sound Pressure Levels dBA
Load 1m 7m 15m 10M **
100% 84.2 79.6 73.4 78.4
75% 84.1 79.2 73.4 78

** Hemisphrical Data

TRANSFORMED BY 6 SIGMA Page 9


One powerful future.

C32 Enclosure – Production


• Paint options - choice of 4 colors
– (Cat yellow, beige, grey, and white)
• Steel Sound Attenuated Enclosure
• Upgraded package mounted radiator
• CE Compliant
• Internally Mounted Silencer
• 150 mph Wind Load
• External E-Stop (left hand mounted)
• DC Lighting (option)

TRANSFORMED BY 6 SIGMA Page 12


One powerful future.

Fuel Tank Options


• 3 fuel tank sizes
– 2000, 1500, 1000 Gal
• Dual UL Listed
– UL - 142 (USA) Available by
– ULCS601 (Canada) May 1, 2010
• Ship loose
Fuel Supply & Return
Additional ports for
Emergency Venting draining and other
(Primary & Secondary
Tank)

Bottom Cable Stub up


Fuel Fill Location
TRANSFORMED BY 6 SIGMA Page 13
One powerful future.

Radiator Upgrade
• 10 inches (254 mm) shorter and 7 inches
(178 mm) wider than standard radiator.
• 4 piece fan guard improves
serviceability.
• ATAAC line routing improved to increase
battery accessibility.
• Increased fuel cooler capacity.
• Coolant level sight gage on back side of
the tank.
• All isolators are in line from front to rear
of package.

Enclosure radiator
available on open gensets
as high ambient option
TRANSFORMED BY 6 SIGMA Page 14
One powerful future.

Cooling Performance (Open Genset)


Ambient Capability
Rating Frequency Strategy Ambient
1100 kVA 50 Hz Low BSFC 54°C
1000 kVA 50 Hz Low BSFC 51°C
910 kVA 50 Hz Low BSFC 31°C
1100 kVA 50 Hz Low Emissions 34°C
1000 kVA 50 Hz Low Emissions 37°C
910 kVA 50 Hz Low Emissions 33°C
1000 ekW 60 Hz Low BSFC 53°C
910 ekW 60 Hz Low BSFC 52°C
830 ekW 60 Hz Low BSFC 54°C
1000 ekW 60 Hz Tier 2 53°C
910 ekW 60 Hz Tier 2 53°C
830 ekW 60 Hz Tier 2 28°C
*Calculated ambient capability at 300m

TRANSFORMED BY 6 SIGMA Page 15


One powerful future.

Differences: C27 and C32 Enclosures

Features / Product C27 - 800 ekW Standby C32 - 1000 ekW / 1000 kVA Standby

Dimensions 238” x 88” x 108” 330” x 91” x 97”


(Length x Width x Height) (Length x Width x Height)
Roof Flat roof Pitched roof (one sided)
Exhaust system 2 silencers in series One silencer
(1 Horiz. + 1 Vert.) (Horizontal)
Doors 6 doors 7 doors
Enclosure Weights 8165 kg (18,000 lbs) 11,217 kg (24,729 lbs)
Sound Pressure Level (at 7m) 76 dBA 80 dBA
Ambient Capability 51°C (60 Hz) 50°C (60 Hz) 49-50°C (50 Hz)
Wind Load Rating - 150 mph
ISO Container - Can be shipped

TRANSFORMED BY 6 SIGMA Page 16


One powerful future.

Compared Genset Enclosure Models

Cat Cummins Kohler Generac SDMO


C32 Acert DQFAC/DFHC 900REOZM MPSD900 X1100/X1100C
Standby: 1000 Standby: 900 Standby: 705- Standby: 900 Standby:
ekW eKW 970 eKW eKW 1100kVA
Prime: 910 ekW Prime: 818 eKW Prime: 640-915 Prime: 720 Prime:
eKW eKW 1000kVA

C32 Acert DQFAD/DFHD 1000REOZM MPS1000


Standby: 1100 Standby: 1000 Standby: 975- Standby: 1000
kVA eKW 1020 eKW eKW
Prime: 1000 Prime: 900 eKW Prime: 890-925 Prime: 825 eKW
kVA eKW

TRANSFORMED BY 6 SIGMA Page 17


One powerful future.

Enclosure Sound Levels

Cat Cummins Kohler Generac SDMO


1) Standard 1) Weather 1) Weather 1) Weather SA Enclosure-
 80 dB(A) Protective: Protective Protective dB(A) @ 7M
60Hz 88 to 93 (steel/ 2) Sound
aluminum)
86 dB(A) - 60Hz
 80 dB(A) dB(A) Attenuate 79 dB(A)– 1000
50Hz 2) Level I: 80 2) Sound
3) Aluminum kVA @
to 83 dB(A) Attenuate :
50HZ
75 dB(A)
3) Level II: 76 CONTENERGY-
to 78 dB(A) ISO container
dB(A) @ 1M
87 dB(A) – 50Hz

TRANSFORMED BY 6 SIGMA Page 18


One powerful future.

Specifications

Criteria Cat Cummins Kohler Generac SDMO


Dimensions 330’’x 91’’x 303’’ x 98’’ x 338’’ x 104”x 220” x 112” 252”x
97’’ 137’’ 168’’ x168” 85”x107”

Enclosure Stainless Stainless Steel Stainless Stainless Steel Stainless Steel


Hardware Steel (standard) or Steel (Std) or w/ Powder
(standard) Aluminum (standard) or Aluminum Coat paint
Material (optional) Aluminum (option)
(optional)
Small Stainless Stainless Steel Not Listed Stainless Steal Stainless Steel
Hardware Steel

Steel Gauge 14 gauge 12/14 gauge Not Listed 12/14 gauge 12 gauge

Roof Cambered/ Cambered Pitched Flat Flat


Pitched
TRANSFORMED BY 6 SIGMA Page 19
One powerful future.

Specifications

Criteria CAT Cummin Kohler Generac SDMO


s
Air Standard Standard Standard Standard Standard
Inlet/Outlet Louvers Fixed Louvers Louvers Louvers (6) Louvers

Motorized Optional
Louvers Gen 2 Optional on motorized Not Listed Not Listed
Air Inlet combination Option Option
louver/damper

Sound Non- Non- Acoustic Advanced 1-2’ Acoustic


Attenuating hydroscopic hydroscopic insulation acoustic material
Material (sound materials
enclosure)

TRANSFORMED BY 6 SIGMA Page 20


One powerful future.

Specifications

Criteria CAT Cummins Kohler Generac SDMO


Vibration seismic Spring Standard
Isolation spring vibration Not Listed Vibration Not Listed
vibration isolation Isolators
isolators system &
(standard) Optional
Seismic
Isolators
Wind Rating 150 mph 120 mph 120 mph 130 mph
(Caterpillar (standard) (standard) (standard) Not Listed
analysis) 150 mph 150 mph
(optional) (optional)
Amb Temp/ ~50 °C Not Listed
Altitude Ambient @ 40 C Ambient
300 M Not Listed Not Listed Temperature
TRANSFORMED BY 6 SIGMA Page 21
One powerful future.

Specifications

Criteria CAT Cummins Kohler Generac SDMO


Spillage Standard Standard Standard
Control exterior oil & flexible oil & interior oil & Not Listed Not Listed
coolant drains coolant drain coolant drain
with internal lines with
valves interior valves-
Optional:
exterior
Exhaust Critical
System Internally Enclosed Silencer, Enclosed Critical
mounted exhaust exhaust exhaust silencer Inside
silencer with silencer with connector system
rain cap rain cap with tailpipe
and rain cap

TRANSFORMED BY 6 SIGMA Page 22


One powerful future.

Enclosure Options

Criteria CAT Cummins Kohler Generac SDMO


Battery Installed–Gen 2 Optional Optional Not Listed Not offered
charger Option
Interior Lights DC - Optional Optional 120 V Standard AC Not Listed Not listed
AC – Gen 2 Optional DC Option
Space heater Gen 2 Not Listed Optional Not Listed Not Listed
Option Option
Ventilation Fan Gen 2 Not Listed Optional Not Listed Not Listed
Option Option
Emergency Standard (LH) Standard Not Listed Not Listed Standard
Stop Button Option Option
(exterior)
Rodent Standard Standard N/A Standard Not Listed
Barriers
Lockable Standard Standard Standard Standard Not Listed
Doors
TRANSFORMED BY 6 SIGMA Page 23
One powerful future.

Sales Support – Power Net


• Presentations
• Spec Sheets
• Links to:
– Photos
– Drawings
• Service Literature
• Video

TRANSFORMED BY 6 SIGMA Page 24


One powerful future.

Pricing List
Available in the SR5 Price List: C32 PGAG

Pricing
Feature Code Arrangement
ENCSA62 GP1494

Paint Colors
Color Feature Code
Cat Yellow ENCOYP1
White ENCOWP1
Beige ENCOBP1
Grey ENCOGP1

TRANSFORMED BY 6 SIGMA Page 25


One powerful future.

C32 Enclosure MGPP


• Program for next generation launched
– Increased level of sound attenuation
– Harsh environment
– Motorized louvers
– Cold weather option

• Product Definition collecting VOC


– Contact Dave Brandes with input

TRANSFORMED BY 6 SIGMA Page 26


One powerful future.

Questions?
One powerful future.

Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the “Power Edge” trade dress as well as
corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

www.Cat-ElectricPower.com

©2010 Caterpillar Inc.


LESE0019-00 (04/10) All rights reserved.

TRANSFORMED BY 6 SIGMA Page 28

You might also like