Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection System Assessment
Doble Engineering Company
Doble F6150 - 2004
Doble F6150 - 2004
Protection’s Role in Electricity Systems
Electricity Business is about providing a
vital service
When managed properly it is also about
making money
Protection Systems remove faulty plant
from the system via unplanned outages
Protection Systems operating correctly
minimise outages
Therefore they also maximise income
WHEN THEY WORK PROPERLY
Doble F6150 - 2004
What Are The Costs Of Failure?
Best Outcome No Loss of Load
Overtime Callout by Technicians
Less than $10,000 in costs
Extended Outage
Overhead Mains minor damage
Excessive Loss of Revenue
Greater than $100,000
Extended Outage + Plant Damage
Repair or Replace Logistics > $250K
Excessive Loss of Revenue >$100K
Catastrophic Failure – Transformer
>$2,000,000
Doble F6150 - 2004
How do we know if they work?
By Testing
What do you test?
How do you test?
When do you test?
Doble F6150 - 2004
Considerations
Primary Plant Vs Protection
Primary plant typically has fixed
operating parameters
CB Motion
Bushing insulation
Transformer Turns Ratio
Protection Relays & Schemes
Almost infinitely variable
Modern relays host multiple schemes
Doble F6150 - 2004
Protection Testing
Traditional
Electrical System was typically simpler to
operate
Less interconnections
More customer tolerance to outages
Check the Characteristic & Timing
Electromechanical Relays performance typically
changes with age
Testing Tools had limitations
Sinusoidal waveform generation - hopefully
Low Output Power
Unable to simulate real faults
Doble F6150 - 2004
Protection Testing – A New Philosophy
Prove
The “SETTING”
NOT
The “CHARACTERISTIC”
WHY?
Doble F6150 - 2004
Protection Testing – Schemes
Protection Systems are not isolated
components or relays working
independently
They ARE
Protection Systems are independent
components or relays working as a team
or scheme
Doble F6150 - 2004
Protection Testing – Modern Schemes
Use both electromechanical and
microprocessor based relays
Complex Characteristics are now possible
Multiple Characteristics operating
simultaneously
Characteristic Testing does NOT reveal if
these all work as expected
It is common to turn off elements to test
characteristics individually
Characteristic is RARELY wrong with
microprocessor Relays
So Why Test at all?
Doble F6150 - 2004
Protection Testing – Modern Schemes
Characteristic testing is still valid if there
is a problem identified.
How do we identify the problems
TEST THE SETTING
HOW?
Doble F6150 - 2004
Doble Test Philosophy
Test the “Complete Scheme”
Protection should operate when expected
ALSO
Protection should NOT operate when expected
Fault Simulation
Transients
Recorded using Digital Fault Recorders
Simulated (PSCAD Relay) PC software
Based on Actual Fault Data
State Simulations
Generated by Fault Study Programs
PSCAD Relay, Aspen, CAPE
Doble F6150 - 2004
Tools to Test the Complete Scheme
Transient Testing (Best)
DFR Recordings replayed subject the scheme to
actual faults under controlled conditions
All faults that can occur rarely happen in real life
Fault Simulation Software (PSCAD Relay)
Generate all possible faults for the scheme under test
Must be certain that the model information is accurate
Subjects the scheme to all possible distortions
State Simulation (Good)
Fault Simulations based on fundamental frequency
Easier to generate faults
Typically each STATE represents a particular stage
of a fault, Pre-Fault, Fault, Post-Fault
Doble F6150 - 2004
How to Test the Complete Scheme
End to End Testing
Complete Scheme can be tested with
real faults under controlled conditions
Using GPS Signals to synchronise
tests sets
Transient and State Simulation testing
Repeatable
Identify any performance issues
Doble F6150 - 2004
End to End Testing
Multiple Ends can be tested simultaneously
No Limit to the number of ends
Good method for simple signalling schemes
Distance (Intertripping etc..)
Differential
Only method for 3 and 4 ended feeders with complex
signalling schemes
Which Setting or Group of Settings are not
performing
Require High Power & Accurate Signal
Generation
What do you do after a problem is identified?
Doble F6150 - 2004
Problem Solving
This is where traditional methods work
After identifying a Setting Error it is essential
to determine if the Characteristic is correct.
Determine if characteristics are correct
Older E/M relays this can be an issue
Rare for microprocessor
But must be eliminated as a cause of error
If Characteristic is Good then Setting
MUST be recalculated
Doble F6150 - 2004
Desired Equipment Requirements
Flexible Configurations
4 voltages + 4 currents minimum
6 currents for differential schemes
Enough Power to Test the Scheme
At high current over 15 – 20 VA can be lost in the test
leads and panel wiring
Electromechanical O/C & E/F Relays can require > 300
VA
Therefore at least 320 VA
High Power is required across all test currents
Can be only be achieved by switchable ranges
Reliable & Guaranteed Output Waveforms
Designed for Field Operation and Support
Doble F6150 - 2004
How Doble Supports this Philosophy
Highly Configurable Test Equipment
High Power Sources
High Quality Output Waveforms
With Error & Distortion Detection
Multiple Ranges for Sources
Source Flexibility – up to 12 sources
Portable and Rugged
Suite of Software Tools
Applications Engineers
User Groups and Forums
Doble F6150 - 2004
The F6150 Power System Simulator
F6150 Power System Simulator
Three 150 VA Voltage/Low Current Sources
Three 150 VA Current Sources
Voltage Ranges - 75/150/300V
Low Current Ranges - 0.5/1.0/2.0A
Current Ranges - 7.5/15/30A
High Accuracy ±0.02%
Low Distortion ±0.02% THD
Six 75 VA V/Low I Sources
Six 75 VA I Sources
8 Logic Inputs
8 Logic Outputs (4x 0.5A & 4x 8A)
Aux DC Source 6 – 300 Vdc (Battery Simulator)
Transducer Inputs (20mA / 10V)
Doble F6150 - 2004
F6150 Sources Cont’d
Sync
Rectifiers
37.5 VA
350 V
DC Inverter
75 VA Sync
Relay
Rectifiers
AC 37.5 VA Switch
Line matrix
Input for Output
Sync
Range 1*150 VA
Inverter Rectifiers
37.5 VA
Selection or
75 VA
2*75 VA
Sync
Rectifiers
37.5 VA
170 kHz
Doble F6150 - 2004
F6150 Cont’d
12 Source Capability
Splitting the 150 VA to 2 (two) 75 VA sources
Paralleling of Current Sources
2 or 3 sources can be combined to make 60A
300VA or 90A 450VA sources
or 6A & 9A respectively
Transient Mode
Current Sources: 150% Power; 200% Range
Low Currents : 130% Power; 150% Range
Doble F6150 - 2004
F6150: Power
Convertible Voltage/Low Current Sources
150 VA continuous
195 VA for 1.5 seconds
Source Mode Range Comment
Voltage 50/60 Hz 75, 150, 300 Volts Continuous
Voltage DC 106, 212, 300 Volts Continuous
Current DC 1.41, 0.707, 0.354 A Continuous
Range Compliance
Current 50/60 Hz 0.5 A 300 Volts Continuous
1.0 A 150 Volts
2.0 A 75 Volts
Current 50/60 Hz 0.75 A 260 Volts 1.5 Seconds
1.5 A 130 Volts
3A 65 Volts
Doble F6150 - 2004
F6150: Power
Current Source
150 VA continuous
225 VA for 1.5 seconds
Source Range Compliance Comment
voltage
Current 7.5 A 20 V Continuous
50/60 Hz 15 A 10 V
30 A 5V
Current 15 A 15 V 1.5 Seconds
50/60 Hz 30 A 7.5 V
60 A 3.75 V
Current DC 5A 30 V Continuous
10 A 15 V
20 A 7.5 V
Doble F6150 - 2004
F6000: Power Output vs. Current
150
125
Output power
100
75
50
25
0
0 10 20 30
Output current
Doble F6150 - 2004
F6000: Power Output vs. Current
7.5 A Range: 150 VA
150
125
Output power
100
75
50
25
0
0 10 20 30
Output current
Compliance Voltage = 20 Volts
Doble F6150 - 2004
F6000: Power Output vs. Current
15 A Range: 150 VA
150
125
Output power
100
75
50
25
0
0 10 20 30
Output current
Compliance Voltage = 10 Volts
Doble F6150 - 2004
F6000: Power Output vs. Current
30 A Range: 150 VA
150
125
Output power
100
75
50
25
0
0 10 20 30
Output current
Compliance Voltage = 5 Volts
Doble F6150 - 2004
F6000: Power Output vs. Current
One Range 15 A 75 VA
150
125
Output power
100 VA
100
75
50
25 25 VA
0
0 10 20 30
Output current
Compliance Voltage = 5 Volts
Doble F6150 - 2004
Example of Relay Burden
Low tap setting 0.2 Amps typ. 3 VA
burden
Impedance = 75 Ohms (I2.R=VA)
Power required
at 5 times the tap (1 A) is 75 VA
at 10 times the tap (2 A) is 300 VA
Power required at 1 A is 75 VA and
power required at 2 A is 300 VA
Doble F6150 - 2004
F6300 High Current Source
Used with the F6150
Additional 2x 450 VA / 90A
Sources
3x 150VA @ 300V Voltages
and 3x 450 VA @ 90A Currents
3x150VA @ 300V Voltages
and 9x 150VA @ 30A Currents
or 9x 225VA @ 60A Transient Currents
for 1.5 seconds
Doble F6150 - 2004
F6000 Case Opened
Doble F6150 - 2004
Software
ProTesT
F6 TesT
TransWin
F6000 Control Panel
F6010 Handheld PC Mini-Controller
Meter and Transducer
PSCAD Relay
Doble F6150 - 2004
ProTesT Software
Software system for protective relay
testing and equipment maintenance.
SQL compliant Client server database
Improve productivity
Quality preventive maintenance
system
Includes all elements of Doble Testing
Philosophy
Doble F6150 - 2004
ProTesT Cont’d
Doble F6150 - 2004
Software Cont’d – F6 TesT
F6 TesT
Suite of powerful test templates
All relay types available
Impedance, Current, Voltage, Frequency
Differential, Directional
State Simulation
Ramp
Doble F6150 - 2004
F6 TesT Cont’d
Doble F6150 - 2004
Software Cont’d – TransWin
10 KHz playback rate
Comtrade binary or ASCII playback
Ethernet port for quick testing
Standalone Transwin application – free of charge
State change to simulate system condition
Dynamic test SSIMUL files playback
AIM viewer
Database driven TRANS macro
Playback *.Pl4 files
TRANS imports EMTP *.PL4 files
Editing capability for accurate simulation
Create user defined wave forms using DATC application
Create special wave shape Comtrade date files
Differential relay inrush wave forms
Doble F6150 - 2004
Software – Analog Input Module
New CPU ($2K Upgrade)
AIM Module ($2.8K Opt)
Recording of 8 channels
of analog/digital data
GPS recorded records
are time stamped
Acquisition of pre-fault,
fault, and post-fault data
in COMTRADE format
User defined trigger
controls and scaling
factors
Doble F6150 - 2004
Software – F6000 Control Panel
Ramp and AutoSense for testing
without manual error
Fault Rotate for testing 3-Phase
relays without wiring
modification
Quick testing without the need
for elaborate test plan
8 timers
Control of 8 inputs and outputs
Virtual front panel controls
Real time phasor display shows
voltage and current relationships
Drag and Drop feature of phasor
display simplifies complex relay
testing
Doble F6150 - 2004
Software Continued
F6010 Handheld PC Mini-Controller
Fast Testing
No need for PC to start up
Supports Control Panel &
Basic Macros Testing
Doble F6150 - 2004
Software Continued
PSCAD Relay
Power System
Modeling for
the Protection
Test Engineer
Graphical
Interface
Up to 55 Nodes
PSCAD Relay
Infinite Nodes
for full version
PSCAD
Doble F6150 - 2004
Meter and Transducer Testing
Quick Testing of
Transducers
High Accuracy
User Friendly
interface
Doble F6150 - 2004
Support & Training
Doble Application Engineers
Product Training at Your Workplace
Regional Repair Service
Not returned to factory
Reducing Post Warranty Repair Costs
Doble F6150 - 2004
Applications Engineers
Software Specialist
Joe Pompeo
Testing Specialists
Dennis Tierney
Yakov Knobel
Jun Verzosa
Fang He
Over 140 years of worldwide
industry experience
Soon to have time zone based
Applications Engineers
Doble F6150 - 2004
Conferences
Doble Client Conferences
Largest Industry asset maintenance
based conference in the world
ProTesT User Group
Meetings in Australia and USA annually
NEW Regional Seminars
Covering Insulation, CB’s and Protection
Doble F6150 - 2004
Why Doble Engineering?
More Than 9000 Protection Test
Instruments Sold Worldwide
Why?
Quality
Support – Conferences & Applications
Creating equipment that meets
requirements & exceed expectations
Reputation – The Industry Standard
Doble F6150 - 2004
F6150 Benefits Vs Competition
Most Configurations
Highest Available Power (VA &Ranges)
Highest Guaranteed Accuracy
Lowest Guaranteed Distortion
Built for Rough Treatment
Field Upgradeable
Field Serviceable
Software to test your way
Local Backup/Support Service
Local Peer Groups for Support
Doble F6150 - 2004
Highest Power 2 Unit System Available
Doble F6150 - 2004
Continuous Improvement
We build good mouse traps
But there is always a smarter mouse
We are ALWAYS working to IMPROVE
Doble F6150 - 2004
Thank-you for Listening
Doble F6150 - 2004