ADVC WSOS5 Modbus R2
ADVC WSOS5 Modbus R2
Internal
Modbus communications - Overview
There are a number of steps required in order to enable the ADVC to communicate with a
master station via Modbus:
Modbus
Internal
1 - Make MODBUS available
MAIN MENU
Operator menu
Method 1: flexVUE panel
Engineer menu
Alerts menu
• DNP3 is enabled via the flexVUE panel after selecting the MENU key and using the
arrow keys to navigate to:
ENGINEERING MENU
Protection menu → ENGINEER MENU
Configuration menu
↕
→ CONFIGURATION MENU
Power quality
Telemetry menu → FEATURE SELECTION
Automation menu
→ COMMUNICATIONS
Measurements menu
→ Modbus Available / Not Available
COMMUNICATIONS
Modbus Available COMMUNICATIONS
Confidential Property of Schneider Electric | Page 3
TCP/IP Available
Internal
1 - Make Modbus available
• Display / Configuration / Feature Selection (or selecting Feature Selection in Switchgear Explorer) and ticking Modbus Available check box
Internal
2 – Select the MODBUS port ADVC2
● The Advanced Controller has 8 communications ports, 7 of which can be selected & configured
for transmission of Modbus messages (the USB B type port is dedicated to WSOS5 only)
Internal
2 – Select the Modbus port ADVC3
● The Advanced Controller has 8 communications ports, 7 of which can be selected & configured
for transmission of Modbus messages (the USB B type port is dedicated to WSOS5 only)
Internal
3 – Assign Modbus to port
Method 2: WSOS5
• select the required port e.g. LAN1 (or other port ) and OK
• Note that if you disable Modbus you will have to select the port again when re-enabled
Confidential Property of Schneider Electric | Page 7
Internal
4 – Configure port settings
• Input / select values as required to configure the port for Modbus communications
• Note that fields in yellow colour are for information and fields in white are configurable settings
Confidential Property of Schneider Electric | Page 8
Internal
5 – Configure Modbus settings
Internal
5 – Configure Modbus settings
• The Communications Configuration Screen provides access to the other Modbus
configuration screens, and allows the selection of the Port used for Modbus
Communications (via the Switchgear Port field)
Internal
Protocol Map Function
• The configurable protocol map tool allows the user to
• Once created a map can be selected for writing to a compatibly configured controller
• Configurable Protocols
• Choose the protocol to be used • Choose the oldest Firmware version that has all the required features and
functions & select OK
• Open the tool box by selecting the hammer & Spanner Icon
• Single click on points in the took box for information on the function
• The port number is generally left at defaults unless there is a very specific reason
to change it
• Enable the check master IP address to only accept control commands for a Master
using the configured IP address
Internal
Questions?
Internal
Confidential Property of Schneider Electric | Page 26