4-Amazon VRF Installation Presentation - 20130325
4-Amazon VRF Installation Presentation - 20130325
Outdoor
Cond. Coil
Liquid Line
Accumulator
Indoor
Reversing
Valve
Tc1
Inverter
Compressor
Suction Line
Separator
VRF Refrigeration Cycle - Heating
Subcooler Coil
LEV
Tc2
Outdoor
Evap. Coil
Liquid Line
Accumulator
Indoor
Reversing
Valve
Tc1
Inverter
Compressor
Suction Line
Separator
Outdoor Parts Identification
Inverter
Liquid Line
Compressor
Accumulator
Suction Line
Separator
2nd Subcooler
Outdoor Parts Identification
Reversing Oil
Valve Separator
Outdoor Parts Identification
Oil Port
Liquid Port
PCB
Gas Port
Installation
Installation
A road map for Installation,
Startup and Commissioning
CONTENT
1 • Indoor unit installation
4 • Wiring
5 • Drain pipe
6 • Leakage test
Warning: Please set Indoor DIP Switches before installing Indoor units into its final position
Installation Quick Guides
4. Outdoor installation
4.1 Outdoor unit foundation work
4.2 Outdoor unit installation
4.3 Refrigerant piping connection
4.4 Leakage test
4.5 Vacuum drying
4.6 Additional refrigerant charging
5. Installation double check, indoor, outdoor, piping, and wiring
Installation
Indoor Installation
Indoor unit installation – Instructions
Level meter
Indoor unit installation – Instructions
Dual nuts should be adopted to fix the indoor unit under the ceiling.
Pack the indoor unit with plastic bag after hoisting to protect them from dust
entering.
Indoor unit installation – Instructions
Typical mistakes
Air outlet too close to wall Full thread hooks not vertical
Indoor unit installation – Four Way Cassette
YVKVXH028/036/045WAR--GX + PB-700IB
Unit size: 570*570*260
Panel size: 700*700*60
Model 028 036/045
Liquid pipe OD ( mm) Φ6.35 Φ6.35
Gas pipe OD. (mm) Φ9.52 Φ12.7
Drain hose (mm) Φ32 (Built-in Pump)
YVKVXH056/071/080WAR--GX+ PB-950JB
Unit size: 840*840*240
Panel size: 950*950*80
Model AB18 AB24/28
Liquid pipe OD ( mm) Φ6.35 Φ9.52
Gas pipe OD. (mm) Φ12.7 Φ15.88
Drain hose (mm) Φ32 (Built-in Pump)
YV8VXH028/036/045/056WAR--GX+ P2B-1055 IB
Unit Size :817*280*620;
Panel: 1055*80*680;
Model 028 036/045/056
Liquid pipe OD ( mm) Φ6.35 Φ6.35
Gas pipe OD. (mm) Φ9.52 Φ12.7
Drain hose (mm) Φ32 (Built-in Pump)
YVFVXH 028/036/045/056/071WAR--GX
Unit size: 990*655*199
Model 028 036/045/056 071
Liquid pipe OD Φ6.35 Φ6.35 Φ9.52
( mm)
Gas pipe OD. (mm) Φ9.52 Φ12.7 Φ15.88
Drain hose (mm) Φ20 (Without Pump & Optional for External
Pump)
YVFVXH080/090/112/140WAR—GX
Unit size: 1580*700*240
Model 112/140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ25 (Without Pump
& Optional for
External Pump)
AD L dimensions
AD L dimensions
YVEVXH056/071/080WAR--GX
Unit size: 990*650*300
Static pressure: 50/96Pa
Model 056 071/080
Liquid pipe OD ( mm) Φ6.35 Φ9.52
Gas pipe OD. (mm) Φ12.7 Φ15.88
Drain hose (mm) Φ32 (Built-in Pump)
YVEVXH090/112/140WAR--GX
Unit size: 1410*645*350
Static pressure: 80/120Pa
Model 090/112/140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ32 (Without Pump &
AD M dimensions Optional for External
Pump)
YVGVXH056/071/080WAR--GX
Unit size: 970*875*360
Static pressure: 100~196Pa
Model 056 071/080
Liquid pipe OD ( mm) Φ6.35 Φ9.52
Gas pipe OD. (mm) Φ12.7 Φ15.88
Drain hose (mm) Φ32 (Without Pump & Optional
for External Pump)
YVGVXH090/112/140WAR--GX
Unit size: 1350*875*360
Static pressure: 100~196Pa
Model 090/112/140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ32 (Without Pump &
Optional for External
Pump)
Note: Refrigerant pipe is flare connection
Indoor unit installation-HSP Duct
YVGVXH226/280WAR--GX
Unit size: 1570*830*360
Static pressure: 100~196Pa
Model 226/280
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ25.4
Drain hose (mm) Φ32 (Without Pump &
Optional for External
Pump)
AD H dimensions
Note: Refrigerant pipe is flare connection, with exception for Φ25.4 with braze connection
Indoor unit installation-Console
YV5VXH022/028/036/056WAR--FX
Unit size: 720*255*640
Model ALL
Liquid pipe OD ( mm) Φ6.35
Gas pipe OD. (mm) Φ12.7
Drain hose (mm) Φ16.5 (Without Pump
& Not optional for
External Pump)
YVHVXH022/028/036/045WAR--FX
Unit size: 938*187*265
Model 022/028/036/045
Liquid pipe OD ( mm) Φ6.35
Gas pipe OD. (mm) Φ12.7
Drain hose (mm) Φ16.8 (Without Pump
& Not optional for
External Pump)
YVHVXH056/071WAR—FX
Unit size: 1046*239*299
Model 056/071
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ16.8 (Without Pump
& Not optional for
External Pump)
Note: Refrigerant pipe is flare connection
Indoor unit installation-Fresh Air Unit
YV4VXH140WAR--GX
Unit size: 1350*875*360
Model 140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ32 (Without Pump &
optional for External
Pump)
YV4VXH226/280WAR--GX
Unit size: 1046*239*299
Model 226/280
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ25.4
Drain hose (mm) Φ32 (Without Pump &
AD P dimensions optional for External
Pump)
Note: Refrigerant pipe is flare connection, with exception for Φ25.4 with braze connection
Indoor unit installation – Fresh Air Unit
When installing modular outdoor units together with normal indoor
units:
C: Outdoor unit capacity
新风机
Fresh
Air
Unit
不推荐使用
Not recommend to Recommend to connect
install more than one one Fresh Air Unit to one
Fresh Air Units in one modular Outdoor unit
outdoor system(either with a indoor capacity of
modular or up to 100% compared to
combination system) the outdoor unit
Indoor unit installation-Heat Recovery Ventilator
YV6VXH015/026CAR—GX
Unit size: 553x813x276
Model 015/026
Liquid pipe OD ( mm) /
Gas pipe OD. (mm) /
Drain hose (mm) /
YV6VXH080/100CAR—GX
Unit size: 1112x1216x387
Model 080/1000
Liquid pipe OD ( mm) /
Gas pipe OD. (mm) /
Drain hose (mm) /
Outdoor Installation
Outdoor unit installation
Caution:
1 、 The unit should be placed far away the flammable, explosive or oily place.
2 、 The noise and the outlet air should not affect the neighbors.
3 、 There should be enough space for air inlet, air outlet and maintenance around
the unit. Fluent ventilation and good heat release. If there is obstacle above the
unit, it must be over 2m away from the air outlet, or there should be extended duct.
4 、 The floor and the steel bracket should be strong enough to afford the 1.5 times
heavier than the unit running weight. The floor and the steel bracket should be
horizontal.
5 、 The floor should be over 100mm higher than the ground, and there should be the
drainage around to ensure the unit not being immersed in the water.
6 、 The unit should be fixed firmly with the anti-vibration cushion.
7. 、 The outdoor should be as near the indoor as possible. Shorten the pipe and
decrease the bend pipe. Pipe length can not exceed the permitted range.
8 、 Try best to install the outdoor units on the same horizontal level, even if different
level for outdoor units is allowed in service manual.
Outdoor unit installation
The distance between two outdoor units in the same line, the distance
from unit to the wall and units line to units line must follow the
Instructions showing hereunder:
Outdoor unit installation
Outdoor unit position (side view)
At least 2m
Outdoor unit installation
Outdoor unit
Foundation
Installation
Piping Installation
Refrigerant pipe installation
For the piping diameter and branch pipe selection, please refer to the
Selection software report.
Refrigerant pipe installation
Should be
less than
At least 2m
200mm
At least
200mm Should be less than 2m
*The distance between Oil
trap and adjacent outdoor
branch pipe
above
below
Refrigerant pipe installation
Outdoor Branch Pipe for combination of outdoor units
HZG-20A is used for 2 outdoor modules combination.
HZG-30A is used for 3 outdoor modules combination.
Outdoor Branch Pipe Size
Outdoor Branch Pipe Refrigerant pipe installation
Refrigerant pipe installation
Manifold pipe for indoor units.
You must cut branch pipe and manifold pipe at middle of each
section.
Adobe Acrobat
Document
Refrigerant pipe for installation
Connecting pipe diameter(mm)
Capacity of indoor total ( ×100W ) Gas pipe Liquid pipe
~28 φ9.52 φ6.35
29~70 φ12.7 φ6.35
70~168 φ15.88 φ9.52
168 ~ 224 φ19.05 φ9.52
224~330 φ22.22 φ9.52
330~470 φ28.58 φ12.7
470~710 φ28.58 φ15.88
710~1010 φ31.8
φ19.05
1010~ φ38.1
③
Refrigerant pipe installation
Two types of pipe connection
You must use the pipe adaptor if the pipe diameter is bigger than
19.05. The pipe can not be expanded.
Refrigerant pipe installation
Connection: brazing !!!
• Nitrogen MUST be used to avoid brazing slag.
• Pressure of nitrogen charged is 0.2 bar.
• Leave only one exit where is brazing point. The others branch should be
sealed.
Refrigerant pipe installation
Cleaning the pipe:
Procedures
From far to near (sequence: ①-②-③-④-⑤-⑥ )
⑥ ⑤ ④ ③ ①
Note
1. When flushing one pipe, the other pipes need to be sealed.
2. After flushing, remember to seal all the pipes.
3. Suggest to do the leakage test for piping works before connecting to
outdoor and indoor units
Refrigerant pipe installation
Diameter (mm) ≤ 20 20 ~ 40 ≥ 40
When the liquid pipe and gas pipe are hung up together, it is determined
by the diameter of liquid pipe.
Refrigerant pipe installation
The insulation of liquid pipe and gas pipe must be separately insulated
Liquid pipe shall be heat insulated at all times and the only exception
when the customer is totally sure the unit will only deliver
COOLING.
Refrigerant pipe installation
Block the nozzle of the pipe when make it through the insulation material.
insulation material.
Ri Wrong
gh
t
Copper pipe
Insulation
Refrigerant pipe installation
Typical mistake.
Obvious no insulation
Drain pipe installation
Exhaust outlet
≥ 1% Condensate pipe
Note
1. If the gradient < 1% , then select drainage pipe with bigger
diameter
2. The length of drainage pipe should be as short as possible
3. The drainage pipe should be independent with other water pipe
4. Never put the drainage pipe together with dirty water pipe
Drain pipe installation
Drainage with pump:
- Lifting the pipe on the pump outlet to form the lean pipe .
Make a lift
for easy drainage
Drain pipe installation
Drainage with pump:
100mm
50mm
plug
plug
If the pressure at the connection of the drain pipe is negative, it needs to
set a drainage trap.
A plug should be installed to make clean easy
Drain pipe installation
To avoid the water flow back to the indoor unit, the branch pipe from the
drainage pan should be connected to the main pipe from the top.
To avoid the bending, supporter must be installed with the drainage pipe.
The distance between each supporter for horizontal pipe should be 1~1.5m.
Drain pipe installation
Wiring Installation
Wiring
Communication wiring
L1 L2 L3 N
Slave 2 Slave 1 Master unit
MCB
L1 L2 L3
Slave 2 Slave 1 Master unit
MCB
MCB
Notes: Use one main power supply for all indoor units
Wiring
L1 N
MCB T
Notes: Use one main power supply for all indoor units
Wiring
4 • Wiring
5 • Drain pipe
6 • Leakage test
For example:
Temp. when charging N2: 24 ℃
Gas side
Liquid side
Oil side
Additional Refrigerant Charging
Make sure the leakage test, vacuum dry, pipe insulation has
been finished
Note:
1. Over much refrigerant will cause liquid harmer.
2. Record the actual amount of additional refrigerant for further
reference.
Additional refrigerant charging
Charge
Outdoor unit
ON ON ON
R410A
Liquid side
Installation
A revisit of roadmap for
Installation, Startup and
Commissioning