4-Amazon VRF Installation Presentation - 20130325

The document provides instructions for installing an Amazon VRF system. It discusses installing the indoor units, including positioning, leveling, supports, and connections for refrigerant piping and drain piping. Tables are included specifying the pipe diameters and connections for different indoor unit models. The outdoor unit installation is also summarized, covering the foundation, installation, refrigerant piping connection, leak testing, vacuum drying and additional refrigerant charging.

Uploaded by

Sony C
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
140 views93 pages

4-Amazon VRF Installation Presentation - 20130325

The document provides instructions for installing an Amazon VRF system. It discusses installing the indoor units, including positioning, leveling, supports, and connections for refrigerant piping and drain piping. Tables are included specifying the pipe diameters and connections for different indoor unit models. The outdoor unit installation is also summarized, covering the foundation, installation, refrigerant piping connection, leak testing, vacuum drying and additional refrigerant charging.

Uploaded by

Sony C
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 93

Amazon VRF Installation

Refrigeration Cycle &


Outdoor Parts Identification
VRF Refrigeration Cycle - Cooling
Subcooler Coil
LEV
Tc2

Outdoor
Cond. Coil

Liquid Line
Accumulator
Indoor

Reversing
Valve

Tc1

Oil Separator Indoor


Evap. Coil

Inverter
Compressor
Suction Line
Separator
VRF Refrigeration Cycle - Heating
Subcooler Coil
LEV
Tc2

Outdoor
Evap. Coil

Liquid Line
Accumulator
Indoor

Reversing
Valve

Tc1

Oil Separator Indoor


Cond. Coil

Inverter
Compressor
Suction Line
Separator
Outdoor Parts Identification

Inverter
Liquid Line
Compressor
Accumulator

Suction Line
Separator

2nd Subcooler
Outdoor Parts Identification

Reversing Oil
Valve Separator
Outdoor Parts Identification

Oil Port

Liquid Port

PCB
Gas Port
Installation
Installation
A road map for Installation,
Startup and Commissioning
CONTENT
1 • Indoor unit installation

2 • Outdoor unit installation

3 • Refrigerant pipe installation

4 • Wiring

5 • Drain pipe

6 • Leakage test

7 • Additional refrigerant charging


Installation Quick Guides

1. Drafting of diagram, select the installing place including the


wiring and piping
2. Pre-installation, including pipe protective sleeves, hooks,
supports, etc.
3. Indoor installation
3.1 Indoor DIP Switch settings
3.2 Indoor unit installation
3.3 Refrigerant piping installation
3.4 Drain piping installation
3.5 Duct work when install the duct indoor unit
3.6 Heat insulation work, including refrigerant pipe and drain
pipe
3.7 Electric wiring work

Warning: Please set Indoor DIP Switches before installing Indoor units into its final position
Installation Quick Guides

4. Outdoor installation
4.1 Outdoor unit foundation work
4.2 Outdoor unit installation
4.3 Refrigerant piping connection
4.4 Leakage test
4.5 Vacuum drying
4.6 Additional refrigerant charging
5. Installation double check, indoor, outdoor, piping, and wiring
Installation

Indoor Installation
Indoor unit installation – Instructions

 Choose the right position to hoist


the indoor unit to make sure the
ventilation of inlet and outlet is
fluent
 All indoor units must be hanged
in horizontal, Gradient is NOT
allowed
 Use level meter to keep the
indoor unit horizontally .
Reduce the running noise
Avoid the condensate water spill
from the water pan

Level meter
Indoor unit installation – Instructions

 Supports must be strong enough. 4 Supports


for indoor
The supports should be full thread
unit
hooks, and their diameters should
be ≥ 10mm.

Full thread hooks


Indoor unit installation – Instructions

Dual nuts should be adopted to fix the indoor unit under the ceiling.

Dual nuts Single nut


Indoor unit installation – Instructions

Pack the indoor unit with plastic bag after hoisting to protect them from dust
entering.
Indoor unit installation – Instructions

Typical mistakes

Air outlet too close to wall Full thread hooks not vertical
Indoor unit installation – Four Way Cassette

YVKVXH028/036/045WAR--GX + PB-700IB
Unit size: 570*570*260
Panel size: 700*700*60
Model 028 036/045
Liquid pipe OD ( mm) Φ6.35 Φ6.35
Gas pipe OD. (mm) Φ9.52 Φ12.7
Drain hose (mm) Φ32 (Built-in Pump)

YVKVXH056/071/080WAR--GX+ PB-950JB
Unit size: 840*840*240
Panel size: 950*950*80
Model AB18 AB24/28
Liquid pipe OD ( mm) Φ6.35 Φ9.52
Gas pipe OD. (mm) Φ12.7 Φ15.88
Drain hose (mm) Φ32 (Built-in Pump)

Note: Refrigerant pipe is flare connection


Indoor unit installation – Four Way Cassette

YVKVXH090/112/140WAR--GX Model YVKVXH090/112/140


+ PB-950JB Liquid pipe OD ( mm) Φ9.52
Unit size: 840*840*280
Panel size: 950*950*80 Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ32 (Built-in Pump)

Note: Refrigerant pipe is flare connection


Indoor unit installation – Two Way Cassette

YV8VXH028/036/045/056WAR--GX+ P2B-1055 IB
Unit Size :817*280*620;
Panel: 1055*80*680;
Model 028 036/045/056
Liquid pipe OD ( mm) Φ6.35 Φ6.35
Gas pipe OD. (mm) Φ9.52 Φ12.7
Drain hose (mm) Φ32 (Built-in Pump)

Note: Refrigerant pipe is flare connection


Indoor unit installation-Floor Ceiling

YVFVXH 028/036/045/056/071WAR--GX
Unit size: 990*655*199
Model 028 036/045/056 071
Liquid pipe OD Φ6.35 Φ6.35 Φ9.52
( mm)
Gas pipe OD. (mm) Φ9.52 Φ12.7 Φ15.88
Drain hose (mm) Φ20 (Without Pump & Optional for External
Pump)

YVFVXH080/090/112/140WAR—GX
Unit size: 1580*700*240
Model 112/140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ25 (Without Pump
& Optional for
External Pump)

Note: Refrigerant pipe is flare connection


Indoor unit installation-Slim LSP Duct

AD L dimensions

Model 020/028 036


YV3VXH022/028/036WAR--GX Liquid pipe OD ( mm) Φ6.35 Φ6.35
Unit size: 610*500*185 Gas pipe OD. (mm) Φ9.52 Φ12.7
Static pressure: 30Pa
Drain hose (mm) Φ24(Built-in Pump)

Model 045/056 071


YV3VXH045/056/071WAR--GX Liquid pipe OD ( mm) Φ6.35 Φ9.52
Unit size: 1105*500*185 Gas pipe OD. (mm) Φ12.7 Φ15.88
Static pressure: 30Pa
Drain hose (mm) Φ24(Built-in Pump)

Note: Refrigerant pipe is flare connection


Indoor unit installation-LSP Duct

AD L dimensions

Model 020/028 036


YVDVXH022/028/036WAR--GX Liquid pipe OD ( mm) Φ6.35 Φ6.35
Unit size: 610*483.5*220 Gas pipe OD. (mm) Φ9.52 Φ12.7
Static pressure: 0/20Pa
Drain hose (mm) Φ24 (Without Pump & Optional
for External Pump)

Model 045/056 071


YVDVXH045/056/071WAR—GX Liquid pipe OD ( mm) Φ6.35 Φ9.52
Unit size: 1105*483.5*220 Gas pipe OD. (mm) Φ12.7 Φ15.88
Static pressure: 0/20Pa
Drain hose (mm)
Φ24 (Without Pump & Optional
for External Pump)
Note: Refrigerant pipe is flare connection
Indoor unit installation-MSP Duct

YVEVXH056/071/080WAR--GX
Unit size: 990*650*300
Static pressure: 50/96Pa
Model 056 071/080
Liquid pipe OD ( mm) Φ6.35 Φ9.52
Gas pipe OD. (mm) Φ12.7 Φ15.88
Drain hose (mm) Φ32 (Built-in Pump)

YVEVXH090/112/140WAR--GX
Unit size: 1410*645*350
Static pressure: 80/120Pa
Model 090/112/140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ32 (Without Pump &
AD M dimensions Optional for External
Pump)

Note: Refrigerant pipe is flare connection


Indoor unit installation-HSP Duct

YVGVXH056/071/080WAR--GX
Unit size: 970*875*360
Static pressure: 100~196Pa
Model 056 071/080
Liquid pipe OD ( mm) Φ6.35 Φ9.52
Gas pipe OD. (mm) Φ12.7 Φ15.88
Drain hose (mm) Φ32 (Without Pump & Optional
for External Pump)

YVGVXH090/112/140WAR--GX
Unit size: 1350*875*360
Static pressure: 100~196Pa
Model 090/112/140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ32 (Without Pump &
Optional for External
Pump)
Note: Refrigerant pipe is flare connection
Indoor unit installation-HSP Duct

YVGVXH226/280WAR--GX
Unit size: 1570*830*360
Static pressure: 100~196Pa
Model 226/280
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ25.4
Drain hose (mm) Φ32 (Without Pump &
Optional for External
Pump)

AD H dimensions

Note: Refrigerant pipe is flare connection, with exception for Φ25.4 with braze connection
Indoor unit installation-Console

YV5VXH022/028/036/056WAR--FX
Unit size: 720*255*640

Model ALL
Liquid pipe OD ( mm) Φ6.35
Gas pipe OD. (mm) Φ12.7
Drain hose (mm) Φ16.5 (Without Pump
& Not optional for
External Pump)

Note: Refrigerant pipe is flare connection


Indoor unit installation-High Wall

YVHVXH022/028/036/045WAR--FX
Unit size: 938*187*265

Model 022/028/036/045
Liquid pipe OD ( mm) Φ6.35
Gas pipe OD. (mm) Φ12.7
Drain hose (mm) Φ16.8 (Without Pump
& Not optional for
External Pump)

YVHVXH056/071WAR—FX
Unit size: 1046*239*299

Model 056/071
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ16.8 (Without Pump
& Not optional for
External Pump)
Note: Refrigerant pipe is flare connection
Indoor unit installation-Fresh Air Unit

YV4VXH140WAR--GX
Unit size: 1350*875*360

Model 140
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ15.88
Drain hose (mm) Φ32 (Without Pump &
optional for External
Pump)

YV4VXH226/280WAR--GX
Unit size: 1046*239*299
Model 226/280
Liquid pipe OD ( mm) Φ9.52
Gas pipe OD. (mm) Φ25.4
Drain hose (mm) Φ32 (Without Pump &
AD P dimensions optional for External
Pump)

Note: Refrigerant pipe is flare connection, with exception for Φ25.4 with braze connection
Indoor unit installation – Fresh Air Unit
When installing modular outdoor units together with normal indoor
units:
C: Outdoor unit capacity

Fresh air General indoor


unit unit capacity B
capacity A
Fresh air C ×80%≤ ( A+B )≤ C×100%
unit + & A ≤ C×30%
general
Indoor unit installation – Fresh Air Unit
When installing either modular or individual outdoor units you can
and can’t do the following:
NOT RECOMMENDED RECOMMENDED

新风机
Fresh
Air
Unit
不推荐使用
Not recommend to Recommend to connect
install more than one one Fresh Air Unit to one
Fresh Air Units in one modular Outdoor unit
outdoor system(either with a indoor capacity of
modular or up to 100% compared to
combination system) the outdoor unit
Indoor unit installation-Heat Recovery Ventilator

YV6VXH015/026CAR—GX
Unit size: 553x813x276

Model 015/026
Liquid pipe OD ( mm) /
Gas pipe OD. (mm) /
Drain hose (mm) /

YV6VXH080/100CAR—GX
Unit size: 1112x1216x387

Model 080/1000
Liquid pipe OD ( mm) /
Gas pipe OD. (mm) /
Drain hose (mm) /

Note: Heat Recovery Media Element Is Replacement As Spare part


Installation

Outdoor Installation
Outdoor unit installation
Caution:
1 、 The unit should be placed far away the flammable, explosive or oily place.
2 、 The noise and the outlet air should not affect the neighbors.
3 、 There should be enough space for air inlet, air outlet and maintenance around
the unit. Fluent ventilation and good heat release. If there is obstacle above the
unit, it must be over 2m away from the air outlet, or there should be extended duct.
4 、 The floor and the steel bracket should be strong enough to afford the 1.5 times
heavier than the unit running weight. The floor and the steel bracket should be
horizontal.
5 、 The floor should be over 100mm higher than the ground, and there should be the
drainage around to ensure the unit not being immersed in the water.
6 、 The unit should be fixed firmly with the anti-vibration cushion.
7. 、 The outdoor should be as near the indoor as possible. Shorten the pipe and
decrease the bend pipe. Pipe length can not exceed the permitted range.
8 、 Try best to install the outdoor units on the same horizontal level, even if different
level for outdoor units is allowed in service manual.
Outdoor unit installation
The distance between two outdoor units in the same line, the distance
from unit to the wall and units line to units line must follow the
Instructions showing hereunder:
Outdoor unit installation
Outdoor unit position (side view)

At least 2m
Outdoor unit installation

Outdoor unit

The unit should be fixed firmly


with the anti-vibration cushion

Foundation
Installation

Piping Installation
Refrigerant pipe installation
For the piping diameter and branch pipe selection, please refer to the
Selection software report.
Refrigerant pipe installation

 For storing the copper pipes:


1. If pipes will be used soon, nozzle should be sealed by plastic bag or tape.
2. If pipes will be stored for a long time, the pipes should be charged into
0.2~0.5MPa Nitrogen and the nozzle should be sealed by welding.
indoor units the maximum height should be 50m
Refrigerant pipe installation
When the outdoor unit is installed above the

Should be
less than
At least 2m
200mm
At least
200mm Should be less than 2m
*The distance between Oil
trap and adjacent outdoor
branch pipe

indoor units the maximum height should be 40m


Note:
a. The connection pipe among outdoors can’t be higher than the outdoor unit stop valve

When the outdoor unit is installed below the


to avoid over oil return to compressor
b. The piping should be installed horizontal or with slope toward the interior units

above

below
Refrigerant pipe installation
Outdoor Branch Pipe for combination of outdoor units
HZG-20A is used for 2 outdoor modules combination.
HZG-30A is used for 3 outdoor modules combination.
Outdoor Branch Pipe Size
Outdoor Branch Pipe Refrigerant pipe installation
Refrigerant pipe installation
Manifold pipe for indoor units.

Manifold pipe selection:

Manifold pipe model


Refrigerant pipe installation

You must cut branch pipe and manifold pipe at middle of each
section.

Adobe Acrobat
Document
Refrigerant pipe for installation
Connecting pipe diameter(mm)
Capacity of indoor total ( ×100W ) Gas pipe Liquid pipe
~28 φ9.52 φ6.35
29~70 φ12.7 φ6.35
70~168 φ15.88 φ9.52
168 ~ 224 φ19.05 φ9.52
224~330 φ22.22 φ9.52
330~470 φ28.58 φ12.7
470~710 φ28.58 φ15.88
710~1010 φ31.8
φ19.05
1010~ φ38.1

Connecting pipe thickness(mm)

Flexible copper pipe Straight copper pipe


Refrigerant pipe installation
1- You MUST cut the pipe with special cutter. The saw is NOT allowed
to use.
2- You must clean the pipe end inside after cutting.
3- The pipe must be sealed before welding or flared. MAKE SURE the
pipe inside is dry, clean, no leakage.


Refrigerant pipe installation
Two types of pipe connection

1- Flared ( connect with indoor unit except


YVGVXH226/280WAR—GX & YV4VXH226/280WAR—GX gas pipe)

The following flared cup is not eligible.


Refrigerant pipe installation
Connection with flared pipe and unit.
Two spanners are required to avoid pipe distortion.
Refrigerant pipe installation
2- Couple joint (pipe in pipe)

Diameter (mm) Cupular deepth (mm)


φ6.35 1
φ9.52 1
φ12.7 1
φ15.88 1
φ19.05 1

You must use the pipe adaptor if the pipe diameter is bigger than
19.05. The pipe can not be expanded.
Refrigerant pipe installation
Connection: brazing !!!
• Nitrogen MUST be used to avoid brazing slag.
• Pressure of nitrogen charged is 0.2 bar.
• Leave only one exit where is brazing point. The others branch should be
sealed.
Refrigerant pipe installation
Cleaning the pipe:

 Purpose: eliminating dust, water vapor and oxides caused by welding.


 Note: the solid can not be eliminated, so please store the pipes carefully
to prevent the solid entering.
 Method:
1. Flush the pipe with 0.5 MPa Nitrogen
2. Block all the nozzles of the pipes
3. Use your hand to block one of the nozzles
4. When the pressure is too high to block, then
remove your hand
5. Repeat the step 3 and 4 to each nozzle
6. After flushing seal all the nozzles
Refrigerant pipe installation
Cleaning the pipe:

 Procedures
From far to near (sequence: ①-②-③-④-⑤-⑥ )

⑥ ⑤ ④ ③ ①

 Note
1. When flushing one pipe, the other pipes need to be sealed.
2. After flushing, remember to seal all the pipes.
3. Suggest to do the leakage test for piping works before connecting to
outdoor and indoor units
Refrigerant pipe installation

 The distance between the supports of the copper pipes.

Diameter (mm) ≤ 20 20 ~ 40 ≥ 40

Distance (m) 1 1.5 2

 When the liquid pipe and gas pipe are hung up together, it is determined
by the diameter of liquid pipe.
Refrigerant pipe installation

Completely no support is not allowed


Refrigerant pipe installation
Heat insulation
• You should cover the heat insulation after pipe joint and before you put the
pipe on the position.
• The heat insulation thickness specs. as following:

• Enlace the tape to protect the insulation.


Refrigerant pipe installation

 The insulation of liquid pipe and gas pipe must be separately insulated

 Liquid pipe shall be heat insulated at all times and the only exception

when the customer is totally sure the unit will only deliver

COOLING.
Refrigerant pipe installation

 The insulation work must be done to every part of the refrigerant


pipes
Refrigerant pipe installation

 Block the nozzle of the pipe when make it through the insulation material.

Wrong Avoid the dust entering the pipe


Refrigerant pipe installation

 The gap between two parts should be well insulated by additional

insulation material.

Ri Wrong
gh
t

Copper pipe

Insulation
Refrigerant pipe installation

 Typical mistake.

Obvious no insulation
Drain pipe installation

Selecting drain pipe size:


Drain pipe installation
 Caution : the gradient of main drainage pipe must be bigger than 1%

Exhaust outlet

≥ 1% Condensate pipe

 Note
1. If the gradient < 1% , then select drainage pipe with bigger
diameter
2. The length of drainage pipe should be as short as possible
3. The drainage pipe should be independent with other water pipe
4. Never put the drainage pipe together with dirty water pipe
Drain pipe installation
 Drainage with pump:

- Lifting the pipe on the pump outlet to form the lean pipe .

Make a lift
for easy drainage
Drain pipe installation
 Drainage with pump:

Well fixed for this part

Lift can not go beyond the pump head of drainage pump


Drain pipe installation

 Drainage without pump:

100mm

50mm
plug

Main drainage pipe

plug
 If the pressure at the connection of the drain pipe is negative, it needs to
set a drainage trap.
 A plug should be installed to make clean easy
Drain pipe installation

To avoid the water flow back to the indoor unit, the branch pipe from the
drainage pan should be connected to the main pipe from the top.

To avoid the bending, supporter must be installed with the drainage pipe.
The distance between each supporter for horizontal pipe should be 1~1.5m.
Drain pipe installation

 Typical mistake: Avoid confront water flow

Drain pipe Drain pipe


Drain pipe 3-way pipe

3-way pipe 3-way pipe

Incorrect Correct Correct


Drain pipe installation

Vent outlet should not be upward Correct way

Make a vent outlet at the highest


position.
Drain pipe installation
sharp bend on the flexible pipe is not allowed
Drain pipe installation

The thickness of insulation material for condensing water pipe is 15mm.

The gap between two pieces of insulation


No insulation
material should be filled with insulation material
and then tape it.
Drain pipe installation

 Water leakage test


 Check leakage at water pipe
After finished installation of drainage pipe, filled the pipe with water,
waiting for 24 hours to check whether there’s any leakage.
 Check leakage from the indoor unit
Charge water from the access hole of indoor unit, ensure the water can
be exhaust smoothly
Installation

Wiring Installation
Wiring
Communication wiring

The communication wire must be twisted shielded wire.


Wiring

Outdoor Power Supply:


380V/3Ph/50-60HZ

L1 L2 L3 N
Slave 2 Slave 1 Master unit

MCB

MCB MCB MCB


M S1 S2
N T
Wiring

Outdoor Power Supply:


220V/3Ph/60HZ

L1 L2 L3
Slave 2 Slave 1 Master unit

MCB

MCB MCB MCB


M S1 S2
T
Wiring

Indoor Power Supply Option A:


220 V/1Ph/50-60HZ
L1 N

MCB

CB-1 CB-2 CB-3 CB-4 T

Notes: Use one main power supply for all indoor units
Wiring

Indoor Power Supply Option B:


220 V / 1 Ph / 50-60 HZ

L1 N

MCB T

Notes: Use one main power supply for all indoor units
Wiring

Rated current of residual Ground Wire


Circuit Breaker(A)
Ground Fault Interruptor(mA)
Response time(S)

Rated current of residual


Circuit Breaker(A)
Ground Fault Interruptor(mA)
Response time(S)
CONTENT
1 • Indoor unit installation

2 • Outdoor unit installation

3 • Refrigerant pipe installation

4 • Wiring

5 • Drain pipe

6 • Leakage test

7 • Additional refrigerant charging


Leakage test
Leakage test

If there’s 1℃ difference in temperature, there will be 0.01 MPa difference in pressure.


Correcting formula:
actual value = pressure when finish charging +(current temp. – temp. when finish
charging) × 0.01MPa

 For example:
Temp. when charging N2: 24 ℃

N2 pressure when charging: 4.05 MPa


Temp. after 24 hours: 22 ℃
N2 pressure after 24hours
= 4.05 MPa + (22 ℃-24 ℃)×0.01 MPa/ ℃
= 4.05 MPa -0.02 MPa
= 4.03 MPa
If the actual pressure after 24hours is lower than 4.03 MPa, you need to check
whether there’s leakage or not.
Vacuum system

 Purpose : remove the air and water in the system.


 Necessary tools : vacuum pump (displacement: 4L/s or more)
 Vacuum degree: less than -755mmHg(-0.1MPa)

Don’t open the valves of outdoor unit when vacuuming

After 3 hours, if the vacuuming degree can not reach -755


mmHg or less, the system need to be checked

Vacuum dry from liquid side and gas side simultaneously


Vacuum system

Gas side

Liquid side

Oil side
Additional Refrigerant Charging

 Additional refrigerant charging procedures:

Calculate necessary amount of additional refrigerant according


to the additional charging requirement in Selection software
report

Make sure the leakage test, vacuum dry, pipe insulation has
been finished

Charge refrigerant to the outdoor unit from Liquid side. The


amount of additional refrigerant must refer to the calculation
result in the 1st step

 Note:
1. Over much refrigerant will cause liquid harmer.
2. Record the actual amount of additional refrigerant for further
reference.
Additional refrigerant charging

220V Mini VRF T1

Charge

Note: Refrigerant pipe size in mm, and it is liquid pipe


Additional refrigerant charging
220V VRF T1

Note: Refrigerant pipe size in mm, and it is liquid pipe


Additional refrigerant charging
380V VRF T1

Note: Refrigerant pipe size in mm, and it is liquid pipe


Additional refrigerant charging
380V VRF T3

Note: Refrigerant pipe size in mm, and it is liquid pipe


Additional refrigerant charging
Additional Refrigerant Charging

Charge the additional refrigerant, then open the stop valve at


outdoor unit and Startup

Outdoor unit

ON ON ON

R410A

Liquid side
Installation
A revisit of roadmap for
Installation, Startup and
Commissioning