Basic Generator Theory
Basic Generator Theory
The Discovery
A Conductor
A Magnetic Field
Relative Motion between the Field and the Conductor
A Basic Diagram
1. Voltage Regulation
The Final Output Voltage shall be monitored at all times by the A.V.R.
to automatically adjust the Excitation Voltage needed to maintain the
voltage we have set the unit at. These changes take place automatically
when Loads are applied or removed. The actual Final Output Voltage
Range will be determined by the configuration of the Main Generator
Windings(Stator), a Series configuration will result in a High Voltage
Range(380-600), a Parallel configuration will result in a Low Voltage
Range(120-250).
The Results of the Process(cont.)
2. Frequency (Hz)(Hertz)(Cycles)
Frequency-
a. The number of repetitions of a complete sequence of values of a periodic function per unit variation of an
independent variable.
b. The number of complete cycles of a periodic process occurring per unit time.
c. The number of repetitions per unit time of a complete waveform, as of an electric current.
The Frequency is controlled by two things:
A. Total number of Poles
The total number of poles that the A.C. Generator has
depends, Most Generators in the Portable Power field today have 4
Poles. Small personal generators are all mostly 2 Poles. The Poles are
the Core of the Rotors that become the magnetic fields, Thus the
identification of the North Pole and South Pole of the Magnets.
Therefore we have 2 North Poles and 2 South Poles, Which allows us
to complete 2 complete Cycles of production per revolution.
The more poles, the slower the speed of the prime mover.
The Results of the Process (cont.)
2. Frequency(cont.)
B. Speed
The Most important of the two, is the Prime
Mover(Diesel Engine). The Prime Mover controls the
speed of rotation of the Rotors inside the Windings. This
speed is determined by the number of poles, which is 2 or 4,
and knowing the Frequency we wish to operate at, which
shall be 60Hz. Our calculation is as follows:
N=f x 120 / 2 or 4 where- N=RPM of the Engine,
f =Frequency, 120 is the division of time and 2 or 4 is the
number of Poles. Answer-60hz x 120 /2 or 4 Poles=3600
or 1800rpm
With this established, we know we must run at 3600 or
1800 rpm to maintain 60hz at all times.
Portable or Installed
1. Portable
A) Speed
Most portable generators we use today are 2 pole,
therefore they operate at a higher rate of speed to maintain
60Hz. (3600 RPM)
B) Voltage
Most portable generators we use today are also
mostly 240/120 vac Single Phase
C) Sound
Most portable generators we use today are also
smaller and quieter than the larger models.
Portable or Installed
1. Installed
A) Speed
Most installed generators we use today are 4 pole,
therefore they operate at a lower rate of speed to maintain 60Hz.
(1800 RPM)
B) Voltage
Most installed generators we use today are capable of
either 240/120vac Single Phase, 208/120vac and/or 480/277vac
Three Phase
C) Sound
Most installed generators produce much noise or are
silenced with special housings.
2 Pole Generator 60Hz 3600 RPM
4 Pole Generator 60Hz 1800 RPM
1Phase Sine Wave of Voltage
3 Phase Sine Wave of Voltage
Keith “Bo” Thomas
+1 409 986 7005 ofc
+1 409 789 8160 mbl
[email protected]