Turbine

Lube Oil System


Operation
Module
Praveen Kumar Sinha

RU - * - V1
System Overview
• Lube Oil System

• Purpose: -
– Lubrication and cooling of the turbine and generator
bearings with turbine oil drawn from the main oil tank
by the oil pumps and forwarded via cooler and filter to
the bearings; pressures and flow rates are set with
throttle valves.
– Supplying motive oil to turning gear.
– Backflow of the turbine oil to main oil tank.

- * - 2
Components of Lube Oil System
• Main oil tank and oil pumps
– Main oil tank
– Main oil pump driven by MAV 21 AP001
– Auxiliary oil pump 1 MAV22 AP001
– Auxiliary oil pump 2 MAV23 AP001
– Emergency oil pump MAV24 AP001

• Turning gear oil supply valve


• Oil coolers and oil filters
– .Oil cooler 1 MAV41 BC001
– Oil cooler 2 MAV41 BC002
– Double multiport butterfly MAV41 AA521
– Oil temperature control valve MAV41 AA001
– Lubricating oil filter MAV42 BT001

• Lubricating oil supply to bearings


• Lubricating oil valve

- * - 3
IP IP IP G E
T T T
MO HPT IPT LPT- LPT-
P 1 2
INJECTO
R-2

SOST
INJECTOR-1

COOL

COOL

FIL

FIL
TE

TE
ER

ER

R
AOP AOP EOP- JOP- JOP-
-1 -2 DC AC DC
MAIN OIL TANK

30
TURBINE LUBE OIL
- * - SCHEME 4
Specification
Main Turbine AOP
Pump
Type 8/8 series 6 model
Manufacturer Mather &Platt pump ltd
Volumetric flow 6900 lpm
Discharge pressure 7.4 bar
Operating temperature 65 C
Flow medium Oil
Speed 1485 rpm
Motor
Type M2BAP3155MBHIC
Duty S11P-55,
Insulation class F
Efficiency 95.4
voltage 415 V
Frequency 50
KW 125 kw
RPM 1485
Bearing DE 63/9C3
Lubrication Qty 45g
Bearing NDE 63/6C3
Lubrication Qty 35g
Grease TJNIREX

- * - 5
Specification cont..

Main Turbine JOP(AC)


Pump
Type T3SA39/46MPSXALXRXXBBNL
Manufacturer Tushaco
flow 120 lpm
Discharge pressure 178 Bar
Speed 1445 rpm
Motor
Manufacturer Crompton Greaves ltd
Current 95 amp
KW 60 kw
Voltage 415 V
RPM 2955 rpm
Main Turbine JOP (DC)
Pump
Manufacturer Tushaco
flow 120 lpm
Discharge pressure 178 Bar
Speed 2900 rpm
Motor
Manufacturer Crompton Greaves ltd
Arm Current 310 amp
KW 60 kw
Arm Voltage 200 V
RPM 2955 rpm
- * - 6
Specification cont..

Main Turbine EOP (DC)


Pump
Input power 10.33kW
flow 108 m3/hr
Head 27.53 mtr
Speed 1425 rpm
Motor
Manufacturer Crompton Greaves ltd
Arm Current 97 amp
KW 13 kw
Arm Voltage 155 V
Field Voltage 220 V
Field Amp 0.6
RPM 1425 rpm
Main Turbine MOT OVEF
Fan
Pressure 220 mmwc
Capacity 396 m3/hr
Numbers 2 set
Motor
Manufacturer Bharat Bijlee
Current 1.05 amp
Power 0.75 kw
Voltage 415 V
Field Amp 0.6
Speed 2830 rpm
- * - 7
Specification cont..

Main Turbine Oil cooler


Cooling surface area provided 640 m2
Oil flow 182.304 m3/h
Heat dissipating capacity 1907.67 kW
Oil I/L Temp 65
Oil O/L Temp 45
Oil side pressure drop 4 mwc
CW I/L Temp 38
CW O/L Temp 41
CW Flow 500 m3/h
CW side pressure drop (approx.) 3.5 mwc
Design pressure – CW side 10 kg/cm2
Design pressure – Oil side 9.4 kg/cm2
Tube material Admiralty Brass
Tube plates material Carbon steel
Casing (shell) material Carbon steel
Water boxes material Carbon steel

- * - 8
Lube Oil System Pre checks:

1. No concern PTW is pending.


2. Fire fighting for lube oil system must be charged condition.
3. Ensure MOT level is adequate and no “tank level low” alarm persisting.
4. Ensure all drains of MOT, Lube oil coolers and filters, are closed and vents opened.
5. Ensure either of Lube oil coolers are lined - up from both oil and DMCW side.
6. Ensure any one filter is lined-up.
7. AOP1, AOP2, EOP, AC JOP, DC JOP, OVEF power supplies are healthy and in
remote. DC oil pumps (EOP, DC JOP) supplies are to be normalised just before
starting, to avoid any unwanted leakage of oil if system is not lined up properly.
8. Discharge MIVs for AC JOP and DC JOP should be full open and filter is lined-up.
9. Ensure all local gauges & transmitters are in service and charged.
10. All local push buttons are released.
11. Ensure individual isolation MIV of Jacking oil line for all bearings is open.
12. Ensure Lube oil temperature control valve power supply is healthy and in remote.

- * - 9
Turbine Oil system start-up activities:

1. Start one Vapour exactor fan.


2. First start EOP and ensure there is no leakage in the
entire lube oil system. Keep running
3. Ensure pressure is built-up in Turbine lube oil
header(>2.5 kg/cm2)
4. Check for any oil leakage in the system. If found,
immediately Stop the pump and inform TMD.
5. Start AOP1 and also take trial ofAOP2,if running normal
then stop AOP2.
6. Start AC JOP pump and observe discharge pressure is
built up to 160 kg/cm2to 170 kg/cm2

- * - 10
Turbine Oil system start-up activities:

7. Take DC JOP trial if AC JOP is running normal.


8. Put lube oil temp control in auto and set point
as 45 degC.
9. Open barring gear MOV and ensure speed is
rising slowly.
10. Check whether speed has reached around 80
RPM.
11. PUT SLC ‘ON’ for AOP, EOP, JOP, Turning
gear ‘ON’.
12. Check for any oil leakage in the system.

- * - 11
Turbine oil system stopping procedure:

• Close barring gear MOV from DCS.


• Check that MOT level is rising.
• Ensure turbine speed is reducing to zero speed.
• Ensure all SLC is in ‘OFF’ condition.
• Stop AC JOP.
• Stop running AOP and check MOT level is increasing.

- * - 12
Interlock and Protection

- * - 13
AUXILIARY OIL PUMP – 1

START SEQUENCE
S.No. DESCRIPTION SET VALUE ALARM

AUTO ON/START

a)SLC AOP –1 ON &(AOP – 2 OFF & MCC disturbance)

OR
< 5.8
Discharge header pressure is < 5.8 KG/CM2 OR KG/CM2
1
OR

b) SGC oil supply step –2 command i.e.,


< 2850 rpm 5 sec
SGC ‘ON’ (all steps completed) and turbine speed OR

2 MANUAL ON
STOP SEQUENCE
AUTO OFF/CLOSE
1 Oil Pressure OR 7 kg/cm2
Protection OFF
2
FIRE PROTECTION 2 OPTD -1050
3 MANUAL OFF

- * - 14
AUXILIARY OIL PUMP – 2

START SEQUENCE
S.No. DESCRIPTION SET VALUE ALARM

AUTO ON/START
a) SLC AOP –2 ON &(AOP – 1 OFF & MCC disturbance)
OR
< 5.8
Discharge header pressure is < 5.8 KG/CM2 OR KG/CM2
1
OR
b) SGC oil supply step –2 command i.e.,
< 2850 rpm 5 sec
SGC ‘ON’ (all steps completed) and turbine speed OR
2 MANUAL ON
STOP SEQUENCE
1 AUTO OFF/CLOSE
Oil Pressure OR 7 kg/cm2
Protection OFF
2
FIRE PROTECTION 2 OPTD -1050
3 MANUAL OFF

* 15

- -
DC EMERGENCY OIL PUMP

(A)PERMISSIVE ON/START

S. No. DESCRIPTION SET VALUE ALARM

PROTECTION ON
a) SLC EOP On &
Lube oil Pressure < 1.5
kg/cm2
1 b)Temperature HP Casing Top OR > 120 DEG C

Temperature HP Casing bottom > 120 DEG C

Lube oil pressure < 1.5


kg/cm2
2 MANUAL ON
STOP SEQUENCE
1 MANUAL OFF

- * - 16
JACKING OIL PUMP

START SEQUENCE
S NO DESCRIPTION SET VALUE ALARM
AUTO ON/START
1 SLC JOPs ON &
Turbine Speed < 510 rpm
2 MANUAL ON
STOP SEQUENCE
JOP –1 Auto Stop
a)SGC OIL SUPPLY STEP 54 SHUT DOWN SEQ OR
1
SLC JOP-1 ON &
Turbine Speed > 540 rpm
b) [JOP –2 ON Command through SLC. ] OR

[i. Turbine Speed& < 510 rpm


ii. Jacking oil pressure (7 Sec Delay)] < 110 kg/cm2

c)JOP-2 SLC ON &


Turbine speed & <2800 rpm
JOP-1 failure
d) JOP-2 SLC ON &
JOP-1 OFF feedback or
JOP-1 MCC disturbance
PROTECTION STOP
2
FIRE PROTECTION 2 OPTD -1050 mm
3 MANUAL OFF
Any -2 number *of JOP’s can’t
- run simultaneously either with SLC ON or OFF. For pump changeover, running pump is stopped first, 17
JACKING OIL PUMP – DC

START SEQUENCE
S NO DESCRIPTION SET VALUE ALARM
AUTO ON/START
a) SLC JOP-2 ON &
Turbine Speed & < 510 rpm
Jacking oil pressure (7 Sec Delay) OR <110 Kg/cm2 7 sec

b) SLC ON &Turbine Speed& < 2800 rpm


AC JOP –1 Voltage failed OR
c) SLC ON & JOP-1 OFF &
1
1 JOP-1 status discrepancy
PERMISSIVE ON
2 JOP-1 OFF
3 MANUAL ON
PROTECTION ON
4
FIRE PROTECTION -2 OPTD
STOP SEQUENCE
1 MANUAL OFF

- * - 18
TURNING GEAR VALVE

START SEQUENCE
S NO DESCRIPTION SET VALUE ALARM
Turning Gear Permissive
a)Turbine speed OR > 15 rpm
> 1.1
b) DP S/O Air H2 side TE & Kg/cm2
1 > 1.1
c) DP S/O Air H2 side EE & Kg/cm2
> 7.0
d) Seal Oil Pr. H2 side Kg/cm2
Auto Open
2
SLC Turning gear ON & Turbine Speed < 210 rpm
3 MANUAL ON
STOP SEQUENCE
Auto Close
a) Through SGC Oil Supply step –51 i.e., SGC Oil Shut down
ON Or
1
b)Turbine Speed& > 240 rpm
c) SLC Turning gear ON
< 1.2
2 Protection Close: Lube Oil Pressure before Bearings kg/cm2
- * - 19
Seal oil System

• Seal oil System


• Purpose:
– To Provide sealing to Hydrogen Filled Generator so that H2 do
not escape from the Generator
– To provide Lubrication in the both Generator End Seal

- * - 20
Components of Seal Oil System
• Seal Oil Storage Tank (SOST)
• Vacuum Oil Tank (VOT)
–Seal Oil Vacuum Pump
• Intermediate Oil tank (IOT)
• Seal oil Pumps
–AC SOP-1
–ACSOP-2
–DCSOP
• Seal Oil Cooler
• Seal Oil Filter
• Bearing Chamber Exhaust Fan

- * - 21
Ring relief Oil
Supply
B.C. EXHAUST FAN-
1 Seal Oil
Supply
TO
ATMOSPHER
E

GENERATO DP
DPR
B.C. EXHAUST FAN- R R
2

Gen. Waste
OIL Gas Sys.
TRAP
DRAI
N
LUB OIL RETURN
SOST VE
HEADER
GEN. NT
WASTE
FLUID P
SYSTEM G
FILTER
S

VACUUM PUMP- IO
T
A

VACUU VE
M TANK
NT

VACUUM PUMP-
B COOLERS

SOP-
SOP- 2
DC
1
SOP
LUBE OIL
TURBINE

SYSTEM
FROM

GENERATOR SEAL
35 - * - . OIL SYSTEM 22
Specification
SEAL OIL SYSTEM
AC Seal Oil Pump-1&2
Kind of pump Three screw pump

Type T3ST-70146
Make Crompton Greaves Ltd

Capacity 420 LPM


Discharge pressure 12 KSC

Pump motor ND132M


Rating 15KW
Voltage/frequency 415V,3PH AC 50HZ

Current 13.6A
Speed 1450 RPM
Type of enclosure TEFC,IP55

Nos. 2X100%
- * - 23
Specification cont..

DC Seal Oil Pump


Kind of pump Three screw pump

Type T3S-52/54
Capacity 420 LPM
Discharge pressure 12 KSC

Pump motor AFS225L


Rating 15KW
Voltage/frequency 220V DC

Current 67A
Speed 1450 RPM
Type of enclosure TEFC,IP55

Nos. 1X100%
Vacuum pump
Capacity 162 LPM
Rating 0.37 KW
Voltage/frequency 415V,3PH AC 50HZ

- * - 24
Specification cont..

Seal oil filters


Kind of filter Strainer-type
Type DUPLEX Filter NB 80
NP 4
Volumetric flow rate 24.6 m3/hr

Degree of filtration 40 micron

Pressure drop across filter 0.3 bar with clean


filter

- * - 25
Specification cont..

SEAL OIL COOLER (2 x 100 %)

Oil flow 15.9 m3/h


Oil I/L Temp 66 oC
Oil O/L Temp 41 oC
Oil Pressure drop 0.2 bar
CW Flow 59.4 m3/h
CW I/L Temp 39 oC
Water O/L Temp 42 oC
Water pressure drop 0.35 bar
Materials
Heat transfer plates SS316
Gaskets Neoprene
CW Pressures
Operating pressure 16 kg/cm2
Test pressure 24 kg/cm2
Oil Side Pressure
Operating pressure 16 kg/cm2
Test pressure 24 kg/cm2

- * - 26
Initial filling of seal oil line:

• Open Seal Oil Storage Tank (SOST) outlet valve (MKW01AA276) to seal oil system for initial
filling.
• OPEN Vacuum tank inlet MIV (MKW10AA101) and check vacuum tank level is rising and
maintained up to 60%.
• OPEN intermediate oil tank inlet valve (MKW06AA151) and check vacuum tank level is rising
and maintained up to 60%.
• OPEN inlet valves (MKW11AA261, MKW12AA261) and outlet valves (MKW11AA051,
MKW12AA051) of both AC pumps.
• OPEN inlet valve (MKW01AA286, MKW13AA261) and outlet valve (MKW13AA051) for DC
pump.
• Charge both seal oil coolers from oil side by keeping rotary transfer valve (MKW21AA151) in
centre position.
• Open oil side vent valves (MKW21AA251, MKW22AA251) provided on both coolers. Close vent
valves when oil emerges without bubbles.
• After Proper venting isolate one cooler from oil side and another oil cooler should be taken in to
service.
• Open inlet & outlet isolation MIV of oil cooler (DMCW side) and close the vents after proper
venting.
• Charge both filters one by one by opening inlet and outlet valves and after proper venting their
vents should be closed.
- * - 27
Pre-checks before start-up of Seal oil Pump:

• Cooling water for seal oil cooler is established.


• Oil cooler is charged from DMCW side & oil side and proper
venting is done.
• Power supplies for Vacuum pumps and seal oil pumps are
normalized.

- * - 28
Start-up of Seal oil Pump:

1. Start DC Seal oil pump for trial and line filling.


2. Check for any abnormal sound from DC seal oil pump.
3. Check pump discharge pressure is more than 10 kg/cm2.
4. Wait till pressure in pressure gauge after seal oil filter is showing steady
reading.
5. If DC seal oil pump running healthy, Start AC seal oil pump and stop DC seal oil
pump.
6. Again, check for any abnormal sound from AC seal oil pump.
7. If seal oil pump header pressure is maintaining more than 10 kg/cm2. Open
isolation MIV (MKW14AA051) for oil coming from turbine lube oil system.
8. While filling CO2 in generator ensure than seal oil pressure is increasing to
maintain DP up to 1.3 to 1.8 kg/cm2 and ring relief oil pressure is at least 1
kg/cm2 above seal oil pressure
9. Start one vacuum pump provided in seal oil skid and put other pump on
standby.
10. Check vacuum is developing in vacuum tank and maintained around >0.12 abs.

- * - 29
- * - 30