Chapter 2 - Jhazel Report
Chapter 2 - Jhazel Report
AND
PROTECTION
CHAPTER 2
Use and Identification of
1 Grounded Conductors
Branch Circuits
2
CONTENTS
Feeders
3
Branch-Circuit Calculations
4
ARTICLE 2.0
U S E A N D I D E N T I F I C AT I O N O F
01 GROUNDED CONDUCTORS
GROUNDED CONDUCTORS
Must be well-insulated and maintain a continuous,
unbroken path to ensure safety. They should be properly
identified typically through white or gray color coding.
For a premises wiring system to be electrically connected
to a supply system, the supply system must contain a
grounded conductor that corresponds to the grounded
conductor of the interior system.
Neutral conductors cannot be shared between multiple
circuits unless allowed by the electrical code.
M e a n s o f I d e n ti f y i n g G r o u n d e d C o n d u c t o r s
1 2
FEEDER CONDUCTORS
Overcurrent Protection
Branch-circuit conductors and equipment shall be
protected by overcurrent protective devices where
a branch circuit supplies continuous loads or any
combination of continuous and noncontinuous loads,
the rating of the overcurrent device shall not be less
than the noncontinuous load plus 125 percent of the
continuous load.
HOW TO DETERMINE BRANCH CIRCUIT CONDUCTORS,
OVERCURRENT PROTECTIVE DEVICES, AND EQUIPMENT
GROUDING CONDUCTORS?
Receptacle Outlets
Receptacle outlets shall be calculated at not
less than 180 volt-amperes for each single or
for each multiple receptacle on one yoke. A
single piece of equipment consisting of a
multiple receptacle comprised of four or more
receptacles shall be calculated at not less than
90 volt-amperes per receptacle.
ANY QUESTION?
THANK YOU!