Unit 2
Unit 2
CONVERTERS IN POWER
GRID
Syllabus
1. Maintain the voltage profiles at each end sides: In large transmission network,
power flow in some of the transmission lines are well below their normal limits
and others overloaded
• The location of the series capacitor depends on the economic and technical
considerations of the line.
• The series capacitor may be located at the sending end, receiving end or at the
center of the line.
• In each case, a special system study concerning load flow, stability, transient
overvoltage, protection requirements, system voltage profile, etc. is necessary
before the optimal location is chosen.
• Sometimes they are located at two or more points along the line.
Advantages of series compensation
• Control of voltage
• Mal operation of distance relay-if the degree of compensation and location is not proper.
• High recovery voltage of lines-across the circuit breaker contacts and is harmful.
Protection scheme for series capacitor
• When the fault or overload occurs the large current will flow across the series
capacitor of the line.
• Thus, the excessive voltage drop occurs across the transmission line
• For protecting the capacitors from such abnormal voltages, spark gaps and surge
diverters are connected to the capacitor terminal.
• The SSSC works like the STATCOM, except that it is serially connected instead
of a shunt.
• The SSSC operates like a controllable series capacitor and series inductor.
• The primary difference is
that its injected voltage is
not related to the line
intensity and can be
managed independently.
• A thyristor valve commutates “naturally”, that is, it turns off when the current
crosses zero.
• Thus a capacitor can be inserted into the line by the thyristor valve only at the
zero crossings of the line current.
v. Thyristor-switched series reactor (TSSR)
• This controller switches thyristors such that they are either fully ON or fully OFF
in order to achieve stepped series inductance.
2. Shunt compensation
• The general purpose of shunt compensation is to keep the voltage rises down
during light or no-load conditions.
• Whenever an inductive load is connected to the transmission line, power factor lags
because of lagging load current.
• If XC=1/ꞷC be the reactance of the shunt capacitor then the reactive power
generated of leading Var supplied by the capacitor:
QC = = ꞷC
• This method is used either when charging the transmission line, or, when there is
very low load at the receiving end.
• Due to very low, or no load – very low current flows through the transmission line.
Shunt capacitance in the transmission line causes voltage amplification (Ferranti
Effect).
• The receiving end voltage may become double the sending end voltage (generally in
case of very long transmission lines).
QL = = /ꞷL
• To control the receiving end voltage generally one shunt reactor is installed and
switched in during the light load condition.
• To meet the variable reactive power demands requisite number of shunt capacitors
are switched in, in addition to the shunt reactor, which results in adjustable reactive
power absorption by the combination.
Examples of shunt compensation
• The device use synchronous voltage sources for generating and absorbing reactive power.
• A STATCOM usually contains an SVS that is driven from a dc storage capacitor and SVS
is connected to the ac system through an interface transformer.
• The transformer steps the ac system voltage down such that the voltage rating of the SVS
switches are within specified limit.
• STATCOM is a shunt-connected device injecting
dynamically inductive or capacitive reactive power
into the transmission grid.
• The reactive component used in the STATCOM are much smaller than those in the
SVC.
• The term “static” refers to the fact that the SVC has not moving parts (other than
circuit breakers and disconnects, which do not move under normal SVC
operation).
• They are a fast and reliable means of controlling voltage of lines and system’s
buses.
Advantages of SVC
• Static VAR compensation is not done at line voltage; a bank of transformers steps
the transmission voltage(for example, 230 kV) down to a much lower level (for
example, 9.5 kV). This reduces the size and number of components.
• Faster in operation
• Smoother control and more flexibility can be provided with the help of thyristors.
a. Thyristor controlled Reactor (TCR)
• Currently available thyristors can block voltage upto 4000-9000 V and conduct current
upto 3000-6000 A.
• Practically 10-20 thyristors are connected in series to meet the required blocking voltage.
• The current in the reactor can be controlled by the method of firing delay angle control.
• The closure of the thyristor valve is delayed with respect to the peak of the applied voltage
in each half-cycle.
b. Thyristor Switched Capacitors (TSC)
• The capacitors serve as filters for harmonics when only the reactor is switched.
• Normally a relatively small surge current limiting reactor is used in series with the
TSC branch. This is needed primarily to limit the surge current in the thyristor
valve under abnormal condition (switching at wrong time)
Combined TCR/TSC compensators
More economical when there are a large number of capacitors to be switched than
using TSCs.
The speed of switching is however longer and this may affect transient stability.
This method is suitable for steady load conditions, where reactive power requirements
are predictable.
12 pulse rectifier bridge
• For high voltage applications, two or more converters can be connected in series
to share the voltage and also to improve the power factor.
• The 30-degree phase shift is usually achieved by using a transformer with two
sets of secondary windings, one in star (wye) connection and one in delta
connection.
• Sometimes the advantages of increasing the pulse number are offset by the
complexity of the transformer connection and by the difficulties of maintaining
balance in the system.
• This happens when two Twelve pulse converter are interconnected to form a 24
pulse one.
• The transformer used in the twelve pulse converter will be normally connected with
primary Y-Y and secondary is Y-Δ windings.
• The main purpose of this is to provide a 30° phase shift, which is can be able to
provide 12 pulse output as well as to provide isolation between the two systems.
Advantages of 12 pulse rectifier
• The lower order harmonics such as 3rd, 5th, 7th, etc are eliminated in the 12-
pulse operation of VSC.
• Ripple content in the output waveform of the 12-pulse converter is comparatively
less as than the 6-pulse converter.
• The total harmonic distortion (THD) is less in 12-pulse operation.
• The output voltage waveform is closer to the sine wave in the 12-pulse operation
of VSC.
Multilevel Inverters
1. Diode-clamped inverter
2. Capacitor-clamped inverter
• Reduced harmonic distortion: Multilevel converters not only can generate the
output voltages with very low distortion, but also can reduce the change in voltage
(dv/dt) stresses, therefore electromagnetic compatibility(EMC) problems can be
reduced.
• Input current: Multilevel converters can draw input current with low distortion.
• Switching frequency: Multilevel converters can operate at both fundamental switching
frequency and high switching frequency PWM. It should be noted that lower
switching frequency usually means lower switching losses.
• The most commonly used multilevel topology is the diode clamped inverter, in
which the diode is used as the clamping device to clamp the dc bus voltage so as
to achieve steps in the output voltage.
• Thus, the main concept of this inverter is to use diodes to limit the power devices
voltage stress.
• An n level inverter needs (n-1) voltage sources, 2(n-1) switching devices and
(n-1) (n-2) diodes.
• By increasing the number of voltage levels the quality
of the output voltage is improved and the voltage
waveform becomes closer to sinusoidal waveform.
• The DC level will discharge when control and monitoring are not precise.
Applications of diode-clamped multilevel inverters
• This can also be used in variable speed control of high power drives.
• This topology has a ladder structure of dc side capacitors, where the voltage
on each capacitor differs from that of the next capacitor.
• The voltage increment between two
adjacent capacitor legs gives the size of the
voltage steps in the output waveform.
• The output voltage is the sum of the voltage that is generated by each cell.
• The number of output voltage levels are 2n+1, where n is the number of cells.
• The switching angles can be chosen in such a way that the total harmonic
distortion is minimized.
• One of the advantages of this type of multilevel
inverter is that it needs less number of
components comparative to the Diode clamped
or the flying capacitor, so the price and the
weight of the inverter is less than that of the
two types.
• Compared with Diode Clamped & Flying • It requires several separate D.C.
Capacitor Multilevel Inverter, it requires least sources thereby limiting its
number of components to produce same level applications.
inverted output. • Duty cycle for each of the voltage
• Soft switching techniques can be used to reduce level is different, this means level – 1
the switching losses & stress. d.c. sources discharges much sooner
than the level – 5 d.c. sources.
• Here packaging is possible because each level
has same structure and no extra clamping diodes • So, switching pattern must be such that
or voltage balancing capacitors. all the d.c. sources can be equally used
or charged accordingly.
Applications